[Amended 6-2004 by Ord. No. 10-2004; 2-13-2007 by Ord. No. 2-2007; 7-26-2016 by Ord. No. 4-2016; 3-14-2023 by Ord. No. 3-2023]
(A) 
The Illinois Plumbing Code, as promulgated by the Illinois Department of Public Health at 77 Ill. Adm. Code Part 890, with amendments to March 1, 2023, is hereby adopted as the Plumbing Code of the City with the following changes, additions or insertions:
(1) 
Appendix A, Table A: All materials shall meet the following requirements or be approved by the Building Commissioner.
(a) 
Approved Materials for Water Service Pipe shall be as permitted by Table 29 (18-29-605.4) of the Chicago Plumbing Code.
(b) 
Approved Materials for Water Distribution Pipe shall be as permitted by Table 29 (18-29-605.5) of the Chicago Plumbing Code.
(c) 
Approved Standards for Fittings shall be as permitted by Table 29 (18-29-605.6) of the Chicago Plumbing Code.
No person shall contract for plumbing and no plumbing contractor shall do plumbing work in the City of Hometown unless he shall be currently certified as a "certified plumbing contractor" by the State of Illinois under the Illinois Plumbing License Law (225 ILCS 320/0.01 et seq.). No person and no employee of a certified plumbing contractor shall engage in plumbing work in the City unless he shall be licensed as a plumber or apprentice in accordance with the Illinois Plumbing License Law.
[1]
Editor's Note: Amended at time of adoption of Code (see Ch. 30, General Provisions, Art. 2).
All plans for the installation, removal, alteration or repair of plumbing work in the City shall be inspected by a certified plumbing contractor or licensed plumber licensed by the State of Illinois under the jurisdiction and supervision of the Building Commissioner.
(A) 
In addition to the building permit fees provided by § 21.30 of this Building Code and other charges required under this code, the certified plumbing contractor shall, at the time the permit is issued for the plumbing work, pay a minimum fee of $75 for up to three fixtures, including, but not limited to, hot water tanks, washer and dryer drains, whirlpools, hot tubs and double vanities (which count as two fixtures) for residential units for the approval of plans, inspection, and testing of plumbing work. An additional fee of $25 per fixture shall be paid for every fixture over the minimum. In commercial buildings, there will be a minimum fee of $150 for up to three fixtures, with a fee of $50 for each additional fixture.
[Amended 4-25-2006 by Ord. No. 5-2006]
(B) 
No person shall do any work without a permit and no permit shall be issued unless the applicant is qualified under this code to receive and the permit fees paid.
[Amended 4-25-2006 by Ord. No. 5-2006]
Where extra inspections are made because of inaccurate or incorrect information, failure to make necessary repairs or faulty construction, a charge of $25 shall be made for each such inspection.
All applications shall be in the name of a certified plumbing contractor and his PCC number shall be stated on the application. It shall be unlawful for any such certified plumbing contractor to allow his name to be used by any other person, directly or indirectly, for the purpose of obtaining a permit or to do plumbing work. It shall be unlawful for any person to represent that he is doing plumbing work for a certified plumbing contractor when he has not been authorized by a certified plumbing contractor to do so.
The Manual of Procedures for the Administration of the Sewer Permit Ordinance as adopted by the Metropolitan Water Reclamation District, and the whole thereof, of which not less than three copies have been and now are on file in the office of the Clerk, is hereby adopted as an integral part of the procedures for the administration of sanitary sewer permits.
All new buildings with basements, floors, rooms or occupancy areas below ground level at the building site, and served by a public or private sewer system, shall have overhead plumbing. No building permit application will be accepted nor any permits issued for construction of any structure unless plans and specifications therefor provide for such overhead plumbing.
Roof drains, foundation footing drains, parking and paved lot or area drains, groundwater drains or surface water connections to the sanitary sewer system are strictly forbidden in all areas. Footing drains shall be connected to sump pumps for further discharge into the storm sewer or drainage ditches.
No filling shall be done without a permit and no filling shall be permitted which may adversely affect the efficiency or the capacity of the floodway or increase flood heights. All filling shall be compensated for by at least an equal volume of excavation in or contiguous to the floodplain so that the volume available for storing and moving floodwaters below the high water elevation shall not be reduced. The term "filling" as used here shall mean structures, temporary or permanent, fill, including fills for roads and levies, deposits, obstructions, storage of material, or other floodplain areas.
