Exciting enhancements are coming soon to eCode360! Learn more 🡪
Village of Freeport, NY
Nassau County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
A. 
Classification and use.
(1) 
Fire-resistive materials shall be classified on a time and temperature basis and used in accordance with the requirements of this code and the rules of the Superintendent of Buildings.
(2) 
The requirements of this article are intended to provide adequate protection against fire and shall not be considered to waive any requirements of other sections of this code for stronger construction in order to provide safe load carrying capacity.
B. 
Fire-resistive construction details.
(1) 
Fire-resistive units of burnt clay or shale, sand-lime, concrete or gypsum shall be laid up in cement mortar, cement-lime mortar or gypsum mortar for gypsum units.
(2) 
Units shall be solidly bedded and shall be thoroughly bonded by broken joints in alternate courses or by approved metal ties.
(3) 
Structures of reinforced concrete meeting the requirements of § 86-61, Reinforced concrete, in respect to the reinforced concrete, and of § 86-13A, Class 1 Fireproof Structures, in respect to other parts, shall be considered as Class 1 Fireproof Structures.
(4) 
Poured in place concrete or gypsum fire-resistive materials for protective purposes shall be reinforced with a sufficient amount of metal bars or mesh to ensure the integrity of the construction.
(5) 
Plaster used in fire-resistive construction shall consist of gypsum or cement mortar or other equally fire-resistive material.
C. 
Spaces exterior to structures.
(1) 
Any space within the grade story in a structure may be considered exterior to the structure, provided that it is cut off from the structure on all sides adjacent thereto by walls having a fire-resistive rating of at least four hours and access to such space is from the outside only.
(2) 
Any area of a grade story of a structure without exterior walls and cut off from the remainder of the structure by partitions or walls having a fire-resistive rating of at least four hours may be considered as outside of the structure.
(3) 
These provisions shall not be construed as permitting the erection of any structure in a manner inconsistent with the provisions of Article V of this code.
D. 
Test for fire-resistive materials. Other materials, appliances or methods of construction for fire-resistive purposes not specifically provided for in this code shall, on written application to the Superintendent of Buildings, be tested in accordance with Subsection F of this section and, if found to comply with the requirements of this code, they shall be approved by the Superintendent of Buildings.
E. 
Thickness and fire-resistive ratings for protection of structural steel. Unless otherwise determined by test in accordance with the rules of the Board, the thicknesses of fire-resistive materials in this table, exclusive of airspaces when used for the protection of structural steel members, shall be assumed to have the following fire-resistive ratings. Such thicknesses are the minimum permissible and their reduction for the embedment of pipes, conduits or wires or for any other purpose is forbidden.
Hours
Inches of
One
Two
Three
Four
Brick (burned clay or shale)
2 1/4
2 1/4
3 3/4
3 3/4
Brick (sand-lime)
2 1/4
2 1/4
3 3/4
3 3/4
Concrete brick, block or title, except cinder concrete units
2 1/4
2 1/4
3 3/4
3 3/4
Hollow or solid cinder concrete block and tile having a compressive strength of at least 700 pounds per square inch of gross area
1 1/2
2
2
2 1/2
Solid gypsum block, provided that to obtain the four-hour rating, such blocks shall be plastered with at least 1/2 inch of gypsum plaster (See Subsection C)
1
1 1/2
2
Gypsum poured in place and reinforced
1
1 1/2
1 1/2
2
Hollow or solid burned clay tile or combinations of tile and concrete (See Subsection C)
1 1/2
2
2
2 1/2
Metal lath and gypsum plaster (See Subsection B)
7/8
1 1/2
2
2 1/2
Cement concrete, Grade I (See Subsection A)
1
1 1/2
2
2
Cement concrete, Grade II (See Subsection A)
1 1/2
2
3
4
Cement concrete, Grade II with wire mesh (See Subsection D)
1 1/2
2
2
3
Hollow gypsum block, provided that to obtain the four-hour rating, such blocks shall be plastered with at least 1/2 inch of gypsum on outer side
3
3
3
3
(1) 
Concrete grades and aggregates. Grade I concrete is concrete in which the aggregate consists of limestone, traprock, blast furnace slag, cinders or calcareous gravel. Grade II concrete is concrete in which the aggregate consists of granite or siliceous gravel.
(2) 
Plaster equivalents. One-half inch of unsanded gypsum plaster shall be taken as the equivalent of 3/4 inch of sanded gypsum or cement plaster. Plaster protections more than one inch in thickness shall have an additional layer of metal lath embedded 3/4 inch or less from the outer surface and securely tied to the protected member. The thickness of the plaster shall be the minimum thickness of plaster measured from the face of the lath or of the masonry.
(3) 
Anchors, bonds and ties. Metal anchors, bonds or caging shall be used with solid sypsum block and cement concrete. For gypsum block protections for all periods and for other block or tile protections for periods of over two hours, metal anchors in the horizontal joints shall be used. Hollow gypsum shall be anchored with U-straps placed between the blocks and running into the hollow spaces. For Grade I or Grade II concrete or poured gypsum, the ties shall consist of wire mesh complying with Subsection E(4) or the equivalent in metal ties or spirally wound wire.
(4) 
Wire mesh. Wire mesh for tying concrete projections shall weigh at least 1 1/2 pounds per square yard and shall be of a type approved by the Superintendent of Buildings.
F. 
Fire tests, unless otherwise provided for under rules. All materials and assemblies shall be tested in accordance with the rules promulgated by the Superintendent of Buildings and approved by the Board of Trustees. In the absence of such rules, all materials and assemblies shall be tested in accordance with the standard fire test formulated under the auspices of the American Standards Association or the standard fire test specifications of the American Society for Testing Materials, D, C19-26T, and the results shall be expressed in time periods of resistance, as for example, four-hour, one-half-hour, etc.
A. 
Protection of columns.
(1) 
Iron or steel columns shall be protected by material or assemblies having a fire-resistive rating of four hours for Class 1 Fireproof Structures and of three hours for Class 2 Fire-Protected Structures, except that interior columns in Class 2 Fire-Protected Structures for residence purposes may have only two-hour protection.
(2) 
Special precautions shall be taken to protect the outer surfaces of iron or steel columns located in exterior walls against corrosion by painting with waterproof paints, by the use of mastic or by other methods of waterproofing approved by the Superintendent of Buildings.
B. 
Protection of lugs, brackets and wind bracing. Where the column is solidly encased with fire-resistive material, the extreme outer edge of lugs, brackets, wind bracing or other supporting parts may extend to within one inch of the outer surface of the protection.
