Exciting enhancements are coming soon to eCode360! Learn more 🡪
City of Town And Country, MO
St. Louis County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
 
Cross References — Building code, §500.010 et seq.; mechanical code, §500.030 et seq.; electrical code, §500.050; plumbing code, §500.060.
[1]
Editor’s Note—Ord. no. 3435 §§1—3, adopted June 9, 2009, repealed sections 220.120—220.140 and enacted new provisions set out herein. Former sections 220.120—220.140 derived from Code 1975 §§19.01—19.03; CC 1989 §§9-41—9-43; ord. no. 2971 §1, 11-10-2004; ord. no. 3134 §1, 4-25-2006.
[Ord. No. 3435 §§1—3, 6-9-2009; Ord. No. 3837 §§1 — 3, 9-8-2014; Ord. No. 4142, 12-11-2017; Ord. No. 4383, 9-28-2020]
A certain document, a copy of which has been on file for at least ninety (90) days in the office of the City Clerk of the City of Town and Country, being marked and designated as "The International Fire Code, 2018 Edition," including Appendixes B through J, with the additions, insertions and changes, if any, prescribed in Section 220.125 of this Article, as published by the International Code Council, be and is hereby adopted and made a part of this Code of Ordinances for regulating fire safety in the City of Town and Country; and each and all of the regulations, provisions, conditions and terms of such International Fire Code, 2018 Edition, published by the International Code Council, on file in the office of the City Clerk are hereby referred to, adopted, and made a part hereof as if fully set out in this Article, with the additions, insertions and changes, if any, prescribed in Section 220.125 of this Article.
[Ord. No. 3435 §§1—3, 6-9-2009; Ord. No. 3837 §§1 — 3, 9-8-2014; Ord. No. 4142, 12-11-2017; Ord. No. 4383, 9-28-2020]
Throughout the International Fire Code, 2018 Edition, wherever the terms "name of jurisdiction" or "local jurisdiction" appear, it shall be deemed to mean "City of Town and Country, Missouri." Wherever the term "code" appears, it shall mean the International Fire Code, 2018 Edition.
[Ord. No. 3435 §§1—3, 6-9-2009; Ord. No. 3837 §§1 — 3, 9-8-2014; Ord. No. 4142, 12-11-2017; Ord. No. 4383, 9-28-2020]
The International Fire Code, 2018 Edition, adopted in Section 220.120 hereof shall be amended as set forth herein:
CHAPTER 1 SCOPE AND ADMINISTRATION
Section 101.1 Title (Amended): The Fire Code of the City of Town and Country ("Fire Code") shall consist of:
1. The International Fire Code, 2018 Edition, one (1) copy of which is on file in the office of the City Clerk of the City of Town and Country.
2. The amendments to the International Fire Code, 2018 Edition, set forth herein. The International Fire Code, 2018 Edition, is referred to herein as the "code."
SECTION 109 BOARD OF APPEALS (Amended): The Board of Adjustment shall hear all appeals from decisions of the Fire Marshal made in the administration of the code, as described in Appendix B of the International Building Code as adopted by the City of Town and Country.
Sections 109.1 through 109.3. Delete.
110.4 Violation penalties (Amended): Persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in violation of the approved construction documents or directive of the Fire Code Official, or of a permit or certificate used under provisions of this code, shall be guilty of an ordinance violation, punishable by a fine of not more than one thousand dollars ($1,000.00) or by imprisonment not exceeding ninety (90) days, or both such fine and imprisonment. Each day that a violation continues after due notice has been served shall be deemed a separate offense.
112.4 Failure to comply (Amended): Any person who shall continue any work after having been served with a stop-work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be liable to a fine of not more than one thousand dollars ($1,000.00). Each day that a violation continues after due notice has been served shall be deemed a separate offense.
CHAPTER 2 DEFINITIONS
SECTION 202 GENERAL DEFINITIONS (Addition):
Term or Phrase
Meaning to Be Ascribed Thereto
Building Code
Article I of Chapter 500 of the Town and Country Municipal Code
Chief appointing authority
Mayor
Chief authority of the municipality
Mayor
City
City of Town and Country
Fire Department
The City's Fire Department
Fire Prevention Bureau
The Fire Department
Legal representative of the City
City Attorney or the City Prosecuting Attorney
Local jurisdiction
City of Town and Country
Residential Building Code
Article VII of Chapter 500 of the Town and Country Municipal Code
The jurisdiction
City of Town and Country
CHAPTER 5 FIRE SERVICE FEATURES
503.7 Design vehicle — apparatus (Addition): The design vehicle for the purposes of turning radii, access and other site plan considerations shall be the largest apparatus currently in service or under order by the West County EMS and Fire Protection District or any of its mutual aid partners; however, under no circumstances shall the design vehicle be smaller than a custom - manufacturer produce aerial ladder truck with tandem rear axles, a 105-foot platform, weighing at least ninety thousand (90,000) pounds and with dimensions of at least nine (9) feet wide, thirteen (13) feet six (6) inches in height and forty-five (45) feet in length.
