Exciting enhancements are coming soon to eCode360! Learn more 🡪
City of Poplar Bluff, MO
Butler County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[R.O. 2007 §37-103; Ord. No. 5130 §2, 10-5-1987]
As used in this Article, the following terms shall have these prescribed meanings:
AIR-GAP SEPARATION
The unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture or other device and the flood level rim of the receptacle and shall be at least double the diameter of the supply line pipe measured vertically above the flood level rim of the vessel. In no case shall the gap be less than one (1) inch.
AUXILIARY SUPPLY
Any water source or system, other than the public water supply, that may be available in the building or premises or which is not a water supply approved by the Missouri Division of Health.
BACK PRESSURE
Backflow caused by a pump, elevated tank, boiler or other means that could create pressure within the system greater than the supply pressure.
BACK SIPHONAGE
A form of backflow due to a negative or subatmospheric pressure within a water system.
BACKFLOW
The flow, other than the intended direction of flow, of any foreign liquids, gases or substances into the distribution system of the public water supply.
BACKFLOW PREVENTION DEVICE
A device to counteract back pressures or prevent back siphonage.
CROSS-CONNECTION
Any physical arrangement whereby a public water supply is connected directly or indirectly with any other water supply system, sewer, drain, conduit, pool, storage reservoir, plumbing fixture or other device which contains or may contain contaminated water, sewage or other waste or liquid of unknown or unsafe quality which may be capable of imparting contamination to the public water supply as a result of backflow. By-pass arrangements, jumper connections, removal of section, swivel or changeover devices and other temporary or permanent devices through which or because of which backflow could occur are considered to be cross-connections.
DOUBLE-CHECK VALVE ASSEMBLY
An assembly composed of two (2) single, independently acting check valves, including tightly closing shutoff valves located at each end of the assembly and suitable connections for the in-line testing of the water-tightness of each check valve.
PUBLIC WATER SUPPLY
Any system of water supply intended for human consumption or other domestic uses, including source, treatment, storage, transmission and distribution facilities, where water is furnished to any community, collection or number of individuals or is made available to the public for human consumption or domestic use, but excluding water supplied serving one (1) single-family residence.
REDUCED PRESSURE PRINCIPAL BACKFLOW PREVENTION DEVICE
A device incorporating two (2) or more check valves and an automatically operating differential relief valve located between the two (2) checks, two (2) shutoff valves and equipped with necessary appurtenances for in-line testing. The device shall operate to maintain the pressure in the zone between the two (2) check valves, less than the pressure on the public water supply side of the device. At cessation of normal flow, the pressure between the check valves shall be less than the supply pressure. In case of leakage of either check valve, the differential relief valve shall operate to maintain this reduced pressure by discharging to the atmosphere. When the inlet pressure is two (2) pounds per square inch or less, the relief valve shall open to the atmosphere, thereby providing an air-gap in the device.
[R.O. 2007 §37-104; Ord. No. 5130 §2, 10-5-1987; Ord. No. 5963 §1, 3-17-1997]
A. 
The purpose of this Article is to establish a cross-connection control program to protect the health of water consumers by the control of actual and/or potential cross-connections through the proper installation and surveillance of backflow prevention devices on service lines leading to premises where cross-connections exist or are likely to occur and through the inspection and regulation of the plumbing within the premises to minimize danger of contamination of the water system on the premises or the public water supply itself.
B. 
All cross-connections, whether or not such cross-connections are controlled by automatic devices, such as check valves or by hand-operated mechanisms such as gate valves or stopcocks, are hereby prohibited.
C. 
Failure on the part of persons, firms or corporations to discontinue the use of any and all cross-connections and to physically separate such cross-connections will be sufficient cause for the discontinuance of the public water service to the premises on which the cross-connection exists.
D. 
Persons bearing proper credentials and identification shall make annual inspections of premises served by the water supply of the City to check for the presence of cross-connections. Documentation of the annual inspection shall be submitted to the Superintendent of Water Distribution, on the proper form, within ten (10) business days from the date of initial installation or annual inspection. Should such a cross-connection be found, the City, giving the customer not less than fifteen (15) days' notice of its intention, will discontinue service. If an immediate hazard to health is caused by the cross-connection, water service to the premises shall be discontinued until it is verified that the cross-connection has been removed. The Superintendent or other duly authorized employee of the Poplar Bluff Water and Sewer Department may make periodic inspections of premises served by the water supply to check for the presence of cross-connections.
