[Adopted 3-30-2011 by Ord. No. 378[1]]
[1]
Editor's Note: This ordinance also repealed
former Art. II, Building Construction, adopted 4-27-2007 by Ord. No.
345, as amended.
This article shall be known as the "West Whiteland Township
Building Code."
[Amended 8-26-2015 by Ord. No. 425]
Except as amended and modified by the Pennsylvania Uniform Construction Code contained in 34 Pennsylvania Code Chapters 401 through 405, the International Building Code, including Appendix Chapters E and F, as published by the International Code Council, Inc., is hereby adopted as the Building Code of West Whiteland Township for the control of buildings and structures as herein provided, with additions, insertions, deletions, and changes prescribed in § 129-16 of this article.
[1]
Editor's Note: Former § 129-10, Enforcement agency, and
§ 129-11, Insurance, were repealed 8-26-2015 by Ord. No. 425.
[Amended 8-26-2015 by Ord. No. 425]
Underground/aboveground storage tanks: building permit required
for installation and demolition permit required for removal.
A.Â
Underground/aboveground storage tanks. A permit is required to install,
remove, repair, or alter a tank used for the storage of flammable
or combustible liquids or other liquids or to modify or replace any
line or dispensing device connected thereto. This includes noncombustible
or nonflammable liquid storage tank repairs and/or removal.
B.Â
All tank installations shall comply with all federal, state, and
local requirements. Complete documentation relating to the removal/installation/modification/repair
is required and shall include but not be limited to the following
items: Pennsylvania Department of Environmental Resources installer's
certification, letters of notification to the Pennsylvania Department
of Environmental Protection and the Pennsylvania State Fire Marshal's
Office for tank removal/installation, contractor's insurance
certificates and excavation sample test reports when required by the
Fire Marshal or Code Administration Officer.
Any change in ownership, occupant, or tenant, use group change
or any other type of change in the way any building is being used
shall require a new use and occupancy permit and an inspection prior
to occupancy. No change or reoccupancy shall take place before the
issuance of a new use and occupancy permit. Transfer of ownership:
within 10 days of transfer of ownership, an application and an inspection
are required. This applies to all use groups except one- and two-family
dwellings.
[1]
Editor's Note: Former § 129-14, Board of Appeals,
and § 129-15, Non-owner-occupied premises, were repealed
8-26-2015 by Ord. No. 425.
[Amended 8-26-2015 by Ord. No. 425]
The following sections of the International Building Code are
amended as follows. To the extent any of the following amendments
exceed the requirements of the Uniform Construction Code, the changes
were adopted by West Whiteland Township by ordinances duly enacted
on or before July 1, 1999.
A.Â
Add a new Section 709.1.2 to read as follows:
709.1.2 Use Groups - A, B, E, F, H, I, M, R, S, and U: Structures having more than one tenant and/or owner/occupier shall
provide tenant separation walls between each such tenant and/or owner/occupier.
Said walls shall be a minimum of one hour' UL (Underwriters Laboratory)
fire-rated assembly, unless other sections of this code require a
higher rating. All fire tenant separation walls shall be constructed
of material consistent with the type construction of the building.
|
B.Â
Sections 903.2.1.1 (Group A-1), 903.2.1.3 (Group A-3), and 903.2.1.4
(Group A-4), Condition Number 1, shall be deleted, and a new section
shall be inserted to read as follows:
1.
|
The fire area exceeds 5,000 square feet in area (465m2).
|
C.Â
Section 903.2.3 shall be deleted, and a new section shall be inserted
to read as follows:
903.2.3 Group E: Where a Use Group E fire area
exceeds 5,000 square feet or is located either above or below the
level of exit discharge of exits that serve the Use Group E fire area,
an automatic fire-suppression system shall be provided.
|
D.Â
Section 903.2.4 shall be deleted, and a new section shall be inserted
to read as follows:
903.2.4 Groups F-1 and F-2: An automatic fire-suppression
system shall be provided where any building or structure of Use Groups
F-1 and F-2 fire area exceeds 5,000 square feet.
|
E.Â
Section 903.2.7 shall be deleted, and a new section shall be inserted
to read as follows:
903.2.7 Group M and Group B: An automatic fire-suppression
system shall be provided where any building or structure of Use Group
M or Use Group B fire area exceeds 5,000 square feet.
|
F.Â
Add a new Section 903.2.8.1 to read as follows:
903.2.8.1 Group R: Built in accordance with the
2009 International Building Code and all dwellings and structures
built in accordance with the 2009 International One- and Two-Family
Residential Code (this applies to all detached, attached, or any other
configuration of dwelling units): An automatic fire-suppression system
shall be provided throughout all buildings and structures, or partitions
thereof, of Use Group R, in accordance with Section 903.3.1.3; this
includes any Use Group R buildings built under the 2009 IRC for One-
and Two-Family Dwelling Code.
| |||
Automatic fire-suppression systems shall be installed, in accordance
with NFPA 13D (2007 Edition), with the following additions:
| |||
1.
|
Drawings: Full shop drawings and hydraulic calculations
shall be submitted to the Code Administration Officer for approval.
