The subdivider shall observe the requirements and principles of land subdivision in the design of each subdivision or portion thereof, as set forth in this article.
The subdivision plat shall conform to design standards that will encourage good development patterns within the Township. Where either or both an Official Map or Master Plan has or have been adopted, the subdivision shall conform to the proposals and conditions shown thereon. The streets, drainage rights-of-way, school sites, public parks and playgrounds shown on an officially adopted Master Plan or Official Map shall be considered in approval of subdivision plats. Where no Master Plan or Official Map exists, streets and drainage rights-of-way shall be shown on the final plat in accordance with N.J.S.A. 40:55D-38 et seq., and shall be such as to lend themselves to the harmonious development of the Township and enhance the public welfare in accordance with the design standards further enumerated in this section. However, any lot which is existing as of the date of adoption of this section and which is, as of said date, otherwise conforming to the area and other bulk requirements of the zone district in which located, such lot shall not be required to conform to the provisions of this section, unless same is proposed for further subdivision, in which case, the provisions of this section shall apply. In the event of a conflict between this article and the Residential Site Improvement Standards (RSIS), the RSIS shall govern.
A. 
Block length and width, or acreage within bounding roads, shall be such as to accommodate the size of lot required in the area by Chapter 550, Zoning, and to provide for convenient access, circulation, control and safety of street traffic.
B. 
Pedestrian crosswalks shall be required in locations deemed necessary by the Land Use Board where the blocks are over 1,000 feet long. Such walkways shall be 10 feet wide and be straight from street to street and shall be subject to all requisite third-party approvals.
C. 
For commercial, group housing or industrial use, block size shall be sufficient to meet all area and yard requirements for such use.
A. 
Each lot shall be served by a driveway meeting the requirements of Chapter 219, Driveways.
B. 
Insofar as is practical, side lot lines shall be at right angles to straight streets, and radial to curved streets.
C. 
Each lot in the proposed subdivision shall have a frontage of at least 50 feet on an approved street and such street right-of-way shall be at least 50 feet in width and as required in § 470-37 above.
D. 
Where extra width has been dedicated for widening of existing streets, lots shall begin at such extra width line and all setbacks shall be measured from such line.
The water distribution system shall be subject to the review and recommendations of the Township Engineer, particularly as to its routing, the locations of fire hydrants and the location of water storage tanks and shall be designed to adhere to the following specific standards:
A. 
All central water facilities shall conform to N.J.A.C. 7:10, commonly known as the "Safe Drinking Water Act Regulations" and any revisions and/or amendments thereto, except where the standards contained herein exceed those contained in the Safe Drinking Water Act Regulations, in which case the standards contained herein shall apply.
B. 
All construction of central water facilities shall comply with all applicable standards as set forth by the American Water Works Association (AWWA) as such standards apply to various components of a central water facility.
C. 
All central water systems shall be designed to operate as a pump storage type of system, using gravity flow, wherever feasible.
D. 
All lots upon which a central water system facility is located shall be deemed to be utility lots and not building lots and shall not be subject to the minimum area and other bulk dimensional requirements otherwise applicable to a building lot in the zone district in which located.
(1) 
Instead, such utility lots shall be subject to the following minimum standards:
(a) 
Lot area: one acre.
(b) 
Lot frontage: 100 feet.
(c) 
Front yard setback: 50 feet.
(d) 
Side yard setback: 25 feet.
(e) 
Rear yard setback: 50 feet.
(2) 
Access to a utility lot may be achieved by means of a permanent deeded easement or right-of-way of such width, location and surface treatment, and shall be subject to such maintenance, as shall make same suitable for access in all weather conditions.
E. 
The following design standards shall be complied with in addition to all other requirements specified in the standards referenced hereinabove. These standards may be modified with the approval of the Township Engineer and/or construction code enforcement official:
(1) 
Wellhouse.
(a) 
Construction drawings of the proposed wellhouse shall be submitted to the Township Engineer and to the construction code enforcement official, with an information copy thereof submitted to the Land Use Board, showing plan view, elevation views of all sides, typical sections, landscaping plan and a plot plan showing all site improvements to be installed to service the wellhouse, including, but not limited to, the following items:
[1] 
Asphalt driveway.
[2] 
Lighting.
[3] 
Chain link fencing.
[4] 
Storm drainage.
[5] 
Landscaping plan.
