A.
The following sections outline a procedure for the
sizing of the water supply piping. The design procedure is based on
the minimum pressure available from the street main or individual
source of supply the head changes in the system due to friction and
elevation, the volume rates of flow required for satisfactory operation
of the fixtures, and the probability of simultaneous use.
B.
The procedure outline is intended to serve as a guide
and does not preclude an engineering design deviating from such procedure
which would accomplish the results sought in this article of the Code.
A.
Basic needs. The calculation of total daily requirements
for water may be used on the unit quantities shown in Tables 860-182A,
"Design Criteria for Daily Water Requirements Based on Building Occupancy,"
and 860-182A(1), "Daily Water Requirements for Common Farm Animals."
The total daily water requirement does not constitute the peak or
simultaneous water requirement of the supply and shall not be used
in sizing water distribution systems. The total of the daily water
requirements shall be used only to determine whether the source of
the water supply is sufficient to provide the water requirements of
people, animals, irrigation, and other water using facilities served.
The rate of flow and pressures at which the total daily water requirements
shall be delivered shall be determined as prescribed hereinafter.
Table 860-182A
Design Criteria for Daily Water Requirements
Based on Building Occupancy
| ||
---|---|---|
Type of Occupancy
|
Minimum Quantity of water per person per
day in gallons (or as indicated)
| |
Small dwellings or cottages with seasonal occupancy
|
50
| |
Single family dwellings
|
75
| |
Multiple family dwellings (apartment)
|
60
| |
Rooming houses
|
40
| |
Boarding houses
|
50
| |
Additional kitchen usage for nonresident boarders
|
10
| |
Hotels without private baths
|
50
| |
Hotels with private baths (2 persons per room)
|
60
| |
Restaurants (toilet and kitchen usage per person)
|
7 to 10
| |
Restaurant (kitchen usage per meal served)
|
2 1/2 to 3
| |
Additional for bars and cocktail lounges
|
2
| |
Tourist camps or trailer parks with central
bathhouse
|
35
| |
Tourist camps or mobile home parks with individual
bath units
|
50
| |
Resort camps (night and day) with limited plumbing
|
50
| |
Luxury camps
|
100 to 500
| |
Work or construction camps (semi-permanent)
|
50
| |
Camp (with complete plumbing)
|
45 (Ind. w.s.)
| |
Camp (with flush toilets — no showers)
|
25 (Ind. w.s.)
| |
Day Camps (no meal served)
|
15
| |
Day Schools, without cafeterias, gymnasiums,
or showers
|
15
| |
Day School with cafeterias, but no gymnasiums
or showers
|
20
| |
Day Schools with cafeterias, gymnasiums and
showers
|
25
| |
Boarding schools
|
75 to 100
| |
Day workers at schools and office (per shift)
|
15
| |
Hospitals
|
150 to 250
| |
Institutions other than hospitals (per bed)
|
75 to 125
| |
Factories (gallons per person per shift, exclusive
of industrial wastes)
|
15 to 35
| |
Picnic parks (toilet usage only)
|
5
| |
Picnic parks with bathhouse, showers and flush
toilets)
|
10
| |
Swimming pools and bathhouses
|
10
| |
Luxury residences and estates
|
100 to 150
| |
Country clubs (per resident member)
|
100
| |
Country club (per non-resident member)
|
25
| |
Motels (per bed space)
|
40
| |
Motels with bath, toilet, and kitchen range
|
50
| |
Drive-in theaters (per car space)
|
5
| |
Movie theaters (per auditorium seat)
|
5
| |
Airports (per passenger)
|
3 to 5
| |
Self-service laundries (gallons per wash, i.e.
per customer)
|
50
| |
Stores (per toilet room)
|
400
| |
Service station (per vehicle serviced)
|
10
|
Table 860-182A(1)
Daily Requirements for Common Farm Animals
| ||
---|---|---|
Animal
|
Minimum daily water requirements in gallons
| |
Horse, mule or steer
|
12
| |
Dairy cow (drinking only)
|
15
| |
Dairy cow (drinking and dairy servicing)
|
35
| |
Sheep
|
2
| |
Hog
|
4
| |
Chicken (100)
|
4
| |
Turkeys (100)
|
7
|
B.