[Amended 9-8-2015 by Ord. No. 10-2015]
The Plumbing Code referred to in § 21.130 is hereby amended to include the following modifications or additions, which shall supersede all similar regulations in the case of conflicting provisions:
(A) 
All new water services shall be metered. All new and replacement plumbing fixtures shall be labeled as a WaterSense® product, as specified by the United States Environmental Protection Agency (USEPA).
(B) 
No potable water shall be used for the flushing of main-line sanitary sewers.
(C) 
Water-saving plumbing fixtures shall be installed as follows:
(1) 
In all new construction and in all repair and replacement of fixtures or trim, only fixtures and trim not exceeding the following flow rates and water usage shall be installed. These ratings are based on a pressure at the fixture of 40 psi to 50 psi.
(a) 
Water closets, tank type: 3.5 gallons per flush.
(b) 
Water closets, flushometer type: 3.0 gallons per flush.
(c) 
Urinals, tank type: 3.0 gallons per flush.
(d) 
Urinals, flushometer type: 3.0 gallons per flush.
(e) 
Shower heads: 3.0 gallons per minute.
(f) 
Lavatory, sink faucets: 3.0 gallons per minute.
(2) 
Lavatories for public use. In addition to the requirements of Subsection (A) above, in all new construction and replacement of fixtures, faucets of lavatories located in rest rooms, intended for public use, shall be of a metering or self-closing type.
(3) 
Car wash installation. In all new construction and replacement of fixtures, car-wash installations shall be equipped with a water recycling system.
(4) 
Air-conditioning systems. Closed air-conditioning systems shall be installed on all new construction or new remodeling.
(A) 
General policy.
(1) 
Purpose. The purpose of these rules and regulations is:
(a) 
To protect the public water supply system from contamination or pollution by isolating within the customer's water system contaminants or pollutants which could backflow through the service connection into the public water supply system.
(b) 
To promote the elimination or control of existing cross-connections, actual or potential, between the public or consumer's potable water system and nonpotable water systems, plumbing fixtures and sources or systems containing substances of unknown or questionable safety.
(c) 
To provide for the maintenance of a continuing program of cross-connection control which will prevent the contamination or pollution of the public and consumer's potable water systems.
(2) 
Application. These rules and regulations shall apply to all premises served by the public potable water supply system of the City.
(3) 
Policy. The owner or official custodian shall be responsible for protection of the public water supply system from contamination due to backflow or backsiphonage of contaminants through the customer's water service connection. If, in the judgment of the Director of Public Works (hereinafter referred to as "Director") or his authorized representative, the City's Plumbing Inspector, an approved backflow prevention device is necessary for the safety of the public water supply system, the Director shall give notice to the customer to install such approved backflow prevention device at each service connection to the premises. The consumer shall immediately install such approved device or devices at his own expense; failure, refusal or inability on the part of the consumer to install such device or devices immediately shall constitute grounds for discontinuing water service to the premises until such device or devices have been installed. The consumer shall retain records of installation, maintenance, testing and repair as required in Subsection (E)(4)(d) below for a period of at least five years. The Director may require the consumer to submit a cross-connection inspection report to the City's Department of Public Works to assist in determining whether or not service line protection will be required. All cross-connection inspections shall be conducted by a Cross-Connection Control Device Inspector certified by the Illinois Environmental Protection Agency.
(B) 
Definitions. The following definitions shall apply in the interpretation and enforcement of these regulations:
AGENCY
The Illinois Environmental Protection Agency.
APPROVED
Backflow prevention devices or methods approved by the Foundation for Cross-Connection Control and Hydraulic Impacts of the University of Southern California Association of State Sanitary Engineers, American Water Works Association, American National Standards Institute or certified by NSF International.[1]
AUXILIARY WATER SYSTEM
Any water source or system on or available to the premises other than the public water supply system and includes the water supplied by the system. These auxiliary waters may include water from another purveyor's public water supply system; or water from a source such as wells, lakes, or streams, or process fluids; or used water. These waters may be polluted or contaminated or objectionable or constitute a water source or system over which the water purveyor does not have control.
BACKFLOW
The flow of water or other liquids, mixtures, or substances into the distribution pipes of a potable water system from any source other than the intended source of the potable water supply.
BACKFLOW PREVENTION DEVICE
Any device, method, or type of construction intended to prevent backflow into a potable water system. All devices used for backflow prevention in Illinois must meet the standards of the Hometown Plumbing Code and the Illinois Environmental Protection Agency.[2]
CONSUMER or CUSTOMER
The owner, official custodian or person in control of any premises supplied by or in any manner connected to a public water system.
