Every park shall contain an electrical wiring system consisting of wiring, fixtures, equipment and appurtenances and shall be installed and maintained in accordance with the local electric power company's specifications, as well as applicable state and local codes regulating such systems.
A. 
Power lines shall be located underground.
B. 
All direct burial conductors or cable shall be buried at least 18 inches below the ground surface and shall be insulated and specially designed for the purpose. Such conductors shall be located not less than one foot radial distance from water, sewer, gas or communications lines.
Each mobile home lot shall be provided with an approved disconnecting device and overcurrent protective equipment. The minimum service per outlet shall be 120/240 volts AC, 100 amperes.
All exposed non-current-carrying metal parts of mobile homes and all other equipment shall be grounded by means of an approved grounding conductor run with branch circuit conductors of other approved method of grounded metallic wiring. The neutral conductor shall not be used as an equipment ground for mobile homes or other equipment.
All mobile home parks shall be furnished with lighting units so spaced and equipped with luminaires placed at such mounting heights as will provide adequate levels of illumination for the safe movement of pedestrians and vehicles at night, which shall not be less than an average 0.4 footcandle on each street.
A telephone distribution system shall also be installed with connection to each mobile home lot, in accordance with telephone company regulations.