Calculating total daily requirements. Total daily
requirements should be calculated by multiplying the unit daily requirement
by the total number of persons in the occupancy involved. See Example
1 below. To this figure must be added any special use quantity, such
as lawn watering, industrial requirement, etc.
C.
Special requirements. The total daily amount of any special requirement shall be added to the figure obtained under Subsection B and Table 860-177G, "Minimum Flow Pressure and Flow Rates," gives special use quantities for some conditions. While the quantity of special use water shall be computed on the rates given in Table 860-177G, the total amount shall be figured for appropriate periods and conditions of use. See Example 2.
(1)
Example: Assume there is a hospital outside the limits
of a community. The hospital has 300 beds. In addition, the hospital
supplies its own dairy products and has a farm with 40 head of cattle.
In Table 860-182A, the daily water requirement per hospital bed is
taken as 250 gallons per bed. From Table 860-182A(1), the water requirement
per head of cattle is taken as 35 gallons per animal. Therefore, the
total daily requirement is 300 by 250 plus 40 by 35 or 76,400 gallons.
(2)
Example: It is assumed that at the hospital cited
in Table 860-182A, there is a lawn sprinkling system operating from
12 sillcocks three hours each day. From Table 860-177G, it is seen
that each sillcock requires 300 gallons per hour. Therefore, the total
special use water will equal 12 by 900 or 10,800 gallons. This amount
is added to that obtained in Example 1. The total quantity required
is, therefore, 76,400 plus 10,800 or 87,200 gallons per day.
A.
Estimating water supply demand. In determining the
size of water supply distribution piping, the maximum momentary volume
rate of flow of water shall first be determined. This is the supply
demand which is based on the numbers and kinds of fixtures installed,
on the rates of flow required by the different kinds of fixtures,
and on the probable simultaneous operation of the various fixtures.
The total daily requirements do not enter into the determination.
In computing supply demand, use shall be made of Table 860-183A, "Supply
Fixture Unit Values for Various Plumbing Fixtures."
Table 860-183A
Supply Fixture Unit Values for Various
Plumbing Fixtures
| |||||
---|---|---|---|---|---|
Type of Supply Fixture
| |||||
Fixture or Group1
|
Supply Control
|
Hot
|
Cold
|
Unit Values Total2
| |
Bathroom group
|
Flush valve
|
3
|
6
|
7
| |
Bathroom group
|
Flush tank
|
3
|
4.5
|
6
| |
Bathtub
|
Faucet
|
1.5
|
1.5
|
2
| |
Combination fixture
|
Faucet
|
2
|
2
|
3
| |
Kitchen sink
|
Faucet
|
1.5
|
1.5
|
2
| |
Laundry tray
|
Faucet
|
2
|
2
|
3
| |
Lavatory
|
Faucet
|
1.5
|
1.5
|
2
| |
Pedestal urinal
|
Flush valve
|
-
|
10
|
10
| |
Restaurant sink
|
Faucet
|
3
|
3
|
5
| |
Service sink
|
Faucet
|
1.5
|
1.5
|
2
| |
Shower head
|
Mixing valve
|
3
|
3
|
5
| |
Stall or wall urinal
|
Flush valve
|
-
|
5
|
5
| |
Stall or wall urinal
|
Flush tank
|
-
|
3
|
3
| |
Water closet
|
Flush valve
|
-
|
10
|
10
| |
Water closet
|
Flush tank
|
-
|
5
|
5
|
Notes:
| ||
---|---|---|
1.
|
For fixtures not listed, factors may be assumed
by comparing the fixture to a listed one using water in similar quantities
and at similar rates.
| |
2.
|
For fixtures with both hot and cold water supplies,
the weights for maximum separate demands may be taken as 3/4 of the
total supply fixture unit value.
|
B.
