Exciting enhancements are coming soon to eCode360! Learn more 🡪
Village of Freeport, NY
Nassau County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
Workmanship in the fabrication, preparation and installation of materials shall conform to generally accepted good practice
A. 
Protection at excavations. Until provision for permanent support has been made, excavations shall be properly guarded and protected so as to prevent the same from becoming dangerous to life or limb and shall be sheetpiled and braced, where necessary, by the person causing she excavation to be made to prevent adjoining earth from caving in.
B. 
Excavations of ten feet or less. When an excavation extends not more than 10 feet below the curb level, the owner of a structure, the safety of which may be affected by such excavation, shall preserve and protect the same from injury and, when necessary, shall underpin and support the same by proper foundation, and for such purpose he shall be permitted, if necessary, to enter upon the premises where such excavation is being made.
C. 
Excavations more than 10 feet deep. When an excavation extends more than 10 feet below the curb level, he person causing such excavation to be made shall, if afforded the necessary license to enter upon adjoining land, at his own expense, preserve and protect from injury every structure, the safety of which may be affected by such excavations and, when necessary, shall underpin and support the same by proper foundations, irrespective of the depth to which the foundations of such structure may extend. If the necessary license is not accorded to the person making the excavation, then it shall be the duty of the owner refusing such license to preserve and protect such structure from injury and, when necessary, to underpin and support the same by proper foundations, and for that purpose shall, if necessary, be permitted to enter upon the premises where such excavation is being made.
D. 
Support of party walls. In case there is a party wall along a lot line of the premises where an excavation is being made, the person causing the excavation to be made shall, at his own expense, preserve such party wall in as safe a condition as it was before the excavation was commenced and shall, when necessary, underpin and support the same by proper foundation.
E. 
Curb level. In case a structure is so located that the curb level to which it is properly referred is at a higher level than the curb level to which the excavation is referred, such part of any necessary underpinning or foundation as may be due to the difference in the curb levels shall be made and maintained at the joint expense of the owners of the adjoining premises at that point.
F. 
Superintendent of Buildings may act. If the person whose duty it shall be under the provisions of this code to properly guard and protect an excavation or to prevent adjoining earth from caving in or to preserve or protect any wall or structure from injury shall neglect or fail so to do after having had twenty-four-hours notice from the Superintendent of Buildings, such Superintendent may enter upon the premises and employ such labor and furnish such materials and take such steps as, in his judgment. may be necessary to prevent adjoining earth from caving in or to make such wall or structure safe and secure or to prevent the same from becoming unsafe or dangerous at the expense of the person whose duty it is to keep the same safe and secure. The Village or any person doing said work or any part thereof under and by direction of the Superintendent of Buildings may bring and maintain an action against the person last herein referred to to recover the value of the work done and materials furnished in and about said premises in the same manner as if he had been employed to do the work by said person.
G. 
Abandoned excavations. Whenever an excavation is made and the structure to be erected thereon has not been begun within 60 days and the excavation lacks a foundation wall of sufficient strength to retain the surrounding earth or the place is dangerous for any other reason such as lack of proper backfill, the excavation shall be considered abandoned. Such abandoned excavation may be ordered filled by the service of notice by the Superintendent of Buildings upon the owner of the plot upon which it is located in person or by mail to his latest known address as it appears on the Village tax rolls. If, thereafter, the owner fails to have the excavation filled within the time specified in the notice or within a reasonable time if no time is specified in the notice, the excavation may be filled by the Village and the cost thereof assessed against the property as a tax lien thereon after due notice to the owner and hearing as to the reasonableness of the cost thereof.
A. 
General requirements. Foundation walls, except those erected upon solid rock or upon wharves or piers on the waterfront and except those of dwellings or two-and-one half-story buildings of frame construction, shall be carried not less than four feet below the adjacent ground level and shall rest on solid ground or on level surface of rock or on files or ranging timbers when solid rock is not found. The foundation walls of dwellings or two-and-one-half-story frame buildings may be stopped at a depth of three feet below grade.
B. 
Footings.
(1) 
Materials. Footings consisting of stone, concrete, reinforced concrete or steel grillages shall be provided under foundation walls that rest on earth. Footings of wood, when permitted by the Superintendent of Buildings, may be used if they are entirely below permanent water level.
(2) 
Steel grillage footings. When steel grillage beams are used, they shall be provided with separators and bolts and shall rest on a proper concrete bed and shall be completely encased in concrete.
(3) 
Protection of metal. Where metal is incorporated in or forms part of a foundation, it shall be protected from rust by paint, asphalt, concrete or by such materials and in such manner as may be approved by the Superintendent of Buildings.
(4) 
Pressure under footings. For the loads exerting pressure under the footings of foundation walls, the full dead loads and the assumed live loads from all floors on the lowest tier of columns, piers or walls shall be taken.
(5) 
Design. Footings shall be so designed that the pressure they produce on the soil per unit of area shall be uniform as far as possible under all parts of the foundation walls, and such pressures shall not exceed the bearing capacity of the soil. In proportioning the areas of footings, the dead loads alone shall be considered; provided, however, that in no case shall the full dead loads, plus the reduced live loads exceed the bearing capacity of the soil.
C. 
Pile foundations.
(1) 
Resistance and method of driving.
(a) 
Piles which are to be used to sustain all of a structure or any part thereof shall be driven to a resistance satisfactory to the Superintendent of Buildings by such methods as will not impair their strength and as will ensure the retention of that resistance.
(b) 
Piles shall be held in correct location during driving. No load shall be permitted upon a pile broken prior to or during driving. If any pile is driven out of plumb more than 2% of the pile length, the design of the foundation shall be modified to support lateral forces properly and additional piles shall be driven if necessary.
(2) 
Loads on piles.
(a) 
The following formula may be used as an approximate indication of the allowable load on any pile not driven to rock, except that in no case shall the maximum allowable loads for the various types of piles be exceeded.
For drop hammers:
For single-acting hammers:
Where
P = the allowable load on the pile in pounds.
W = the weight of the striking part of the hammer in pounds.
H = the fall, in feet, of the striking part of the hammer.
S = the average penetration, in inches, under the last five blows after the pile has been driven to a point where successive blows produce equal penetration.
(b) 
When a double-acting steam hammer is used in which steam or compressed air is employed to increase the blow of the driving ram, the term "W" shall be equal to the weight of the driving ram, plus the area of the piston multiplied by the mean effective pressure of the steam or compressed air on the piston during the stroke, but "W" shall not exceed the total weight of the hammer.
(3) 
Tests of sustaining of power of piles. Where any doubt exists as to the safe sustaining power of the piles, the Superintendent of Buildings may order loading tests of individual piles or groups of piles to be made at the expense of the owner of the proposed structure or of the person causing the piles to be driven. Tests shall be made with 150% of the proposed load and shall be considered unsatisfactory and the result unacceptable, if, after standing 24 hours, the total net settlement after deducting rebound is more than 0.01 inch per ton of total test load. The record of every test shall be filed with the Department.
(4) 
Jetting of piles. Exterior jetting of piles shall be permitted only by special permission of the Superintendent of Buildings. If conditions require jetting, such conditions shall be fully set forth in the application and such permission requested. If jetting is used, it shall be carried out in such a manner that the carrying capacities of piles already in place shall be unimpaired.
(5) 
Wood piles.
(a) 
Wood piles shall be of dense or sound grade southern pine, structural or common grade douglas fir, spruce, mixed hardwoods or other species approved for such use. Piles shall be of sound timber and free from wind shakes, short or reversed bends. They shall be cut above the ground swell, shall have a reasonably uniform taper and shall be so straight that a line between the center of the point and the center of the butt shall not depart from the body of the pile more than 1% of the length of the pile. The least diameter at the point of the pile shall be six inches. The least diameter of the butt of a pile shall be 12 inches, except that where a pile is less than 25 feet in length, it may be 10 inches or more in diameter. Measurements shall be taken under the bark. The minimum total penetration of any pile shall be 12 feet.
(b) 
Piles, other than those used as foundations for wood frame structures over submerged or marsh lands, shall be cut off below permanent water level. Piles used as foundations for wood frame structures over submerged or marsh lands shall be impregnated with creosote or other preservative as approved by the Superintendent.
(c) 
The maximum allowable load on a wood pile having a six-inch point shall be 15 tons and on a pile having a point of eight inches or over 20 tons.
(d) 
Nothing in this section shall prohibit the use of piles with a butt at least eight inches in diameter when, in the opinion of the Superintendent of Buildings, such is adequate, in the case of a light private dwelling.
(6) 
Concrete filled steel piles.
(a) 
Piles consisting of concrete steel tubes shall have a minimum inside diameter of 10 inches and a shell thickness of at least 3/8 inch, except that ten-and-twelve-inch piles may have a shell thickness of 5/16 inch. The concrete shall be of a mixture at least equal to reinforced concrete as specified in § 86-47D(3). The ends of each tube shall be perpendicular to its axis, and all bearing surfaces shall be smooth and true-cut by an approved method. Splices shall be of such material and design as to assure good alignment of tubes. If splices below the upper splice are closer together than 20 feet, a 5% reduction in load values shall be made for each additional splice used.
(b) 
Where the borings indicate that piles will be less than 60 feet in length, the maximum designed outside diameter of the tube shall be at least 1/40 of the length. If, as actually driven, such piles exceed 40 diameters in length, a one-percent reduction in load shall be made for each diameter of excess length. Where borings indicate that the piles will be 60 feet or more in length, the minimum diameter shall be 18 inches and the minimum shell thickness shall be 1/2 inch, and no reduction from the allowable loading need be made for the slenderness ratio.
