Exciting enhancements are coming soon to eCode360! Learn more 🡪
Allegheny County, PA
 
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
This article is designed to point out those items of the hospital plumbing system which differ from plumbing systems of other building types. Special care should be accorded the hospital plumbing system because of its direct relationship to the provision of adequate medical care and the need to protect hospital personnel and patients from health hazards involved in such systems. It is understood that this hospital plumbing system shall conform not only to the criteria in this article but to the requirements contained in the body of the Code.
Acceptable flush rim bedpan hoppers (clinic sinks), bedpan washers, and/or other acceptable fixtures and equipment shall be provided for the disposing of bedpan contents and the cleansing and disinfection of bedpans in soiled utility (hopper) rooms.
A. 
Clinic sink. A clinic sink shall have an integral trap in which the upper portion of a visible trap seal provides a water surface. The fixture shall be so designed as to permit complete removal of the contents by siphonic and/or blowout action, and to reseal the trap. A flushing rim shall provide water to cleanse the interior surface. The fixtures shall have flushing and cleansing characteristics similar to a water closet.
B. 
Prohibited use of clinic sinks and service sinks. A clinic sink serving a soiled utility room shall not be considered as a substitute for, nor shall it be used as a janitor's service sink. A janitor's service sink shall not be used for the disposal of urine, fecal matter, or other human wastes.
C. 
Ice prohibited in soiled utility rooms. No machine for manufacturing ice, or any device for the handling or storage of ice shall be located in a soiled utility room. Machines for manufacturing ice, or devices for handling or storage of ice intended for either human consumption or packs, may be located in clean utility room, floor pantry, or diet kitchen.
D. 
Sterilizer equipment requirements.
(1) 
Descaling of equipment prohibited. It shall be unlawful to descale or otherwise submit the interior of water sterilizers, stills, or similar equipment to acid or other chemical solutions while the equipment is connected to the water and/or drainage system.
(2) 
ASME Standard. New pressure sterilizers and pressure instrument washer-sterilizers hereafter installed shall display in a location to be clearly visible at all times the ASME Standard symbol and data plate.
(3) 
Sterilizer piping. All sterilizer piping and/or devices necessary for the operation of sterilizers shall be accessible for inspection and maintenance.
(a) 
Steam supply. Steam supplies to sterilizers, including those connected by pipes from overhead mains or branches, shall be drained to prevent any excess moisture from reaching the sterilizer. The condensate drainage from the steam supply shall be discharged by gravity.
(b) 
Steam condensate return. Steam condensate return from sterilizers shall not be connected to pressure or vacuum return systems; only gravity return shall be acceptable. Steam condensate returns from sterilizers shall not be connected to overhead mains or branches.
(c) 
Condensers.
[1] 
Pressure sterilizers should be equipped with an acceptable means of condensing and cooling the exhaust steam vapors.
[2] 
Non pressure sterilizers should be equipped with an acceptable device which will automatically control the vapors in a manner to confine them within the vessel, or equipped with an acceptable means of condensing and cooling the vapors.
(d) 
Gas fired equipment. Gas fired equipment or apparatus requiring either water or drainage connections or both shall meet the Standards of the American Gas Association.
E. 
Special elevations. Control valves, vacuum outlets, and devices which protrude from a wall of an operating, emergency, recovery, examining, or delivery room, or a corridor, and/or other locations where patients may be transported on a wheeled stretcher, shall be so located at an elevation which will preclude bumping the patient or stretcher against the device. When necessary to install at a low elevation, safety precautions should be taken to protect the personnel.
F. 
Plumbing in mental hospitals. In mental hospitals, special consideration should be given to piping, controls, and fittings of plumbing fixtures as required by the types of mental patients being treated. No pipes or traps should be exposed and fixtures should be substantially bolted through walls.
NOTE: Those fixtures not covered in this chapter having to do with hospital plumbing will be covered in Table 860-102A, "Minimum Number of Plumbing Fixtures."[1]
A. 