C. 
Protection of fire-resistive covering. Where the fire-resistive covering on columns is exposed to injury from moving vehicles or the handling of merchandise, it shall be jacketed to a height of five feet from the floor with an adequate protective covering.
D. 
Protection of wall girders and other steel supporting masonry. Wall girders and other steel supporting masonry shall be protected by material or assemblies having a fire-resistive rating of three hours.
E. 
Protection of beams and girders.
(1) 
Beams and girders supporting floor or roof construction in Class 1 Fireproof Structures shall be individually encased with materials or assemblies having a three-hour fire-resistive rating, except that in areas of 500 square feet or less, secondary beams may be protected by a suspended ceiling with a three-hour fire-resistive rating, provided that such areas are completely fire-stopped, and that where such ceilings extend into the web of the main girders, the fireproofing of such girders may also be omitted above the ceiling if the girder webs are solid.
(2) 
Beams and girders supporting floor and roof construction in Class 2 Fire-Protected Structures shall be individually encased with materials or assemblies having a one-and-one-half-hour fire-resistive rating, except that in areas of 500 square feet or less, secondary beams may be protected by a suspended ceiling with a one-and-one-half-hour fire-resistive rating, provided that such areas are completely fire-stopped, and that where such ceilings extend into the web of the main girders, the fireproofing of such girders may also be omitted above the ceiling if the girder webs are solid, and except that the floor above the cellar or basement shall have a fire-resistive rating of at least three hours.
(3) 
Firestopping, as required in this section, shall be done with materials or assemblies having the same fire-resistive rating as the fireproofing.
F. 
Protective of lintels.
(1) 
In Class 1 Fireproof Structures, iron or steel lintels over openings more than four feet wide in walls shall be protected as required for wall girders, unless the lintel is supported from a fireproof member above, provided that when the span of any such opening is six feet or less and such opening is spanned by an adequate masonry arch above the lintel, the protective covering may be omitted.
(2) 
In Class 2 Fire-Protected Structures, iron or steel lintels over openings more than six feet wide in walls shall be protected as required for wall girders, unless the lintel is supported from a fireproof member above, provided that when the span of any such opening is eight feet or less and such opening is spanned by an adequate masonry arch above the lintel, the protective covering may be omitted.
(3) 
In Class 3 Nonfireproof Structures of two stories or more in height, iron or steel lintels over openings more than eight feet wide in walls shall be protected as required for wall girders, unless the lintel is supported from a fireproof member above.
G. 
Use of stone lintels restricted. The use of stone lintels is forbidden unless supplemented on the inside of the wall with iron or steel lintels or with suitable masonry arches carrying the masonry backing or by other methods if approved by the Superintendent of Buildings.
H. 
Protection of trusses.
(1) 
Trusses in Class 1 Fireproof Structures and Class 2 Fire-protected Structures shall be entirely protected by material or assemblies having fire-resistive ratings of three hours and 1 1/2 hours, respectively. The protective covering may be omitted from members of trusses, including beam and subpurlins, in one-story structures and in multistory structures when supporting only roof loads, access passageways or ventilating equipment and having a clear height of at least 20 feet below the lower chords of the trusses.
(2) 
The protective covering may be omitted from roof truss members, including beams and subpurlins, if a continuous ceiling having a fire-resistive rating of three hours is provided below the lower chords of the trusses and the space above the ceiling is completely enclosed and fire-stopped and contains no passageways or apparatus of any kind. Access to the enclosed roof space shall be permitted by an access door having a fire-resistive rating of at least one hour and having maximum dimensions of three feet by three feet.
A. 
Form and fire-resistive ratings of floor and roof construction.
(1) 
Floor and roof construction between supporting beams in Class 1 Fireproof Structures shall consist of arches or slabs of incombustible material or assemblies and shall, either by itself or in combination with its protective ceiling, have a fire-resistive rating of at least three hours, except as specifically provided otherwise. Nothing in this section shall prevent the application of cork or fiber insulation board applied directly to the fire-resistive floor or roof construction, in cement, provided that such insulation is covered by at least a one-and-one-half-inch thickness of portland cement concrete or other equally fire-resistive material of equal thickness. Similar floor and roof construction in Class 2 Fire-Protected Structures shall, either by itself or in combination with its protective ceiling, have a fire-resistive rating of at least 1 1/2 hours, except as otherwise specifically provided.
(2) 
Where the fire-protective covering is omitted from roof trusses, as provided in § 86-70H, Protection of trusses, blocks of book tile, gypsum, concrete or other equivalent fire-resistive materials may be used for horizontal or sloping roofs directly above such trusses, provided that the necessary strength requirements are met.
(3) 
A floor or roof construction in which the structural members are not individually encased in fire-resistive materials or assemblies shall be fire-stopped as provided in § 86-70E, Protection of beams and girders.
B. 
Concrete floor and roof construction.
(1) 
Minimum proportions for stone and cinder concrete. Unless designed in accordance with the provisions of § 86-61, Reinforced concrete, concrete floor and roof construction shall consist of a mixture of one part of cement by volume, two parts of sand by volume and a maximum of five parts of coarse aggregate measured separately by volume and reinforced with steel as provided in Subsection B(4), Strength of concrete floor and roof construction. Cinder aggregate shall be clean and well-burned and shall contain a maximum of 35% by weight of unconsumed carbon and 1 1/2% by weight of sulfur. Other aggregates shall conform to § 86-47D(1), Aggregates.
(2) 
Reinforcements to concrete floor and roof construction. Reinforcement shall consist of steel fabric, rods or other suitable shapes. The reinforcement shall be at least 0.015% for continuous steel fabric and at least 0.025% for other forms of steel reinforcement, the percentage to be based on the sectional area of the slab above the center of reinforcement. The center of the reinforcement shall be at least one inch above the bottom of the slab, but all parts of the reinforcement shall be at least 3/4 inch from the bottom of the slab.
(3) 
Thickness of concrete floor and roof construction. Unless designed in accordance with the provisions of § 86-61, Reinforced concrete, the minimum thickness of concrete floor and roof construction shall be determined by the following formula:
where
t = total thickness in inches.
L = span in feet between steel flanges.
w = gross uniform load in pounds per square foot.
But t shall be at least four inches with the following two exceptions:
(a) 
Special forms of construction which have passed a three-hour fire test as specified in § 86-69F.