Calculation of demand. When the water supply fixture
units are used to estimate the supply demand, the supply fixture unit
values as given in Table 860-183A shall be used in conjunction with
Table 860-183B, "Supply Demand for Various Loads in Supply Fixture
Units."[1]
Table 860-183B
Supply Demand for Various Loads in Supply
Fixture Units
| |||
---|---|---|---|
Load
Supply fixture units
|
Flush valve water closets predominate
(curve 1)
gpm
|
Tank water closets predominate (curve
2)
gpm
| |
5
|
22
|
4
| |
10
|
27
|
8
| |
20
|
35
|
14
| |
30
|
42
|
20
| |
40
|
46
|
24
| |
50
|
51
|
28
| |
60
|
54
|
32
| |
88
|
64
|
40
| |
124
|
74
|
48
| |
160
|
81
|
56
| |
236
|
98
|
72
| |
300
|
108
|
85
| |
400
|
127
|
106
| |
470
|
135
|
118
| |
500
|
143
|
124
| |
600
|
157
|
143
| |
660
|
162
|
152
| |
700
|
170
|
161
| |
800
|
183
|
178
| |
850
|
189
|
185
| |
900
|
197
|
195
| |
1,000
|
208
|
208
| |
1,060
|
216
|
216
| |
1,280
|
243
|
243
| |
1,510
|
270
|
270
| |
1,990
|
324
|
324
| |
2,480
|
378
|
378
| |
2,900
|
432
|
432
|
(1)
The estimated demand load in gallons per minute for
fixtures used intermittently on any water supply pipe shall be obtained
by multiplying the total number of each kind of fixture, supplied
through that pipe by its Supply Fixture unit value from Table 860-183A
adding the products, then referring to the appropriate columns of
Table 860-183B or using the figure, select the Demand in GPM. Examples
given below.[2]
[2]
Editor's Note: The examples are on file in
the Health Department.
(2)
The additional load of any continuously flowing outlets
such as hose outlets shall be computed separately and added to the
total demand of intermittently used fixtures. See Example 2. below.
(a)
Assume a water line serving a public washroom
in which are three flushometer pedestal urinals, six flushometer closets
and six lavatories with hot and cold water. First prepare a tabulation
as shown:
Name of Plumbing Fixture
|
Number on system (or section1)
|
Supply fixture unit value per fixture
Table 860-183A
|
Total supply fixture units
| ||||
---|---|---|---|---|---|---|---|
Hot
|
Cold
|
Total
|
Hot
|
Cold
|
Total
| ||
Pedestal Urinal
| |||||||
Flush Valve
|
3
|
10
|
10
|
30
|
30
| ||
Flushometer Closet
|
6
|
10
|
10
|
60
|
60
| ||
Lavatory
|
6
|
1.5
|
1.5
|
2
|
9
|
9
|
12
|
Total
|
9
|
99
|
102
| ||||
Supply demand in GPM
|
7
|
67
|
68
|
[1]
See Subsection C. Referring to Table 860-183A for these fixtures, it is found that the total demand in supply fixtures units for hot was nine s.f.u., for cold was 99 s.f.u., and a total demand of 102 s.f.u. By using Figure Table 860-183B curve number 2, it is determined that the supply demand in GPM for hot water is 7, and by using the same figure but curve 1, it is determined that the demand for cold water in GPM is 67 and the total demand in GPM is 68. This break-down is used in order to size the hot water supply branch, the cold water supply branch and the building service line.
[2]
Assume an apartment building (private type occupancy)
having 200 bathrooms groups with flushometer closets and 200 kitchen
sinks. The apartment lawn has installed in it a sprinkler system operating
from seven sillcocks. What is the demand flow for which the water
service to the apartment must be designed? The intermittent use fixtures
are figured as in Example 1. to have a demand of 326 GPM.
Name of Fixture
|
Number on system
|
Supply fixture unit value per fixture
Table 860-183A
|
Total supply fixture units
| ||||
---|---|---|---|---|---|---|---|
Hot
|
Cold
|
Total
|
Hot
|
Cold
|
Total
| ||
Bathroom group
|
200
|
3
|
6
|
8
|
600
|
1,200
|
1,600
|
Kitchen sink
|
200
|
1.5
|
1.5
|
2
|
300
|
300
|
400
|
Total
|
900
|
1,500
|
2,000
| ||||
Demand in GPM (Table 860-183B)
|
195
|
270
|
326
|
[3]
The lawn sprinkler system outlets have a demand
of five GPM each (Table 860-177G). The total sprinkler system demand
is, therefore, 35 GPM. This is added to the total demand (326) of
the intermittently used fixture making a total water demand of 361
GPM. This total figure would then be used in determine the size of
the building service pipe. The 35 GPM demand figure would also be
added to the cold water demand figure of 270 giving total cold water
demand of 305 GPM and this figure would be used in sizing the cold
water distribution piping.
