Exciting enhancements are coming soon to eCode360! Learn more 🡪
Lancaster Area Sewer Authority, PA
Lancaster County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
A. 
Minimum pipe size: eight inches.
B. 
Polyvinyl chloride pipe (PVC).
(1) 
Pipe: Type PSM SDR-35, ASTM D3034, or Type PS-46, ASTM F789, or ASTM F794 (ribbed or closed profile, smooth interior) or ASTM F949 (corrugated, smooth interior). Use ASTM F679 for over 15 inches in diameter. Depth of construction of ASTM D3034 pipe shall be limited to 15 feet; deeper sewers shall be SDR 21.
(2) 
Fittings: conforming to same applicable ASTM specification requirements for pipe.
(3) 
Joints: push-on with elastomeric gasket, ASTM D3212, and ASTM F477 for gasket specifications.
(4) 
See Detail Drawings 1, 2, 3, 8, 9, 10, 11, 12, 13A, 13B, 14, 17, 18, 19, 21, 22, 24, 30, 31, 32, 33, 34, 35, 36, 37, 38, 39, 53, 54, 55, and 56 in Appendix SB.
[Amended 10-22-2015 by Res. No. 15-10-003]
C. 
Cement-lined ductile iron pipe (DICL): ductile iron pipe conforming to ANSI A21.51 or AWWA C151 for the material class or pressure designated, and ANSI A21.50 or AWWA C150 for wall thickness.
(1) 
Minimum wall thickness: Class 52 unless indicated otherwise on the drawings or as may be required for flanged pipe or restrained joints.
(2) 
Cement mortar lining: conforming to ANSI A21.4 or AWWA C104, except the thickness of linings should not be less than 1/8 inch.
(3) 
Fitting:
(a) 
Ductile iron in accordance with the standard specification set forth in the ANSI A21.10 or AWWA C110. All fittings shall be minimum Class 250 with cement lining and joints as required for pipe restraint.
(b) 
Iron fittings to be enclosed by valve and cleanout manholes shall be of the short body flanged type in order to minimize the size of the manholes.
(4) 
Joints: push-on type or mechanical joint type in accordance with ANSI A21.11 or AWWA C111 for all pipe.
(5) 
Corrosion protection coatings:
(a) 
Exterior (for pipe and fittings): factory coated with bituminous material, one mil minimum DFT.
(b) 
Interior (for pipe and fittings):
[1] 
Ceramic epoxy lining.
[2] 
Calcium aluminate mortar coating.
[3] 
Coating material selection by pipe manufacturer.
(6) 
See Detail Drawings 1, 2, 3, 8, 9, 10, 11, 12, 13A, 13B, 14, 17, 18, 19, 21, 22, 23, 24, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35, 36, 37, and 38 in Appendix SB.
D. 
Flexible pipe coupling: made of flexible elastomeric PVC with two Series 300 stainless steel adjustable clamps. See Detail Drawings 9, 11, 12, 31, 32, 33, 34, 35, and 37 in Appendix SB.
A. 
Pipe, fitting, and joint materials: minimum pipe size.
(1) 
Lateral sewer: six-inch minimum.
(2) 
Service line: four-inch minimum.
(3) 
In all cases, the lateral sewer and service line shall be of adequate size to carry projected sewer flows.
(4) 
Grinder pump service lines shall have a minimum size of 1 1/4 inches.
[Added 10-22-2015 by Res. No. 15-10-003]
B. 
Cast iron soil pipe (service lines only) shall not be permitted.
C. 
Polyvinyl chloride pipe (PVC):
(1) 
Pipe: Type PSM SDR-35, ASTM D 3034.
(2) 
Fittings: conforming to ASTM D 3034.
(3) 
Joints: push-on with elastomeric gasket, ASTM D 3212; and ASTM F 477 for gasket specification. Rigid pipe joints, including glued or solvent welded joints, will not be permitted for buried service.
(4) 
See Detail Drawings 31, 32, 33, 34, 35, and 39 in Appendix SB.
D. 
High-density polyethylene pipe.
[Amended 10-22-2015 by Res. No. 15-10-003]
(1) 
Material. Polyethylene pipe shall conform to ASTM D-1248 and D-3350 for Type III Grade P34, Category 5, and Plastic Pipe Institute Material Designation PE-3408. Pipe shall be SDR-11 or approved equal.
(2) 
Joints. Pipes shall be joined by thermal butt-fusion in accordance with ASTM D-2657 and the pipe manufacturer's recommendations. Termination to pump basins, valves and fittings shall be flange assemblies. The pipe adjacent to these joints must be rigidly supported for a distance of one foot beyond the flange assembly.
(3) 
Fittings. Fittings shall conform to all applicable ASTM D3261 (HDPE) and other ASTM specifications. Fittings shall have plain ends for thermal butt-fused joining. Fittings shall have the same type, grade and class of PE compound. Mechanical compression fittings shall be used only when joining to different piping materials.
E. 
Pipe plug materials: designed for permanent installation and removable. Obtain plugs for various types of pipe used from respective pipe manufacturers.
F. 
Saddle materials:
[Amended 10-22-2015 by Res. No. 15-10-003]
(1) 
Cast iron: correctly contoured for outside diameter of pipe and incorporating a gasket and band assembly.