(b) 
In Class 2 Fire-Protected Structures, floor construction, except the floor construction above the cellar or basement, and roof construction may be used consisting of two inches or more of reinforced concrete or gypsum top slab or two inches or more of stone or cinder concrete poured over rib lath and secured to the top of steel beams or steel joists and at least a seven-eighths-inch gypsum or cement plaster ceiling on metal lath or any other material or assembly having a fire-resistive rating of at least 1 1/2 hours. (See also § 86-13B, Class 2 Fire-Protected Structures, and § 86-76A, Floor sleepers, bucks, nailing blocks and grounds.) Four-inch slabs may be used for spans of eight feet or less, provided that the gross floor load is 200 pounds per square foot or less.
(4) 
Strength of concrete floor and roof construction.
(a) 
Unless designed in accordance with § 86-61, Reinforced concrete, the safe carrying capacity of concrete floor and roof construction shall be determined by the following formula:
where
w = gross uniform floor load in pounds per square foot.
As = cross-sectional area of reinforcement in square inches per foot of width of slab.
L = clear span, in feet, between steel flanges and shall not exceed 10 feet in any case, and when the gross floor load exceeds 200 pounds per square foot, the span shall not exceed eight feet.
C = the following coefficient for steel having an ultimate strength of at least 55,000 pounds per square inch:
For cinder concrete:
Twenty thousand when reinforcement is continuous.
Fourteen thousand when reinforcement is hooked or attached to one or both supports.
For stone concrete:
Fifteen thousand when reinforcement is hooked or attached to one or both supports.
Twenty-three thousand when reinforcement is continuous.
(b) 
The use of this formula is forbidden unless the reinforcement is hooked or attached to one or both supports or is continuous and the slab is stone or cinder binder concrete at least four inches in thickness.
(c) 
The concrete in such floor and roof construction shall have an ultimate compressive strength of at least 700 pounds per square inch at the end of 28 days. For such concrete, the safe fiber stress may be taken as 200 pounds per square inch, the bond at 50 pounds per square inch and n equals 30, and the strength may be figured by the usual methods.
(d) 
If steel of an ultimate strength in excess of 55,000 pounds per square inch is used, the above coefficient may be increased in the ratio of the ultimate strength to 55,000 but at most 30%, provided that a certificate of the manufacturer, certifying to the minimum strength of the wire fabric actually to be used, is submitted before erection.
C. 
Gypsum floor and roof construction. Gypsum floor and roof construction may be either of reinforced poured gypsum or precast units and may be either of the suspension type or of the slab and ceiling type with the slabs constructed of such thickness as to support the imposed loads, provided that the floor or roof construction complies with the requirements of Subsection A, Form and fire-resistive ratings of floor and roof construction.
D. 
Hollow tile arches.
(1) 
Material for hollow tile arches. Hollow blocks of burnt clay or shale used in hollow tile arches for fire-resistive construction shall be medium or hard and of uniform density. Shells and webs shall be at least 5/8 inch thick. The maximum spacing of interior vertical and horizontal webs shall be four inches. The blocks shall have at least two cells in depth and shall be laid in cement mortar and be properly keyed.
(2) 
Depth of flat arches. The depth of flat arches of burnt clay or shale hollow blocks shall be at least 1 1/2 inches for each foot of span, exclusive of the portion of the block extending below the underside of the beam, with a minimum thickness of six inches.
E. 
Brick arches. Brick arches shall be built of common or hollow brick solidly bonded. They shall be segmental in form with a minimum thickness of four inches for spans of five feet or less and of eight inches for spans exceeding five feet unless suitably reinforced. The rise of such arches shall be at least one inch per foot of span, and the joints shall be filled with cement.
F. 
Rise of segmental arches. Segmental arches for floor and roof construction shall have a rise of at least one inch per foot of span. The minimum thickness of this type of arch shall be six inches.
G. 
Special roof construction. For mansards and dormers having a slope of more than 30° from the horizontal blocks of book tile, gypsum, concrete or other fire-resistive materials may be used subject to the load test specified in Subsection H, Load tests for floor and roof construction, and provided that they have a fire-resistive rating of at least one hour.
H. 
Load tests for floor and roof construction. When the strength of any floor or roof construction cannot be determined by the methods prescribed in this section or by the application of accepted engineering formulas, the safe uniformly distributed carrying capacity shall be taken as a fraction of the total load causing failure in a full-sized test sample when applied along two lines, each distant 1/3 of the span from the supports. This fraction shall be 1/4 when the specimens are tested as simple spans and 1/6 when tested as continuous spans.
I. 
Span of floor and roof construction. Unless designed in accordance with § 86-61, Reinforced concrete, the maximum clear span for floor and roof slabs or arches between supporting beams shall be eight feet, except as otherwise permitted by Subsection B(4), Strength of concrete floor and roof construction.
J. 
Openings in floors and roofs. Suitable metal framing or reinforcement shall be provided in fire-resistive floor and roof construction around any opening having an area in excess of two square feet. When openings are provided for pipes and conduits, the unoccupied space shall be filled with approved incombustible material for the full depth of the slab unless close fitting individual sleeves, solidly embedded in the construction, are used or the opening is enclosed as a shaft and constructed in compliance with § 86-73A, Protection of closed shafts.
K. 
Tie-rods. The supporting beams in fire-resistive floors and roofs shall be tied together by steel tie-rods of proper size, spacing and location, provided that when the floor filling is in the form of reinforced slabs and the reinforcement is continuous over the supports or securely attached to the supports, tie-rods may be omitted.
L. 
Top filling. In Class 1 Fireproof Structures, the space between the floor slab and the finished floor shall be filled with concrete consisting of one part of cement to a maximum of 10 parts of cinders or with other incombustible material approved by the Superintendent of Buildings.
A. 
Materials and thicknesses of fire walls, four-hour.
(1) 
Fire walls shall be constructed of the following materials and minimum thicknesses, exclusive of any required plaster:
(a) 
Solid brick, solid structural units or plain concrete eight inches thick.
(b) 
Solid reinforced concrete six inches thick.
(c) 
Solid cinder concrete blocks eight inches thick.
(d) 
Solid cinder concrete blocks six inches thick and plastered on both sides.
(e) 
Hollow clay tile 12 inches thick, two units and three cells in wall thickness.
(f) 
Hollow clay tile eight inches thick, three cells in wall thickness and plastered on both sides.
(g) 
Hollow concrete blocks (one piece) 12 inches thick, webs and shells to be at least 1 1/2 inches thick and at least two cells in wall thickness.