[1]
Editor's Note: A figure representing a graphical
representative to this table is on file in the Health Department.
C.
Selection of pipe size.
(1)
Pipe sizes may be selected according to the following water pipe sizing procedure except that in no case shall a pipe size be less than shown in Table 860-177A nor in the case of water service lines, less than specified in § 860-176A.
(a)
The water pipe sizing procedure is based on
a system of pressure requirements and losses, the sum of which must
not exceed the minimum pressure available at the street main or other
source of supply.
(2)
These pressures are expressed as follows:
(a)
Pressure required at fixture to produce adequate
flow — See Table 860-177G.
(b)
Static pressure loss — This is computed
at 0.43 psi per ft. of pipe rise or drop and is added or subtracted
respectively.
(c)
Loss through water meter — Pressure or
friction losses for various size meters are shown in Table or Figure
860-183C(1).
(d)
Loss through taps in water main — Losses
for various size taps as Shown in Table 860-183C(3).
(e)
Losses through special devices such as filters,
water softeners, backflow preventers, etc. — These must be obtained
from the manufacturer, or estimated and added to the total.
(f)
Loss through fittings and valves — Losses
for these devices are computed by converting the fittings or valves
to equivalent straight sections of pipe and adding this length to
the total for the pipe section being considered. Table 860-183C(2)
shows equivalent lengths of pipe for fittings and valves.
(g)
Loss due to pipe friction — This loss
may be readily computed when (a) the pipe size, (b) its length and
(c) the flow through the pipe are known. When these three factors
are known, the friction loss can be determined from either Table 860-183C(4)
to (7) or the figures.[3] The table and the figure used depends on the type of pipe
used. An example of this sizing procedure is given in the following
section.
Table 860-183C(1)
Loss of Pressure Through Disk-type Meters
in Pounds per Square Inch (psi)
| ||||||||
---|---|---|---|---|---|---|---|---|
Size of Meter
| ||||||||
Gallons per minute
|
5/8
|
3/4
|
1"
|
1"
|
2"
|
3"
|
4"
|
6"
|
4
|
1.0
| |||||||
5
|
1.6
| |||||||
6
|
2.2
| |||||||
7
|
3.0
|
1.1
| ||||||
8
|
4.0
|
1.4
| ||||||
9
|
5.0
|
1.7
| ||||||
10
|
6.1
|
2.1
| ||||||
15
|
14
|
5.0
|
2.0
| |||||
20
|
-
|
8.8
|
3.5
|
1.0
| ||||
30
|
-
|
19
|
8.0
|
2.3
| ||||
40
|
-
|
-
|
14
|
4.0
|
1.6
| |||
50
|
-
|
-
|
22
|
6.2
|
2.4
| |||
60
|
-
|
-
|
-
|
9.0
|
3.6
| |||
70
|
-
|
-
|
-
|
12
|
4.9
|
1.3
| ||
80
|
-
|
-
|
-
|
16
|
6.2
|
1.7
| ||
90
|
-
|
-
|
-
|
20
|
8.0
|
2.0
| ||
100
|
-
|
-
|
-
|
-
|
10
|
2.5
|
1.0
| |
120
|
-
|
-
|
-
|
-
|
14
|
3.7
|
1.30
| |
140