507.5.7 Color coding of public fire hydrants (Addition): All public fire hydrants shall be painted yellow. All fire hydrant bonnets are to be painted as follows:
Color
Water Main Size
Green
12-inch and larger
Orange
8-inch and 10-inch
Red
6-inch and smaller
507.5.8 Color coding of private fire hydrants (Addition): All private fire hydrants shall be painted yellow, including the bonnet.
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES
704.2.1 Fire caulk (Addition): Wherever fire caulk is required as a fire block, fire stop or necessary to maintain the integrity of a wall rating, the fire caulk shall meet a UL 1479 or UL 2079 standard. Expended tubes must be maintained on a job site for inspection as part of any permit. If the inspector is unable to verity the product used, reapplication with a verified product may be required.
704.2.2 Fire foam (Addition): Fire foam may not be used as a fire block, fire stop or as part of any rated wall or building assembly.
CHAPTER 9 FIRE PROTECTION AND LIFE SAFETY SYSTEMS
903.5.1 Water flow tests (Addition): Water flow tests for automatic sprinkler systems shall be conducted between the hours of 9:00 A.M. and 4:30 P.M., Monday through Friday. Tests shall be within the last twelve (12) months.
903.7 Post indicator valves (Addition): All automatic sprinkler systems, except limited-area sprinkler systems, shall be provided with a post indicator valve that shall control the water supply to all automatic sprinkler systems in that building.
907.11 Monitoring (Addition): All fire alarm and detection systems shall be monitored by an approved central station as defined in NFPA 72. Effective January 1, 2015, the central station service shall be UL-listed for all new alarm installations or changes in alarm service provider for existing alarm systems.
Exception: Supervisory is not required for:
1. Single- and multiple-station smoke alarms required by Section 907.2.10.
2. Smoke detectors in Group I-3 occupancies.
3. Automatic sprinkler systems in one- and two-family dwellings.
907.12 Fire alarm automatic notification (Addition): Any commercial building with a fire alarm or fire-suppression system shall have a monitored fire alarm system that automatically notifies the monitoring service (and 911 Dispatch via that service) of the activation of the fire alarm, including specific details as to the nature of the alarm. The system shall also feature notification devices in all public areas of the building.
907.13 Qualifying systems (Addition): A fire alarm or fire suppression system shall be defined as any local fire alarm or extinguishment system regulated by the International Fire Code, including Type 1 hoods.
907.14 Remote annunciator (Addition): If a fire alarm panel is not installed in the immediate vicinity of the main public entrance, a remote annunciator shall be installed in the main lobby or in the immediate vicinity of the main public entrance. The remote annunciator shall be capable of full control of the alarm system, including viewing active alarms, trouble alarms and faults and shall be capable of silencing and resetting the alarm system.
907.15 Fully addressable alarm systems (Addition): All new installations of fire alarm systems shall feature a fully addressable alarm system identifying each detector by a description of its physical location.
907.16 Devices similar to fire alarm prohibited (Addition): No commercial building shall have any device or system not part of a monitored fire alarm system that provides audible and/or visual warning that could be reasonably mistaken for a fire alarm system or otherwise provide an indication that an automatic fire response is or will be underway.
907.17 Fire alarm dialer (Addition): All new installations of fire alarm systems and replacement of fire alarm panels shall feature a fire alarm dialer that is capable of transmitting detailed data to the alarm monitoring service, including the alarm type, alerting device location and a description of the device/and or nature of the specific alarm (i.e., smoke, heat, water flow, etc.).
907.18 Alarm transmission time defined (Addition): All fire alarm signals shall be transmitted to the remote monitoring service within ninety (90) seconds per NFPA 72-16. Additionally, the alarm service shall transmit the alarm signal, and all other identifying point information to Central County 911 Dispatch within ninety (90) seconds of the alarm monitoring service receipt of the alarm.