CONSUMER'S WATER SYSTEM
Any water system located on the consumer's premises. A building plumbing system is considered to be a customer's water system.
CONTAMINATION
An impairment of the quality of the water by entrance of any substance to a degree which could create a health hazard.
CROSS-CONNECTION
Any physical connection or arrangement between two otherwise separate piping systems, one of which contains potable water and the other a substance of unknown or questionable safety or quality, whereby there may be a flow from one system into the other.
DIRECT CROSS-CONNECTION
A cross-connection formed when a water system is physically joined to a source of unknown or unsafe substance.
DOUBLE CHECK VALVE ASSEMBLY
An assembly composed of single, independently acting check valves approved under ASSE Standard 1015. A double check valve assembly must include tight shutoff valves located at each end of the assembly and suitable connections for testing the watertightness of each check valve.
FIXED PROPER AIR GAP
The unobstructed vertical distance through the free atmosphere between the water discharge point and the flood level rim of the receptacle.
HEALTH HAZARD
Any condition, device or practice in a water system or its operation resulting from a real or potential danger to the health and well-being of consumers. The word "severe" as used to qualify "health hazard" means a hazard to the health of the user that could be expected to result in death or significant reduction in the quality of life.
INDIRECT CROSS-CONNECTION
A cross-connection through which an unknown substance can be forced, drawn by vacuum or otherwise introduced into a safe potable water system.
INSPECTION
A plumbing inspection to examine carefully and critically all materials, fixtures, piping and appurtenances, appliances and installations of a plumbing system for compliance with requirements of the Hometown Plumbing Code.
NONPOTABLE WATER
Water not safe for drinking, personal, or culinary use as determined by the requirements of the Illinois Environmental Protection Agency.[3]
PLUMBING
The actual installations repair, maintenance, alteration or extension of a plumbing system by any person. Plumbing includes all piping, fixtures, appurtenances and appliances for a supply of water for all purposes, including without limitation lawn sprinkler systems, from the source of a private water supply on the premises or from the main in the street, alley or at the curb to within and about any building or buildings where a person or persons live, work or assemble. Plumbing includes all piping, from discharge of pumping units to and including pressure tanks in water supply systems. Plumbing includes all piping, fixtures, appurtenances, and appliances for a building drain and a sanitary drainage and related ventilation system of any building or buildings where a person or persons live, work or assemble, from the point of connection of such building drain to the building sewer or private sewage disposal system five feet beyond the foundation walls.
POLLUTION
The presence of any foreign substance (organic, inorganic, radiological, or biological) in water that tends to degrade its quality so as to constitute a hazard or impair the usefulness of the water.
POTABLE WATER
Water which meets the requirements of the Illinois Environmental Protection Agency for drinking, culinary, and domestic purposes.[4]
POTENTIAL CROSS-CONNECTION
A fixture or appurtenance with threaded hose connection, tapered spout, or other connection which would facilitate extension of the water supply line beyond its legal termination point.
PROCESS FLUID(S)
Any fluid or solution which may be chemically, biologically or otherwise contaminated or polluted in a form or concentration such as would constitute a health, pollutional, or system hazard if introduced into the public or a consumer's potable water system. This includes, but is not limited to:
(1) 
Polluted or contaminated waters;
(2) 
Process waters;
(3) 
Used waters originating from the public water supply system which may have deteriorated in sanitary quality;
(4) 
Cooling waters;
(5) 
Questionable or contaminated natural waters taken from wells, lakes, streams, or irrigation systems;
(6) 
Chemicals in solution or suspension;
(7) 
Oils, gases, acids, alkalis and other liquid and gaseous fluids used in industrial or other processes or for fire-fighting purposes.
PUBLIC WATER SUPPLY
All mains, pipes and structures through which water is obtained and distributed to the public, including wells and well structures, intakes and cribs, pumping stations, treatment plants, reservoirs, storage tanks and appurtenances, collectively or severally, actually used or intended for use for the purpose of furnishing water for drinking or general domestic use and which serve at least 15 service connections or which regularly serve at least 25 persons at least 60 days a year. A public water supply is either a "community water supply" or a "non-community water supply."
REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION DEVICE
A device containing a minimum of two independently acting check valves together with an automatically operated pressure differential relief valve located between the two check valves and approved under ASSE Standard 1013. During normal flow and at the cessation of normal flow, the pressure between these two checks shall be less than the supply pressure. In case of leakage of either check valve, the differential relief valve, by discharging to the atmosphere, shall operate to maintain the pressure between the check valves at less than the supply pressure. The unit must include tightly closing shutoff valves located at each end of the device, and each device shall be fitted with properly located test cocks.
SERVICE CONNECTION
The opening, including all fittings and appurtenances at the water main through which water is supplied to the user.
SURVEY
The collection of information pertaining to a customer's piping system regarding the location of all connections to the public water supply system and must include the location, type and most recent inspection and testing date of all cross-connection control devices and methods located within that customer's piping system. The survey must be in written form and should not be an actual plumbing inspection.
SYSTEM HAZARD
A condition through which an aesthetically objectionable or degrading material not dangerous to health may enter the public water supply system or a customer's potable water system.
USED WATER
Any water supplied by a public water supply system to a customer's water system after it has passed through the service connection and is no longer under the control of the water supply official custodian.
WATER PURVEYOR
The owner or official custodian of a public water system.
[1]
Editor's Note: Amended at time of adoption of Code (see Ch. 30, General Provisions, Art. 2).
[2]
Editor's Note: Amended at time of adoption of Code (see Ch. 30, General Provisions, Art. 2).
[3]
Editor's Note: Amended at time of adoption of Code (see Ch. 30, General Provisions, Art. 2).
[4]
Editor's Note: Amended at time of adoption of Code (see Ch. 30, General Provisions, Art. 2).
(C) 
Water system.
(1) 
The water system shall be considered as made up of two parts: the public water supply system and the consumer's water system.
(2) 
The public water supply system shall consist of the source facilities and the distribution system, and shall include all those facilities of the potable water system under the control of the Director up to the point where the consumer's water system begins.[5]
[5]
Editor's Note: Amended at time of adoption of Code (see Ch. 30, General Provisions, Art. 2).
(3) 
The source shall include all components of the facilities utilized in the production, treatment, storage, and delivery of water to the public water supply distribution system.
(4) 
The public water supply distribution system shall include the network of conduits used to deliver water from the source to the consumer's water system.
(5) 
The consumer's water system shall include all parts of the facilities beyond the service connection used to convey water from the public water supply distribution system to points of use.
(D) 
Cross-connection prohibited.
(1) 
Connections between potable water systems and other systems or equipment containing water or other substances of unknown or questionable quality are prohibited except when and where approved cross-connection control devices or methods are installed, tested and maintained to ensure proper operation on a continuing basis.
(2) 
No physical connection shall be permitted between the potable portion of a supply and any other water supply not of equal or better bacteriological and chemical quality as determined by inspection and analysis by the Agency.
(3) 
There shall be no arrangement or connection by which an unsafe substance may enter a supply.
(E) 
Survey and investigations.
(1) 
The consumer's premises shall be open at all reasonable times to the approved cross-connection control device inspector for the inspection of the presence or absence of cross-connections within the consumer's premises, and testing, repair and maintenance of cross-connection control devices within the consumer's premises.
(2) 
On request by the Director or his authorized representative, the consumer shall furnish information regarding the piping system or systems or water use within the customer's premises. The consumer's premises shall be open at all reasonable times to the Director for the verification of information submitted by the inspection consumer to the public water supply custodian regarding cross-connection inspection results.
(3) 
It shall be the responsibility of the water consumer to arrange periodic surveys of water use practices on his premises to determine whether there are actual or potential cross-connections to his water system through which contaminants or pollutants could backflow into his or the public potable water system. All cross-connection control or other plumbing inspections must be conducted in accordance with all relevant statutes and regulations.
(4) 
It is the responsibility of the water consumer to prevent backflow into the public water system by ensuring that:
(a) 
All cross-connections are removed; or approved cross-connection control devices are installed for control of backflow and backsiphonage.
(b) 
Cross-connection control devices shall be installed in accordance with the manufacturer's instruction.
(c) 
Cross-connection control devices shall be inspected at the time of installation and at least annually by a person approved by the Agency as a cross-connection control device inspector (CCCDI). The inspection of mechanical devices shall include physical testing in accordance with the manufacturer's instructions.
(d) 
Testing and records.
(i) 
Each device shall be tested at the time of installation and at least annually or more frequently if recommended by the manufacturer.
(ii) 
Records submitted to the community public water supply shall be available for inspection by Agency personnel in accordance with all relevant statutes and regulations.