|
-
|
-
|
-
|
-
|
20
|
5.1
|
2.0
| |
160
|
-
|
-
|
-
|
-
|
-
|
6.2
|
2.4
| |
180
|
-
|
-
|
-
|
-
|
-
|
8.1
|
3.3
| |
200
|
-
|
-
|
-
|
-
|
-
|
10
|
4.0
|
1.0
|
250
|
-
|
-
|
-
|
-
|
-
|
16
|
6.1
|
1.7
|
300
|
-
|
-
|
-
|
-
|
-
|
23
|
9.0
|
2.3
|
350
|
-
|
-
|
-
|
-
|
-
|
-
|
13.0
|
3.0
|
400
|
-
|
-
|
-
|
-
|
-
|
-
|
16.0
|
4.0
|
500
|
-
|
-
|
-
|
-
|
-
|
-
|
25.0
|
6.1
|
600
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
9.0
|
700
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
13
|
800
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
16
|
900
|
-
|
-
|
-
|
-
|
-
|
-
|
-
|
20
|
Table 860-183C(2)
Allowance in Equivalent length of pipe
for Friction Loss in Valves and Threaded Fittings
| |||||||
---|---|---|---|---|---|---|---|
Diameter of fitting (inches)
|
90° Std. ell, feet
|
45° Std. ell, feet
|
90° side tee, feet
|
Coupling or straight run of tee, feet
|
Gate Valve, Feet
|
Gate Valve, Feet
|
Angle Valve, Feet
|
3.8
|
1
|
0.6
|
1.5
|
0.3
|
0.2
|
8
|
4
|
1/2
|
2
|
1.2
|
3
|
0.6
|
0.4
|
15
|
8
|
3/4
|
2.5
|
1.5
|
4
|
0.8
|
0.5
|
20
|
12
|
1
|
3
|
1.8
|
5
|
0.9
|
0.6
|
25
|
15
|
1 1/4
|
4
|
2.4
|
6
|
1.2
|
0.8
|
35
|
18
|
1 1/2
|
5
|
3
|
7
|
1.5
|
1.0
|
45
|
22
|
2
|
7
|
4
|
10
|
2
|
1.3
|
55
|
28
|
2 1/2
|
8
|
5
|
12
|
2.5
|
1.6
|
65
|
34
|
3
|
10
|
6
|
15
|
3
|
2
|
80
|
40
|
3 1/2
|
12
|
7
|
18
|
3.6
|
2.4
|
100
|
50
|
4
|
14
|
8
|
21
|
4.0
|
2.7
|
125
|
55
|
5
|
17
|
10
|
25
|
5
|
3.3
|
140
|
70
|
6
|
20
|
12
|
30
|
6
|
4
|
165
|
80
|
Table 860-183C(3)
Loss of Pressure Through Taps and Tees
in Pounds per Square Inch (psi)
| |||||||
---|---|---|---|---|---|---|---|
Size of Tap or Tee
| |||||||
Gallons per minute
|
5/8"
|
3/4"
|
1"
|
1 1/4"
|
1 1/2"
|
2"
|
3"
|
10
|
1.35
|
0.64
|
0.18
|
0.08
| |||
20
|
5.38
|
2.54
|
0.77
|
0.31
|
0.14
| ||
30
|
12.1
|
5.72
|
1.62
|
0.69
|
0.33
|
0.10
| |
40
|
-
|
10.2
|
3.07
|
1.23
|
0.58
|
0.18
| |
50
|
-
|
15.9
|
4.49
|
1.92
|
0.91
|
0.28
| |
60
|
-
|
-
|
6.46
|
2.76
|
1.31
|
0.40
| |
70
|
-
|
-
|
8.79
|
3.76
|
1.78
|
0.55
|
0.10
|
80
|
-
|
-
|
11.5
|
4.90
|
2.32
|
0.72
|
0.13
|
90
|
-
|
-
|
14.5
|
6.21
|
2.94
|
0.91
|
0.16
|
100
|
-
|
-
|
17.94
|
7.67
|
3.63
|
1.12
|
0.21
|
120
|
-
|
-
|
25.8
|
11.0
|
5.23
|
1.61
|
0.30
|
140
|
-
|
-
|
35.2
|
15.0
|
7.12
|
2.20
|
0.41
|
150
|
-
|
-
|
17.2
|
8.16
|
2.52
|
0.47
| |
160
|
-
|
-
|
-
|
19.6
|
9.30
|
2.92
|
0.54
|
180
|
-
|
-
|
-
|
24.8
|
11.8
|
3.62
|
0.68
|
200
|
-
|
-
|
-
|
30.7
|
14.5
|
4.48
|
0.84
|
225
|
-
|
-
|
-
|
38.8
|
18.4
|
5.67
|
1.06
|
250
|
-
|
-
|
-
|
47.9
|
22.7
|
7.00
|
1.31
|
275
|
-
|
-
|
-
|
-
|
27.4
|
7.70
|
1.59
|
300
|
-
|
-
|
-
|
-
|
32.6
|
10.1
|
1.88
|
Table 860-183C(4)
Pressure Loss of Water in Pounds per Square
inch per 100 Feet of Fairly Smooth Pipe.