907.19 Pretest of alarm system (Addition): All fire alarm systems under permit for the modification or installation of a fire alarm system shall be pretested prior to requesting a final inspection. Signed pretest documentation shall be provided to the Fire Marshal upon their arrival for the final inspection. Failure to have the appropriate documentation will cancel the final alarm inspection and require rescheduling.
907.20 Signing (Addition): The room containing the fire alarm control panel (FACP) shall be clearly marked with a sign. The sign shall have the legend "FACP" in white letters six (6) inches in height on a red retro-reflective background. The sign shall be permanently affixed to the door on the room containing the FACP, the nearest exterior door providing access to the building from outside and on any doors and along any corridors leading between the exterior door and the room containing the FACP as necessary.
907.21 Trouble signals (Addition): A fire alarm that experiences a supervisory or trouble signal shall be serviced by a qualified technician within two (2) business days unless directed to be done sooner by the Fire Marshal.
912.8 Use groups R-3 and R-4 (Addition): There shall be no more than six (6) dwelling units constructed prior to the installation of a public water system with fire hydrants as set forth herein so as to be accessible for fire district use in the event of a fire emergency.
912.9 Other use groups (Addition): In all other use groups, public water systems with fire hydrants shall be installed with commencement of construction.
912.10 Fire hydrant placement (Addition): Fire hydrants shall be placed within the guidelines of Section 912.10 through 912.10.9.
912.10.1 Single-family residential (Addition): In Use Groups R-2 and R-4, single-family residential developments, fire hydrant spacing shall not exceed six hundred (600) feet from hydrant to hydrant, or as special site conditions may dictate.
912.10.1.1 Water supply required (Addition): In Use Groups R-3 and R-4 single-family developments, when the density is one (1) dwelling unit per ten thousand (10,000) square feet of developed property or less and there are five (5) or more dwelling units in a single development.
912.10.2 Multifamily residential(Addition): In Use Group R-2, multifamily residential developments, fire hydrant spacing shall not exceed four hundred (400) feet from hydrant to hydrant, or as special site conditions may dictate. Local conditions may be such that this distance may vary as much as seventy-five (75) feet to one hundred (100) feet in either direction.
912.10.2.1 Water supply required (Addition): In Use Group R-2 multifamily residential developments, when there are four (4) or more dwelling units within one (1) building or structure.
912.10.3 Other use group development (Addition): In all other use groups, fire hydrant spacing shall not exceed four hundred (400) feet from hydrant to hydrant, or as special site conditions may dictate. No part of a building shall be more than four hundred (400) feet from a fire hydrant. Local conditions may be such that the distance between fire hydrants or from a building to a fire hydrant may vary as much as seventy-five (75) feet to one hundred (100) feet in either direction, if otherwise approved by the Fire Marshal.
912.10.4 Area to be provided with fire hydrants (Addition): Fire hydrants and water mains shall be placed along the full length of the property to be developed that abuts an existing and/or proposed improved public way. Considerations may be required by the water agency because of water quality considerations.
912.10.5 Fire hydrants (Addition): Spacing of fire hydrants along a public way shall be regulated by the use group classification of the development that abuts the existing and/or proposed public way.
912.10.6 Private hydrants (addition): Where a development, other than Use Group R-3 or R-4, is greater than one hundred fifty (150) feet from an existing and/or proposed improved public way, measured along the drivable access, additional private fire hydrants shall be required on said developed property, private streets and/or parking lots, at a spacing between fire hydrants as required by the Use Group as set forth in Section 912.6.4.
912.10.7 No-parking area at fire hydrants (Addition): Where fire hydrants are required to be installed in areas where vehicles would be parked or standing, said vehicle parking or standing shall be restricted for ten (10) feet in each direction from the fire hydrant.
912.10.8 Unacceptable locations for fire hydrants (Addition): Fire hydrants shall not be permitted in the locations indicated in Section 912.6.8.1.
912.10.8.1 Prohibited locations (Addition): A fire hydrant shall not be placed at any location where the fire hydrant could be damaged by vehicular traffic.
912.10.9 Relocation of fire hydrants (Addition): Relocation of fire hydrants requested or required by a property owner and/or developer shall be located as specified by the water agency's policies and procedures and approved by the Fire Marshal.
912.11 Fire hydrant installation (Addition): All fire hydrants shall be installed in accordance with Sections 912.11.1 through 912.11.3.