The Code Administration Officer can waive the requirement for complete
drawings and calculations if it is deemed unnecessary.
| ||
2.
|
Flow Switch and separate fire alarm device (bell
or horn) shall be provided.
| ||
3.
|
Static Test. Systems shall be hydrostatic-tested
for 200-PSI water test for two hours. A representative of West Whiteland
Township shall be present.
| ||
4.
|
Actual Flow Test Required. All NFPA 13D sprinkler
systems shall be tested and approved prior to occupancy. The test
shall consist of an actual sprinkler head flow test. The system shall
meet or exceed sprinkler head manufacturer's flow requirements
for the design and area protected by the heads installed. The test
shall be performed at the most hydraulically remote area of the system.
The systems shall meet both the one- and two-head design criteria.
The test shall be performed with a representative of the West Whiteland
Township Code Administration's office present. NFPA 13R systems
are required to be flow-tested and shall meet the design requirements
listed above, except a four-head flow test shall be performed.
|
G.Â
Section 903.2.9 shall be deleted, and a new section shall be inserted
to read as follows:
903.2.9 Group S-1: An automatic fire-suppression
system shall be provided where any building or structure of Use Group
S-1 fire area exceeds 5,000 square feet.
|
H.Â
Section 903.2.9.1 shall be deleted, and a new section shall be inserted
to read as follows:
903.2.9.1 Repair Garages: An automatic fire-suppression
system shall be provided throughout all buildings used as repair garages
in accordance with Section 406, as shown, where the S-1 fire area
exceeds 5,000 square feet.
|
I.Â
Add new Section 903.2.9.2 to read as follows:
903.2.9.2 Group S-2: An automatic fire-suppression
system shall be provided where any building or structure of Use Group
S-2 fire area exceeds 5,000 square feet.
|
J.Â
Add new Section 903.3.1.4 to read as follows:
903.3.1.4 NFPA 13 Light-Hazard Systems: All NFPA
13 light-hazard systems shall be designed to have maximum of 168 square
feet (or less) of head spacing. This is the maximum that heads shall
be spaced in any occupancy permitted to be designed under a light-hazard
type classification per NFPA 13.
|
K.Â
Add new Section 903.3.1.5 to read as follows:
903.3.1.5 Safety Factor: All NFPA 13, 13R, and
13D fire-suppression systems shall be designed as to provide a 10
PSI safety factor, as defined in NFPA 13.
|
L.Â
Add new Section 1011.6 to read as follows:
1011.6 Additional Locations/Low-Level Exit Signs: In all A-1, A-2, A-3, B, E, R, I-1, and I-2 occupancies that are
required to have more than one exit or exit access, it shall be supplemented
by additional low-level exit signs reading "EXIT." Additional exits
signs shall be located on the latch side of the door frame wall within
six inches to eight inches of the floor, in addition to the one above
or egress access areas. Self-illuminated or luminous exit signs shall
be UL-listed for this purpose and approved by the Fire Marshal or
Building Official.
|
M.Â
Add a new Section 1211.0 to read as follows:
1211.0 Radon: At the time of application for a
building permit, plans must depict reasonable measures to be constructed
below grade level for future radon mitigation. Designs should accommodate
the addition of a venting system for removal of radon gas from the
premises in the future if such gas becomes present in levels of concentration
exceeding safe levels as defined by the United States Environmental
Protection Agency. A minimum four-inch perforated pipe shall be installed
below the basement slab around the interior perimeter of the foundation
and shall terminate into a sump pit.
|
N.Â
Add a new Section 1808.1.1 to read as follows:
1808.1.1 Frost Line: For footing purposes, the
frost line in West Whiteland Township shall be a minimum of 36 inches
below grade. This shall be considered a minimum depth to the bottom
of footings.
|
O.Â
Add a new Section 3303.7 to read as follows:
3303.7 Extermination Required: The applicant shall
show proof that the building or structure has been exterminated for
rodents, vermin, and other pests two weeks prior to the demolition.
|
P.Â
Add a new Section 116.6 to read as follows:
116.6 Required Demolition: If the code official
determines that more than 50% of any structure has been damaged by
a natural disaster, structural collapse, fire, or other disaster,
the code official shall require the structure to be demolished. Every
building damaged in the disaster shall be inspected, and a determination
shall be made on a case-by-case basis. The cost of demolition shall
be the owner's responsibility.
|
Ordinance No. 345, dated April 27, 2007, as amended, of West
Whiteland Township is hereby repealed.
The granting of any permit, the performance of any review or
inspection, or any other action under this article by the Township
or any of its designated officials shall not constitute a representation,
guaranty, or warranty of any kind by the Township or any of its officials
or employees as to the proper manner of construction or repairs and
shall create no liability upon or a cause of action against the Township,
its officials or employees for any damages or injury that may result
pursuant thereto.
Nothing in this article or in the International Building Code hereby adopted shall be construed to affect any suit or proceeding pending in court, or any rights acquired, or liability incurred, or any cause or causes of action acquired or existing under any act or ordinance hereby repealed cited in § 129-17 of this article, nor shall any preexisting legal right or remedy of any character be lost, impaired, or affected by this article.