(a) 
Saddle body: cast iron, ASTM A48, Class 35, coated inside and out to prevent corrosion.
(b) 
Gasket: compound rubber (neoprene) tubular O-ring design, ASTM C361.
(c) 
Band: Type C 304 stainless steel band assembled with two three-fourths-inch Type C 304 stainless steel T-bolts, washers, and hex nuts.
(d) 
Provide spigot or bell inlet and proper adaptor or coupling suitable for connection of the type and size of service connection pipe.
(e) 
Acceptable manufacturer(s) are listed in § 150-13 of this chapter.
(2) 
PVC: correctly contoured for the outside diameter of the pipe and incorporating a gasket and band assembly.
(a) 
Molded PVC solvent weld 45° saddle wye, with a captive rubber O-ring flange gasket and stainless steel strap(s) with stainless steel bolts for attachment to the lateral sewers.
(b) 
Fittings meet ASTM D3034 for SDR 35 pipe and are listed in the Uniform Plumbing Code.
(3) 
See Detail Drawings 31, 32, 33, 34, 35, and 36 in Appendix SB.
G. 
Flexible pipe coupling: as specified for gravity sewer main.
H. 
Sewer service check valve:
(1) 
Sewer service check valve shall be installed in a horizontal portion of the sewer service line and shall prevent the reverse flow of wastewater into the structure.
(2) 
The check valve shall be supplied in a kit from one manufacturer consisting of a valve body, disk, disk seat and upper collar. It shall comply with CSA B181-4, and the plastic materials shall conform to ASTM D1784, cell classification 12454-B and NSF 14.
(3) 
The check valve shall include an access sleeve that is a pipe opening through which access is gained to the disk or valve seat. The access sleeve shall be cut to length in the field and attached to the socket on the top of the valve body.
(4) 
The collar, insert pipe and disk assembly shall be designed to fit inside the access sleeve, the removable assembly shall consist of a length of insert pipe permanently attached to the access collar on the top and a disk assembly on the bottom. It is then removed vertically from the access sleeve, the attached disk assembly is also removed allowing above grade repair. The internal lifting device is self-aligning, self-seating and provided with an alignment indicator located with 12 inches of the upper access opening.
(5) 
The check valve shall be installed on horizontal drainage systems with uniform slope. The access sleeve shall terminate above grade and shall have a maximum length of 12 feet.
I. 
Low-pressure force mains:
[Added 10-22-2015 by Res. No. 15-10-003]
(1) 
High-density polyethylene pipe, tubing and fittings: as specified for lateral sewers and service lines.
A. 
Cement-lined ductile iron pipe (DICL): ductile iron pipe conforming to ANSI A21.51 or AWWA C151 for the material class or pressure designated, and ANSI A21.50 or AWWA C150 for wall thickness.
(1) 
Minimum wall thickness: Class 52 unless indicated otherwise on the drawings or as may be required for flanged pipe or restrained joints.
(2) 
Cement mortar lining: conforming to ANSI A21.4 or AWWA C104, except the thickness of linings should not be less than 1/8 inch.
(3) 
Fittings: ductile or gray iron in accordance with ANSI A21.10 or AWWA Specification C110. All fittings shall be minimum Class 250 with cement lining and joints as required for pipe restraint.
(a) 
Iron fittings to be enclosed by valve, and cleanout manholes shall be of the short-body flanged type in order to minimize the size of the manholes.
(4) 
Joints: push-on type or mechanical joint type in accordance with ANSI A21.11 or AWWA C111 Specifications. Restrained joint pipe shall be used for pressure applications.
(5) 
See Detail Drawings 15, 17, 18, 19, 21, 23, 25, 26, 27, 28, and 29 in Appendix SB.
(6) 
Pipe thrust restraint:
(a) 
Concrete thrust blocking: sizing in accordance with the Standard Details. See Detail Drawings 27, 28, and 29 in Appendix SB.
(b) 
Restrained joint pipe, manufactured of ductile iron per ANSI/AWWA C151/A21.51, with restrained push-on joints. Restraint system shall be designed to allow disassembly of joints, if required. See Detail Drawing 26.
(c) 
Restrained joint pipe, manufactured of ductile iron per ANSI/AWWA C151/A21.51, with rigid restrained mechanical joints. Restraint system shall be designed to allow disassembly of joints, if required. See Detail Drawing 26.
(d) 
Mechanical joint restraint, utilizing a ductile iron follower gland with twist-off nuts, shall not be permitted.
(e) 
Tie rods providing full joint restraint and extending to the adjacent fitting or joint, and beyond to each successive fitting or joint, to provide adequate restrained length in accordance with the Standard Details, and as approved by the National Board of Fire Underwriters No 124, "Standard for Outside Protection." All rods, clamps, nuts, and washers utilized for anchorage shall be stainless steel.
(f) 
Restrained mechanical joint retainer glands will not be permitted.
(7) 
Corrosion protection coatings: as specified for gravity sewer mains.
B. 
Detectable utility warning tape:
[Amended 10-22-2015 by Res. No. 15-10-003]
(1) 
Tape shall be a tri-layer laminate consisting of a printed film, a solid foil core and a clear encapsulating film.