912.11.1 Fire hydrant setback distance (Addition): All fire hydrants shall be set back from the curb or edge of payment. The setback exceeds twelve (12) feet.
912.11.2 Fire Hydrant connection height (Addition): Fire hydrants shall be installed a minimum of fourteen (14) inches and maximum of thirty-six (36) inches above finished grade, measured from the center of the steamer connection.
912.11.3 Fire hydrant type (Addition): All fire hydrants shall be approved by the American Water Works Association (AWWA) and/or Missouri American Water.
912.12 Obstructions (Addition): There shall be no obstructions, plantings, bushes, trees, signs, light standards, etc., within six (6) feet of any fire hydrant in all directions.
912.13 Minimum fire flow - single hydrant (Addition): The minimum fire flow from a single fire hydrant in any use group shall be one thousand five hundred (1,500) gallons per minute at twenty (20) psi residual pressure unless the new hydrant is ordered on a preexisting main.
912.14 Minimum fire flow - next two (2) hydrants (Addition): The minimum fire flow from the next two (2) fire hydrants in any use group shall be a cumulative one thousand five hundred (1,500) gallons per minute at twenty (20) psi residual pressure.
912.15 Size (Addition): Fire Department connections (FDC) shall consist of a five-inch Storz connection into a minimum five-inch piping system. The piping system from the FDC to the main sprinkler system piping shall be a minimum of five (5) inches in diameter. The Storz connection shall be installed on a thirty-degree angle.
912.16 Location (Addition): Fire Department connections (FDC) shall be located no more than seventy-five (75) feet from a hydrant capable of a minimum flow of one thousand five hundred (1,500) GPM and shall be located no more than ten (10) feet from a paved surface capable of supporting a ninety-thousand-pound aerial fire apparatus.
912.17 Walkway (Addition): A walkway shall be provided between the paved apparatus access and the FDC. The walkway shall be of hot-placed asphalt pavement or of poured-in-place concrete and shall be a minimum of thirty-six (36) inches in width.
912.18 Visibility (Addition): The Fire Department connection (FDC) shall be clearly marked with a sign. The sign shall have the legend "FDC" in white letters six (6) inches in height on a red retro-reflective background. The sign shall be permanently affixed to the building above the FDC. The FDC shall be visible from the apparatus access area and shall not be obstructed by any landscaping or other concealment device.
912.19 Residual pressure (Addition): Fire flow demand calculations shall require a twenty percent (20%) reserve at system design demand; however, the residual shall be at least twenty (20) psi. The Fire Marshal may require a higher residual at their discretion if special circumstances warrant.
912.20 Fire main definition (Addition): Any water main installed as part of any public or private construction project that directly serves one (1) or more fire sprinkler systems shall be considered a fire main and shall be installed and inspected to NFPA standards.
912.20.1 Fire main sizing (Addition): Fire mains shall be sized according to required demand; however, no fire main shall be sized less than as required below without specific approval from the Fire Marshal.
912.20.2 Fire main tied-in at 2 or more locations (Addition): Fire mains tied into the Missouri American water system at two (2) or more locations shall use a minimum six-inch-diameter pipe.
912.20.3 Fire mains tied-in at 1 location (Addition): Fire mains tied into the Missouri American water system at only one (1) location shall use a minimum of eight-inch-diameter pipe.
912.20.4 Fire mains not to connect to smaller service main (Addition): Fire mains required to be sized at a certain minimum size shall not be supplied from water service mains of a smaller diameter.
APPENDIX
Appendix A - Delete
Appendix B - Delete
Appendix C - Delete
APPENDIX D FIRE APPARATUS ACCESS ROADS
D102.1 Access and loading (Amended): Facilities, buildings or portions of buildings hereafter constructed shall be accessible to fire department apparatus by way of an approved fire apparatus access road with an asphalt, concrete or other approved driving surface capable of supporting the imposed load of fire apparatus weighing up to ninety thousand (90,000) pounds.
D102.2 Fire lane designation (Addition): Fire lanes shall be located as necessary to ensure access for fire and emergency medical services. Fire lanes shall be designated by the Fire Marshal. Fire lanes must be maintained to full compliance for any adjacent buildings to pass new occupancy and/or annual inspection.
D102.3 Maintenance and repair (Addition): It shall be the responsibility of the property owner to install and maintain fire lanes. Active pavement and/or curb repairs shall have the markings restored upon completion of repair work; however, no fire lane markings shall be absent for more than thirty (30) calendar days due to repairs.