Ice storage chest drains. Any drain serving an ice chest or box shall discharge over an indirect waste receptor separate from all other fixture wastes. Each terminal shall discharge through an air gap above the receptor. The end shall be covered with a removable screen of not less than ten mesh per inch; and if discharging vertically, the terminal shall be cut at an angle of 45°.
B. 
Bedpan washers and clinic sinks. Bedpan washers and clinic sinks shall be connected to the soil pipe system and vented following the requirements as applied to water closets except that bedpan washers require additional local vents. See § 860-192L(1).
C. 
Sterilizer wastes.
(1) 
Indirect wastes required.
(a) 
All sterilizers shall be provided with individual and separate indirect wastes, with air gaps of not less than two diameters of the waste tailpiece. The upper rim of the receptor, funnel, or basket type waste fitting shall be not less than two inches below the vessel or piping, whichever is lower.
(b) 
Except as provided in Subsection C(3) and (5), a "P" trap shall be installed on the discharge side of and immediately below the indirect waste connection serving each sterilizer.
(2) 
Floor drain required. In all recess rooms containing the recessed, or concealed portions of sterilizers, not less than one acceptable floor drain, connecting to the drainage system, shall be installed in a manner to drain the entire floor area.
(3) 
Recess room floor drains, trap seal maintenance. The recess room floor drain waste and trap shall be a minimum diameter of three inches. It shall receive the drainage from at least one sterilizer within the recess room to assure maintenance of the floor drain trap seal. The sterilizer drain shall be installed on a branch taken off between the floor drain trap and the drain head. No individual sterilizer waste trap shall be required on this type of installation.
(4) 
Prohibited connections. Branch funnel and branch basket type fittings, except as provided in Subsection C(2), are prohibited on any new installation or when relocating existing equipment. Existing branch funnel or branch basket type installations shall be provided with an acceptable indirect waste below the branch connections.
(5) 
Battery assemblies. A battery assembly of not more than three sterilizer wastes may drain to one trap, provided the trap and waste are sized according to the combined fixture unit rating; the trap is located immediately below one of the indirect waste connections; the developed distance of a branch does not exceed four feet; and the branches change direction through a tee-wye or wye pattern fitting.
(6) 
Bedpan streamers, additional trap required. A trap with a minimum seal of three inches shall be provided in a bedpan steamer drain located between the fixture and the indirect waste connection.
(7) 
Pressure sterilizer. Except when an exhaust condenser is used, a pressure sterilizer chamber drain may be connected to the exhaust drip tube before terminating at the indirect waste connection. If a vapor trap is used, it shall be designed and installed to prevent moisture being aspirated into the sterilizer chamber. The jacket steam condensate return, if not connected to a gravity steam condensate return, shall be separately and indirectly wasted. If necessary to cool a high temperature discharge, a cooling receiver, trapped on its discharge side, may serve as the fixture trap.
(8) 
Pressure sterilizer exhaust condensers. The drain from the condenser shall be installed with an indirect waste as prescribed in the Code. If condensers are used on pressure sterilizers, the chamber drain shall have a separate indirect waste connection.
(9) 
Water sterilizer. All water sterilizer drains, including tank, valve leakage, condenser, filter and cooling, shall be installed with indirect waste or according to Subsection C(2).
D. 
Aspirators. In operating rooms, emergency rooms, recovery rooms, delivery rooms, examining rooms, autopsy rooms, and other locations, except laboratories where aspirators are installed for removing blood, pus and/or other fluids, the discharge from any aspirator shall be provided with a bottle or similar trap to protect the water supply.
E. 
Vacuum system stations. Vacuum system stations location shall be considered from a standpoint of convenience and practical use. The receptacles should be built into cabinets or recesses, but shall be visible and readily accessible.
F. 
Bottle systems. Vacuum (fluid suction) systems intended for collecting, removing and/or disposing of blood, pus and/or fluids by the so-called bottle system shall be provided with receptacles which are equipped with an overflow preventive device at each vacuum outlet station. Each vacuum outlet station should be equipped with a secondary safety receptacle as an additional safeguard against fluids, other than air, entering the vacuum piping systems.