(b) 
The wellhouse shall be sized to provide at least three feet of clearance around the various components of the water system to permit ready access to the plant operators.
(c) 
A complete auxiliary generator system with interconnecting wiring and automatic transfer switch shall be provided for all central water facilities.
(d) 
Pressure gauges, graduated in increments not higher than five psi, shall be provided at appropriate locations in the wellhouse piping system.
(e) 
Sampling taps shall be provided for raw water samples and finished water samples in the wellhouse. There shall be at least 18 inches of clearance below these taps to permit the use of large sampling bottles.
(f) 
Floor drains in wellhouses shall be piped to discharge approved by the New Jersey Department of Environmental Protection (NJDEP) and the Township Health Department.
(g) 
Wellwater level indicators shall be provided with indicator gauges that can be calibrated to read the water level in the well directly on the gauge. An electrically powered air compressor shall be supplied as part of the standard equipment in the wellhouse.
(h) 
A stainless steel test sink shall be provided in the wellhouse to test for chlorine residual. The waterline serving the sink shall be tapped into the water main and supplied with a separate curb stop and curb box. The tap shall be located a sufficient distance away from the point of chlorination to allow at least the minimum amount of contact time specified by the NJDEP. Calculations shall be submitted to support the proposed design.
(i) 
All central water systems shall be provided with the following materials and equipment in a wall-mounted storage cabinet furnished in the wellhouse:
[1] 
DPD test kit with a one-year supply of reagents to test for chlorine residual.
[2] 
Repair parts needed to service any treatment equipment or pumping equipment installed in the wellhouse.
[3] 
A precut bypass pipe with the necessary fittings to permit the removal of the main meter in the wellhouse for servicing while keeping the water system operable at the same time.
[4] 
A one-year supply of reagents used in the treatment processes performed in the wellhouse.
[5] 
Two comprehensive manuals containing manufacturer's information on all components of the central water system, suppliers and service representatives, serial numbers and model numbers of all components and warranties.
[6] 
Two prints and one mylar of an as-built map showing the layout of the central water system, complete with ties from permanent structures to every gate valve and curb box in the system. One print shall be mounted on the wellhouse wall in a sealed frame.
[7] 
A gate valve wrench and curb box wrench large enough to operate every valve in the system.
[8] 
An industrial size first aid kit.
[9] 
A ten-pound type ABC fire extinguisher.
[10] 
A wall-mounted electric clock with a minimum six-inch diameter face.
(j) 
Warning signs shall be posted on the exterior of the wellhouse in accordance with BOCA, OSHA, and right-to-know compliance requirements indicating any dangerous chemicals or substances used in the wellhouse.
(2) 
Wells. All central water systems shall be provided with at least two wells regardless of the number of users or average daily water demand upon the system. All such wells shall have a minimum horizontal separation distance between them of at least 100 feet.
(3) 
Storage tanks.
(a) 
Storage tanks shall be sized to provide at least 1 1/2 days' water requirements, based on the average annual demand, plus the volume of water required for fire protection.
(b) 
Cathodic protection for corrosion control shall be provided for the storage tanks. A one-eighth-inch corrosion allowance shall be provided for all steel water tanks. All components of the cathodic protection system shall be designed to withstand the forces of ice.
(c) 
Level control in storage tanks shall be provided by electronic methods. The water level in the storage tanks shall be displayed to the nearest 1/2 foot.
(d) 
Visible and audible alarm systems shall be installed in the central water system wellhouse to indicate low or high water levels in the water storage tanks.
(e) 
Methods of measuring and permanently recording the water level in any water storage tank involved with the central water system as a function of time shall be provided.
(f) 
Warning devices required by the Federal Aviation Administration (FAA) shall be provided.
(g) 
Exterior and interior painting systems shall comply with all NJDEP and EPA requirements for potable water. Painting systems shall be a minimum of six mils thick.
(4) 
Distribution system.
(a) 
All distribution lines shall be looped to eliminate dead-end waterlines in the water system. The distribution lines shall be extended to the main roads on which the development fronts, and shall be constructed along the tract's entire frontage on such main road, from outermost property line to outermost property line, to permit future tie-ins. The distribution lines shall also be extended to the outside property lines of the development in areas where future expansion is possible on adjacent property to promote additional looping of the distribution system. The size of such distribution lines shall be as recommended by the Township Engineer.