(c) 
After driving, the inside of the tube shall be cleaned of any foreign matter before placing the concrete filling. When tubes exceed 50 diameters in length, the concrete in the tube below the upper 50 diameters shall be deposited with a tremie or fully lowered bottom-dump bucket. The concrete shall never be placed through water except on specific written approval of the Superintendent of Buildings after submission of the detailed method of procedure.
(d) 
The allowance load on any such pile when driven to bedrock shall not exceed 500 pounds per square inch on the concrete and 7,500 pounds per square inch on the steel, provided that in computing the effective area of the steel, the outer 1/16 inch of thickness shall be deducted from the thickness of the tube. When driven open-ended to refusal in boulders or a mixture of gravel and boulders with no softer material underlying, the maximum unit loads shall be 50% of the above values. Piles so used shall be spaced at least 20 inches, plus the diameter of the tube.
(7) 
Piles cast in place.
(a) 
Concrete piles cast in place shall be so made and placed as to ensure the exclusion of any foreign matter and to ensure a continuous and full size pile. Piles shall be driven in such order and with such spacing as to ensure against distortion or injury to the finished pile. Concrete shall be of a mixture at least equal to reinforced concrete, as specified in § 86-47D(3), and shall be placed in the dry and shall not be placed in a form containing water. The average diameter of such piles shall be at least 11 inches, and the diameter of the point shall be at least eight inches.
(b) 
The maximum load for cast-in-place piles shall be 30 tons. When not driven to rock or hardpan, their carrying capacities shall be determined by test.
(8) 
Precast concrete piles.
(a) 
Concrete piles moulded and cured before driving shall be designed and reinforced to permit handling and driving them without injury. Reinforcing steel shall be so located that it will be covered by at least two inches of concrete. The diameter or least lateral dimension of such piles shall be 10 inches or more at the point and shall average at least 12 inches throughout the length of the pile for piles up to 20 feet, 14 inches for piles up to 30 feet and 15 inches for piles up to 40 feet. For piles over 40 feet in length, the diameter or least lateral dimension shall be 1/35 of the length, except that all piles shall be at least 15 inches and shall not be required to exceed 24 inches in diameter or least lateral dimension.
(b) 
The concrete shall be of a mixture at least equal to reinforced concrete as specified in § 86-47D(3).
(c) 
Piles shall be reinforced with longitudinal reinforcing at least equal to 2% of the volume of the concrete in the pile, together with lateral reinforcing in the form of hoops or spirals, at least one-fourth-inch round rods or wire, spaced 12 inches on centers throughout the length of the pile, except the bottom and top three feet where this spacing shall be reduced to three inches.
(d) 
The maximum allowable load, in tons, shall not exceed two times the average diameter or least lateral dimension in inches, but shall not exceed 40 tons in any case. The center-to-center spacing of piles shall be one inch per ton of load, but not less than 30 inches. Average penetration shall be at least 10 feet.
A. 
Materials. Foundation walls shall be built of approved masonry, reinforced concrete or steel encased in masonry, provided that no hollow blocks of burnt clay shall be used unless they are vitrified or are salt-glazed, except for surfaces in contact with mortar.
B. 
Thickness.
(1) 
Foundation walls shall be of adequate strength and thickness to resist lateral pressures from adjacent earth and to support their vertical loads and shall be at least of the same thickness as the wall next above.
(2) 
If built of rubble stone, the thickness shall not be less than 18 inches. If built of brick, concrete or hollow building blocks, the thickness shall be not less than 12 inches, provided that when such walls for dwellings do not extend more than five feet below adjacent ground level, the minimum thickness shall be eight inches.
C. 
Hollow building blocks.
(1) 
Foundation walls of hollow building blocks may be used only when the upper walls are of frame or hollow building block construction.
(2) 
When required for stability or for other reasons, the hollow spaces in the blocks shall be filled as the construction progresses with concrete of a mixture as specified under § 86-47D(2).
A. 
Construction. Walls built to retain or support adjoining earth or rock shall be constructed of approved masonry or reinforced concrete of adequate strength and stability.
B. 
Hydraulic head. Unless provision is made to drain off water, a hydrostatic pressure, due to a head equal to the height of the wall, shall be assumed.
C. 
Soil pressure. The maximum pressure on the soil under such walls shall not exceed the safe bearing capacities as specified in § 86-54.
A. 
Materials. Approved masonry shall be constructed of brick, stone, concrete or hollow building blocks or a combination of these materials as provided in this article.
B. 
Protection against freezing. Unless adequate precautions against freezing are taken, no masonry shall be built when the temperature is below 28° F. on a rising temperature or 32° F. on a falling temperature at the point where work is in progress. The use of any frozen material or building upon any frozen masonry or frozen soil is forbidden.
C. 
Erection of walls and piers.
(1) 
In each story, the walls shall be carried up full thickness to the top of the beams above.
(2) 
Except when carried independently by girders at each floor, no wall shall be built up more than two stories in advance of any other portions of the walls of the buildings.
(3) 
All walls that meet or intersect shall be adequately bonded or anchored. Piers having less than four square feet of cross section, when located at an intersection with a wall, shall be bonded into and built as part of that wall.
D. 
Piers.
(1) 
Every pier supporting a girder, arch or column or a lintel carrying a wall over an opening of more than 10 feet shall be built of approved masonry.
(2) 
Isolated piers shall not exceed, in height, 10 times their least dimension and, if built of brick, shall be so bonded as approved by the Superintendent of Buildings.
E. 
Arches and lintels.
(1) 
Openings in walls shall be spanned by a lintel or arch of incombustible materials.
(2) 
Where steel or reinforced masonry lintels are used, they shall be of such strength that the maximum deflection is 1/360 of the clear span and shall have at least five inches of bearing on each end and shall rest upon solid bearing.
(3) 
Lintels of manufactured or natural stone shall be of sufficient strength to carry the superimposed load without deflection.
(4) 
Masonry mullions less than 12 inches in width on either face of the wall shall be suitably reinforced or doweled if of stone.
(5) 
Masonry arches shall have at least one-inch rise for each foot of span and shall be so designed as to carry the superimposed load. Proper provision shall be made for resisting lateral thrust.
F. 
Timber in walls.
(1) 
No timber, except nailing blocks not exceeding an ordinary brick in size, shall be placed in masonry walls, provided that in nonfireproof construction, timber lintels may be placed over openings on the inside of the wall, resting at each end not more than two inches on the wall and chamfered or cut to serve as centers for rowlock or keyed arches.
(2) 
No masonry shall be supported on wood girders or other form of wood construction.
G. 
Bracing during construction. The walls and beams of every structure during erection or alteration shall be strongly braced from the beams of each story and, when required, shall also be braced from the outside until the structure is enclosed.
H. 
Anchorage of masonry walls.
(1) 
Masonry walls shall be anchored to each tier of joists or beams bearing on them, at maximum intervals of four feet, by metal anchors having a minimum cross section of 1/4 inch by 1 1/4 inches and at least 16 inches long, securely fastened to the joists or beams and provided with split and upset ends or other approved means for building into masonry.
(2) 
Masonry walls parallel to joists or beams shall be provided with similar anchors, at maximum intervals of six feet, engaging three joists or beams. Girders shall be similarly anchored at their bearings. Upset and T-ends on anchors shall develop the full strength of the anchor strap.
I. 
Brick masonry.
(1) 
Bonding of solid masonry walls. In solid brick walls there shall be the equivalent of at least one full header course for each six courses of each wall surface. Where facing brick is used of a different thickness from the brick used for backing, the courses of the facing brick and backing shall be brought to a level at least once in each six courses in the height of the backing, and the facing brick shall be properly tied to the backing by a full header course of the facing brick or other approved method. Facing brick shall be laid at the same time as the backing. In walls more than 12 inches thick, the inner joints of header courses shall be covered with another header course which shall break joints with the courses below.
(2) 
Wetting of brick. All brick having an appreciable absorption shall be thoroughly wet before laying.
(3) 
Joints in solid masonry walls. All horizontal and vertical joints in brick masonry shall be filled with mortar.
J. 
Stone masonry. Stone masonry walls shall be anchored as specified in § 86-60H, except that anchors for bearing walls shall be at least three feet long and at least 1/4 inch by two inches in section. All stone shall be laid in cement or cement-lime mortar, and all joints and spaces shall be thoroughly filled. Natural stone shall be laid in the masonry on its natural bed. Rubble stone walls shall be at least four inches thicker than required for solid bearing walls and shall not be used in structures over 60 feet high.
K. 
Construction of hollow walls.
(1) 
Hollow block walls.
(a) 
Where walls of hollow building blocks are decreased in thickness, the blocks in the top course of the thicker wall shall be filled solidly with concrete or covered with slabs of hardburned terra cotta or concrete at least one inch in thickness.
(b) 
Terra cotta, concrete or steel templates of approved size and thickness shall be placed under all floor beams and girders to properly distribute the loads.
(c) 
In walls built only one unit in thickness, each unit shall break joints with those next above. When more than one unit is required to produce a given wall thickness, the units shall break joints with the units next above and shall be laid with a masonry bond equivalent to one course of headers to each course of stretchers.
(d) 
For nonbearing interior partitions of one story or less in height and constructed of units to be left exposed on one or both sides for architectural effect, these bonding requirements may be waived.
(e) 
Hollow block walls shall be anchored as specified in Subsection H, except that all anchors shall be galvanized or of noncorroding metal.
(f) 
Where hollow units are set with the cells horizontal, they shall be set in a full bed of mortar 1/2 inch or less in thickness and with vertical joints buttered full on shells and webs. Where hollow units are set with the cells vertical, the bearing members shall be buttered and vertical joints slushed full of mortar.
(2) 
Hollow walls of solid masonry units. At points where wall thicknesses decrease in hollow walls of solid masonry units, a course of solid masonry shall be interposed between the wall section below such point and that next above. Anchorage requirements shall be the same as for hollow block walls. Other construction requirements shall conform with Subsection I.