| |
---|---|
For convenience this table is developed from
the accompanying figure.[4]
|
Table 860-183C(5)
Pressure Loss of Water in Pounds per Square
Inch per 100 Feet of Fairly Rough Pipe.
| |
---|---|
For convenience this table is developed from
the accompanying figure.[5]
|
Table 860-183C(6)
Pressure Loss of Water in Pounds per Square
Inch per 100 Feet of Rough Pipe.
| |
---|---|
For convenience this Table is developed from
the accompanying figure.[6]
|
Table 1503.3G.
Pressure Loss of Water in Pounds per Square
Inch per 100 Feet of Smooth Pipe.
| |
---|---|
For convenience, this table is developed from
the accompanying figure.[7]
|
[3]
Editor's Note: The figures are on file in
the Health Department.
[4]
Editor's Note: The table and figure are on
file in the Health Department.
[5]
Editor's Note: The table and figure are on
file in the Health Department.
[6]
Editor's Note: The table and figure are on
file in the Health Department.
[7]
Editor's Note: The table and figure are on
file in the Health Department.
(3)
Example: What size copper water pipe, service and
distribution will be required to serve a two story factory building
having on each floor, back to back two toilet rooms each equipped
with four flushometer closets, two flushometer pedestal urinals and
four lavatories with hot and cold water?
(a)
The highest fixture is 21 feet above the street
main which is tapped with a two inch corporation cock at which point
the minimum pressure is 55 psi
(b)
In the building basement a two inch meter and
three inch reduced pressure zone backflow preventer with a maximum
pressure drop of nine psi are to be installed. The system is shown
by the following diagram. To be determined are the pipe sizes for
the service main, and the cold and the hot water distribution pipes.
(c)
A tabular arrangement such as shown following
should first be constructed. The steps to be followed in solving the
problem are indicated by the table itself as they are in sequence,
Columns 1 through 8 and lines a through 1.
(d)
Recommended tabular arrangement for use in solving
pipe sizing problems:
Line
|
Lbs. Per square inch — psi
| |||
---|---|---|---|---|
a.
|
Minimum pressure available at main
|
55.00
| ||
b.
|
Highest pressure required at a fixture (Table
860-177G)
|
15.00
| ||
c.
|
Meter loss — 2" meter [Table 860-183C(1)]
|
11.00
| ||
Service & Water
|
d.
|
Tap in main-loss 2" tap [Table 860-183C(1)]
|
1.29
| |
Distribution
|
e.
|
Static head loss 21 x .043 psi
|
9.03
| |
Piping
|
f.
|
Special fixture loss — backflow preventer
|
9.00
| |
g.
|
Special fixture loss — filter
|
0.00
| ||
h.
|
Special fixture loss — other
|
0.00
| ||
i.
|
Total overall losses and requirements, sum of
lines b through h
|
45.32
| ||
j.
|
Pressure available to overcome pipe friction,
lines a minus sum of lines both
|
9.68
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
---|---|---|---|---|---|---|---|
Pipe Section
|
Gal per minute through section (determine
as in Section 1503.2)
|
Length of section (ft)
|
Trial pipe size (in)
|
Equivalent length of fittings &
valves Table 1503.3B (ft)
|
Total equivalent length Col 3 &
5 100'
|
Friction loss, per 100' of trial size
pipe Table 1503.3G
|
Friction loss in equivalent length
Col 6 x Col 7 psi
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
AB
|
104
|
54
|
2 1/2
|
12.3
|
0.67
|
3.0
|
2.00
|
BC
|
102
|
8
|
2 1/2
|
8
|
0.16
|
2.8
|
0.45
|
CF
|
76
|
150
|
2 1/2
|
1.6
|
1.52
|
1.7
|
2.58
|
CD
|
76
|
13
|
2 1/2
|
8
|
0.21
|
1.7
|
0.36
|
DE
|
76
|
150
|
2 1/2
|
1.6
|
1.52
|
1.7
|
2.58
|
k.
|
Total pipe friction losses (cold) 7.97
psi
|
7.97
| |
l.