(2) 
The solid foil core shall be encased between a one-hundred-percent virgin polyolefin pigmented film and a clear protective film that allows a full view of the foil to insure continuity. The solid core provides for detectability utilizing either the inductive or conductive modes using a pipe and cable locator.
(3) 
The ink used to print the material is permanent and cannot be removed by normal handling or upon burial.
(4) 
Tape shall be installed at a depth between 12 and 18 inches below the finish surface for all nonmetallic pipeline materials unless the force mains are installed by the directional boring method.
(5) 
See Detail Drawings 17, 18, 19 and 21 in Appendix SB.
C. 
Mechanical joint coupling: consisting of one cylindrical steel middle ring, two follower rings, two resilient gaskets, and a set of steel trackhead bolts. Acceptable manufacturer(s) are listed in § 150-13 of this chapter.
D. 
Tracer wire:
[Added 10-22-2015 by Res. No. 15-10-003]
(1) 
Tracer wire is to be installed with all force main materials.
(2) 
Tracer wire shall be #12 AWG CHS-CCS high-strength copper clad steel conductor, insulated with a 30 mil, high-density, high-molecular-weight polyethylene (HDPE) and rated for direct burial use at 30 volts. Insulation color shall meet the APEAZ color code standard for identification of buried utilities. For sewer lines, the color is green. The tracer wire shall be attached to the force main at five-foot intervals with plastic zip ties. (Attaching the wire with tape is expressly prohibited.)
(3) 
Install a tracer wire test station at no greater interval than 300 feet without a tracer wire magnetized tracer box. The boxes shall have a cast iron cover and shall be extended to grade. Use boxes rated for traffic loads in roadway installations. For tracer boxes located in sidewalks and driveways, use a tracer box that has the appropriate top section for concrete or driveway applications. The tracer wires shall terminate in the tracer boxes. The boxes shall have covers with "sewer" designated.
(4) 
Install grounding anodes at all dead ends and stubs. Anodes shall be specifically manufactured for use with tracer wire pipe location equipment.
(5) 
All splices of the tracer wire underground shall be made with connectors manufactured for this type of service. At tees, the three wires shall be joined using a single three-way lockable connector. At crosses, the four wires shall be joined using a four-way connector. Connectors shall have dielectric silicon filled to seal out moisture and corrosion and shall be installed in a manner so as to prevent any uninsulated wires to be exposed. Nonlocking friction-fit, twist-on or taped connectors are prohibited.
(6) 
Test the continuity of wire from test point to test point using equipment compatible with LASA locating equipment.
(7) 
See Detail Drawings 49, 50, 51, 53, 54, 55 and 56 in Appendix SB.
A. 
General. Manholes and other concrete structures shall conform to the requirements in ASTM C478, latest edition, except as indicated below. Design and dimensions of base, tapered and straight riser sections, top section and pipe connections shall be as indicated on the Standard Details.
(1) 
Concrete: composition and compressive strength conforming to ASTM C478 except use Type II or Type III cement in manhole components and increase compressive strength to 4,500 psi (at 28 days) in precast bases.
(2) 
Casting and curing: wet cast and steam curing process in accordance with Section 3.6.11 and 3.7.2 of AWWA C302.
(3) 
See Detail Drawings 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13A, 13B, 14, 36, 37, and 38 in Appendix SB.
B. 
Manhole bases shall be precast with factory precast flow channels, unless otherwise approved by LASA. The invert channels shall be smooth and semicircular in shape conforming to the inside of the adjacent sewer section. Changes in direction of flow shall be with a smooth curve of as large a radius as the size of the manhole will permit. Changes in size and grade of the channels shall be made gradually and evenly. The floor of the manhole outside the channels shall be smooth and shall slope towards the channels at 1/2 inch per foot. The use of cast-in-place bases or channels may be permitted by special exception from LASA for specific manholes; the bases and channels shall conform to the requirements of this section.
C. 
Precast top sections: design and dimensions as required by conditions of materials and construction as specified previously except additional and differing requirements as follows:
(1) 
Frame hold-down bolt inserts. Factory cast in top section, four three-fourths-inch slotted, moveable, polypropylene-coated, threaded inserts, of three inches depth, to accommodate manhole frame hold-down bolts. Inserts shall be designed for an ultimate load in tension of 12,500 pounds. Inserts shall be factory plugged for shipping. Coordinate insert location with frame manufacturer to assure proper location in top sections.
(a) 
See Detail Drawings 4, 5, 6, and 7 in Appendix SB.
(2) 
Flat slab tops (for shallow manholes and manholes with thermoplastic liner):
(a) 
Thickness versus diameter as indicated on Details.
(b) 
Tops factory-formed to properly accept and support required manhole frame and cover and formed to join riser section in a matching joint.
(c) 
See Detail Drawings 1 and 2 in Appendix SB.
(3) 
Eccentric cone tops: manufacture to minimum wall thickness shown on Details and with same area of circumferential steel reinforcement as riser sections.
D. 
Preformed butyl rubber sealing compound: Manhole component joints shall be factory formed for self-centering, concrete-to-concrete-bearing, employing preformed butyl rubber base, sealing compound, conforming to Fed. Spec. SS-S210A, Type 1, Rope Form, shipped protected in a removable two-piece wrapper. Size cross-section of rope form to provide squeeze-out of material around entire interior and exterior circumference when joint is completed. Provide two strips of material, one around the interior and one around the exterior circumference of the joint. Products not containing butyl rubber are not acceptable. Acceptable manufacturers are listed in § 150-13 of this chapter. See Detail Drawings 1, 2, 3, 4, 5, 6, 7, 13A, and 13B.