D103.3.1 Culs-de-sac (Addition): New public and private residential streets with a cul-de-sac less than ninety-six (96) feet in diameter shall be built without any island, median or other obstruction in the center of the cul-de-sac.
D103.5 Fire apparatus access road gates (Amended): Gates meeting the conditions described hereinafter may be accepted from the application of D103.5.1. In such case a developer, owner, Board of Trustees, may install a gate if first approved by the Fire Marshal. Gates securing the fire apparatus access roads shall comply with all of the following criteria:
1. That the gate to be erected is at least forty (40) feet back from the edge of the cross street from which access to the gated road is obtained.
2. The minimum gate width shall be twenty (20) feet or have net clear opening of twelve (12) feet for single-lane access.
3. Gates shall be of the swinging or sliding type. Construction of gates shall be of materials that allow manual operation by one (1) person from the public side of the gate.
4. Gate components shall be maintained in an operative condition at all times and replaced or repaired when defective.
5. Manual opening gates shall not be locked with a padlock or chain and padlock unless they are capable of being opened by means of a Fire Department Master Key - Rapid Entry Knox System.
6. Locking device specifications shall be submitted for approval by the Fire Marshal.
7. Electric gates shall be equipped with a means of opening the gate by Fire Department personnel for emergency access. Emergency opening devices shall be approved by the Fire Marshal.
8. That the developer and/or Board of Trustees, its successors and assigns of the subdivision install an entry-operated switch through the Knox-Box® System, known as a "rapid entry system," approved by the Fire Marshal.
9. All developers or trustees shall install a lock box of adequate size so that all keys needed to gain access to the exterior and interior designated areas (such areas designated for common use and/or all service equipment areas) shall be accessible at all times. Owners shall clearly mark all keys within the lock box and shall indicate doors to which such keys belong. All tags, marking systems, location and size of lock box, shall be at the discretion of and with the approval of the Fire Marshal.
10. The developer or trustee of said development shall install the lock box system according to the manufacturers' recommendations and direction, and at the direction and approval of the Fire Marshal.
11. The developer or trustee of said development shall be responsible for any key changes and additions to the plan, or plat filed with the Fire Marshal, and it shall be the responsibility of the owner to notify the Fire Marshal, in writing, of any changes or additions required in or to the lock box.
12. The cost of purchase, installation and maintenance of the lock box security system shall be the responsibility of the developer and/or trust of the subdivision.
13. That the gate shall have installed a power failure override and spring design system which will open the gates in the event of an electric power failure and/or pull pin system.
14. That the developer or Board of Trustees of the subdivision shall agree to keep the gates open at all times during inclement weather.
15. That the developer or Board of Trustees of the subdivision agrees to incorporate and adopt in their indenture of subdivision restrictions a provision accepted by the City. The provision must hold the City, its agents and employees harmless from any and all liability as a result of increased response time directly resulting from the gated community and the system described and/or damage to gates in answering of an emergency call. The maintenance and cost of repair of the gates and supplies shall be at the sole cost of the subdivision.
16. To provide a means to manually release the gate from the electronically operated mechanism.
17. The trustees and/or property management shall notify the City of any change in the trustees or property management company.
D103.7 Street obstructions (Addition): No person shall erect, construct, place or maintain any bumps, humps, fences, bars, pipes, wood or metal horse or any other type of obstruction in or upon any street within the City.
D103.7.1 Exception for traffic-calming devices as part of engineering study (Addition): Where a private street or road exhibits a significant traffic safety concern, traffic-calming devices may be allowed at the discretion of the Fire Marshal subject to the following:
A. A traffic study has been performed by a licensed professional traffic operations engineer.
B. The study is sealed by the same who shall be a licensed professional engineer in the State of Missouri.
C. The traffic study identifies one (1) or more specific problems, as verified through engineering study, where traffic-calming devices are proposed by the traffic engineer as a likely solution.
D. The installation and maintenance of the traffic-calming devices is to be performed by a municipal, county or State agency under whose jurisdiction the maintenance of the driving surface lies.
E. The responsible agency agrees to remove the traffic-control devices if the fire district finds that the devices adversely affect the fire district's ability to provide adequate EMS and fire protection services due to physical damage to the fire district equipment or inability to adequately navigate the device(s) or retain access to property.
F. The devices do not require personnel to stop and exit the response apparatus to open, move or otherwise adjust the traffic-calming device(s).