(iii) 
Each device shall have a tag attached listing the date of most recent test, name of CCCDI (cross-connection control device inspector), and type and date of repairs.[6]
[6]
Editor's Note: Amended at time of adoption of Code (see Ch. 30, General Provisions, Art. 2).
(iv) 
A maintenance log shall be maintained and include:
1. 
Date of each test;
2. 
Name and approval number of person performing the test;
3. 
Test results;
4. 
Repairs or servicing required;
5. 
Repairs and date completed; and
6. 
Servicing performed and date completed.
(F) 
Where protection is required.
(1) 
An approved backflow device shall be installed on all connections to the public water supply as described in the Plumbing Code, 77 Ill. Adm. Code 890, and the Agency's regulations, 35 Ill. Adm. Code 681. In addition, an approved backflow prevention device shall be installed on each service line to a consumer's water system serving premises where, in the judgment of the Director, actual or potential hazards to the public water supply system exist.[7]
[7]
Editor's Note: Amended at time of adoption of Code (see Ch. 30, General Provisions, Art. 2).
(2) 
An approved backflow prevention device shall be installed on each service line to a consumer's water system serving premises where the following conditions exist:
(a) 
Premises having an auxiliary water supply unless such auxiliary supply is accepted as an additional source by the Director and the source is approved by the Illinois Environmental Protection Agency.
(b) 
Premises on which any substance is handled which can create an actual or potential hazard to the public water supply system. This shall include premises having sources or systems containing process fluids or waters originating from the public water supply system which are no longer under the sanitary control of the Director.
(c) 
Premises having internal cross-connections that, in the judgment of the Director and/or the cross-connection control device inspector, are not correctable or intricate plumbing arrangements which make it impractical to determine whether or not cross-connectors exist.
(d) 
Premises where, because of security requirements or other prohibitions or restrictions, it is impossible or impractical to make a complete cross-connection survey.
(e) 
Premises having a repeated history of cross-connections being established or reestablished.
(3) 
An approved backflow device shall be installed on all connections to the public water supply as described in the Plumbing Code, 77 Ill. Adm. Code 890, and the Agency's regulations, 35 Ill. Adm. Code 653. In addition, an approved backflow prevention device shall be installed on each service line to a consumer's water system serving, but not necessarily limited to, the following types of facilities unless the Director determines that no actual or potential hazard to the public water supply system exists:
(a) 
Hospitals, mortuaries, clinics, nursing homes.
(b) 
Laboratories.
(c) 
Piers, docks, waterfront facilities.
(d) 
Sewage treatment plants, sewage pumping stations or stormwater pumping stations.
(e) 
Food or beverage processing plants.
(f) 
Chemical plants.
(g) 
Metal plating industries.
(h) 
Petroleum processing or storage plants.
(i) 
Radioactive material processing plants or nuclear reactors.
(j) 
Car washes.
(k) 
Pesticide, herbicide or extermination plants and trucks.
(l) 
Farm service and fertilizer plants and trucks.
(G) 
Type of protection required.
(1) 
The type of protection required under Subsection (F)(2)(a), (b) or (c) of this section shall depend on the degree of hazard which exists as follows:
(a) 
An approved fixed proper air gap separation shall be installed where the public water supply system may be contaminated with substances that could cause a severe health hazard.
(b) 
An approved fixed proper air gap separation or an approved reduced pressure principle backflow prevention assembly shall be installed where the public water supply system may be contaminated with a substance that could cause a system or health hazard.
(c) 
An approved fixed proper air gap separation or an approved reduced pressure principle backflow prevention assembly or a double check valve assembly shall be installed where the public water supply system may be polluted with substances that could cause a pollution hazard not dangerous to health.
(2) 
The type of protection required under Subsection F(2)(d) and (e) of this section shall be an approved fixed proper air gap separation or an approved reduced pressure principle backflow prevention device.
(3) 
Where a public water supply or an auxiliary water supply is used for a fire protection system, reduced pressure principle backflow preventers shall be installed on fire safety systems connected to the public water supply when:
(a) 
The fire safety system contains antifreeze, fire retardant or other chemicals;
(b) 
Water is pumped into the system from another source;
(c) 
Water flows by gravity from a nonpotable source; or water can be pumped into the fire safety system from any other source; or
(d) 
There is a connection whereby another source can be introduced into the fire safety system.
(4) 
All other fire safety systems connected to the potable water supply shall be protected by a double check valve assembly on metered service lines and a double detector check valve assembly on unmetered service lines.