(b) 
A Hardy-Cross analysis of the proposed central water system shall be provided showing that the flow required for fire protection at a fire hydrant can be achieved without lowering the water pressure on the first floor of any dwelling unit served by the water system to less than 30 psi.
(c) 
Water main pipe shall be ductile iron, Class 54 or higher, double cement lined. Bronze wedges, supplied and approved by the water main pipe manufacturer, shall be installed in each joint to assure electrical conductivity. Water main pipe shall be buried to provide at least 4 1/2 feet of suitable cover material over the top of the pipe. Concrete sand shall be placed around the water main pipe to provide at least six inches of concrete sand below and above the pipe, and at least 12 inches on each side of the pipe. A blue warning ribbon with the words "CAUTION — WATER MAIN BELOW" shall be placed in all water main trenches 1 1/2 feet below finished grade.
(d) 
Water main fittings, including, but not limited to, tees, wyes, bends and offsets, shall be mechanical joint type, and shall be provided with integrally cast lugs to accommodate reinforcing rods and other types of restraint devices. Each water main fitting shall be provided with concrete thrust blocks poured against virgin earth. The size of each thrust block shall be sufficient enough to withstand at least twice the maximum thrust force that the fitting is ever expected to experience, or a two-hour pressure test at 200 psi, whichever is greater.
(e) 
Gate valves shall be provided on all legs of any tee, wye or cross-type fitting, on each fire hydrant lead, on each blowoff pipe and at the terminus of any water main that may be extended in the future. All gate valves shall be resilient seat gate valves and shall be double rodded back to the nearest fitting for restraint. Gate valves shall open by turning the operating nut in a counterclockwise direction when viewed from the top.
(f) 
Valve boxes of the cast-iron type shall be provided on all gate valves. The internally cast lugs at the top section of the valve box shall not bear directly on the lower portion of the valve box or any extension. The top portion of the valve box shall be 1/2 inch below finished grade. The cast-iron valve box cover shall have the word "water" integrally cast in it.
(g) 
In locations where vent pipes or blowoffs may discharge water, suitable protection must be provided to prevent erosion and/or discharge onto adjacent properties. Easements permitting the open discharge of water from the central water system through blowoffs must be provided.
(h) 
Each dwelling unit shall have its own individual service line, complete with individual corporation stop, double strap saddle, curb stop, curb box and meter with remote readout on the exterior of the building. The curb box shall be located at least three feet from the face of the curb, but within the right-of-way of the roadway or in a utility casement in lieu thereof. The size of each service line shall be calculated to supply each dwelling unit with sufficient water pressure to meet the requirements of the local building codes, Residential Site Improvement Standards (RSIS), and NJDEP.
(i) 
All service lines providing potable water shall be metered, including service lines used for lawn watering purposes. Gate valves and NJDEP approved backflow prevention devices shall be provided to protect against back siphonage and cross connections.
(j) 
The distribution system shall be subjected to static pressure tests and dynamic flow tests prior to being accepted. Such tests shall be witnessed by the Township Engineer, or his/her representative, and by a representative of the Fire Department.
(5) 
Fire protection.
(a) 
All central water systems shall conform to all applicable standards of the National Fire Protection Association (NFPA), American Water Works Association (AWWA), N.J.A.C. 7:10 (commonly known as the "Safe Drinking Water Act"), Residential Site Improvement Standards (RSIS), BOCA and OSHA, and any revisions and/or amendments thereto.
(b) 
Total fire protection water supply shall be no less than 2,000 gallons per dwelling unit, or the requirement set forth by any of the applicable codes referenced above, whichever is greater.
(c) 
Water storage facilities for fire-fighting water shall be designed to automatically maintain the required capacity for fire-protection purposes.
(d) 
The maximum distance from each dwelling unit to the nearest fire hydrant shall not exceed 400 feet, measured along the street right-of-way, per RSIS 5:21-5.4(a). If any of the codes referred to above require a closer fire hydrant spacing, the more restrictive spacing shall apply.
(e) 
Each fire hydrant shall be capable of supplying a minimum flow of at least 500 gallons per minute at no less than 30 psi residual system pressure. If any of the codes referenced above require a larger flow rate and/or a higher residual pressure, the more restrictive requirements shall apply.
(f) 
All nonresidential occupancies shall conform to NFPA Standard 1231 as a minimum water supply requirement for fire-protection purposes.