G. The devices do not create a physical obstruction that would damage apparatus.
H. The installation of devices at any given location shall not automatically approve or qualify installation of similar devices at any other location within the City.
D105.5 Rooftop access (Addition): All buildings with at least one side elevation of less than seventy (70) feet, as measured from the ground to the top edge of any wall, roof or other building assembly shall have a location designated for aerial apparatus rooftop access.
D105.6 Paved access (Addition): The property shall feature a location on the paved parking/driving area or accessed from the paved parking/driving area that is designated an "aerial ladder access" location. The designated area shall be able to accommodate an aerial apparatus fifty (50) feet in length, twenty (20) feet in width and capable of supporting a tandem drive axle apparatus with a gross weight of ninety thousand (90,000) pounds. The location shall be such that the aerial turntable of the apparatus is no more than forty-five (45) feet from the side of the building. The location may be part of the driveway, loading area or other paved driving surface but shall not be a location where vehicles are allowed to be parked and left unattended for any amount of time.
D105.7 Marking (Addition): The aerial apparatus access location shall be marked with a twelve-inch-by-eighteen-inch sign, with a legend of "Aerial Ladder Access" consisting of white letters and border on a red retro-reflective background. Additionally, the location of the center line of the aerial apparatus turntable shall be marked with a painted or epoxy thermoplastic four-inch red strip placed horizontally across the pavement.
D105.8 Rooftop ladder landing (Addition): There shall be an established rooftop ladder landing location on the flat roof of any building where the top edge of the building measures seventy (70) feet or less from the adjacent ground surface to receive the ladder from the aerial apparatus at the designated access area as designated by the Fire Marshal.
D105.8.1 Delineation (Addition): The landing shall be delineated by two (2) permanently affixed red posts, a minimum of eighteen (18) inches tall as measured from the top of outermost edge of the roof to the top of the posts, and wrapped in red retro-reflective sheeting. The posts shall be flexible delineation posts as typically found on highway or aviation taxiway systems and shall give or bend if they come into contact with the aerial ladder. The posts shall be placed six (6) feet apart (center to center) on the edge of the building roof or parapet wall and shall be clearly visible from the ground level.
D105.8.2 Landing platform (Addition): On any building with a parapet wall that extends more than six (6) inches above the plane of the roof, a platform shall be built as a landing area for egress from the aerial ladder. The platform shall be a minimum of six (6) feet wide by six (6) feet long and shall extend between the delineation posts required in Section D105.5.9. The platform shall feature a handrail on at least one side that extends forty-two (42) inches above the platform landing and stairs.
D105.8.3 Materials (Addition): The landing shall be made of metal. All standing, walking and landing stairway surfaces shall be made of diamond safety grating punched metal tread plate.
D105.8.4 Stairway access to land platform (Addition): Any elevated landing platform shall be accessed from the rooftop surface by stairs conforming to the 2018 International Building Code.
D105.8.5 Securement (Addition): Any landing and stairway access shall be permanent affixed to the roof by bolted or welded connections.
D105.8.6 Roof edge suitable for aerial ladder (Addition): The edge of the roof or parapet wall at the identified aerial ladder landing area shall be built of a material that can accommodate the placement of the aerial ladder gently against the building without damaging the building or aerial apparatus.
[Ord. No. 3435 §§1—3, 6-9-2009; Ord. No. 3837 §§1 — 3, 9-8-2014]
Nothing in this Article or in the code hereby adopted shall be construed to affect any suit or proceeding impending in any court, or any rights acquired, or liability incurred, or any cause or causes of action acquired or existing, under any act or ordinance hereby repealed as cited in Section 220.135 of this Article; nor shall any just or legal right or remedy of any character be lost, impaired or affected by this Article.
[Ord. No. 3435 §§1—3, 6-9-2009; Ord. No. 3837 §§1 — 3, 9-8-2014]
All other ordinances or parts of ordinances in conflict herewith are hereby repealed.
[Ord. No. 3435 §§1—3, 6-9-2009; Ord. No. 3837 §§1 — 3, 9-8-2014]
Any person who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, construct, alter or repair a building or structure in violation of an approved plan of or directive of the Code Official, or of a permit or certificate issued under the provision of this code, shall be guilty of an ordinance violation, punishable by a fine of not more than one thousand dollars ($1,000.00) or by imprisonment not exceeding ninety (90) days, or both such fine and imprisonment. Each day that a violation continues after due notice has been served shall be deemed a separate offense.