G. 
Central disposal system equipment. Because of dependence placed upon central vacuum (fluid suction) systems, all such systems shall assure continuous service. Systems equipped with collecting and/or control tanks shall provide for the draining and cleaning of the tanks while the system is in operation. In hospitals or like institutions having emergency power provisions, the system shall be capable of remaining in service during the use of emergency power. The exhaust from a vacuum pump used in connection with a vacuum (fluid suction) system shall discharge separately to the outer atmosphere above the roof. The exhaust discharge shall not create a nuisance and/or hazard within, without, around and/or above premises.
H. 
Central vacuum, and/or disposal system.
(1) 
Wastes. The waste from a central vacuum (fluid suction) system of the disposal type and/or which is connected to the drainage system whether the disposal be by barometric leg, collecting tanks, or bottles, shall be directly connected to the sanitary drainage system through a trapped waste.
(2) 
Piping. The piping of a central vacuum (fluid suction) system shall be of corrosion resistant material having a smooth interior surface. No branch shall be less than one-half inch for one outlet and sized according to the number of vacuum outlets, and no main shall be less than one inch. The pipe sizing shall be increased according to the manufacturer's recommendation as stations are increased. All piping shall be provided with adequate and accessible clean-out facilities on mains and branches, and shall be accessible for inspection, maintenance, and replacements.
I. 
Water systems for space cooling and heating condensate drains. The lowest point of a condensate riser or risers shall be trapped and discharged over an indirect waste sink. The trap may be either "P" or a "running trap" with a cleanout. A branch shall be installed upstream from the condensate drain trap for flushing and resealing purposes. The condensate drain and trap shall be located above the lowest floor level of the building.
J. 
Vent material. Material for local vents serving bedpan washers and sterilizer vents serving sterilizers, shall be sufficiently rust proof, erosion and corrosion resistant to withstand intermittent wetting and drying from steam vapors, to withstand the distilled water solvent action of the steam vapors, and to withstand frequent and immediate changes of temperatures. Such material shall be not less in quality than the requirements specified for sanitary vents as outlined in Article V, § 860-64.
K. 
Vent connections prohibited. Connections between local vents serving bedpan washers and sterilizer vents serving sterilizing apparatus, and/or normal sanitary plumbing systems, are prohibited. Furthermore, only one type of apparatus shall be served by a given vent.
L. 
Local vents and stacks.
(1) 
Bedpan washers. Bedpan washers shall be vented to the outer atmosphere above the roof by means of one or more local vents. The local vent for a bedpan washer shall be not less than a two inch diameter pipe. A local vent serving a single bedpan washer may drain to the fixture served.
(2) 
Multiple installations. Where bedpan washers are located above each other on more than one floor, a local vent stack may be installed to receive the local vent on the various floors. Not more than three bedpan washers shall be connected to a two inch local vent stack; six to a three inch local vent stack; and 12 to a four inch local vent stack. In multiple installations, the connections between a bedpan washer local vent and a local vent stack shall be made by use of the tee or tee-wye sanitary pattern drainage fittings, installed in an upright position.
(3) 
Trap required. The bottom of the local vent stack, except when serving only one bedpan washer, shall be drained by means of a trapped and vented waste connection to the plumbing sanitary drainage system. The trap and waste shall be the same size as the local vent stack.
(4) 
Trap seal maintenance. A water supply of not less than 1/4 inch minimum tubing shall be taken from the flush supply of each bedpan washer on the discharge or fixture side of the vacuum breaker, trapped to form not less than a three inch seal, and connected to the local vent stack on each floor. The water supply shall be so installed as to provide a supply of water to the local vent stack for cleansing and drain trap seal maintenance each time a bedpan washer is flushed. Alternate method may be utilized with the approval of the Administrative Authority.
M. 
Sterilizer vents and stacks.
(1) 
Connections. Multiple installations of pressure and nonpressure sterilizers shall have their vent connections to the sterilizer vent stack made by means of inverted wye fittings. Such vent connections shall be accessible for inspection and maintenance.