(3) 
Limitation of hollow walls. Hollow walls of brick or walls of hollow block shall not be used as bearing walls in structures exceeding 40 feet or three stories in height and, except in buildings of one story in height or of frame construction, shall not be used as party walls.
L. 
Ashlar facing.
(1) 
Stone, architectural terra cotta or other approved material used for the facing of a wall shall have a thickness of not less than 1/8 of the height of the unit, but in no case less than 3 3/4 inches.
(2) 
Facings of brick or solid structural units shall be bonded into the backing with headers or stretchers at least four inches thicker than the facing, the equivalent of 1/6 of the area of the wall.
(3) 
Stone ashlar facing shall have at least 20% of the superficial area not less than four inches thicker than the remainder of the facing to form bond stones, which shall be uniformly disposed in the wall.
(4) 
In stone ashlar, every stone that is not a bond stone and every stone that projects wholly or partly beyond the face of the wall shall be securely anchored to the backing with at least one noncorroding metal anchor at least 3/16 inch by one inch or the equivalent in cross-sectional area.
(5) 
Faced walls shall be at least as thick as required for masonry walls of the material forming the backing.
M. 
Veneer.
(1) 
Masonry veneer shall consist of bricks, stone, concrete, terra cotta, hollow building blocks or other approved material.
(2) 
Such veneer shall rest directly upon a foundation wall or upon other approved masonry or reinforced concrete or steel.
(3) 
It shall be securely attached with noncorroding ties at intervals of not more than 16 inches vertically and 24 inches horizontally to the wall or, in the case of frame construction, to approved sheathing combined with a weatherproof lining.
(4) 
Flashing to prevent moisture from penetrating behind the veneer shall be provided at wall openings. All wood sills must be protected by weatherproof lining or flashing.
(5) 
In all cases, the veneering shall be excluded in calculating the bearing wall thickness and the required thickness of the wall. The maximum height of veneering on walls, other than panel or enclosure walls, shall be 40 feet above the foundations.
N. 
Stucco.
(1) 
Stucco for frame construction shall consist of cement mortar on expanded metal lath weighing not less than 3 4/10 pounds per square yard or on woven or welded wire lath not lighter than No. 19 gauge.
(2) 
Stucco shall be kept at least eight inches above adjacent ground surfaces.
(3) 
Flashing to prevent moisture from penetrating behind the stucco shall be provided at wall openings.
O. 
Mortar.
(1) 
In masonry construction, no mortar other than cement mortar shall be used in footings, foundation walls or rubble stone walls.
(2) 
No mortar, other than cement mortar or cement-lime mortar, shall be used in hollow walls of brick, hollow building block masonry, chimneys, backing of walls faced with ashlar, exterior walls in skeleton construction, curtain walls, parapet walls, isolated piers or linings of existing walls.
P. 
Wall thickness.
(1) 
Thickness of solid bearing walls.
(a) 
The thickness, in inches, of solid masonry bearing walls for the respective story heights, except in private dwellings 35 feet or legs in height and except as otherwise provided in this subsection, shall be at least:
8
12
7
12
12
6
12
12
12
5
12
12
12
12
4
16
12
12
12
12
3
16
16
12
12
12
8
2
16
16
16
12
12
12
8
1
20
16
16
16
12
12
12
8
Stories
8
7
6
5
4
3
2
1
(b) 
For calculation of wall thicknesses, 13 feet shall be assumed as the maximum height of a story.
(c) 
No twelve-inch wall shall exceed four stores of 55 feet in height.
(d) 
When the clear span between bearing walls or between a bearing wall and an intermediate support is more than 26 feet, much wall shall be increased four inches in thickness for each 12 1/2 feet or fraction thereof that such span is in excess of twenty.six feet, except where such bearing walls are adequately reinforced by buttresses.
(2) 
Thickness of interior walls in residence structures.
(a) 
The thickness, in inches, of interior bearing walls, with bearing on both sides, in residence structures for the respective story heights shall be at least:
6
8
5
8
8
4
8
8
8
3
8
8
8
8
2
12
8
8
8
8
1
12
12
8
8
8
8
Stories
6
5
4
3
2
1
(b) 
Where interior walls in residence structures have bearing on one side only or are nonbearing, the required thickness, in inches, shall be eight inches for the uppermost 55 feet of wail height and 12 inches below the fifty-five foot distance from the top of the wall, provided that no eight-inch wall shall be over five stories in height.
(c) 
Where wood floor and roof beams bear on both sides, such beams shall be staggered on the bearing wall and there shall be at least three inches of masonry between any two such wood beams.
(d) 
The maximum length of such bearing and non-bearing walls between cross walls, cross bracing, piers or buttresses shall be 30 feet.
(3) 
Solid masonry walls above roof levels. Solid masonry walls above roof levels, 12 feet or less in height, enclosing stairways, elevator shafts, penthouses or bulkheads shall be at least eight inches thick and may be considered as neither increasing the height nor requiring any increase in the thickness of the wall below, provided that the allowable working stress requirements are met.
(4) 
Solid masonry walls for private dwellings. In any private dwelling, bearing walls of brick, including party walls, may be eight inches in thickness, provided that such dwellings are not more than 35 feet in height and that the eight-inch walls do not exceed 50 feet in length between cross walls or adequate buttresses, except that when the walls are not pierced by openings of any kind, such length may be 60 feet.
(5) 
Eight-inch solid masonry walls.
(a) 
In one-story buildings, the walls may be eight inches in thickness, provided that no such wall shall exceed 50 feet in length between cross walls or adequate buttresses.
(b) 
Outside of the fire limits, buildings not exceeding 30 feet or two stories in height, the walls of which under this code could be of frame construction, may be eight inches in thickness, provided that no such wall shall exceed 50 feet in length between cross walls or adequate buttresses.
(c) 
When the clear span between bearing walls or between a bearing wall and an intermediate support is more than 26 feet, such wall shall be increased four inches in thickness for each 12 1/2 feet or fraction thereof that such span is in excess of 26 feet, except where such walls are adequately reinforced by buttresses.
(6) 
Increased thickness of masonry walls.
(a) 
The thickness of masonry walls shall conform to the provisions of this subsection and shall in all cases, irrespective of other requirements of this section, be sufficient to keep the stresses in the masonry within the working stresses prescribed in § 86-53.
(b) 
The maximum percentage of openings in any horizontal section of bearing wall shall be 50% of the gross sectional area when cement mortar is used and 35% when other mortars are used, except upon the following conditions: that the thickness of the wall be increased four inches for each 15% or fraction thereof of increased opening area in excess of 50% or 35% respectively, and, in all cases, the total percentage of openings shall be less than 75% or the horizontal sectional area of the wall.
(c) 
The total thickness of any wall whose thickness is increased in accordance with the requirements of this section shall be governed by that requirement producing the maximum thickness.
(7) 
Bracing of masonry walls. Masonry walls in structures, except as otherwise provided in this subsection, shall be braced either horizontally or vertically at right angles to the wall face at maximum intervals of 20 times the wall thickness. Horizontal bracing may be obtained by floors or roofs. Vertical bracing may be obtained by cross walls, wall columns or buttresses or by increasing the wall thickness.
(8) 
Masonry walls in skeleton construction.
(a) 
Panel walls of masonry in skeleton frame structures shall be at least eight inches thick if constructed of solid masonry or at least 12 inches thick if constructed of hollow masonry or at least 10 inches thick if constructed of a combination of hollow and solid masonry, except that spandrel and apron walls may be eight inches thick or may be of materials or of assemblies of materials other than masonry meeting the requirements of this article. Combinations of hollow and solid masonry shall be constructed with at least four inches of solid masonry on the exterior face. The maximum height between supports of such walls when constructed of these minimum thicknesses shall be 13 feet. When such walls exceed 13 feet in height, they shall be increased two inches in thickness for each 6 1/2 feet or fraction thereof.
(b) 
Panel walls shall be bonded or otherwise so secured to the structure as to furnish adequate lateral support to the wall.
(c) 
Exterior nonbearing enclosure walls anchored to columns, piers or floors, but not built between columns or piers nor wholly supported at each story in skeleton construction, shall meet all the requirements for height, thickness and type of construction required for bearing walls.
(9) 
Masonry curtain walls.
(a) 
Curtain walls of solid masonry shall be at least eight inches thick for the uppermost 13 feet and at least 12 inches thick for the next 52 feet or fraction thereof below and shall be increased in thickness four inches for each succeeding 60 feet or fraction thereof below.
(b) 
When built of masonry, other than solid masonry, they shall be at least 10 inches thick for the first 13 feet, 12 inches thick for the next lower 39 feet and shall be increased four inches in thickness for each 39 feet or fraction thereof next below, provided that the maximum horizontal distance between lateral supports shall be 20 feet. When the distance between the lateral supports exceeds 20 feet, the thicknesses of all walls specified in this section shall be increased four inches for each additional 10 feet or fraction thereof between lateral supports. Curtain walls of hollow masonry 12 inches or more in thickness shall be made of at least two bonded units.
(10) 
Thickness of hollow bearing walls.
(a) 
Bearing walls of hollow block masonry in structures not exceeding 40 feet or three stories in height, except as hereinafter provided, shall be not less than 10 inches in thickness for the uppermost 20 feet of their height and 12 inches in thickness below that.
(b) 
When hollow walls of solid masonry units are used as bearing walls in structures not exceeding 40 feet or three stories in height, they shall be not less than eight inches in thickness for the uppermost 10 feet of their height and 12 inches in thickness below that.
(c) 
In any private dwelling, hollow bearing walls not less than eight inches in thickness may be used in place of solid masonry bearing walls as specified in Subsection P(4).
(d) 
In one and two-story buildings, the walls of which under this code could be of frame construction, hollow bearing walls not less than eight inches in thickness may be used in place of solid masonry bearing walls as specified in Subsection P(5).
