Town of New Castle, NY
Westchester County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[Added 4-28-1959]
Henceforth no refrigeration equipment or air-conditioning equipment requiring the use of water supplied by the Water District No. 1 of New Castle, New York, shall be installed within the district unless a permit authorizing such installation shall have been issued by the Superintendent of the water district.
Henceforth all installations of any individual or collective system of refrigeration or air conditioning in any premises within the district for a single consumer shall be made only in accordance with the following specifications:
A. 
Installations with a capacity of three tons or more shall be equipped with a water-conserving device, such as an economizer, evaporative condenser, water-cooling tower or similar apparatus, which device shall not consume for makeup purposes in excess of 5% of the consumption that would normally be used without such a device.
B. 
Installations of such equipment under the capacity of three tons shall be provided with an automatic water supply regulating device so as to limit the flow of water in relation to the condenser temperature reduction requirements of the apparatus, and in no such case shall the equipment use in excess of two gallons per minute for each ton of capacity.
C. 
Each direct water connection to any such equipment using water district water for cooling purposes shall be equipped with an approved backflow preventer device, except in installations where the water supply piping has no contact with the refrigerant. For the purposes thereof, the water supply shall be deemed to have no contact with the refrigerant when such supply is separated from the refrigerant by two substantial and independent wall thicknesses of metal.
[Amended 6-25-1974]
D. 
Any such refrigerating or air-conditioning unit with a capacity of more than 20 pounds of refrigerant shall be provided with a relief valve installed on the outlet side of the check valve of the water supply connection, which relief valve shall be set at five pounds above the maximum water pressure at the point of installation.
The provisions of this article shall be interpreted and administered in accordance with the following:
A. 
The term "air conditioning," as used herein, applies to that equipment used primarily for human comfort cooling, which equipment shall be considered on the basis that one compressor motor horsepower is equal to one ton of refrigeration.
B. 
Equipment used for a purpose other than air conditioning shall be considered on the basis that one compressor motor horsepower is equal to 0.6 of a ton of refrigeration.
C. 
Refrigeration or air-conditioning equipment using illuminating gas for energy shall be rated on the basis that one ton is equal to the removal of 12,000 British thermal units per hour with an evaporating temperature of 5° F. and a condensing temperature of 86° F.