(h) 
Hollow concrete blocks (one piece) eight inches thick, plastered on both sides, and shells to be at least 1 1/2 inches thick.
(2) 
Fire walls of other materials or forms of construction shall have a fire-resistive rating of four hours.
B. 
Construction of fire walls.
(1) 
Fire walls shall be constructed with solid joints of cement or cement-lime mortar. Where plaster is required, unsanded gypsum plaster shall be at least 1/2 inch thick and sanded gypsum or cement plaster shall be 3/4 inch thick.
(2) 
In a Class 2 Fire-Protected Structure or a Class 3 Nonfireproof Structure, a fire wall shall be continuous from its foundation to three feet above the roof surface, except as provided in the following paragraph, and except that in residence structures of these two classes, fire walls may be carried only to the underside of the roof in Class 2 Fire-Protected Structures and only to the underside of the roof boards in Class 3 Nonfireproof Structures, provided that the junction between the roof and the fire wall is thoroughly fire-stopped.
(3) 
Fire walls may be offset from floor to floor in any structure, provided that the entire offset is of fire-resistive construction having a fire-resistive rating of four hours.
(4) 
Combustible structural members built into a solid fire wall shall be separated from each other and from the outside of the wall by at least four inches of solid masonry.
(5) 
When combustible members project into hollow fire walls, the hollow space shall be filled solidly with incombustible fire-resistive materials for the full thickness of the wall and for four inches or more above, below and between the members.
(6) 
Fire walls of masonry used as party or bearing walls shall conform in thickness and material to the requirements for such walls as specified in § 86-60, Masonry construction.
(7) 
The application of cork or fiber insulation board may be permitted if cemented or attached directly to the face of the wall, laid up with no intervening airspaces and protected as required by the rules of the Superintendent of Buildings.
C. 
Materials for fire partitions, three-hour.
(1) 
Fire partitions shall be constructed of the following materials and minimum thicknesses, exclusive of any required plaster:
(a) 
Solid brick, solid structural units or plain concrete eight inches thick.
(b) 
Solid reinforced concrete five inches thick.
(c) 
Solid cinder concrete blocks six inches thick.
(d) 
Hollow clay tile, two cells in wall thickness, six inches thick and plastered on the room side.
(e) 
Hollow concrete block eight inches thick, provided that calcareous, burnt clay or cinder aggregates are used and the shells are at least 1 1/2 inches thick if unplastered and at least one and 1/4 inches thick if plastered.
(f) 
Hollow gypsum block four inches thick and plastered on both sides.
(g) 
Hollow gypsum block six inches and two cells in wall thickness and plastered on one side.
(2) 
Where combustible insulation board is permitted, it shall be applied directly to the face of the partition by cement or other approved method, but in no case shall it be built into the required partition construction.
(3) 
Fire partitions of other materials or forms of construction shall have a fire-resistive rating of three hours.
D. 
Construction of fire partitions.
(1) 
The maximum unsupported height of a fire partition shall be 30 times its total thickness unless suitably anchored and reinforced or constructed in accordance with the requirements for walls as specified in § 86-60, Masonry construction. Intermediate support for fire partitions shall be of construction having a fire-resistive rating of three hours. Fire partitions may be offset from floor to floor in any structure, provided that the entire offset is of fireproof construction having a fire-resistive rating of three hours.
(2) 
Combustible structural members built into a fire partition wall shall be separated from each other and from the outside of the wall by at least four inches of solid masonry.
(3) 
Where combustible insulating boards are permitted on a fireproof partition, they shall be cemented or directly attached to the face of the partition and may not be built into the required construction.
(4) 
Fire partitions shall be constructed and plastered, if plastering is required, as prescribed for fire walls in Subsection B, Construction of fire walls.
E. 
Fire-resistive stairway enclosures, two-hour.
(1) 
Fire-resistive stairway enclosures constructed of the following materials and minimum thicknesses, exclusive of any required plaster, may be used in Class Fireproof Structures, exclusively for school purposes, and in Class 2 Fire-Protected Structures:
(a) 
Solid brick or solid structural units eight inches thick.
(b) 
Solid concrete, plain or reinforced, four inches thick.
(c) 
Solid cinder concrete blocks four inches thick and plastered on both sides three inches thick.
(d) 
Solid gypsum, poured or block, three inches thick.
(e) 
Hollow clay tile, two cells in wall thickness, four inches thick and plastered on both sides or six-inch partition tile, two cells in wall thickness and plastered on one side.
(f) 
Hollow concrete block eight inches thick or four inches thick and plastered on both sides.
(g) 
Hollow gypsum block three inches thick and plastered on both sides.
(2) 
Fire-resistive stairway enclosures of other materials or forms of construction shall have a fire-resistive rating of at least two hours.
F. 
Fireproof partitions, one-hour.
(1) 
Fireproof partitions shall be constructed of the following materials and minimum thicknesses, exclusive of any required plaster:
(a) 
Solid or hollow brick or solid structural units four inches thick.
(b) 
Solid gypsum, poured or block, two inches thick.
(c) 
Solid cinder concrete, poured or block, three inches thick.
(d) 
Solid walls of cement mortar or concrete 2 1/2 inches thick and reinforced in two directions with at least 1/8 of 1% of steel in each direction.
(e) 
Solid walls at least 2 1/2 inches thick of gypsum or cement plaster and supported by incombustible studding and metal lath or mesh.
(f) 
Hollow clay tile three inches thick and plastered on both sides.
(g) 
Hollow gypsum blocks three inches thick.
(h) 
Hollow concrete blocks three inches thick and plastered on both sides.
(i) 
Hollow walls of gypsum board at least 1/2 inch thick on incombustible studding three inches thick and plastered on both sides with 1/2 inch of unsanded gypsum plaster.
(j) 
Hollow partitions of metal lath or mesh or welded wire ribbed lath and plaster on incombustible studding with 3/4 inch of cement or gypsum plaster on each side. When paper-backed lath is used, the paper shall be flameproof.
(k) 
Hollow walls, at least three inches thick, of gypsum board, at least 1/2 inch thick, on both sides of incombustible studding spaced not over 16 inches on centers and covered on both sides with one-eighth-inch-thick hard asbestos cement composition sheets with all joints covered with two-inch-wide batten strips of the same material as sheets or of approved type metal strips.