(e) 
All wall thicknesses given in this section are minimum thicknesses, and all hollow bearing walls shall comply with all requirements governing increases in thickness of solid bearing walls as provided in Subsection P(1) and (6).
(11) 
Party and fire walls.
(a) 
Party walls may be of any type of masonry provided for herein and shall comply with all the requirements of bearing walls.
(b) 
No party wall shall be loaded on either side to more than 50% of its allowable loading.
(c) 
Fire walls of masonry and party walls which function also as fire walls shall meet all the requirements for fire walls as specified in Article XI.
Q. 
Existing walls.
(1) 
Use of existing walls. Walls heretofore built, whose thickness at the time of their erection was in accordance with the requirements of the then existing laws but which are not in accordance with the requirements of this article, may be used without change, if in good condition, in buildings hereafter erected or altered, provided that the stresses in the masonry do not exceed the working stresses prescribed by this code and the height of such walls is not increased, except insofar as may be necessary to make the height uniform.
(2) 
Lining of walls. In case it is desired to use and increase the height of an existing wall, which is less in thickness than required by this code, such wall shall be reinforced by a lining of brickwork so that the combined thickness with the old wall shall be not less than four inches more than the thickness required for a new wall corresponding with the total height of the wall when increased in height, provided that such lining shall not be used to a greater height than 40 feet, and that such wall shall not be increased to exceed 75 feet in height. Such lining shall be supported on proper foundations and shall be not less than eight inches in thickness and thoroughly anchored to the old wall with suitable anchors placed two feet apart and properly fastened or driven into the old wall in rows alternating vertically and horizontally with each other, the old wall being first cleaned of plaster or other coating where any lining is to be built against the same. No wall, however, shall be lined, unless in good condition, and not until the approval of the Superintendent of Buildings has been given.
R. 
Parapet walls.
(1) 
Every open area of any roof permitted to be used by occupants for any purpose and every area of a roof used as a means of exit shall be protected, in a manner approved by the Superintendent of Buildings, by a parapet wall or a guardrail not less than three feet six inches in height above the level of such area.
(2) 
Exterior or division walls of masonry, other than fire walls, over 15 feet high in nonfireproof structures shall have parapet walls carried two feet above the roof, except in residence structures and detached structures with overhanging roofs or where such walls are to be finished with cornices or gutters.
(3) 
Parapet walls shall be of the same thickness as the wall below, except that in no case shall a thickness of more than 12 inches be required.
(4) 
Residence structures shall have parapet walls carried at least two feet above the roof with the following exceptions:
(a) 
Parapet walls between structures of the same height and 40 feet or less in height shall extend at least eight inches above the roof.
(b) 
Party walls in structures, the roofs of which pitch at an angle of 30° or more from the horizontal, may stop at the top of the roof boards, provided that no combustible material passes through the wall and that the junction of roof and wall is thoroughly fire-stopped.
(c) 
Fire partition walls for the purpose of subdividing nonfireproof residence structures may be carried to the bottom of the roof boards and thoroughly grouted with cement mortar.
(5) 
When parapet walls function as parts of party or fire walls, they shall conform to the requirements for such walls.
S. 
Chases and recesses.
(1) 
Chases in eight-inch walls or within the required area of any pier are prohibited. The maximum depth of any permitted chase in any wall shall be 1/3 of the wall thickness. The maximum length of any horizontal chase without suitable structural support shall be four feet, and the maximum horizontal projection of any diagonal chase shall be four feet.
(2) 
Recesses shall have at least eight inches of material at the back.
(3) 
The maximum aggregate area of recesses and chases in any wall shall be 1/4 of the whole area of the face of the wall in any story, except that for stairs, elevators and dumbwaiters, the walls, including foundation walls behind such facilities, may be reduced to 12 inches.
(4) 
Chases or recesses in fire walls, fire partitions and in fire protection of structural members, which would reduce the thickness below the minimum specified in this code, are prohibited.
(5) 
Chases and recesses may be built into hollow walls and walls constructed of hollow block or tile, but the cutting of chases or recesses in walls of these types of construction is prohibited.
A. 
Basis of designs. The design of reinforced concrete members shall be based on the generally accepted theory of flexure as applied to reinforced concrete and shall be in accordance with the requirements of this code.
B. 
Span length.
(1) 
The span length of freely supported beams and slabs shall be the clear span, plus the effective depth of beam or slab, but shall not exceed the distance between centers of the supports.
(2) 
The span length for continuous or restrained beams built to act integrally with supports shall be the clear distance between faces of supports.
(3) 
For continuous or restrained beams having brackets to act integrally with both beam and support and at least as wide as the beam and making an angle of 45° or more with the horizontal, the span shall be measured from the section where the combined depth of the beam and bracket is at least 1/3 more than the depth of the beam. No portion of such a bracket shall be considered as adding to the effective depth of the beam. Brackets making an angle of less than 45° with the horizontal may be considered as increasing the effective depth of the beam, but not as decreasing the span length.
(4) 
Maximum negative moments are to be considered as existing at the ends of the span as defined above.
C. 
Depth of beams or slabs and minimum thickness of slabs.
(1) 
The effective depth of the beam or slab shall be taken as the distance from the centroid of the tensile reinforcement to the top surface of the structural slab.
(2) 
The minimum thickness of reinforced concrete floor slabs shall be 3 1/2 inches or four inches when finished monolithically, and roof slabs shall be at least 3 1/2 inches thick, except as specified in Subsection E.
(3) 
The minimum thickness of reinforced concrete for mansard roofs, dormers, roofs of bulkheads and all roofs having a slope of more than 30° from the horizontal shall be three inches.
(4) 
Topping of approved incombustible materials may be included in the minimum thickness required for fire resistance of slabs.
(5) 
See also § 86-71B, Concrete floor and roof construction.
D. 
T-beams. In T-beam construction, the slab shall be built integrally with the beam. The effective flange width of symmetrical T-beams shall not exceed 1/4 of the span length of the beam, and its overhanging width on either side of the web shall not exceed eight times the thickness of the slab nor 1/2 the clear distance to the next beam.
E. 
Ribbed floor construction.
(1) 
Ribbed floor construction includes floor systems with slabs and ribs placed monolithically between permanent or removable fillers in which the ribs are spaced 30 inches or less from face to face. The ribs shall be straight, at least four inches in width and of a maximum clear depth of three times the average width.
(2) 
When concrete or scored burnt clay tile is used, the thickness of the slab shall be at least 1/12 of the clear distance between the ribs with a minimum of 1 1/2 inches. Where such tile is of strength at least equal to that of concrete and the joints are staggered, the shells in contact with the concrete may be included in the resisting sections. In two-way construction, provided that the tile filler is completely surrounded by concrete ribs as specified, the exterior shells of the tile in contact with the concrete may be used for strength calculations for shear and bending, and where the top slab is not required for strength, such top slabs may be omitted, provided that the construction is protected by at least two inches of incombustible material.
(3) 
When removable forms or fillers not complying with the requirements of the preceding paragraph are used, the thickness of the slab shall be at least 1/10 of the maximum clear distance between the ribs with a minimum thickness of three inches in structures where the minimum required live load is 60 pounds per square foot or less and 3 1/2 inches where the minimum required live load exceeds 60 pounds per square foot. Where the underside of the floor construction is protected by a ceiling of metal lath and plaster at least 7/8 inch thick, these thicknesses may be decreased by one inch.
(4) 
Conduits or pipes shall not be buried in the slab, except where expressly permitted by the Superintendent of Buildings, and in such latter cases under the following conditions only: where the slab contains conduits or pipes, the thickness shall be at least one inch, plus the total overall depth of such conduits or pipes at any point. Such conduits or pipes shall be so placed as not to reduce the strength of the construction.
F. 
Shrinkage and temperature reinforcement. Reinforcement for shrinkage and temperature stresses normal to the principal reinforcement shall be provided in floor and roof slabs where the principal reinforcement extends in one direction only. Such reinforcement shall be spaced at most 18 inches in floors and 12 inches in roofs. The area, per foot of width, shall be at least 0.073 square inches for floors and 0.11 square inches for roofs.
G. 
Types of web reinforcement.
(1) 
Web reinforcement may consist of any one of the following types or any combination of them:
(a) 
Vertical stirrups or web reinforcing bars.
(b) 
Inclined stirrups or web reinforcing bars forming an angle of 30° or more with the axis of the beam.
(c) 
Longitudinal bars bent up at an angle of 15° or more with the axis of the beam.
(2) 
Stirrups or bent-up bars to be considered effective as web reinforcement shall be anchored at both ends according to the provisions of Subsection I.
H. 
Spacing of stirrups. Where the shearing stress of any section is equal to or less than S5 and greater than S4, the maximum distance between two consecutive stirrups, measured normal to the direction of stirrups, shall be 3/4d, and when the shearing stress exceeds S5, the maximum distance between two consecutive stirrups, measured normal to the direction of stirrups, shall be 3/8d.
I. 
Anchorage of web reinforcement.
(1) 
Web reinforcement shall be anchored at both ends by one of the following methods or a combination of them, but only anchorage meeting the requirements of Subsection I(1)(a), (b) or (c) shall be used for shearing stresses in excess of S5.
(a) 
Providing continuity with the main longitudinal reinforcement.
(b) 
Bending around the longitudinal bar or steel shape.
(c) 
A hook which has a radius or bend at least four times the diameter of the web bar.
(d) 
A length of embedment sufficient to develop the stress in the stirrup by bond as provided below, provided that the other end of the stirrup is anchored as in Subsection I(1)(a).
(2) 
The end anchorage of a web member not bearing on the longitudinal reinforcement shall be such as to engage an amount of concrete sufficient to prevent the bar from pulling out. In all cases, the stirrups shall be carried as close to the upper and lower surfaces as fireproofing requirements permit.