E. 
Grout: Nonshrink, nonmetallic, ready-mix requiring only the addition of water. Acceptable manufacturers are listed in § 150-13 of this chapter. See Detail Drawings 1, 3, 4, 5, 6, 7, 9, 10, 11, 13A, 13B, 14, 15, 36, 37, and 38.
F. 
Manhole steps: factory installed in manhole components, prealigned vertically, spaced on twelve-inch centers, with a minimum clear step width of 10 1/2 inches. The rungs shall have a drop front to prevent side slippage. The first step shall not be more than 24 inches from the top of the manhole. Steps to be manufactured of aluminum or polypropylene as designated. Manhole steps shall be cast-in-place or inserted into polypropylene inserts. Acceptable manufacturers are listed in § 150-13.
(1) 
Reinforced plastic step: composed of a one-half-inch Grade 60, ASTM A615, deformed steel reinforcing bar, completely encapsulated in copolymer polypropylene compound conforming to ASTM D4101.
(2) 
Aluminum step: Aluminum Alloy AA Designation 6061-16. Coat that portion of the step embedded in concrete with heavy-bodied bituminous paint.
(3) 
See Detail Drawings 1, 2, 3, 10, 13A, 13B, 14, and 15.
G. 
Precast or LASA-approved plastic grade rings: leveling and adjusting units of thickness required to the minimize number of rings (maximum of 2), and of materials and construction as specified previously. Factory cast or LASA-approved plastic type grade rings shall have hold-down bolt holes matching location of same in manhole frame. Design must provide for full bearing of manhole frame.
(1) 
See Detail Drawings 1, 2, 3, 4, 5, 13A, 13B, 14, and 15.
H. 
Manhole frame and cover: gray iron castings conforming to ASTM A48, Class No. 30, designed for AASHTO Highway Loading Class HS-25. Provide castings of uniform quality, free from blowholes, porosity, hard spots, shrinkage distortion, or other defects.
(1) 
Finish: Bearing surfaces of cover and frame shall be machined smooth to prevent rocking and rattling under traffic.
(2) 
Identification: Cast the word "LASA" integrally in two-inch-size raised letters on all covers, except those on sampling manholes and manholes on private lines; these covers shall read "SEWER."
(3) 
Frame hold-down bolts: All manhole frames shall be bolted with four three-fourths-inch stainless steel anchor bolts, evenly spaced.
(a) 
Watertight manhole frame and bolted lid: gray iron castings conforming to previously specified requirements for manhole frame and cover shall have concealed pickholes, furnished with four one-inch anchor holes.
(b) 
Shall have a T-seal.
(c) 
Shall have four Type 316 stainless steel bolts for holding the cover to the frame.
(4) 
See Detail Drawings 4, 5, 6, and 7.
(5) 
All manhole frames and covers that are dedicated to the Authority shall comply with all applicable steel procurement laws.
I. 
Manhole insert. Designed to fit the manhole frame rim, shall be manufactured from high-density polyethylene copolymer material meeting requirements of ASTM D1248, Class A, Category 5, Type III. Insert shall be 1/8 inch thick minimum and shall have two one-fourth-inch vent holes located 180° apart, 1 1/2 inches from the top. Insert shall be made no less than eight inches deep to allow the manhole cover to swing free when being removed. Insert shall have a close cell neoprene gasket with adhesive backing, installed on the insert rim by the manufacturer, and shall have a corrosion-resistant nylon lifting strap for removal and reinstallation. Manhole cover shall sit flush with the adjacent grade when insert is in place. Acceptable manufacturers are listed in § 150-13 of this chapter. See Detail Drawings 4 and 5.
J. 
Interior plastic liner: Air-release manholes, manholes to which force mains discharge and the next five manholes downstream, and other manholes as required by LASA, shall be fitted with thermoplastic liners. Liners shall be semirigid PVC formed to fit manhole contours. Acceptable manufacturers are listed in § 150-13 of this chapter.
(1) 
Liner sheets formed with dovetail ribs to accommodate factory casting integrally in each manhole component.
(2) 
Provide liner in white color to reflect light.
(3) 
Protection between the lined manhole and the frame and cover shall be obtained by installing either a PVC telescoping connector, of the same manufacturer as the liner, or a one-piece liner cover manufactured from semirigid PVC.
(4) 
See Detail Drawing 3.
(5) 
If the manholes downstream indicated for interior plastic liners are existing, then use the interior corrosion-resistant coatings as listed below.
K. 
Exterior waterproofing of manhole and concrete structures:
(1) 
Prepare surfaces to be coated in accordance with the written instructions of the coating manufacturer, including cleaning, sandblasting or acid etching as necessary.
(2) 
Coat precast components with bitumastic material at the factory; 20 mil minimum thickness.
(3) 
Acceptable manufacturers and their products are listed in § 150-13 of this chapter.
(4) 
See Detail Drawings 1, 2, 3, 12, 13A, 13B, 14, and 15.
L. 