(2) 
In nonfireproof structures, wood-stud fire-retarding partitions may be used as fireproof partitions with a maximum spacing of 16 inches on centers and metal lath or mesh weighing at least three pounds per square yard fastened to the studding at maximum intervals of six inches vertically and plastered on both sides with gypsum or cement plaster to at least three-fourths-inch grounds, or three-eighths-inch plasterboard on both sides plastered with 1/2 inch of unsanded gypsum plaster, or one-half-inch plasterboard on both sides covered with hard asbestos cement composition sheets at least 1/8 inch in thickness with all joints covered with two-inch batten strips of the same material or with approved metal battens. Grounds for chair rails, baseboards and similar appurtenances, if used in such partitions, shall be of metal-covered wood or of incombustible material. Continuous vertical spaces in such walls shall be fire-stopped as required in § 86-80, Firestopping. Spaces between studs shall be filled with incombustible material when required by the Superintendent of Buildings.
(3) 
Fire partitions of other materials or forms of construction shall have a fire-resistive rating of one hour.
G. 
Construction of fireproof partitions.
(1) 
Fireproof partitions in Class 1 Fireproof Structures and Class 2 Fire-Protected Structures shall be carried at each tier of a structure on incombustible supports and, unless suitably anchored or reinforced, the maximum unsupported height shall be 30 times the total thickness.
(2) 
Where plaster is required, unsanded gypsum plaster shall be at least 1/2 inch thick and sanded gypsum or cement plaster shall be 3/4 inch thick.
(3) 
The thickness of the material and construction of fireproof partitions of masonry as given are the minimum for fire-resistive purposes and shall be increased as required to comply with § 86-60, Masonry construction.
A. 
Protection of closed shafts.
(1) 
A series of floor openings consisting of two or more openings in successive floors or a floor and a roof shall be deemed to be a shaft and shall be enclosed.
(2) 
Such shafts shall be constructed of materials or assemblies having a fire-resistive rating of three hours, except as provided in Subsection C, Protection of vent shafts in nonfireproof residence structures, and Subsection I, Dumbwaiter shafts.
B. 
Protection of elevator shafts in existing structures.
(1) 
Shafts for elevators, escalators or similar hoisting devices in existing Class 3 or Class 4 public structures, as defined in § 86-12A(1), Public buildings, which are not already enclosed with fire-resistive materials shall be enclosed as provided in Subsection A, Protection of closed shafts, except as otherwise herein provided in Subsection J, Existing shaftways.
C. 
Protection of vent shafts in nonfireproof residence structures. In nonfireproof residence structures occupied by one or two families, vent shafts shall be supported on and be constructed of materials having a fire-resistive rating of one hour and shall extend at least three feet above the roof and be covered by a ventilating skylight of metal and glass.
D. 
Enclosure at the top of shafts. In nonfireproof structures, except one- and two-family residence structures, shafts extending into the top story shall be carried through and at least three feet above the roof. Every shaft extending above the roof, except open shafts and elevator shafts, shall be enclosed at the top with a roof of materials having a fire-resistive rating of three hours and shall have a metal skylight covering at least 3/4 of the area of the shaft in the top story, except that the required skylight may be replaced by a window or windows of equivalent area in the side of the shaft, provided that the sills of such windows are at least three feet above the roof and that the windows do not face within 10 feet of a property line. Any shaft terminating below the top story of a structure shall have the top enclosed with material having a fire-resistive rating of three hours.
E. 
Enclosure of the bottom of shafts. The bottom of shafts which do not extend to the ground, except vent shafts, shall be enclosed with materials having a fire-resistive rating of three hours elsewhere than in one- or two-family residence structures.
F. 
Enclosure for hoisting machinery. Any compartment containing machinery which communicates with a shaft enclosure shall have its enclosing walls constructed of materials or assemblies having at least the same fire-resistive rating as the shaft enclosure with which it communicates.
G. 
Number of elevators in a shaft. Not more than two elevators shall be placed hereafter in any one shaft, and where there are only two elevators in any building, they shall be placed in separate shafts.
H. 
Enclosure of open shafts. Open shafts shall be enclosed with materials having a fire-resistive rating as required for exterior walls or of any other form of construction having a fire-resistive rating of three hours and possessing proper weatherproof qualities.
I. 
Dumbwaiter shafts. Dumbwaiter shafts in residence structures and having a cross-sectional area of nine square feet or less shall have a fire-resistive rating of at least one hour for shafts extending not more than three stories or 40 feet above the basement or cellar and a fire-resistive rating of at least two hours for shafts extending more than three stories or 40 feet but not more than six stories or 75 feet above the basement or cellar, except that any part of such dumbwaiter shafts which extend into the cellar or basement shall be protected by materials or assemblies having a fire-resistive rating of at least three hours.
J. 
Existing shaftways.
(1) 
Any existing hoistway, elevator or wellhole not already enclosed, as provided in this code, and not provided with fireproof doors, the opening thereof through and upon each floor of said building shall be provided with and protected by substantial guards or gates and with such good and sufficient trapdoors as may be directed and approved by the Superintendent of Buildings. When, in the opinion of the Superintendent, automatic trapdoors are required to the floor openings of any unenclosed elevator, the same shall be constructed so as to form a substantial floor surface when closed and so arranged as to open and close by the action of the elevator in its passage either ascending or descending.
(2) 
Except as otherwise provided by law or ordinance, the Superintendent of Buildings shall have power and authority to require the openings of hoistways, elevators and wellholes in buildings to be enclosed or secured by trapdoors, guards or gates and railings.
(3) 
All guards or gates required by this section shall be kept closed at all times, except when in actual use, and the trapdoors shall be closed at the close of the business of each day by the occupant or occupants of the building having the use or control of the same.
A. 
Protection of exterior opening required. Every opening in the exterior walls of public and business structures more than 40 feet high, which is distant in a direct line less than 30 feet from any frame structure or from any opening in any other structure and in a different plane or is less than 50 feet in a vertical direction above a nonfireproof roof of an adjoining structure within a distance of 30 feet of the wall in which the opening is located, shall be equipped with a protective opening having a fire-resistive rating of 3/4 hour, except that one-fourth-inch-thick plate glass may be used on the street fronts of such structures, regardless of the separation from other structures, and all windows shall be of the automatic type or fixed sash type, and all doors shall be self-closing.
B. 
Exterior window frames and sash. When the height of a structure exceeds 150 feet, all exterior window frames and sash shall be of incombustible materials throughout the full height of the structure.
C. 