(3) 
The stress in a stirrup or web reinforcement bar shall be less than a value equal to the surface area of the bar embedded within the upper or lower 1/2 of the beam multiplied by S10 for plain bars or S11 for deformed bars, except that when wire fabric is used for web reinforcement, it shall have welded intersections at maximum intervals of six inches, but, in any case, the maximum stress shall be 16,000 pounds per square inch.
J. 
Reinforced concrete columns.
(1) 
Limiting dimensions. Principal reinforced columns in buildings shall have a minimum total thickness of 12 inches. Posts that are noncontinuous from story to story shall have a minimum total thickness of six inches.
(2) 
Unsupported length of columns.
(a) 
The unsupported length of reinforced concrete columns shall be taken:
[1] 
In flat slab construction, as the clear distance between the floor and underside of the capital.
[2] 
In beam and slab construction, as the clear distance between the floor and the underside of the shallowest beam framing into the column at the next higher floor level.
[3] 
In floor construction with beams in one direction only, as the clear distance between floor slabs.
(b) 
When reinforced concrete brackets are used at the junction of beams or struts with columns, the clear distance between supports may be considered as reduced by the depth of the bracket, provided that the width of the bracket is at least equal to that of the beam and at least 1/2 of the column.
(3) 
Columns with longitudinal and spiral reinforcement.
(a) 
The permissible axial load (P) on columns reinforced with longitudinal bars and closely spaced spiral hooping enclosing a circular core shall be determined by the following formula:
P = Ac fc (1 plus 15p plus 50p')
where
fc does not exceed S15 or, in any case, 850 pounds.
Ac = area of core of spirally-hooped column measured to the outside diameter of the spiral.
p = ratio of effective area of longitudinal reinforcement to the area of concrete core.
p' = ratio of volume of lateral reinforcement to the volume of concrete core.
(b) 
The minimum longitudinal reinforcement shall be 0.0075 of the gross area of the column, and the maximum longitudinal reinforcement shall be 0.04 of the gross area of the column. The minimum volume of spiral reinforcement shall be twenty-five hundredths of the volume of vertical reinforcement but, in any case, at least 0.005 at most 0.02 of the volume of the core.
(c) 
The spiral reinforcement shall consist of cold-drawn steel wire having a maximum diameter of 5/8 inch. The minimum clear space between wires shall be one inch.
(d) 
The value of P shall be within the value Ag 2fc, where Ag equals gross area of reinforced concrete.
(4) 
Columns with longitudinal reinforcement.
(a) 
The permissible axial load (P) on columns reinforced with longitudinal bars and separate lateral ties shall be determined by the formula:
P = fc Ag (1 plus npg)
where
fc does not exceed S15.
Ag = gross area of reinforced concrete.
pg = ratio of longitudinal reinforcement to the gross area of columns.
(b) 
The minimum longitudinal reinforcement shall be 0.005 of the gross area of the column, and the maximum longitudinal reinforcement shall be 0.04 of the gross area of the column. The longitudinal reinforcement shall consist of at least four bars having a minimum diameter of 5/8 inch.
(c) 
Lateral ties at least 1/4 inch in diameter shall be spaced at vertical intervals of at most 15 times the diameter of the vertical reinforcement with a maximum of 12 inches. Crossties shall be provided for the vertical reinforcement at maximum intervals equal to the minimum column dimension but at least 12 inches and at most 24 inches in any case. The total cross-sectional area of lateral and crossties per foot of length of column shall be at least one-fifteenth of the area of the vertical reinforcement.
(5) 
Bending in reinforced concrete columns. Bending stresses in all columns should be computed on the basis of loading conditions and end restraint. Columns shall be designed for the bending moments developed by unequally loaded panels, eccentric loads, etc., and the concrete and steel areas shall be increased so that the maximum unit stresses shall not exceed the allowable working stresses.
(6) 
Composite columns. The permissible load on composite columns in which structural steel columns are thoroughly encased in concrete, reinforced with between 1/2% and 4% of longitudinal steel and between 1/2% and 2% of spiral reinforcement, shall be determined as follows:
(a) 
The steel core shall be between four and 25% of the gross area of the column.
(b) 
Loads carried by the steel core shall be transferred to it by positive structural means consisting of billets or brackets.
(c) 
The unit stress on the steel section shall be within 16,000 pounds per square inch.
(d) 
The ratio unsupported length of columns divided by the least radius of gyration, shall be within 120.
(e) 
The diameter of the concrete core, measured outside of the spiral, shall be at least 16 inches.
(f) 
The structural steel column shall be at least three inches from the inside of the spiral at any point.
(g) 
The steel column shall be solid or of the open-section type.
(h) 
The net area of concrete, bounded by the outside of the spiral, shall be at least that required to carry the total floor load of one or more stories above at a unit stress within: fc (1 plus 15p plus 50p') and the same load shall not stress the entire area of concrete beyond a unit stress equal to 2 fc. See § 86-61J(6)(j).
(i) 
The entire load carried by the steel and concrete shall not create an average unit stress on an area, equal to the total area of concrete, plus the steel section, times (n), greater than 2 fc.
(j) 
The entire load carried by the steel and concrete shall not create an average unit stress on an area, equal to the area of concrete bounded by the outside of the spiral, plus the steel section, times (n), greater than: fc (1 plus 15p plus 50p').
(k) 
The value of p and p' shall be computed for the greater stress given by Subsection J(6)(h) or (j).
(7) 
Transfer or stress at base of columns. The comprehensive stress in longitudinal reinforcement at the base of a column shall be transferred to the pedestal or footing by dowels. There shall be at least one dowel for each column bar, and the total sectional area of the dowels shall be at least the sectional area of the longitudinal reinforcement in the column, The dowels shall extend into the column and into the pedestal or footing at least 30 diameters of the dowels for plain bars or 24 diameters for deformed bars.
K. 
Reinforced concrete walls.
(1) 
The minimum thickness of reinforced concrete bearing walls shall be 1/25 of the unsupported height but at least eight inches. Approved buttresses, built-in columns or piers designed to carry all vertical loads may be used in place of greater thickness. The allowable working stress in compression in such walls shall be within those established by the column formulas.
(2) 
Bearing walls shall be reinforced with an area of steel in each direction, vertical and horizontal, at least equal to 0.0025 of the cross-sectional area. Walls more than eight inches thick shall have 1/2 the steel at each face of the wall. The maximum spacing of the bars shall be 18 inches in either direction. Reinforcement shall be at least 3/8 inch in diameter. The vertical steel shall not be relied on to carry load unless arranged and tied as in reinforced concrete columns.
(3) 
In buildings of skeleton construction, reinforced concrete walls, when supported at each story, shall be at least eight inches thick. Such walls shall be reinforced in the same manner as bearing walls.
L. 
Inspection of controlled concrete. When concrete structures are designed as provided in § 86-53C(3), Controlled concrete, all concrete work shall be inspected by the architect or engineer responsible for its design. A record shall be kept of such inspection, which shall cover the quality and quantity of concrete materials, including water, the mixing and placing of the concrete and the placing of the reinforcing steel. The inspection record shall also include a complete record of the progress of the work and of the temperatures, when these fall below 50° F., and of the protection given to the concrete while curing. These records shall be available for inspection by the Superintendent of Buildings at all times during the progress of the work and shall be preserved for two years after the acceptance of the structure.
M. 
Load tests.
(1) 
The Superintendent of Buildings may order the test under load of any portion of a completed reinforced concrete structure when there is any doubt as to the stability of the structure. The minimum age of any concrete construction which may be subjected to such tests shall be 60 days.
(2) 
In such tests, the member or portion of the structure under consideration shall be subjected to a superimposed load equal to 1 1/2 times the live load, plus 1/2 of the dead load. This load shall be left in position for a period of 24 hours before removal. If, during the test. evidence of weakness develops in any portion of the structure, such changes or modifications shall be made as are necessary to make the structure adequate for the rated capacity or, where lawful, a lower rating shall be established. The structure will have passed the test if the total deflection does not exceed the deflection computed by accepted formulas. When the total deflection exceeds the computed deflection, the structure will have failed to pass the test if, within 24 hours after the removal of the load, it recovers less than 75% of the maximum deflection shown during the 24 hours while under load.
N. 
Mixing of concrete.
(1) 
The fine and coarse aggregates shall be measured separately, and the proportion of fine to coarse aggregate shall be such as to produce concrete that will work readily around the reinforcement without excess puddling or spading. The ratio of fine to coarse aggregate by weight shall be at least 1/2 and at most two.
(2) 
The proportions shall be such as to prevent segregation of the materials during transportation and placing and to prevent the collection of an appreciable amount of water on the surface of the concrete in place.
(3) 
The amount of coarse material shall be such as to eliminate harshness in placing or honeycombing in the structure. When forms are removed, the faces and comers of the members shall show smooth and sound throughout.
(4) 
The methods of measuring and mixing concrete materials shall be such that the proportions of fine and coarse aggregate to cement and water to cement ratio can be accurately controlled during the progress of the work and easily checked at any time by the Superintendent of Buildings.
(5) 
The concrete shall be mixed until there is a uniform distribution of the materials and the mass is uniform in color and homogeneous.
O. 
Field tests of concrete.
(1) 
During the progress of the work, a reasonable number of compression tests shall be made as required by the Superintendent of Buildings, and at least one specimen shall be tested for each 100 cubic yards of concrete of any one strength. The test cylinder shall be made and stored in accordance with the Standard Method of Making and Storing Compression Test Specimens of Concrete in the Field, D, C31-31 of the American Society for Testing Materials, and tested at the age of 28 days.
(2) 
The twenty-eight-day strengths shall be at least 1,750 pounds per square inch for concrete mixed in the proportions as specified in § 86-47D(3).