|
Difference line j minus line k
|
1.71
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
---|---|---|---|---|---|---|---|
Hot Water Distribution Piping
| |||||||
AB'
|
104
|
54
|
2 1/2
|
12.8
|
0.67
|
3.1
|
2.00
|
B'C'
|
16
|
8
|
2
|
15.3
|
0.23
|
1.2
|
0.28
|
C'F'
|
9
|
150
|
2
|
1.3
|
1.51
|
0.8
|
1.21
|
C'D'
|
9
|
13
|
1 1/2
|
5
|
0.18
|
3.2
|
0.58
|
D'E'
|
9
|
150
|
1 1/2
|
1.0
|
1.51
|
3.2
|
4.84
|
k.
|
Total pipe friction losses (hot) 8.85
psi
|
8.91
| |
l.
|
Difference line j minus line k
|
0.77
|
[1]
Step 1.
[a]
Column 1 — Divide the system
into sections breaking at major changes in elevation or where branches
lead to fixture groups. After point (B) (See sketch) separate consideration
will be given to the hot and cold water piping in Column 1 of the
tabular arrangement.
[2]
Step 2.
[a]
Line a — Enter the minimum
pressure available at the main source of supply. This is 55 psi.
[b]
Line b — Determine from Table
860-177G the highest pressure required for the fixtures on the system.
Which is 15 psi to operate a flushometer valve.
[c]
Line c — Select from Table
860-183C(1) the pressure loss for the meter size given or assumed.
The total water flow from the main through the service as determined
in Step 1 will serve to aid in the meter selected.
[d]
Line d — Select from Table
860-183C(3) and enter the pressure loss for the tap size given or
assumed.
[e]
Line e — Determine the difference
in elevation between the main or source of supply and the highest
fixture on the system and multiply this figure, expressed in feet,
by 0.43 psi. Enter the resulting psi product on Line e.
[f]
Line f, g, h — The pressure
losses through filters, backflow preventers or other special fixtures
must be obtained from the manufacturer or estimated and entered on
these lines.
[3]
Step 3. Line i — The sum of (line b through
h) the pressure requirements and losses which affect the overall systems
is entered on this line.
[4]
Step 4. Line J — Subtract line i from
line a. This gives the pressure which remains available for overcoming
friction losses in the system. This figure is a guide to the pipe
size which is chosen for each section as the total friction losses
through all the sections should not exceed this value.
[5]
Step 5. Column 3 — Enter the length of
each section.
[6]
Step 6. Column 4 — Select a trial pipe
size. A rule of thumb is that size will become progressively smaller
as the system extends farther from the main or source of supply.
[7]
Step 7. Column 5 — Select from Table 860-183C(2)
the equivalent lengths for the trial pipe size of fittings and valves
on the section. Enter the sum for each section in Column 5. (The number
of fittings to be used in the installation of this piping must be
an engineering estimate)
[8]
Step 8. Column 6 — Add the figures from
Column 3 and Column 5, and enter in Column 6. Express the sum in 100's
or feet.
[9]
Step 9. Column 7 — Select from Table 860-183C(7)
the friction loss per 100 feet of pipe for the GPM flow in a section
(column 2) and the trial pipe size (column 4).
[10]
Step 10. Column 8 — Multiply the figures
in Columns 6 and 7 for each section and enter in Column 8.
[11]
Step 11. Line k — Enter the sum of the
values in Column 8.
[12]
Step 12. Line l — Subtract line k from
line j.
[13]
The result should always be a positive or plus
figure. If it is not, it is necessary to repeat the operation utilizing
Columns 4, 5, 7 and 8 until a balance or near balance is obtained.
If the difference between lines j and k is positive and large, it
is an indication that the pipe sizes are too large and may, therefore,
be reduced thus saving materials. In such a case the operations utilizing
Columns 4, 5, 7 and 8 should again be repeated.
[14]
Answer. The final figures entered in Column
4 become the design pipe size for the respective sections. Repeating
this operation a second time using the same sketch but considering
the demand for hot water, it is possible to size the hot water distribution
piping. This has been worked up as a part of the overall problem in
the tabular arrangement used for sizing the service and cold water
distribution piping. It should be noted that consideration must be
given the pressure losses from the street main to the water heater
(section AB) determining the hot water pipe sizes.