Protection of openings in exterior stairs, fire towers and fire escapes. Door and window openings, where permitted on exterior stairs. fire towers and fire escapes or under or adjacent to exterior stairs or fire escapes, shall be protected by self-closing fire doors or fixed or automatic fire windows or automatic fire shutters. Doors, windows and shutters in openings serving as means of egress to exterior stairs, fire towers and fire escapes shall be so arranged as not to obstruct any exit.
D. 
Protection of open shafts. In open shafts having a cross-sectional area at any point of 36 square feet or less, openings shall be equipped with protective assemblies having a fire-resistive rating of at least 3/4 hour, except that this provision shall not apply to such openings in shafts of private dwelling structures when the openings are at least three feet distant from any other structure.
E. 
Fire shutters to open readily. When fire shutters are used in exterior openings, at least one row in every three vertical rows of shutters on front window openings shall be arranged to open readily from the outside. Distinguishing marks shall be provided on these shutters as required by the Superintendent of Buildings.
F. 
Vertical separation of windows.
(1) 
In business structures over 40 feet high, exterior openings above the second story, which are located vertically above one another, shall have a space of at least three feet between the top of one opening and the bottom of the one next above. Such space shall be enclosed with materials having a fire-resistive rating as required for exterior walls or of any other form of construction having a fire-resistive rating of three hours.
(2) 
A maximum of one-third (1A) of the height of such enclosing materials may be replaced by wire glass in fixed metal sash and trim or other assemblies having equivalent fire-resistive properties.
G. 
Closing of protective assemblies. Protective assemblies on exterior openings, unless provided with approved automatic closing devices operative from either side, shall be closed when not required to be open and, at the close of business each day, shall be closed by the occupant or occupants of the structure having the use or control of them.
H. 
Protection of openings in lot line walls. All openings in walls erected on the lot lines shall be protected by fixed self-closing or automatic-closing assemblies having a fire-resistive rating of at least 3/4 hour.
A. 
Protection of openings in fire walls. The maximum area of an opening in a fire wall shall be 80 square feet, the total width of all openings on any level less than 25% of the length of the wall, except that openings for the passage of motor trucks may be a maximum of 140 square feet and the minimum distance between such openings shall be three feet unless special permission is secured from the Superintendent of Buildings. Each opening, except where used as a required means of exit, shall be equipped with an automatic protective assembly or an automatic and self-closing protective assembly having a fire-resistive rating of three hours. Where openings in the fire wall are used as exits, at least one such exit shall be equipped with a self-closing protective assembly of a three-hour fire-resistive rating on each side of the exit, and other exit openings shall have an automatic and self-closing assembly of equal rating.
B. 
Protection of openings in fire partitions. The only openings permitted in fire partitions shall be those required for doors and there shall be but one opening, unless the provision of additional openings would not exceed 25% of the length of the wall in total width. The maximum area for a door opening shall be 80 square feet, except that openings for the passage of motor trucks may be a maximum of 140 square feet, and each opening shall be equipped with a self-closing protective assembly having a fire-resistive rating of 1 1/2 hours.
C. 
Protection of openings in fireproof partitions. The only openings permitted in fireproof partitions enclosing public hallways leading to required exits shall be those required for doors. Each opening shall be equipped with a self-closing protective assembly having a fire-resistive rating of at least 3/4 hour.
D. 
Protection of openings in interior shafts.
(1) 
Protection of openings in vent shafts. Openings into vent shafts, except nonfireproof vent shafts, shall be equipped with protective assemblies having a fire-resistive rating of one hour.
(2) 
Protection of openings in elevator shafts. Doors opening into elevator shafts shall be equipped with protective assemblies having a fire-resistive rating of 1 1/2 hours, except that where the elevator shaft opens into a vestibule constructed of materials or assemblies having a fire-resistive rating of at least three hours and in which openings are protected by assemblies having a fire-resistive rating of at least 3/4 hour, the openings into the elevator shaft shall be protected by assemblies having a fire-resistive rating of at least 3/4 hour. Other openings into such shafts, except window openings to the outer air and openings to elevator machinery rooms, are forbidden.
(3) 
Protection of openings in dumbwaiter shafts. Openings in dumbwaiter shafts shall be equipped with self-closing protective assemblies having a fire-resistive rating of 3/4 hour.
(4) 
Protection of openings in other shafts. Openings in shafts otherwise unprovided for in this subsection shall be equipped with self-closing protective assemblies having a fire-resistive rating of 1 1/2 hours, except that where such a shaft opens into a vestibule constructed of materials or assemblies having a fire-resistive rating of at least three hours and in which openings are protected by assemblies having a fire-resistive rating of at least 3/4 hour, the openings into the shaft shall be protected by assemblies having a fire-resistive rating of at least 1/4 hour.
E. 
Protection of openings in basement and cellar partitions. In nonfireproof structures, except structures occupied exclusively for residence purposes by one or two families, openings in cellar partitions required by § 86-17, Restrictions as to height and area, or in any story more than 1/2 below the curb shall have self-closing protective assemblies having a fire-resistive rating of 1 1/2 hours or fixed or self-closing windows having a fire-resistive rating of 3/4 hour.
F. 
Separation of attached or built-in garages. Where private garages are attached to or form a part of a story within a residential structure of Class 1 Nonfireproof Structures or Class 4 Wood Frame Structures, walls, ceilings and floors enclosing such garages shall be separated from the remainder of the structure by assemblies having a fire-resistive rating of one hour, and all openings between the garage and the remainder of the structure shall be provided with self-closing or automatic protective assemblies having a fire-resistive rating of 3/4 hour, except as may be otherwise provided in Article XVII, Multiple Dwellings. Where living quarters are located above such a garage, the egress facilities from the living quarters shall not pass through the garage section.
Wood or other combustible material may be used in the construction or interior finish of Class 1 Fireproof Structures and Class 2 Fire-Protected Structures only as hereafter provided.
A. 
Floor sleepers, bucks, nailing blocks and grounds. Floor sleepers, bucks, nailing blocks and grounds, if only the railing surface is exposed, may be of wood in Class 1 Fireproof Structures and Class 2 Fire-Protected Structures. When floor sleepers of combustible material are used, the space between the floor construction and the wood flooring shall be filled with incombustible material, except that in Class 2 Fire-Protected Structures, combustible floor sleepers may be used without filling in such space, provided that such floors are fire-stopped at the girder lines in areas of 400 square feet or less and under all permanent partitions.
B. 