(3) 
Should the twenty-eight-day strength fall below the values provided for in this section, the Superintendent may require a load test under the provisions of Subsection M.
P. 
Placing, curing and depositing concrete.
(1) 
Concrete shall be handled from the mixer to the place of final deposit as rapidly as practicable by methods which will prevent the separation or loss of the ingredients. The deposition of partially hardened concrete is prohibited.
(2) 
When concreting is once started, it shall be carried on as a continuous operation until the placing of the section or panel is completed. Where construction joints are necessary, they shall be made in accordance with Subsection S, Construction joints.
(3) 
Concrete shall be kept moist for a period of at least seven days after being deposited.
(4) 
The deposition of concrete which has a temperature less than 50° F. is prohibited, and the concrete shall be maintained at a temperature of at least 50° F. for not less than 72 hours or until thoroughly hardened.
Q. 
Forms and details of reinforced concrete construction.
(1) 
Design of forms. Forms shall conform to the shape, lines and dimensions of the member as called for on the plans. They shall be substantial and sufficiently tight to prevent leakage of mortar, and they shall be properly braced or tied together so as to maintain position and shape and ensure safety to workmen and passersby. Temporary openings shall be provided, where necessary, to facilitate cleaning and inspection immediately before depositing concrete.
(2) 
Removal of forms. The removal of forms shall be carried out in such a manner as to ensure the complete safety of the structure. Where the structure as a whole is supported on shores, beam and girder sides, column and similar vertical forms may be removed within 24 hours, provided that the concrete has hardened sufficiently and that it is uninjured thereby. The supporting forms shall be undisturbed until the concrete has hardened sufficiently to permit their removal with safety. Shoring shall be kept in place until the concrete has acquired sufficient strength to safely support its weight and the load upon it.
R. 
Reinforcement.
(1) 
Cleaning and bending reinforcement.
(a) 
Metal reinforcement, before being placed, shall be free from scales of rust or other coatings that will destroy or reduce the bond. Reinforcement shall be formed to the dimensions indicated on the plans before it is embedded in the concrete. Cold bends shall have a radius of at least two times the least dimensions of the bar.
(b) 
Metal reinforcement shall not be bent or straightened in a manner that will injure the material. Heating of reinforcement for bending is prohibited.
(2) 
Placing of reinforcement. Metal reinforcement shall be accurately placed and secured and shall be supported by concrete or metal chairs or spacers or metal hangers. The minimum center-to-center distance between parallel bars shall be 2 1/2 times the diameter for round bars or three times the side dimension for square bars, but, in all cases the clear spacing between bars shall be at least one inch or 1 1/3 times the maximum size of the coarse aggregate. Bars at the upper face of any member shall be embedded a clear distance of at least one diameter or at least one inch.
(3) 
Splices in reinforcement.
(a) 
Splices in column bars shall provide a lap of at least 24 diameters for deformed bars and 30 diameters for plain bars.
(b) 
When bars in members subject to flexure only are spliced, they shall be lapped sufficiently to transfer the stress by bond and shear. Splices at points of maximum stress are prohibited unless approved by the Superintendent of Buildings.
(4) 
Protection of reinforcement.
(a) 
Metal reinforcement shall be protected by at least 3/4 inch of concrete in walls and slabs, 1 1/2 inches in beams and girders and two inches of columns.
(b) 
At those surfaces of footings and other principal structural members in which the concrete is deposited directly against the ground, metal reinforcement shall have a minimum covering of three inches. At other surfaces of concrete exposed to the ground and at the outside surfaces of exterior walls, columns, girders and beams, metal reinforcement shall have a minimum covering of two inches, except stirrups, which shall have a minimum covering of 1 1/2 inches.
S. 
Construction joints.
(1) 
Joints not indicated on the plans shall be so made and located as to cause the least impairment of the strength of the structure. Where a horizontal joint is to be made, any excess water and laitance shall be removed from the surface after concrete is deposited. Before depositing of concrete is resumed, the hardened surface shall be cleaned and roughened and all weak concrete removed.
(2) 
At least two hours must elapse after depositing concrete in the columns or walls before depositing in beams, girders or slabs supported thereon. Beams, girders, brackets, column capitals and haunches shall be considered as part of the floor system and shall be placed monolithically therewith.
(3) 
Construction joints in floors shall be located near the middle of spans of slabs, beams or girders unless a beam intersects a girder at this point, in which case the joints in the girders shall be offset a distance equal to twice the width of the beam. In this last case, provision shall be made for shear by use of inclined reinforcement.
A. 
Cast-iron columns.
(1) 
Dimensions. Cast-iron columns shall not have a smaller outside diameter or side than five inches nor shall they have an unsupported length greater than that allowed by § 86-53E.
(2) 
Thickness of metal. The thickness of metal shall not be less than 1/12 the diameter or least dimension of cross section but never less than 3/4 inch. When necessary, the thickness shall be increased near the end so that the core of the column below a joint shall not be larger than the core of the column above, in which case the metal may be tapered down for a distance of not less than six inches or a joint plate may be inserted of sufficient strength to distribute the load. Whenever the core of a cast-iron column has shifted more than 1/4 the thickness of a shell, the thickness of the metal all around shall be assumed equal to the thinnest part.
(3) 
Joints. Cast-iron columns shall be machine faced at the end to a true surface perpendicular to the axis. They shall be bolted together with at least four bolts, not less than 3/4 inch in diameter, passing through the flanges, the bolts being of sufficient length to allow the nuts to be screwed up tightly; and as each column is placed in position, the bolts shall also be placed in position and the nuts shall be screwed up tightly.
(4) 
Flanges. Where cast-iron columns rest one on top of another, the top flange of the lower column shall project on all sides not less than three inches from the outer surface of the column, and the shape and dimensions of the bottom flange of the upper column shall be the same as those of the top flange of the lower column, except that when a column is placed on a lot line, the flanges on the side toward such lot line may be omitted if not required for bolting. Flanges shall be at least one inch in thickness when finished and reinforced by fillets and brackets when necessary.
(5) 
Bolt holes. All holes in cast-iron columns shall be drilled. The diameter of the holes shall not exceed that of the bolts by more than 1/16 inch.
(6) 
Limitation. Cast-iron columns shall not be used in any case where the load is so eccentric as to cause tension in the cast iron nor shall they be used for such parts of the structural frame of buildings which are required to resist stresses due to wind.
(7) 
Inspection. No cast-iron column shall be set in place until it has passed an inspection satisfactory to the Superintendent of Buildings. Wherever blowholes or imperfections are found in a cast-iron column which reduce the area of the cross section at that point more than 10%, such columns shall be condemned. Cast-iron columns not cast with one open side or back shall have three-eighths-inch holes drilled in the shaft to exhibit the thickness of the castings as may be required by the Superintendent of Buildings. Cast-iron columns shall not be painted before inspection.
(8) 
Cast-iron column bases. All parts of a cast-iron base or bearing plate shall be at least one inch in thickness.
B. 
Cast-iron lintels. Cast-iron lintels shall not be less than 3/4 inch in thickness at any point and shall not be used for spans exceeding six feet.
C. 
Structural steel.
(1) 
Quality and workmanship. The material used in structural steelwork shall be of uniform quality and free from defects which would influence the strength or stability of the structure. Workmanship shall be good and shall conform to the best accepted standards of practice. Methods of fabrication, transportation and erection shall be such that the finished structure is free from defects or injuries which would render it unfit for use or occupancy.
(2) 
Design requirements. All steelwork shall be designed to sustain the total imposed dead load, including the weight of the steelwork itself, together with the required live load as specified in this code. Proper provisions shall be made in the design for temporary stresses occurring during erection, for eccentricity of loading and for the influence of live loads producing impact or vibration. In addition to the plans and specifications required by § 86-6, Applications for permits, the applicant shall submit to the Superintendent of Buildings a copy of such computations for the design of the structural steelwork of the proposed structure as the Superintendent requests.
(3) 
Eccentric loading. Full provision shall be made for stresses caused by eccentric loading. All columns shall be fully investigated for conditions of loading in the preparation of the design and these conditions shall be reviewed when the erection plans are approved and the location of all framing determined by figures. Where the design is predicated on special details to reduce eccentric conditions, such details shall be illustrated on the design drawings. Eccentric conditions shall be fully considered also in the examination and approval of shop drawings. The column formula given under § 86-53D(2) shall be assumed to produce the maximum allowable extreme fiber stress at the floor line without eccentric loading. Where the bending stress due to eccentric loading exceeds 10% of the working stress in the column under direct load, additional material shall be added to keep this excess within 10%. In all cases of eccentric loading, special attention shall be given in the design to typing columns securely above and below the point of loading at the nearest floor line where it can be done adequately.
(4) 
Joints in structural steel. Columns and compression members, when faced for bearings, shall be spliced sufficiently to hold the connecting members securely in place. When not faced for bearing, all splices shall be fully riveted or bolted.
(5) 
Structural steel column bases. All bases or shoes used to distribute column loads to foundations shall be designed to meet the requirements of this code and may be made as a part of the columns.
(6) 
Structural steel beams and girders. Rolled beams shall be proportioned according to the moment of inertia of their net section. Plate girders, with webs fully spliced for tension and compression, shall be so proportioned that the unit stress of the net section is within the maximum stress, specified in § 86-53D, as determined by the moment of inertia of the net section.
(7) 
Flange plates. Flange plates of all riveted girders shall be limited in width so as not to extend more than six inches or more than 12 times the thickness of the thinnest plate beyond the outer row of rivets connecting them to the angles.
(8) 
Plate girder webs.
(a) 
Plate girder webs shall have a thickness of at least one 1/160 of the clear distance between flange angles for medium structural steel and, in any case, at least 1/4 inch.