Interior corrosion-resistant coatings (existing manholes or concrete structures): Where interior corrosion-resistant coatings are required by the Authority, prepare manhole surfaces to be coated in accordance with the written instructions of the coating manufacturer, including cleaning, sandblasting, or acid etching as necessary.
(1) 
Finished protective liner shall be installed by someone certified and trained in the application of the specified process.
(2) 
Coat inside of manhole and concrete structures with a spray-applied resin manhole liner, or equal to the Spray Wall as manufactured by Sprayroq. Inc.
M. 
Pipe openings: custom preformed during manufacturing in each base and riser section requiring such, to accommodate type of pipe and pipe opening seal provided.
N. 
Pipe opening seals - rubber gaskets (for new manholes): resilient rubber gasket type, cast integrally with manhole component conforming to requirements specified in ASTM C923.
(1) 
Acceptable manufacturers are listed in § 150-13 of this chapter.
(2) 
See Detail Drawings 1, 2, and 9.
O. 
Pipe opening seals - mechanical pipe seals (for existing manholes): Modular mechanical type, consisting of interlocking synthetic rubber links shaped to continuously fill the annular space between the pipe and wall opening. Links shall be connected with stainless steel bolts to form a continuous belt.
(1) 
Acceptable manufacturers are listed in § 150-13 of this chapter.
(2) 
See Detail Drawings 10, 11, 37, and 38.
P. 
Pipe opening seals - expandable sleeve and boot seals (for new or existing manholes) shall consist of a stainless steel expandable sleeve, rubber boot and stainless steel take-up ring installed to manufacturer's specifications. Pipe opening seals shall conform to ASTM C923.
Q. 
Drop manholes: construct in accordance with type indicated in details on drawings. Use same type pipe and fittings in drop connection as used in sewer line from which drop connection is made.
R. 
Manhole protection posts. Schedule 20 black steel pipe, filled with 3,000 psi concrete, embedded in concrete as shown in the Standard Details.
(1) 
Exposed portion of pipe shall be painted with two coats of yellow, rust-inhibiting paint.
(2) 
See Detail Drawing 16.
A. 
Sewage air release valve: designed to automatically release air, gas, or vapor under pressure during system operation. Valve design shall feature short body and float stem components so that the operating mechanism is kept free from contact with sewage during operation. Valve construction as follows:
(1) 
Valve body and cover: ASTM A126 Class B cast-iron body and cover with a threaded inlet connection of the size shown on the Drawings and with a one-half-inch NPT outlet connection near the top and one-inch NPT port near the bottom to permit the installation of flushing attachments.
(2) 
Maximum working pressure: 150 psi.
(3) 
Valve shall have an 18-8 stainless steel float and a replaceable seat of Buna-N or other suitable material. Internal leakage mechanism shall be 18-8 stainless steel. Plastic or bronze linkage is not acceptable. The linkage mechanism shall be capable of being removed from the cover without disassembly of the mechanism. Valves shall have three-sixteenth-inch diameter stainless steel orifice for working pressures up to 150 psi.
(4) 
Provide flushing attachments to include one-half-inch flushing valve, one-inch blow off valve, five feet of rubber hose and quick-disconnect couplings.
(5) 
Acceptable manufacturers are listed in § 150-13 of this chapter.
(6) 
See Detail Drawing 15.
B. 
Sewage air and vacuum valves: designed to automatically exhaust large quantities of air during the filling of a system and to allow air to reenter the system during draining or when a vacuum (negative pressure) occurs. Valve design shall feature short body and float stem components so that the operating mechanism is kept free from contact with sewage during operation. Valve construction is as follows:
(1) 
Air and vacuum valves shall be of the size listed in the schedule or shown on plans with threaded inlet and outlet to three-inch size. Body and cover shall be ASTM A126 Class B cast iron. Valve body shall be tapped one-half-inch NPT near the top and one-inch NPT near the bottom to permit the installation of flushing attachments and have a two-inch NPT plugged port near the base to facilitate cleanout of large solids.
(2) 
Valves shall have a 316 stainless steel plug and removable 316 stainless steel seat ring in a ductile iron cage. The plug shall contain a renewable resilient O-ring seat of Buna-N or other suitable material retained in a dovetail groove. There shall be a single float ball of 18-8 stainless steel, attached to a stainless steel stem by means of a universal connection.
(3) 
Provide flushing attachments to include one-half-inch flushing valve, one-inch blow off valve, five feet of rubber hose and quick-disconnect couplings.
(4) 
Maximum working pressure: 150 psi.
(5) 
Acceptable manufacturers are listed in § 150-13 of this chapter.
(6) 
See Detail Drawing 15.
C. 
Sewage combination air valves: consisting of an air-release valve and an air and vacuum valve factory piped into a compact assembly. The combination assembly shall automatically release air, gas or vapor under system operating pressure and shall also allow air to reenter the system during draining or when a vacuum (negative pressure) occurs. Combination valve designs shall feature short bodies and float stem components so that the operating mechanisms are kept free from contact with sewage during operation. Valve construction as follows:
(1) 
Sewage combination air valve shall have a large orifice for the air and vacuum function and a small orifice for the air-release function valve contained in a single body. The air and vacuum orifice shall be the same size as the nominal size of the combination air valve.