Interior trim. Wood flooring, interior doors, sash with their frames, trim and casings, other interior wood and other approved combustible trim, when backed solidly with fire-resistive material, may be used as provided in § 86-96, Construction of special occupancy structures, and § 86-97, Construction of stage and proscenium wall, and elsewhere than in stair enclosures, public hallways and passageways in Class 1 Fireproof Structures, 150 feet or less in height, and Class 2 Fire-Protected Structures.
C. 
Wearing surfaces.
(1) 
Wearing surfaces 1/2 inch or less in thickness made of cork or rubber composition, linoleum, asphalt composition tile or similar material having the same fire-resistive qualities when cemented to the upper surface of an approved type of fire-resistive floor construction may be used elsewhere than in stair enclosures. Where wood flooring is permitted, such wearing surfaces may be cemented directly to the wood floor.
(2) 
Untreated wood finish flooring 7/8 inch or less in aggregate thickness, when cemented or attached directly to the surface of an approved type of fire-resistive floor construction, may be used elsewhere than in stair enclosures and corridors, and in structures exceeding 150 feet in height, a wood subflooring may be used to support such combustible finish flooring or a wearing surface as permitted in the preceding paragraph, provided that such subflooring and the sleepers supporting it shall be treated to render them fire-resistive in accordance with the rules of the Superintendent of Buildings.
(3) 
Untreated combustible insulation board, in a single layer not to exceed 1/2 inch in thickness when cemented or attached directly to the surface of an approved type of fire-resistive floor construction, may be used elsewhere than in stair enclosures and corridors when covered by an incombustible wearing surface in accordance with the rules of the Superintendent of Buildings.
D. 
Subdividing partitions. Subdividing partitions in Class l Fireproof Structures and Class 2 Fire-Protected Structures shall be made of incombustible material or wood or other approved combustible material treated to render it fireresistive, except that partitions made of a single thickness of wood or wood and glass may be used in Class 1 Fireproof Structures, 150 feet or less in height, and Class 2 Fire-Protected Structures to subdivide rooms or spaces 5,000 square feet or less in area, except as provided in § 86-72F, Fire-proof structures, one-hour, if separated from adjoining rooms or spaces, corridors, elevator and stair enclosures by fireproof partitions or walls made of incombustible material having a fire-resistive rating of at least one hour.
E. 
Use of treated wood for fire protection.
(1) 
Wood flooring treated to render it fire-resistive in accordance with the rules of the Superintendent of Buildings may be used elsewhere than in stairs, halls and corridors.
(2) 
Wood window sash, frames and trim treated to render them fire-resistive may be used elsewhere than in stair halls and corridors, except for exterior windows where otherwise provided in § 86-74, Protection of exterior openings.
(3) 
Wood treated to render it fire-resistive may be used for other interior trim elsewhere than in stair halls or in corridors.
(4) 
Wooden doors with their frames and trim treated or protected to render them fire-resistive may be used in any location, provided that they meet the fire-resistive requirements for such location.
F. 
Freestanding molding and veneers. Untreated wood may be used, except in stair halls and required exit corridors, for freestanding moldings having a cross-sectional area of two square inches or less and for face veneers, 1/8 inch or less in total or aggregate thickness and glued to treated cores or backing. Untreated wood veneers, 1/20 inch or less in thickness when mounted directly upon incombustible material, may be used without restriction as to location.
A. 
Doors for openings in fire walls shall be constructed without any glass.
B. 
Doors for openings in fire partitions may be constructed with glass, provided that they meet the fire-resistive requirements for such doors, except that in structures used exclusively as schools, hospitals, museums and libraries, vision panels having a maximum total area of four square feet per door and divided into panes with a maximum area of one square foot per pane shall be permitted.
C. 
Doors for openings in fireproof partitions may be constructed with a total maximum exposed area of wired glass of 720 square inches.
D. 
All wired glass shall be at least 1/4 inch thick and shall enclose a layer of wire fabric reinforcement having a maximum mesh of 7/8 inch, and the size of the wire shall be at least No. 25 steel wire gauge or of equivalent fire-resistive qualities and shall be set at least 5/8 inch into the frame.
A. 
In Class 3 Nonfireproof Structures and in commercial buildings of Class 4 construction, the ceilings of all stories below grade and over the lowest story, if such story is partially below the curb or surrounding ground level, shall be covered with metal lath and plaster, plasterboard and plaster, plasterboard and sheet metal, one-half-inch plasterboard and one-eighth-inch-thick hard asbestos cement composition sheets with joints covered with two-inch-wide battens of the same material or approved metal strips or other material having a fire-resistive rating of one hour. In Class 3 Nonfireproof Structures heretofore erected in which the classification by occupancy is hereafter changed to business, cellar ceilings, if not already of fireproof construction, shall be of materials or assemblies having a fire-resistive rating of at least one hour. Such a ceiling, however, shall not be required if the floor construction immediately above this lower story is of incombustible material having a fire-resistive rating of at least three hours.
B. 
The ceilings of motion-picture theaters or other structures for public assemblage not required to be fireproof as well as all rooms, entrances or exits used in connection therewith shall have ceilings of five-eighths-inch unsanded gypsum plaster or seven-eighths-inch cement or sanded gypsum plaster on metal lath, measured from the face of the lath, or any form of construction having, a fire-resistive rating of one hour as required by the rules of the Superintendent of Buildings.
A. 
Materials required for roof structures and roofing. All construction, other than water tanks, hereinafter placed above the roof of any part of any structure within the fire limits or of any structure more than 40 feet in height outside of the fire limits shall be of incombustible materials, except when otherwise specifically provided for in this code.
B. 
Bulkheads.
(1) 
The walls of any bulkhead hereafter erected on the roof of a fireproof structure shall be constructed of incombustible material having a fire-resistive rating of one hour and shall be covered on the outside with material meeting the requirements of Subsection K, Roofing, unless constructed in accordance with § 86-60, Masonry construction.
(2) 
The walls of any bulkhead hereafter erected on the roof of any nonfireproof structure may be of wood-stud partition construction having a fire-resistive rating of one hour and shall be covered on the outside with material meeting the requirements of Subsection K(1), Materials for roofing.
C. 
Penthouses. The exterior walls of penthouses shall consist of materials having a fire-resistive rating of three hours and shall be covered on the outside with material meeting the requirements of Subsection K(1), Materials for roofing, unless constructed in accordance with § 86-60, Masonry construction. Floors of such structures shall be constructed as required for the other floors of the structure.
D. 
Doors and windows. Doors, door frames and windows in bulkheads or penthouses, except where otherwise specifically provided for, shall be constructed as other doors, door frames and windows similarly located in the structure.