(b) 
Intermediate stiffeners shall be required at all points where:
where
h = clear distance between flanges in inches.
s = greatest unit shear at the point in question, in pounds per square inch, under any condition of complete or partial loading.
t = thickness of web in inches.
(c) 
The clear distance between stiffeners, when stiffeners are required by the foregoing, shall not exceed 72 inches or that given by the formula:
where
d = clear distance between stiffeners in inches.
(9) 
Minimum thickness of structural steel framework. For the main structural framework of structures, all steel used shall be at least 0.20 inch thick for interior work and at least 0.30 inch thick for exterior work, except that in residence structures whose maximum height is 2 1/2 stories or 35 feet above the foundation wall or supporting framework, a minimum thickness of 0.125 inch shall be permitted for interior and exterior walls when the vertical members are spaced a maximum of 24 inches apart, provided that the safe loads and unsupported lengths specified elsewhere in this code are not exceeded and that the material used is copper-bearing or other rust-resisting steel.
(10) 
Rivet spacing. The maximum distance between rivets in the line of stress in compression members shall be 16 times the thickness of the thinnest outside plate or shape and 20 times the thickness of the thinnest enclosed plate or shape but in no case to exceed 12 inches. At right angles to the direction of stress, the maximum distance between lines of rivets shall be 30 times the thickness of the thinnest plate or shape. In built sections with angles having two gauge lines, the maximum distance between centers of rivet holes in the line of stress in each gauge line shall be 24 times the thickness of the thinnest plate or shape but never more than 18 inches. The maximum distance from the center of rivet holes to any edge shall be 12 times the thickness of the thinnest plate or shape.
(11) 
Rivet grips. Rivets carrying calculated stresses and whose grip exceeds five diameters shall have their number increased 1% for each additional 1/10 inch in the rivet grip. Special care shall be used in heating and driving such rivets.
(12) 
Field riveted and bolted connections.
(a) 
In tier structures less than 125 feet high in which the height is less than 2 1/2 times the minimum horizontal dimensions, all column splices and field connections may be bolted.
(b) 
In structures in which the height is over 100 feet and is more than 2 1/2 times the minimum horizontal dimension and in structures 100 feet or less in height in which the height is more than four times the minimum horizontal dimension, column splices and connections to columns shall be riveted or welded.
(c) 
In structures over 125 feet in height and in all structures of a special character, connections of beams and girders to columns and beams and girders bracing columns and column splices shall be riveted. Column splices in tier structures less than 125 feet high, except as provided in the preceding paragraph, may be bolted.
(d) 
All other field connections may be bolted, except that in all structures, the connections for supports for running machinery or other moving loads shall be riveted or welded.
(e) 
Within existing structures, steelwork for alterations or additions, except to the main structural framework, which do not affect existing column splices, connections and other riveted work may be bolted.
(13) 
Painting. Steelwork, except that which is to be welded or to be encased in concrete made of noncorrosive aggregates and noncorroding alloy steel, shall, before erection, be thoroughly cleaned and given one coat of acceptable metal protection and well-worked into the joints and open spaces. After erection, steelwork, except that which is to be encased in concrete made of noncorrosive aggregates and noncorroding alloy steel, shall be given an additional coat of acceptable metal protection of another color. Steel parts for which paint is required and which are not in contact but inaccessible after assembling shall be properly protected by paint.
(14) 
Protection of structural steel from weather. Exterior steel columns in walls, which are not protected by glass or similar materials, shall be protected from the weather by efficient and approved waterproof material or by at least eight inches of masonry.
(15) 
Templates. When any lintel, beam, girder or truss is supported at either end by a wall or pier, it shall be properly anchored thereto and shall rest upon a template or shoe of cast iron, steel or stone of such design and dimensions as to safely distribute its load on the masonry, except that when beams not exceeding six inches in depth are placed not more than 30 inches on centers, no templates shall be required.
(16) 
Gas cutting. Gas cutting may be employed in the fabrication of structural steel members or parts used in building construction in accordance with rules promulgated by the Superintendent of Buildings. Gas cutting on any member while it is carrying stress is prohibited.
(17) 
Structural steel for stair construction. Steel strings for interior stairs shall have a minimum thickness of 3/16 inch. Material for risers, treads and landing plates for interior stairs shall have a minimum thickness equal to No. 12 Unites States standard gauge iron. Material used for the construction of exterior steel stairs or fire escapes shall be at least 1/4 inch in thickness.
D. 
Steel joists.
(1) 
Form of steel joists. The term "steel joist" shall denote any approved form of open-webbed beam or truss less than 20 inches in depth and produced directly by rolling or pressing or fabricated from rolled or pressed shapes by welding, pressing, riveting or expanding. Limiting provisions in the following paragraphs do not apply to structural steel sections such as hot-rolled solid web T-beams, channels or plate girders which may be used as steel joists, their design, spacing and loading to be governed only by the stresses required in this code, and provided that bridging, as specified in Subsection D(5) hereof, shall be used.
(2) 
Use of steel joists. Steel joists may be used elsewhere than around stairs, shafts and other floor openings as secondary members for floor fillers in structures 100 feet or less in height.
(3) 
Design of steel joists. Steel joists small be designed using stresses not exceeding those allowed under the Building Code. Web members shall have the same section throughout.
(4) 
Span and spacing of steel joists. The span of joists having an all steel top chord shall be within 550 times the lateral radius of gyration of the top chord, but in case the top chord consists of a flat top section continuous with a center web, the radius or gyration of the top plate alone shall be taken. The span shall be within 24 times the depth of the joist. The maximum deflection shall not be greater than 1/360 of the span for the total load as determined by test. The maximum spacing of the joists shall be the safe span of the top slab or flooring over the joist and in no case greater than 24 inches in floors and 30 inches in roofs, except that steel joists may be used to support wood or sheet metal roofs only if not over seven feet apart.
(5) 
Loading and bridging of steel joists. Every steel joist shall be capable of sustaining a concentrated load at any panel point of at least 800 pounds, except as required elsewhere for concentrated loads, and shall be securely bridged so that it shall develop, without failure, 2 1/4 times the total uniformly distributed load for which it is designed, provided that the bridging is the same as that to be actually used in the construction, but in no case shall the bridging be more than six feet apart or six feet from supports. Such bridging shall securely support the top chord of the joist against lateral displacement and shall be rigid in character and capable of transmitting directly at least 500 pounds to the two adjoining joists at each line of bridging. The steel joists shall be designed to carry directly the total dead load of partitions where they occur in addition to all other dead and live loads imposed. During testing, the character of the bridging shall be such as not to relieve the member of any fraction of the test load.
(6) 
Bearing and anchoring of steel joists. Where steel joists have a bearing on masonry or concrete, at least four inches of their length shall be on each such bearing, and the joists shall be securely anchored to the masonry or concrete. When bearing on steel, steel joists shall have at least 2 1/2 inches of their length on each such bearing. The bearing stresses shall not exceed 200 pounds per square inch on masonry or concrete and 1,000 pounds per square inch on steel. All joists shall be anchored to supports so as to prevent dislodgment during erection, and they shall be belted or welded to all steel supports. Any joists at the end of a panel shall be braced laterally by anchors or ties at each line of bridging.
(7) 
Connections of steel joists. Connections of the various members of steel joists shall be designed with as little eccentricity as possible, and all stresses due to eccentricty shall be included with primary stresses in designing. All such connections shall be made by leaving a portion of the metal intact or by fusion welding. All joints and connections shall be capable of resisting at least three times the designed stress.
(8) 
Painting of steel joists. Painting of steel joists shall be in accordance with the requirements of § 86-62C(13), Painting, or the joists shall be dipped once in hot asphalt at the place of manufacture or given two coats of cold asphalt, either by dipping or spraying, at the place of manufacture. When either hot or cold asphalt is used, all abrasions shall be touched up at the job with the same material.
(9) 
Tests of steel joists. In floor systems constructed with steel joists, as described in § 86-62D, Steel joists, all joists shall meet the requirements of such fire tests as may be required by Article XI and such load tests as may be considered necessary by the Superintendent of Buildings.
E. 
Welding.
(1) 
Fusion welding may be substituted for or used in connection with riveting and bolting, provided that the welding be done in accordance with the rules promulgated by the Superintendent of Buildings and approved by the Board of Trustees.
(2) 
In the absence of such rules, all welding shall be done in accordance with the Code of Fusion Welding and Gas Cutting in Building Construction, 1928 Edition of the American Welding Society, as amended currently, or its equal.
(3) 
Whenever welding is substituted for riveting or bolting, either wholly or partly, the Superintendent of Buildings may retain such professional advisors and others qualified to inspect the welding, as he may deem necessary, to ensure compliance with this section and the structural safety of all welded portions of a structure. These services and all expenses attached thereto shall be at the expense of the owner.
A. 
Thickness of wood beams. No wood floor or roof beam used in any multiple dwelling or in any building hereafter erected within the fire limits shall be less than three inches thick.
B. 
Support of wood structural members.
(1) 
The ends of wood beams, joists and rafters resting on masonry walls shall be cut to a bevel of three inches in their depth and shall have a bearing of at least four inches on the masonry.
(2) 
The ends of wood beams resting on girders shall have bearings of at least four inches.
(3) 
The ends of wood beams framing into girders may be supported by approved metal stirrups, hangers or bolted hardwood cleats, provided that all bearings of timber shall be at least four inches or as may be otherwise designed and shown in detail on the framing plans and having a bearing within the working stress of the timbers.
(4) 
In no case, except in one- and two-family dwellings, shall either end of a floor or roof beam be supported on stud partitions. Tail beams over four feet long and trimmer and header beams shall be hung in approved metal stirrups or hangers and shall be spiked unless supported on a wall or girder.
(5) 
Notching or cutting of wood beams, joists or rafters is forbidden unless they are suitably reinforced.