(2) 
Drainage. The connection between sterilizer vent and/or exhaust openings and the sterilizer vent stack shall be designed and installed to drain to the funnel or basket-type waste fitting. In multiple installations, the sterilizer vent stack shall be drained separately to the lowest sterilizer funnel or basket type waste fitting or receptor.
N. 
Sterilizer vent stack sizes.
(1) 
Bedpan steamers. The minimum size of a sterilizer vent serving a bedpan steamer shall be 1 1/2 inches in diameter. Multiple installations shall be sized according to Table 860-192N(2), "Stack Sizes for Bedpan Steamers and Boiling Type Sterilizers."
(2) 
Stack sizes for bedpan steamers and boiling type sterilizers.
Table 860-192N(2)
Number of Connections of Various Sized Sterilizer Vent Stacks
Connection Size
Stack Size
1 1/2"
2"
1 1/2 inch1
1 or
0
2 inch1
2 or
1
2 inch2
1 and
1
3 inch1
4 or
2
3 inch2
2 and
2
4 inch1
8 or
4
4 inch2
4 and
4
NOTES:
1.
Total of each size.
2.
Combination of sizes.
(a) 
Boiling type sterilizers. The minimum size of a sterilizer vent stack shall be two inches in diameter when serving a utensil sterilizer, and 1 1/2 inches in diameter when serving an instrument sterilizer. Combinations of boiling type sterilizer vent connections shall be based on Table 860-192N(2), "Stack Sizes for Bedpan Steamers and Boiling Type Sterilizers."
(b) 
Pressure sterilizers. Sterilizer vent stacks shall be two and one-half inches minimum; those serving combinations of pressure sterilizer exhaust connections shall be sized according to Table 860-192N(2), "Stack Sizes for Pressure Sterilizers."
(c) 
Pressure instrument washer-sterilizer sizes. The minimum size of a sterilizer vent stack serving an instrument washer-sterilizer shall be two inches in diameter. Not more than two sterilizers shall be installed on a two-inch stack, and not more than four on a three-inch stack.
(3) 
Stack sizes for pressure sterilizers.
Table 860-192N(3)
Number of Connections of Various Sizes Permitted to Various Sized Vent Stacks
Connection Size
Stack Size
3/4"
1"
1 1/4"
1 1/2"
1 1/2 inches1
3 or
2 or
1
1 1/2 inches2
2 and
1
2 inches1
6 or
3 or
2 or
1
2 inches2
3 and
2
2 inches2
2 and
1 and
1
2 inches2
1 and
1 and
1
3 inches1
15 or
7 or
5 or
3
3 inches2
1 and
2 and
2
3 inches2
1 and
5 and
1
NOTES:
1.
Combination of sizes.
2.
Total of each size.
O. 
Radioactive materials. All radioactive materials shall be disposed of in a manner so as to create no hazard to operation and maintenance personnel of the institution or to the public. Specific permission shall be secured from the Administrative Authority to dispose of any radioactive material to the drainage system.
A. 
Water service. All hospitals shall have dual water services installed, where dual services are available; installed in a manner to provide an uninterrupted supply of water in case of a main break.
B. 
Hot water heater and tanks. The hot water heating equipment shall have sufficient capacity to supply six and one-half gallons of water at 125° F. per hour per bed for kitchens; four and one-half gallons of water at 180° F. per bed for laundry. The hot water storage tank or tanks shall have an adequate storage and heating capacity to satisfy the above needs. Consideration of dual water heating services should be given so as to provide an uninterrupted supply of hot water in the event one system is down for repair.
C. 
Hot water system. Hot water circulating mains and risers should be run from the hot water storage tank to a point directly below the highest fixture at the end of each branch main. Where the building is higher than three stories, each rise shall be circulated. Each main, branch main, riser and branch to a group of fixtures of the water system shall be valved.
D. 
Vacuum breaker installations.
(1) 
Hose connections. For ordinary hose connections the maximum height at which any hose is to be used shall be treated as its flood level.
