Exciting enhancements are coming soon to eCode360! Learn more 🡪
Town of Goshen, NY
Orange County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
If a builder, developer or contractor desires to extend or install mains, it shall be at his own cost and expense and such extension or installation shall be accomplished in accordance with the provisions hereof and to the approval of the Town of Goshen. Plans for such extension shall first be approved by the New York State Board of Health, and all such work shall conform to specifications approved by the New York State Board of Health and Orange County Health Department and approved by the Town and be subject to Town inspection. Title to all such extensions, including service connections between the main and the curb box, shall be vested in the Town, and upon the acceptance of any such work by the Town, the Town shall maintain and replace the same when necessary as in the case of Town-installed work.
All mains shall be Class 150 cast iron (thickness Class 22) cement-mortar lined or asbestos cement pipe Class 2400 pounds, maximum length for six-inch pipe not to exceed 10 feet zero inches (AWWA approved), a minimum of six inches in diameter and shall be adequate for fire protection purposes. Dead-end mains over 600 feet long shall be a minimum of eight-inch-diameter pipe and shall be provided with a hydrant or blowout at the end. Pipe may be push-on joint or mechanical joint. Two bronze wedges shall be used with push-on joints. Pipes shall have five feet of cover.
Cast-iron fittings shall be standard-sized, mechanical joint, short body cast-iron fittings for 250 pounds per square inch water pressure plus water hammer in full accordance with American Standard Specification A21.10 — 1952 for short body fittings and A21.11 — 1964 for mechanical joints, the latest specification to be used for push-on-type fittings. The fittings shall be cement-mortar lined and seal-coated in accordance with American Standard Specification A21.4 — 1964. Mechanical joint fittings shall come with lead-tipped gaskets.
A. 
Valves shall be installed at every street intersection and at every place where a main is tapped. Valves shall also be installed along each street so that there is a valve within 1,000 to 1,200 feet of the next valve.
B. 
All valves shall be mechanical joint, double-gate valves with O-ring packing designed for a waterworking pressure of 150 pounds per square inch and shall be in full conformance with the latest AWWA Specification C-500 for Gate Valves for Ordinary Water Works Service. All valves shall open by turning to the left or counterclockwise and have a square operating nut. They shall be the same as or equal to those manufactured by the Mueller Co., or approved equal, with lead-tipped gaskets.
C. 
Valve boxes shall be a two-piece, cast-iron, standard screw type, with cast-iron cover of proper length for actual trench depth. Valve box covers shall fit flush with the outside casting rim, shall not rattle or rock and shall be capable of removal with a bar or pick. Each cover face shall be lettered "Water" and have an arrow indicating the direction of opening.
A. 
Hydrants shall be installed at such spacing that each house within the area shall be located within 600 feet of a hydrant. A hydrant or blowout shall be installed at the end of every dead-end water main. In all instances hydrant spacings shall meet the requirements of the New York rating organizations.
B. 
Fire hydrants shall be in accordance with the latest AWWA Specification C-502, Fire Hydrants for Ordinary Water Works Service. Each hydrant shall be equipped with two nozzles and one pumper connection if requested by the Town, of proper size to meet fire protection requirements of the Town. The nozzle and pumper threads and type of operating nut also shall meet these standards.
C. 
All hydrants shall open by turning to the left or counterclockwise.
D. 
All hydrants furnished shall be for a trench depth of five feet from the ground line to the bottom of the six-inch mechanical joint bell connection. All hydrants shall have a six-inch mechanical joint connection and a valve opening of four inches. The hydrants shall be the same as or equal to those manufactured by Mueller or other well-known manufacturer of hydrants. The hydrants furnished shall be true breakaway traffic-type hydrants.
A. 
House services shall be installed to each existing house at the time the water main is placed in the street. Locations for all lots' services to curb box are to be installed in a development before street is double-surfaced treated, prior to acceptance by the Town. Services shall be a minimum of 3/4 inch and laid at the depth of five feet.
B. 
Corporation stops shall be standard waterworks stops similar or equal to the Mueller Style H-15000.
C. 
The main shall be tapped at an angle of 45° from the vertical in order that a flexible copper tubing can be laid in a gooseneck position to take care of pipe movement. All taps shall be installed in accordance with the pipe manufacturer's directions, allowing three threads of the corporation tap to be exposed.
D. 
Copper service pipe shall be Type K copper tubing annealed after coiling, conforming to the requirements of the latest ASTM Designation B-88. All couplings required to join sections of tubing shall be similar or equal to the Mueller H-15400, three-part union, copper to copper.
E. 
Curb stops shall be standard waterworks, inverted key, round-way, ground key curb stops, similar or equal to Mueller Style H-15200, with coupling for copper tubing on the inlet and outlet.
F. 
Curb boxes shall be extension type for 5 1/2 to 6 1/2 foot cover, arch pattern base with one-inch upper section, and shall be complete with stationary rod and two-hole cover. The word "Water" shall be lettered on the cover.
A. 