E. 
Greenhouses and conservatories. Greenhouses or conservatories may be erected on the roof of any structure, provided that only incombustible materials are used in their construction, and the floors of such structures are constructed as required for the other floors of the structure.
F. 
Dormers. Dormers hereafter erected shall be constructed in the same manner as the roof on which they are placed. The sides and top shall be covered with material meeting the requirements of Subsection K(2), Fire tests of roof coverings.
G. 
Skylights.
(1) 
The frame and sash of all skylights shall be constructed of metal, except that in structures in which corrosive fumes are present, wood frame and sash may be permitted in the discretion of the Superintendent of Buildings. The frames and other parts of skylights shall be securely anchored to the supporting structure.
(2) 
Skylights placed over shafts, including stairways, shall be glazed with plain glass 3/16 inch or less in thickness. The maximum area of any pane of glass used in such skylights shall be 720 square inches. Skylights over places other than shafts shall be glazed with wire glass.
(3) 
Skylights in which plain glass is used shall be protected by wire screens placed between four and 10 inches above the glazed portion of the skylight at all points. Such screen shall be of No. 12 steel wire gauge or heavier, the wire shall have a mesh between 3/4 inch and one inch and shall extend beyond the glazing on all sides for a distance of at least the height of the screen above the glazing. When any such skylight is located over any passageway, stairway, elevator or any occupied room, a similar screen shall also be placed below the skylight.
H. 
Scuttles. Unless provided with some other means of access to the roof, every structure over 15 feet high, except roofs with a pitch greater than 20° from the horizontal, shall have a scuttle in the roof with a substantial ladder leading to it. Scuttles shall be covered on the top and edges with sheet metal or other approved incombustible material. Scuttle openings shall be at least two feet by three feet in size.
I. 
Tanks.
(1) 
Tanks of more than 500 gallons of capacity hereafter placed in or on any structure shall be supported on masonry, reinforced concrete or steel construction.
(2) 
Every tank shall have, in the bottom or on the side near the bottom, a pipe or outlet at least two inches in diameter and fitted with a suitable valve for discharging the contents in an emergency.
(3) 
The location of a tank over or near a line of stairs or an elevator shaft is forbidden unless there is a solid roof or floor underneath the tank.
(4) 
Unenclosed roof tanks shall have covers sloping at an angle of at least 30°.
(5) 
When hoops are used in the construction of tanks, they shall be of metal and round in section.
J. 
Cooling towers. Cooling towers hereafter erected above any roof shall be of incombustible material, except the drip bars which may be of wood.
K. 
Roofing.
(1) 
Materials for roofing. Every roof hereafter placed on a structure shall be covered with an approved roofing of brick, concrete, tile, slate, metal asbestos or built-up roofing finished with asphalt, slag or gravel or with other approved fire-retardant material.
(2) 
Fire tests of roof coverings. All roof coverings shall be subject to a brand test. The fire test specifications of the American Society for Testing Materials, D, C19-26T, shall be used and will be accepted by the Superintendent of Buildings when made by a laboratory of recognized reputation.
L. 
Slanting roofs, mansards and dormers.
(1) 
Every mansard or other slanting roof having a pitch of more than 30° placed on any non-fireproof structure over 40 feet high shall be constructed in accordance with the provisions of § 86-71G, Special roof construction.
(2) 
Every mansard or other slanting roof having a pitch of less than 30° placed on any non-fireproof structure may be constructed of the same materials as the roof construction of the structure, provided that the face and back of the mansard or slanting roof is covered with roofing material meeting the requirements of Subsection K(2), Fire tests of roof coverings.
M. 
Cornices, gutters and half-timber decoration. Cornices and gutters, inclusive of those on show windows, hereafter placed or replaced on the exterior of any structure, except structures of frame construction, shall be of incombustible materials, except that wood half-timbering and other wood decorative treatment may be used on the face of masonry construction in structures of Class 3 and Class 6 construction and less than 45 feet in height. Such cornices and gutters shall be secured to the wall with metal brackets and anchors with a maximum spacing of four feet and extending at least four inches into the wall at the top and bottom.
N. 
Signs. All materials used for the framing of signs or for their support upon the roofs or any part of any such structures within the fire limits or of any such structures more than 40 feet in height outside the fire limits shall be constructed of incombustible materials.
A. 
Firestopping required.
(1) 
Structures, whether fireproof or nonfireproof, shall have all concealed draft openings firestopped with incombustible material to form an effectual fire barrier between stories and between the upper story and the roof space.
(2) 
All partitions dividing any structure into more than one store or other occupancy shall be fireproof partitions as prescribed in § 86-72F, Fireproof partitions, one-hour.
B. 
Firestopping of openings for pipes, belts and shafting.
(1) 
Openings around exposed pipes, belts or power shafting shall be filled with incombustible material or shall be closed off by close fitted metal caps at the ceiling and floor line or on each side of the wall. For nonfireproof construction, metal sleeves shall be provided in addition to the caps.
(2) 
Openings for belts shall be provided with approved slotted doors or otherwise closed off. Belts shall not pass through fire walls or fire partitions.
C. 
Firestopping of furred walls, partitions and concealed roof spaces. Walls, including masonry walls furred with combustible material, and stud bearing partitions shall be fire-stopped with incombustible material at floors, ceilings and roofs. The firestopping shall extend from the ceiling to the underside of the flooring or roofing. Concealed roof spaces in Class 3 Nonfireproof structures shall be cut off into areas of 2,500 square feet or less by firestops.
D. 
Firestopping of stairs. Stairs, except in one- and two-family residence structures, shall be fire-stopped between wooden stair carriages by headers at top and bottom. The location of closets beneath stairs is forbidden, except in Class 1 Fireproof Structures, unless they are entirely lined with incombustible material. The underside of stairs of combustible material shall be covered with metal lath and plaster to a total thickness of 3/4 inch, measured from the back of the lath, or with plasterboard and a minimum of one-half-inch unsanded gypsum plaster or one-half-inch-thick plasterboard covered with one-eighth-inch-thick hard asbestos cement composition boards with joints covered with a two-inch batten strip of the same material or approved metal strips, except where such stairs are enclosed by a partition of lawful construction as specified in Article VII, Means of Egress.
E. 
Materials for firestopping. Firestopping shall be done with the following materials: brick, concrete, gypsum, asbestos, metal lath and cement or gypsum plaster, mineral wool, rock wool or other approved materials.