(6) 
Built-up girders shall be securely bolted together. Other built-up members shall be securely spiked or bolted together. Spiked trusses shall be of types which have been tested and approved.
C. 
Bridging of wood beams. Wood floor beams and beams in flat roofs exceeding eight feet in clear span shall be braced with mitered cross bridging, measuring at least one inch by 2 1/2 inches (actual) and nailed twice at each bearing or, if metal bridging is used, it must have equivalent effective strength and durability. The maximum distance between bridging or between bridging and bearing shall be eight feet.
D. 
Anchoring wood beams and girders to masonry. Each tier of beams parallel to masonry and beams and girders bearing on masonry shall provide adequate lateral stability by anchorage as required in § 86-60H, Anchorage of masonry walls.
E. 
Fastening of wood beams on girders. The ends of wood beams resting upon girders, walls or bearing partitions required to be anchored in accordance with § 86-60H, Anchorage of masonry walls, except as otherwise provided, shall lap each other at least six inches and be well-bolted or spiked together or shall be butted end to end and fastened by approved metal straps, ties or dogs in the same beams as the wall anchors.
F. 
Fastening of wood girders. The ends of wood girders shall be fastened to each other by approved straps, ties or dogs.
G. 
Fire prevention.
(1) 
Trimming around flues and fireplaces. Wood beams shall be trimmed away from flues and chimneys. The header and trimmer beams shall be at least four inches from the face of chimneys and backs of fireplaces. In front of a fireplace, an opening shall be trimmed to support a trimmer arch or approved masonry hearth at least 20 inches from the face of the breast and at least 12 inches wider on each side than the fireplace opening.
(2) 
Separation of combustible members in masonry walls. Combustible members entering a masonry wall shall be separated from each other and from the outside of the wall by at least four inches of solid masonry.
H. 
Wood columns and posts.
(1) 
Wood columns and posts shall have level bearings and shall be supported and shall have properly designed metal bases or base plates.
(2) 
Where timber columns are superimposed, they shall be squared at the ends perpendicular to their axis and supported on metal caps with brackets or shall be connected by properly designed metal caps, pintles and base plates.
I. 
Bolting in wood construction. Bolts in wood construction shall be provided with washers and, when carrying tensile stress, they shall be of such proportions that the compression on the wood at the face of the washer will be less than the working stresses prescribed in § 86-53F, Lumber and timbers.
J. 
Stud-bearing partitions. Stud-bearing partitions which rest directly over each other and are not parallel with wood floor beams shall run down between the wood floor beams and rest on the top plate of the partition girder or foundation below. For wood frame dwellings, this may be waived by the Superintendent of Buildings. Stud-bearing partitions parallel to the floor joists shall be supported on doubled joists or beams at least as wide as the studs supported.
K. 
Fire stops.
(1) 
Firestopping of stud-bearing partitions. Exterior stud walls and stud-bearing partitions shall have the studding filled in solid between the uprights to the depth of all floor beams with suitable incombustible materials. In wood frame dwellings, other firestopping may be used as approved by the Superintendent of Buildings.
(2) 
Firestopping of furred spaces. Where walls are furred off or studded off, the space between the inside of the furring or studding and the wall shall be fire-stopped from the ceiling to the underside of the flooring or roof above with incombustible material.
(3) 
Firestopping of wainscoting. The surface of the wall or partition behind wainscoting shall be plastered flush with the grounds and down to the floor line.
A. 
Piers and wharves. Piers and wharves shall be constructed in accordance with plans prepared by a professional engineer licensed by the State of New York, said plans to be based on computations using generally accepted engineering principles and in conformity with applicable provisions of the Building Code. Live loads must be acceptable to the Building Department Superintendent. Piers and wharves shall be constructed on pile or other approved foundations. Piles shall conform to the specifications for bulkhead piles with regard to type of wood, treatment, dimensions, taper, straightness and defects.
B. 
Bulkheads.
(1) 
No plot fronting on navigable water shall be used for any dwelling or business purpose, nor shall a permit be issued for the erection, addition or alteration or improvement of any structure until an approved bulkhead has been erected for the full width of the plot. All bulkheads erected under this provision shall be maintained and kept in good state of repair at all times.
[Added 11-9-1970]
(2) 
Bulkheads shall be constructed so as to have adequate structural strength and stability to retain and support the abutting banks or the material behind some, together with any superimposed loads, and to resist the action of the tides, boats and the elements. No portion of any bulkhead shall extend beyond the private property line. The tops of all bulkheads shall have a minimum elevation of 5.9 feet NAVD (North American Vertical Datum).
[Amended 12-6-1993 by L.L. No. 5-1993; 3-10-2014 by 2-2014]
C. 
Minimum bulkhead requirements.
(1) 
The minimum bulkhead requirements herein specified are applicable to conditions where the existing depth of compressible material (bog) does not exceed eight feet. When the existing depth of compressible material (bog) exceeds eight feet, the applicant must submit plans and design computations for bulkhead construction as prepared by a professional engineer licensed by the State of New York, said plans and computations to be based on generally accepted engineering principles and satisfactory to the Village Building Department Superintendent.
(2) 
Minimum requirements for the construction of bulkheads are shown on the drawing annexed hereto, made a part hereof and entitled "Minimum Bulkhead Requirements -- Village of Freeport," and shall consist of:
(a) 
Vertical wood piles spaced six feet center to center.
(b) 
Two horizontal timber rangers or wales spaced five feet center to center.
(c) 
Timber tongue and groove sheathing boards or sheetpiling.
(d) 
Galvanized steel tie-rods.
(e) 
Wood tiebacks or anchorages.
(3) 
Where plans accompanying application for permit vary from the minimum bulkhead requirements, the applicant must submit design computations prepared by a professional engineer licensed by the State of New York, said plans and computations based on generally accepted engineering principles and satisfactory to the Village Building Department Superintendent.
(4) 
Piles shall penetrate into good granular material a minimum of 1/3 their length. Minimum pile length shall be 20 feet.
(5) 
Sheathing boards shall penetrate into good granular material a minimum of five feet. Minimum length of sheathing boards shall be 18 feet.
(6) 
All timbers, including piles, shall be air-seasoned and full-cell treated (Bethell process) with creosote-coal tar solution and shall retain the minimum weights of preservative as recommended by the American Wood-Preservers Association standards for coastal waters.
D. 
Specifications for wood bulkheads.
(1) 
Piles. Piles shall be of sound southern pine or Douglas fir. Oak piles are not permitted. The minimum tip diameter shall be six inches, and the minimum butt diameter shall be 12 inches three feet from the end. Piles shall have reasonably uniform taper and be so straight that a straight line joining the centers of the butt and tip shall not be outside the body of the pile. They shall be free from all defects which may impair their strength and durability.
(2) 
Rangers of wales. Rangers of wales shall be Douglas fir or southern pine with a minimum allowable stress of 1,600 pounds per square inch. They shall be six inches by eight inches rough with the eight-inch dimension horizontal. All splices shall be at pile locations. Wales shall be fastened to piles and sheathing at pile locations with three-fourths-inch diameter through bolts and OG washers.
(3) 
Sheathing boards. Sheathing boards shall be Douglas fir or southern pine with a minimum allowable stress of 1,600 pounds per square inch. They shall be three-inch nominal thickness, tongue and groove and tightly set in place. Each sheathing board shall be spiked to each wale with two 60D spikes.
(4) 
Tieback or anchorage. All piles shall be tied back by the use of tie-rods and anchorages. Tie-rods shall be of steel, ASTM A307, with a minimum one-inch diameter. Anchorages shall consist of a continuous four-by-twelve-inch creosoted plank set horizontally, with a minimum of four feet of cover and located at least 12 feet behind the nearside face of the sheathing boards. These planks shall be of Douglas fir or southern pine with a minimum allowable stress of 1,600 pounds per square inch. Splices in this plank shall be at anchor piles only. On the bulkhead side of the aforementioned plank, anchor piles on twelve-foot spacing shall be installed. Anchor piles shall be of untreated oak or creosoted pine or fir and be a minimum of 12 feet long. The tops of all anchor piles shall have at least three feet of cover above same. The tie-rods shall extend through the center of both anchor pile and/or plank. At the bulkhead, timber filler blocks, six inches by eight inches, shall be installed at each pile location between the pile and the sheathing boards. The tie-rods shall extend through the sheathing board, filler block and pile at a point 12 inches below the top wale.
(5) 
Backfill behind bulkheads. All existing compressible material along the line of the bulkhead and for a minimum distance of one foot behind same shall be excavated and removed. No compressible material shall be used for backfill within one foot of the inside face of the bulkhead. Backfill in this area shall be granular material.
(6) 
General.
(a) 
All work shall conform to the best practices for the trade involved. All steel rods, bolts, nuts, washers, nails, spikes, screws, etc., shall conform to ASTM A307, Grade A, and be hot-dip galvanized after fabrication in conformity with ASTM A153. OG washers shall be used behind all bolt and rod heads and nuts. All field cuts, including drilled holes, in timber or piles shall be field-treated with two applications of hot creosote or hot creosote-coal tar solution.
(b) 
The final position of the bulkhead, after back-filling behind same, shall be straight, vertical and true. The tops of piles shall also be uniform as to line and grade and set to the required elevation. The Building Department Superintendent may require, and the applicant must furnish upon his request, certification regarding the quality of materials used or to be used for the construction of the applicant's bulkhead.
(c) 
Prior to the delivery of bulkhead materials to the site, the contractor shall, in the presence of a Building Department representative, make subsurface soundings at the bulkhead line in order to determine the elevation of the granular material into which the piles and sheathing boards must penetrate. The soundings must be made in a manner satisfactory to the Building Department. In lieu of the above procedure, the Building Department will accept subsurface boring data submitted and certified by a professional engineer licensed in the State of New York.