(2) 
The valve body shall have a threaded inlet and outlet to three-inch size and ANSI B16.1 Class 125 flanged inlet and threaded outlet in larger sizes. Body and cover shall be ASTM A 126 Class B cast iron. Valve body shall be tapped two-inch NPT near the bottom to permit cleanout of large debris. Additional one-inch and one-half-inch NPT taps shall be provided for the installation of flushing attachments.
(3) 
Valves shall have a 316 stainless steel plug and removable 316 stainless steel seat ring in a ductile iron cage. The plug shall contain a renewable resilient O-ring of Buna-N or other suitable material retained in a dovetail groove connection. All other internal metal components shall be stainless steel. Bronze or plastic components are not acceptable. The air release orifice shall be stainless steel orifice for working pressures up to 150 psi.
(4) 
Provide flushing attachments to include one-half-inch flushing valve, one-inch blow off valve, five feet of rubber hose and quick-disconnect couplings.
(5) 
Air release valve maximum working pressure: 150 psi.
(6) 
Acceptable manufacturers are listed in § 150-13 of this chapter.
(7) 
See Detail Drawing 15.
A. 
Casing pipe: Seamless pipe, ASTM A53, minimum twenty-foot length.
(1) 
Thirty-five thousand psi minimum yield strength.
(2) 
Full circumference welded joints.
(3) 
Asphalt coated on the exterior.
(4) 
Minimum wall thickness: as indicated on the drawings or as required by LASA or owner of the crossing.
(5) 
Steel casing pipe diameter: as indicated on the drawings, or if not indicated shall be at least six inches larger than the combined outside diameter of the pipe bells, or as required by the owner of the right-of-way or entity issuing the permit.
(6) 
Smooth wall steel pipes with a nominal diameter of over 54 inches will not be permitted.
(7) 
See Detail Drawings 24 and 25.
B. 
Casing spacers: band and risers constructed of 304 stainless steel, or HDPE, with a 90 mil thick PVC or neoprene liner. Runners shall be constructed of UHMW polymer. All fasteners shall be stainless steel. See Detail Drawings 24 and 25.
C. 
Casing end seals: by same manufacturer as spacers, wraparound type, fabricated from one-eighth-inch synthetic rubber. Seals shall be secured to casing utilizing 304 stainless steel straps with worm gear mechanism. See Detail Drawings 24 and 25.
A. 
Pipe bedding, initial backfill, and backfill materials to restoration depths as indicated on the Standard Details.
B. 
Final restoration over trenches and at manhole locations as indicated on the Standard Details.
Construction of new pump stations and alterations, additions, or modifications to existing pump stations shall be in accordance with the Authority's requirements. The developer shall acquire the necessary drawings and specifications from the Authority prior to commencing with design of a pump station.
[Amended 12-15-2011 by Res. No. 11-12-001]
A. 
The individual pump station shall be a factory-built and tested wetwell/drywell grinder pump station consisting of a grinder pump suitable mounted in a basin constructed of high density polyethylene (HDPE) for simplex stations. NEMA 6P electrical quick-disconnect, pump removal system, stainless steel discharge assembly/shut-off valve, anti-siphon valve/check valve, each assembled in the basin, electrical alarm panel and all necessary internal wiring and controls. All components and materials shall be in accordance with the Authority Rules and Regulations. The individual grinder pump system shall be manufactured by Environment One or Authority-approved equal. The normal grinder pump unit shall be a Model DH071 or any update or modification model thereto or Authority-approved equal. The developer's (or homeowner's) engineer shall review the hydraulic requirements of the application and confirm that the use of the normally specified pump is acceptable or shall specify an alternative pump model that would be acceptable to the Authority. For each individual grinder pump unit installed in a development within the LASA service area, the developer shall provide a lump-sum cash payment to LASA to cover the cost of inspection; which fee shall be established by resolution of the LASA Board.
B. 
Pumps.
(1) 
The pump shall be a custom designed, integral vertical rotor, motor driven solids handling pump of the progressing cavity type with a single mechanical seal. Double radial O-ring seals are required at all casting joints to minimize corrosion and create a protective barrier. All pump castings shall be cast iron, fully epoxy coated to 8-10 mil nominal dry thickness wet applied. The rotor shall be through-hardened, highly polished, precipitation hardened stainless steel. The stator shall be a specifically compounded ethylene propylene synthetic elastomer. This material shall be suitable for domestic wastewater service. Its physical properties shall include high tear and abrasion resistance, grease resistance, water and detergent resistance, temperature stability, excellent aging properties, and outstanding wear resistance.
(2) 
The pump shall be capable of delivering 15 GPM against rated total dynamic head of 0 feet (0 PSIG), 11 GPM against a rated total dynamic head of 92 feet (40 psig) and 7.8 GPM against a rated total dynamic head of 185 feet (80 PSIG). The pump must be capable of operating at negative total dynamic head without overloading the motor; under no conditions shall in-line piping or valving be allowed to create a false apparent head.
C. 
Grinder assembly and construction.
