[Ord. of 12-3-1974, Arts. I—III; Ord. of 8-6-1984, § 1]
(a) A "multiple unit dwelling" shall be any building or structure which contains three or more individual dwelling units or spaces with a common roof or otherwise physically connected and shall include structures commonly known as "townhouses," "garden apartments," "motels," "hotels," "apartment houses," "rooming houses" and "condominiums."
(b) Every multiple unit dwelling shall be equipped with a supervisory circuited fire and smoke detection system which meets the standards of a nationally recognized testing laboratory. Smoke detection censors shall be located in or adjacent to all sleeping quarters and thermal detection units shall be located in all other areas of the building outside individual apartments, including attics, basements, utility rooms and storage rooms. Each area between fire walls shall be separately zoned. The annunciator panel and alarm bells shall be located where specified by the Chief or Acting Chief of the Fire Department or the Fire Marshal.
(c) Prior to the construction of any building, water mains shall be installed on the construction site, unless approval is first obtained from the Chief or Acting Chief of the Milford Fire Department. Fire hydrants shall be immediately connected and maintained in an operative condition. Access to all hydrants shall be provided.