(g) 
All developments must be designed to allow for the access of emergency vehicles, including fire apparatus, ambulances and police cars. Fire lanes shall be provided for commercial and industrial-type developments to provide access to fire-protection facilities.
(h) 
If a stream or pond exists on a property that requires a central water system, and the stream or pond can be developed into an adequate and reliable water supply, then a standpipe shall be constructed as a backup supply of water to the central water system for fire-protection purposes. The central water system shall not be connected or used in conjunction with any standpipe system.
(i) 
Prior to obtaining final approval of any major subdivision or site plan requiring a central water system, the Township Fire Department shall conduct any and all tests necessary to ensure that the system meets the fire-fighting requirements of the Fire Department. The Fire Department shall then issue a letter to the Land Use Board indicating that the central system has been tested and is accepted by the Fire Department for fire-protection purposes.
(6) 
General provisions.
(a) 
All components of the central water system, including, but not limited to, wellhouses, gate valves and storage tank covers shall be secured with commercial grade padlocks or door locks keyed alike. Panic bar hardware shall be provided on all doors.
(b) 
All components of the central water facility shall be designed to be compatible and standardized with equipment that presently exists in the water system being tied into, or other water supply facilities owned and operated by the Township.
(c) 
A cost estimate for the construction of the central water facility shall be provided.
(d) 
The annual cost of operating and maintaining the central water system shall be calculated and submitted. The estimated quarterly charge to the users of the central water system shall also be calculated and submitted.
(e) 
A hydraulic profile of the water system shall be provided, starting at the source of the water, through the wellhouse and distribution system, to the user's tap.
A. 
Easements along rear property lines, or elsewhere, may be required for utility installation in large scale developments. Such easements shall be a minimum of 20 feet wide for sanitary sewers that are not more than 15 feet deep. For sewers that are more than 15 feet deep, easements shall be a minimum of 30 feet wide. Water main easements shall be a minimum of 20 feet wide. All easements shall be located in consultation with the companies or Township departments concerned.
B. 
Stormwater easements or drainage rights-of-way shall be provided where a subdivision is traversed by a watercourse, drainageway channel or street. Storm drain easements shall be a minimum of 20 feet wide and shall conform substantially with the lines of such watercourse.
C. 
Natural features, such as trees, brooks, hilltops and views, shall be preserved whenever possible in designing any subdivision containing such features.
A. 
It is anticipated that in particular cases, on account of impracticability and/or undue hardship which would attend an applicant because of peculiar conditions pertaining to the land which is the subject of a development application, in the event the foregoing design standards were to be strictly adhered to, that certain waivers of design standards may be sought.
B. 
It is further recognized that the Municipal Land Use Law, N.J.S.A. 40:55D-51, provides a general procedural mechanism for the Planning Board, when acting upon applications for minor subdivision, preliminary major subdivision or preliminary site plan approvals, to entertain and, in appropriate cases, grant such waiver request.
C. 
However, it is additionally recognized that the foregoing design standards represent minimum standards necessary to the protection of the zoning and other land use regulations, the Master Plan and the Official Map of the Township of Fredon and are, in nearly all cases, required to be strictly complied with in order to promote the orderly growth and development of the Township.
D. 
It is additionally recognized that certain of the foregoing design standards are minimum standards required to protect the public health and safety.
E. 
Therefore, prior to the granting of any waivers of the otherwise required design standards, in accordance with the foregoing, the Board shall first determine whether the design standard for which a waiver has been sought is a minimum standard necessary to protect the public health and safety. If such is the case, the Board shall only grant a waiver of any such design standard when all of the following criteria have been satisfied to the Board's satisfaction:
(1) 
That the design waiver request is reasonable.
(2) 
That the altered design, resulting from the granting of the design waiver sought shall be in accordance with the general intent and purpose of the provisions of the applicable development ordinances, subdivision or site plan review.
(3) 
That there are peculiar conditions uniquely relating to the land which is the subject of the development application, for which a design standard waiver has been requested, such that the literal enforcement of such design standard is impracticable or will exact undue hardship.
(4) 
That the alternate design resulting from the granting of the waiver sought is engineeringly acceptable, applying prevailing standards of engineering design practice.
(5) 
That the resultant alternative design adequately protects the public health and safety.
F. 
In the event that the Board shall not be convinced that all of the above criteria have been satisfied, the Board shall deny the design standard waiver request and shall require strict compliance with all the foregoing design standards.