(1) 
The grinder shall be placed immediately below the pumping elements and shall be direct driven by a single, one-piece motor shaft. The grinder impeller (cutter wheel) assembly shall be securely fastened to the pump motor shaft by means of a threaded connection attaching the grinder impeller to the motor shaft. The grinder impeller shall be one-piece, 4140 cutter wheel of the rotating type with inductively hardened cutter teeth. The cutter teeth shall be inductively hardened to Rockwell 50-60c for abrasion resistance. The shredder ring shall be of the stationary type and the material shall be white cast iron. The teeth shall be ground into the material to achieve effective grinder. The shredder ring shall have a staggered tooth pattern with only one edge engaged at a time, maximizing the cutting torque.
(a) 
The assembly shall be dynamically balanced and operate without objectionable noise or vibration over the entire range of recommended operating pressures. The grinder shall be constructed so as to minimize clogging and jamming under all normal operating conditions including starting. Sufficient vortex action shall be created to scour the tank free of deposits or sludge banks which would impact the operation of the pump.
(b) 
The grinder shall be capable of reducing all components in normal domestic sewage; including a reasonable amount of foreign objects such as paper, wood, plastic, glass, wipes, rubber and the like, to finely divided particles which will pass freely through the passages of the pump and the one-and-one-fourth-inch diameter stainless steel discharge piping.
(2) 
As a maximum, the motor shall be a one HP, 1,725 RPM, 240 volt 60 Hertz, one-phase capacity start, ball bearing air-cooled induction type with Class F installation, low starting current not to exceed 30 amperes and high starting torque of 8.4 foot pounds. The motor shall be press-fit into the casting for better heat transfer and longer winding life. Inherent protection against running overloads or locked rotor conditions for the pump motor shall be provided by the use of an automatic-reset, integral thermal overload protector incorporated into the motor. The motor protector combination shall be listed by Underwriters Laboratories, Inc., for the application. The wet portion of the motor armature must be 300 Series stainless steel.
(3) 
The pump/core shall be provided with a mechanical shaft seal to prevent leakage between the motor and pump. The seal shall have a stationary ceramic seat and carbon rotating surface with faces precision lapped and held in position by a stainless steel spring.
(4) 
The tank shall be a wetwell/drywell design made of high density polyethylene, with a grade selected to provide the necessary environmental stress cracking resistance. Corrugated sections are to be made of a double wall construction with the internal wall being generally smooth to promote scouring. The corrugations of the outside wall are to be minimum amplitude of 1 1/2 inches to provide necessary transverse stiffness. Any incidental sections of a single wall construction are to be 0.250 inch thick (minimum). All seams created during tank construction are to be thermally welded and factory tested for leak tightness. The tank wall and bottom must withstand the pressure exerted by saturated soil loading at maximum burial depth. All station components must function normally when exposed to 150% of the maximum external soil and hydrostatic pressure.
(a) 
The tank shall be furnished with one EPDM grommet fitting to accept four-inch SDR 35 pipe. The tank capacity shall be 70 gallons.
(b) 
The drywell accessway shall be an internal extension of the wetwell assembly and shall include a lockable cover assembly providing low profile mounting and watertight capacity. The cover shall be high-density polyethylene, green in color, with a load rating of 150 pounds per square foot. The accessway designed and construction shall enable field adjustment of the station height in increments of three inches or less without the use of any adhesives or sealants requiring cure time before installation can be completed. The station shall have necessary penetrations molded in and factory sealed. To ensure a leak-free installation, no field penetrations will be acceptable.
(c) 
All discharge piping shall be constructed of 304 stainless steel. The discharge shall terminate outside the accessway bulkhead with a stainless steel, one-and-one-fourth-inch female NPT fitting. The discharge piping shall include a stainless steel ball valve rated for 235 psi WOG, PVC. The bulkhead penetration shall be factory installed and warranted by the manufacturer to be watertight.
(d) 
The accessway shall include a single NEMA 6P electrical quick-disconnect for all power and control functions, factory installed with accessway penetrations warranted by the manufacturer to be watertight. The quick disconnect will be supplied with 32 feet of usable electrical supply cable outside the station to connect to the alarm panel. The cable shall be installed in the basin by the manufacturer. The quick disconnect shall require no tools for connecting, seal against water before the electrical connection is made, and include radial seals to assure a watertight seal regardless of tightening torque. The accessway shall also include an integral two-inch vent to prevent sewage gases from accumulating in the tank.
(5) 
The pump discharge shall be equipped with a factory-installed, gravity-operated flapper-type integral check valve built into the stainless steel discharge piping. The check valve will provide a full-ported passageway when open, and shall introduce a friction loss of less than six inches of water at maximum rated flow. Moving parts will be made of a 300 series of stainless steel and fabric reinforced synthetic elastomer to ensure corrosion resistance, dimensional stability and fatigue strength. A nonmetallic hinge shall be an integral part of the flapper assembly providing a maximum degree of freedom to assure seating even at a very low back-pressure. The valve body shall be an injection molded part made of an engineered thermoplastic resin. The valve shall be rated for continuous operating pressure of 235 psi.
(6) 
The pump discharge shall be equipped with a factory-installed, gravity-operated flapper-type integral anti-siphon valve built into the stainless steel discharge piping. Moving parts will be made of 300 series stainless steel and fabric reinforced synthetic elastomer to ensure corrosion resistance, dimensional stability and fatigue strength. A nonmetallic hinge shall be an integral part of the flapper assembly, providing a maximum degree of freedom to ensure proper operation even at a very low pressure. The valve body shall be injection-molded from an engineered thermoplastic resin. The anti-siphon port diameter shall be no less than 60% of the inside diameter of the pump discharge piping.