Pipe shall be laid in a workmanlike manner, at a cover depth of five feet and under Town supervision. Selected backfill shall be placed by hand and be tamped along the side of the pipe. Fill to 12 inches above the pipe shall be carefully placed and tamped. Rock shall be excavated to a depth of six inches below the pipe and the excavation backfilled with bank-run gravel. A-C pipe shall be laid in sand and in accordance with manufacturer's specifications.
B. 
Reaction or thrust backing shall be applied on all pipelines at all tees, plugs, caps and at joints deflecting 22 1/2° or more. Thrust backing shall be of concrete of a mix having a compressive strength of not less than 2,000 pounds per square inch, and backing shall be placed between solid ground and the fitting to be anchored. The backing shall be so placed that the pipe and fitting joints will be accessible for repair.
C. 
Testing pipelines.
(1) 
All pipelines shall be tested after installation. The test shall consist of a pressure test and a leakage test. Under the pressure test the hydrostatic pressure shall be equivalent to a pressure of 50% above normal operating pressure, based on the elevation of the test gauge. Under the leakage test the hydrostatic pressure shall be set at the maximum operating pressure for the particular location.
(2) 
The pressure test shall be at least one hour in length, before complete backfilling of the pipeline, when the joints are exposed. All visible leaks, any cracked or defective pipe, fittings, valves or hydrants discovered in consequence of the pressure test shall be repaired and the test shall be repeated until results are satisfactory.
(3) 
The leakage test shall be conducted after the pressure test has been completed satisfactorily. Push-on joints may be tested for leakage prior to complete backfilling. Leakage is defined as the quantity of water to be supplied into the newly laid pipe necessary to maintain the specified leakage test pressure after the pipe has been filled with water and the air expelled.
(4) 
The allowable leakage shall not exceed 25 United States gallons per 24 hours per mile of pipe per inch nominal diameter for pipe in eighteen-foot lengths, evaluated on a pressure basis of 150 pounds per square inch. Should any test of pipe laid disclose leakage greater than that specified, the contractor shall locate and repair the defective joints.
D. 
Disinfection of pressure water pipelines. Disinfection of water mains shall be equal in substance to the Standards for Disinfecting Water Mains prepared by the American Water Works Association, C-601-54 (excepting Item 18.4.1), and include the following:
(1) 
Before being placed into general use, all pressure water piping and pipelines shall be flushed thoroughly, disinfected with chlorine and flushed again, in accordance with sound engineering practice. The method of disinfection shall consist of introducing a solution of hypochlorite or chlorine and water in controlled quantities into the piping system in such proportion that the chlorine water mixture entering the piping shall contain at least 50 parts per million of chlorine. Outlets in the piping shall be opened to ensure complete distribution of the chlorine water mixture throughout the system to be disinfected. The mixture shall remain in the system long enough to destroy all non-sphere-forming bacteria, at least 24 hours and preferably longer, as may be directed.
(2) 
The chlorine residual at the end of the required retention time shall be at least 10 parts per million at pipe extremities. If the residual is less than 10 parts per million, the disinfection procedure shall be repeated until a residual of 10 parts per million after retention is obtained at pipe extremities.
(3) 
Upon completion of the disinfection process, the chlorine water mixture shall be flushed thoroughly from the system and samples for bacteriological examination shall be taken from the system to assure that complete disinfection has been accomplished. Arrangements for bacteriological sampling and examination shall be made by the contractor with a recognized laboratory, meeting the New York State Department of Health's requirements for examination of water samples for bacteriological examination. Water samples shall be taken at the locations selected by the Town Inspector. Results of laboratory test shall be forwarded to the Town. If results are not satisfactory, the contractor shall repeat the disinfection procedure. The acceptance and connection to the Town system of the installation is contingent on the receipt of satisfactory laboratory testing.
E. 
Setting hydrants.
(1) 
The hydrants shall be located as shown or as directed and in a manner to provide complete accessibility, and also in such a manner that the possibility of damage from vehicles or injury to pedestrians will be minimized. The plans show the approximate location of hydrants. In general, hydrants shall be installed on the same side of the street as the main.
(2) 
All hydrants shall stand plumb and shall be set to the established grade, as directed in the field, with nozzles at least 18 inches above the ground. Whenever a hydrant is set in soil that is pervious, drainage shall be provided at the base of the hydrant by placing coarse gravel or crushed stone mixed with coarse sand to a depth of at least six inches above the waste opening in the hydrant and to a distance of one foot around the elbow. Whenever a hydrant is set in clay or impervious soil, a drainage pit two feet in diameter and three feet deep shall be excavated below each hydrant and filled compactly with crushed stone mixed with coarse sand. The crushed stone shall be placed under and around the elbow of the hydrant and to a level of six inches above the waste opening.
(3) 
The bowl of each hydrant shall be well braced against unexcavated earth at the end of the trench with concrete backing. All hydrants shall be installed with a six-inch double-gate valve on the branch line leading from the main.
(4) 
The hydrant shall be painted the color approved by the Town of Goshen. Upon completion of that section of main installation, two copies of record maps are to be forwarded to the Town Clerk. These record maps shall show location of all valves and hydrants, and reference to all valve locations shall be shown.