(2) 
Low volume flows. Where low volume flows might cause leaking or spitting at the vacuum breaker parts, back pressure may be developed by installing an acceptable minimum orifice valve on the discharge side of the vacuum breaker. This shall be in addition to the regular control valve. This type of installation shall be subject to review and acceptance by the Administrative Authority before installation.
E. 
Prohibited water closet and clinic sink supply. No jet or water supplied orifices, except those supplied by the flush connection, shall be located in and/or connected with a water closet bowl or clinic sink. This section shall not prohibit an acceptable bidet installation.
F. 
Special equipment, water supply protection. Table 1803.6, "Fixtures and Their Water Supply Protection," sets forth the requirements which shall be followed in protecting the water supply for hospital fixtures against backflow or back-siphonage.
Table 860-193F
Fixtures and Their Water Supply Protection
Fixtures
Type of Protection1
Remarks
Aspirators:
Laboratory
Vacuum breaker
Portable
Vacuum breaker
Vacuum system
Vacuum breaker
Bedpan:
Washers
Vacuum breaker
Washer hose
Vacuum breaker
Locate 5 feet above floor
Boiling type sterilizer
Air gap
Not less than twice the effective opening of the water supply
Exhaust condenser
Vacuum breaker
Flush floor drain
Vacuum breaker
Hose connection
Vacuum breaker
Locate 6 feet above floor
Pressure instrument washer-sterilizer
Vacuum breaker
Vacuum system:
Cleaning
Air gap or vacuum breaker
Fluid suction
Air gap or vacuum breaker
NOTE:
1
Where vacuum breakers are used, they shall be installed after the last control valve.
G. 
Clinical, hydrotherapeutic and radiological equipment.
(1) 
All clinical, hydrotherapeutic, radiological, or any equipment, whether mentioned or not, which is water supplied and/or discharges to the waste system, shall meet the requirements of this section and the Code covering cross-connections, air gaps, vacuum breakers, and check valves.
(2) 
Special equipment and devices found under these classes include:
Clinical
Hydrotherapeutic
Radiological
Other
Dental cuspidors
Control Units
Violet Rays
Surgical cuspidors
Arm bath
Diagnostic X-ray
Dental (flush rim) lavatories
Leg bath
Therapy X-ray
Colonic irrigation
Foot bath
Sitz bath
Tub bath
X-ray transformers
Emergency bath
Immersion bath
X-ray oil tank
Receiving bath
Shower bath
Diffraction
Prenatal bath
Needle bath
Infant bath
Tank
X-ray developing
Prophylaxis
Pool
Photographic developing
Shampoo
Hose
Film developing Microscopic
Massage
Syringe Douche
H. 
Condensate drain trap seal. A water supply shall be provided for cleaning, flushing and resealing the condensate trap. The source of the water supply shall be a refrigerator condenser discharge, a drinking fountain waste, or other acceptable method of flushing and resealing the trap. The water supply shall be not less that 1/2 inch diameter pipe, and shall discharge through an air gap not less than twice the diameter of the supply pipe.
I. 
Valve leakage diverter. Each water sterilizer, which may be filled with water through directly connected piping, shall be equipped with an acceptable leakage diverter and/or bleed-line on the water supply control valve to indicate and conduct any leakage of unsterile water away from the sterile zone.
J. 
Water supply for fire protection.
(1) 
Stand pipe systems. The stand pipe system shall be installed as required by the Administrative Authority. Where no codes are in force, the stand pipe system should comply with the requirements of the National Board of Fire Underwriters, Pamphlet No. 14.
(2) 
Sprinkler system. Automatic sprinkler systems shall be installed in those area considered hazardous from a fire safety point of view. Such hazardous areas may include the soiled linen rooms, basement corridors, paint shops, wood working shops, trash rooms, storage rooms, accessible attics, laundry and trash chutes. Sprinkler systems should comply with the requirements of the National Fire Protective Association, Pamphlet No. 13.
Where oxygen systems are installed, the oxygen piping, outlets, manifold rooms and storage rooms should be installed in accordance with the requirements of the National Fire Bulletins No. 56 and 565.