(7) 
The grinder pump station shall have a cartridge type, easily removable core assembly consisting of pump, motor, grinder, all motor controls, check valve, anti-siphon valve, level controls, electrical quick disconnect and wiring. The core unit shall be installed in the basin by the manufacturer. The core unit shall seal to the tank deck with a stainless steel latch assemble. The latch assembly must be actuated utilizing a single quick-release mechanism requiring no more than a half turn of a wrench. The watertight integrity of each core unit shall be established by a one-hundred-percent factory test at a minimum of 5 PSIG.
(8) 
All necessary motor starting controls shall be located in the cast-iron enclosure of the core unit secured by stainless steel fasteners. The wastewater level sensing controls shall be housed in a separate enclosure from the motor starting controls. The level sensor housing must be sealed via a radial-type seal. The level sensing control housing must be integrally attached to a pump assembly so that it may be removed from the station with the pump and in such a way as to minimize the potential for the accumulation of grease and debris accumulation, etc. The level sensing housing must be high-impact thermoplastic copolymer over-molded with a thermoplastic elastomer.
(a) 
Nonfouling wastewater level controls for controlling pump operation shall be accomplished by monitoring the pressure changes in an integral air column connected to a pressure switch. The air column shall be internally molded from a thermoplastic elastomer suitable for use in wastewater and with excellent impact resistance. The air column shall have only a single connection between the water level being monitored and the pressure switch. All connections are to be sealed radially with redundant O-rings. The level detection device shall have no moving parts in direct contact with the wastewater and shall be integral to the pump core assembly in a single, readily exchanged unit. Depressing the push-to-run button must operate the pump even with the level sensor housing removed from the pump.
(b) 
All fasteners throughout the assembly shall be 300 series stainless steel. High-level sensing will be accomplished in the manner detailed above by a separate air column sensor and pressure switch of the same type. Closure of the high-level sensing device will energize an alarm circuit as well as a redundant pump-on circuit. For increased reliability, pump ON/OFF and high-level alarm functions shall not be controlled by the same switch. To assure reliable operation of the pressure switches, each core shall be equipped with a factory installed equalizer diaphragm that compensates for any atmospheric pressure or temperature changes. The grinder pump will be furnished with a 6 conductor 14 gauge, type SJOW cable, pre-wired and watertight to meet UL requirements with a factory-installed NEMA 6P disconnect half attached to it.
(9) 
Each grinder pump station shall include a NEMA 4X, UL-listed alarm panel suitable for wall or pole mounting. The NEMA 4X enclosure shall be manufactured of thermoplastic polyester to ensure corrosion resistance. The enclosure shall include a hinged, lockable cover with padlock, preventing access to the electrical components and creating a secured safety front to allow access only to authorize personnel. The enclosure shall not exceed 10.5 inches by 14 inches by seven inches.
(a) 
The alarm panel shall contain one fifteen-amp, double-pole circuit breaker for the pump core's power circuit and one fifteen-amp single-pole circuit breaker for the alarm circuit. The panel shall contain a push-to-run feature, an internal run indicator and a complete alarm circuit. All circuit boards in the alarm panel are to be protected with a conformal coating on both sides, and the AC power circuit shall include an auto resetting fuse.
(b) 
The alarm panel shall include the following features: external audible and visual alarm; push-to-run switch; push-to-silence switch; redundant pump start; and high-level alarm capacity. The visual alarm lamp shall be inside a red, oblong lens at least 3.75 inches in length by 2.38 inches in width by 1.5 inches in height. The visual alarm shall be mounted to the top of the enclosure in such a manner as to maintain NEMA 4X rating. The audible alarm shall be externally mounted on the bottom of the enclosure, capable of 93dB at two feet. The audible alarm shall be capable of being deactivated by depressing a push-type switch that is encapsulated in a weatherproof silicone boot and mounted on the bottom of the enclosure (push-to-silence button).
[Added 10-22-2015 by Res. No. 15-10-003]
A. 
Grease interceptors shall be watertight and gastight and shall be engineered to withstand the H-20 vehicular traffic loading.
B. 
All grease interceptors shall be properly sized in accordance with the Table 10-3 of the 2009 Uniform Plumbing Code and shall be based on the number of DFUs. The minimum size of interceptor shall be 1,000 gallons of effective volume, and the minimum depth of liquid shall be 46 inches.
C. 
The interceptor shall be designed to remove grease from effluent by gravity and be made of concrete construction, shall be coated both on the inside and on the outside, and shall be tested in the same manner as the requirements for manholes and other concrete structures.
D. 
The inlet and outlet pipe shall have a two-way cleanout tee installed. Inlet piping shall enter at four inches above the liquid level. Inlet piping shall connect to a tee, which shall extend to 12 inches below the water level. The outlet pipe shall start at a depth as shown on the standard details above the bottom of the interceptor and extend vertically to a tee. The tee and pipe shall be not less than four inches in diameter. The tee shall be installed with the run in the vertical direction.
E. 
The grease interceptor shall have a frame and cover and extend to finish grade. The cover shall have cast inscription indicating "GREASE."
F. 
See Detail Drawing 57 in Appendix SB.