(H) 
Backflow prevention devices.
(1) 
All backflow prevention devices or methods required by these rules and regulations shall be approved by the Foundation for Cross-Connection Control and Hydraulic Impacts of the University of Southern California, American Water Works Association, American Society of Sanitary Engineering, or American National Standards Institute or certified by the NSF International to be in compliance with applicable industry specifications.[8]
[8]
Editor's Note: Amended at time of adoption of Code (see Ch. 30, General Provisions, Art. 2).
(2) 
Installation of approved devices shall be made in accordance with the manufacturer's instructions. Maintenance as recommended by the manufacturer of the device shall be performed. A manufacturer's maintenance manual shall be available on-site.
(I) 
Inspection and maintenance.
(1) 
It shall be the duty of the consumer at any premises on which backflow prevention devices required by these regulations are installed to have inspection, tests, maintenance and repair made in accordance with the following schedule or more often where inspections indicate a need or are specified in manufacturer's instructions:
(a) 
Fixed proper air gap separations shall be inspected to document that a proper vertical distance is maintained between the discharge point of the service line and the flood level rim of the receptacle at the time of installation and at least annually thereafter. Corrections to improper or bypassed air gaps shall be made within 24 hours.
(b) 
Double check valve assemblies shall be inspected and tested at the time of installation and at least annually thereafter, and required service performed within five days.
(c) 
Reduced pressure principle backflow prevention assemblies shall be tested at the time of installation and at least annually or more frequently if recommended by the manufacturer, and required service performed within five days.
(2) 
Testing shall be performed by a person who has been approved by the Agency as competent to service the device. Proof of approval shall be in writing.
(3) 
Each device shall have a tag attached listing the date of most recent test or visual inspection, name of tester and type and date of repairs.
(4) 
A maintenance log shall be maintained and include:
(a) 
Date of each test or visual inspection;
(b) 
Name and approval number of person performing the test or visual inspection;
(c) 
Test results;
(d) 
Repairs or servicing required;
(e) 
Repairs and date completed; and
(f) 
Servicing performed and date completed.
(5) 
Whenever backflow prevention devices required by these regulations are found to be defective, they shall be repaired or replaced at the expense of the consumer without delay as required by Subsection (I)(1).
(6) 
Backflow prevention devices shall not be bypassed, made inoperative, removed or otherwise made ineffective without specific authorization by the Director.
(J) 
Booster pumps.
(1) 
Where a booster pump has been installed on the service line to or within any premises, such pump shall be equipped with a low-pressure cut-off device designed to shut off the booster pump when the pressure in the service line on the suction side of the pump drops to 20 psi or less.
(2) 
It shall be the duty of the water consumer to maintain the low-pressure cut-off device in proper working order and to certify to the Director, at least once a year, that the device is operable.
(K) 
Violations.[9]
(1) 
The Director shall deny or discontinue, after reasonable notice to the occupants thereof, the water service to any premises wherein any backflow prevention device required by these regulations is not installed, tested, maintained and repaired in a manner acceptable to the Director, or if it is found that the backflow prevention device has been removed or bypassed, or if an unprotected cross-connection exists on the premises, or if a low-pressure cut-off required by these regulations is not installed and maintained in working order.
(2) 
Water service to such premises shall not be restored until the consumer has corrected or eliminated such conditions or defects in conformance with these regulations and to the satisfaction of the Director.
(3) 
Neither the City of Hometown, the Director, or its agents or assigns shall be liable to any customers of the City of Hometown for any injury, damages or lost revenues which may result from termination of said customer's water supply in accordance with the terms of this section, whether or not said termination of the water supply was with or without notice.
(4) 
The consumer responsible for backsiphoned material or contamination through backflow, if contamination of the potable water supply system occurs through an illegal cross-connection or an improperly installed, maintained or repaired device, or a device which has been bypassed, must bear the cost of clean-up of the potable water supply system.
(5) 
Any person found to be violating any provision of this section shall be served with written notice stating the notice of the violation and providing a reasonable time limit (not to exceed 30 days) for the satisfactory correction thereof. The offender shall, within the period of time stated in such notice, permanently cease all violation.
(6) 
Any person violating any of the provisions of this section, in addition to the fine provided by § 21.200, shall become liable to the City for any expense, loss or damage occasioned by the City by reason of such violation, whether the same was caused before or after notice.
[9]
Editor's Note: Amended at time of adoption of Code (see Ch. 30, General Provisions, Art. 2).