[R.O. 2007 §37-105; Ord. No. 5130 §2, 10-5-1987]
A. 
Backflow prevention devices shall be installed at the service connection or within any premises wherein the judgment of the Superintendent, the nature and extent of activities on the premises or the materials used in connection with the activities or materials stored on the premises would present an immediate hazard to health should a cross-connection occur, even though such cross-connection does not exist at the time the backflow prevention device is required to be installed. This shall include, but not be limited to, the following situations:
1. 
Premises having an auxiliary water supply, unless the quality of the auxiliary supply is in compliance with local standards and is acceptable to the Superintendent;
2. 
Premises having internal cross-connections that are not correctable or intricate plumbing arrangements which make it impractical to ascertain whether or not cross-connections exist;
3. 
Premises where entry is restricted so that inspections for cross-connections cannot be made with sufficient frequency or at sufficiently short notice to assure that cross-connections do not exist;
4. 
Premises having a repeated history of cross-connections being established or re-established;
5. 
Premises on which any substance is handled under pressure so as to permit entry into the public water supply or where a cross-connection could reasonably be expected to occur. This shall include the handling of process waters and cooling waters;
6. 
Premises where materials of a toxic or hazardous nature are handled such that, if back siphonage should occur, a serious health hazard may result;
7. 
The following types of facilities will fall into one (1) of the above categories where a backflow prevention device is required to protect the public water supply. A backflow prevention device shall be installed at these facilities, unless the Superintendent determines no hazard exists.
Auxiliary water systems;
Chemical plants using a water process;
Cooling systems;
Farming operations;
Film processing equipment;
Fire protection systems;
Food or beverage processing plants;
Hospitals, mortuaries, clinics;
Irrigation systems;
Laboratories;
Laundry and dyeing facilities;
Metal-plating industries;
Paper processing plants;
Petroleum processing or storage plants;
Radioactive material processing plants or nuclear reactors;
Sewage treatment plants;
Sprinkler systems filled with antifreeze solution;
Steam generating systems.
Storage tanks, cooling towers and circulating systems.
[R.O. 2007 §37-106; Ord. No. 5130 §2, 10-5-1987]
The type of protective device required shall be determined by the Superintendent and shall depend on the degree of hazard which exists.
[R.O. 2007 §37-107; Ord. No. 5130 §2, 10-5-1987]
A. 
An air-gap separation or a reduced pressure principal backflow prevention device shall be installed where the water supply may be contaminated with sewage, industrial waste of a toxic nature or other contaminant which would cause a health or system hazard.
B. 
In case of a substance which may be objectionable but not hazardous to health, a double-check valve assembly, air-gap separation or a reduced pressure principle backflow prevention device shall be installed.
[R.O. 2007 §37-108; Ord. No. 5130 §2, 10-5-1987]
A. 
Backflow prevention devices required by this Article shall be installed at a location and in a manner approved by the water Superintendent and shall be installed at the expense of the water consumer.
B. 
Backflow prevention devices shall be installed at the meter or at a location designated by the Superintendent. The device shall be located so as to be readily accessible for maintenance and testing and where no part of the device will be submerged.
[R.O. 2007 §37-109; Ord. No. 5130 §2, 10-5-1987]
Any protective device required in this Article shall be a model approved by the Superintendent.
[R.O. 2007 §37-110; Ord. No. 5130 §2, 10-5-1987]
Backflow prevention devices shall be inspected and tested annually by the Superintendent or other duly authorized employees of the City bearing proper credentials and identification or more often where successive inspections indicate repeated failure. The devices shall be repaired, overhauled or replaced at the customer's expense whenever they are found to be defective.
[R.O. 2007 §37-111; Ord. No. 5130 §2, 10-5-1987]
Failure of the customer to cooperate in the installation, maintenance, testing or inspection of backflow prevention devices required in this Article shall be grounds for the termination of water services to the premises.