AMENDMENTS TO THE ICC INTERNATIONAL FIRE CODE, 2021 EDITION
| |||
Section 101.1 is amended by substituting "The City of Clayton,
Missouri," for [NAME OF JURISDICTION] on line two thereof.
| |||
Section 103.1 delete existing text. Insert:
| |||
103.1 General. The Bureau of Fire Prevention is
established within the jurisdiction under the direction of the code
official. The function of the bureau shall be the implementation,
administration, and enforcement of the provisions of this code.
| |||
Section 103.2 delete existing text. Insert:
| |||
103.2 Enforcement Official. It shall be the duty
and the responsibility of the chief executive officer, designated
as the Fire Chief, to enforce the provisions of this code. The Fire
Chief shall be the Code Official.
| |||
Section 103.2.1 add a new Section. Insert:
| |||
103.2.1 Bureau Organization. The Bureau of Fire
Prevention shall operate under the direct supervision of the Fire
Marshal. The Fire Marshal shall be a uniformed member and chief officer
of the Fire Department and operate under the direct supervision of
the Fire Chief. The Fire Marshal shall be appointed on the basis of
his/her administrative abilities and qualifications to understand,
interpret and enforce the technical provisions of this code. All uniformed
members of the Fire Department shall be considered members of the
Bureau of Fire Prevention. The Fire Marshal may assign or appoint
technical assistants, inspectors or other employees that may be necessary
for the effective and efficient operation of the Bureau of Fire Prevention.
All appointments to the bureau shall be made in conformance with the
provisions of the Municipal Code.
| |||
Section 103.3 delete existing text. Insert:
| |||
103.3 Bureau members code enforcement duties and authority. The Fire Marshal, and all properly assigned or appointed members
of the Bureau of Fire Prevention shall have the duty to assist the
Fire Chief in the administration and enforcement of the provisions
of this code. As agents of the Fire Chief, all properly assigned or
appointed members of the Bureau of Fire Prevention shall have the
authority to exercise all of the powers of the code official as detailed
within this code.
| |||
Section 104.12.4 add a new Section as follows. Insert:
| |||
104.12.4 Compliance with orders. A person shall
not willfully fail or refuse to comply with any lawful order or direction
of the fire official or interfere with the compliance attempts of
another individual.
| |||
Section 104.12.5 add a new Section as follows. Insert:
| |||
104.12.5 Vehicles crossing hoses. A vehicle shall
not be driven or propelled over any unprotected fire hose of the Fire
Department when laid down on any street, alleyway, private drive or
any other vehicular roadway without the consent of the fire official
in command of said operation.
| |||
Section 104.12.6 add a new Section as follows. Insert:
| |||
104.12.6 Vehicles following emergency apparatus. It shall be unlawful for the operator of any vehicle, other than
one on official emergency business, to follow closer than three hundred
(300) feet from any fire apparatus or other emergency vehicle traveling
in response to a fire alarm or other emergency or to drive any vehicle
within the block or immediate area where a fire apparatus or other
emergency vehicle has stopped in answer to a fire alarm or other emergency.
| |||
Section 104.12.7 add a new Section as follows. Insert:
| |||
104.12.7 Unlawful boarding or tampering with emergency
equipment. A person shall not, without proper authorization
from the fire official in charge of said Fire Department emergency
equipment, cling to, attach oneself to, climb upon or into, board
or swing upon any Fire Department emergency vehicle, whether the same
is in motion or at rest; or sound the siren, horn, bell or other sound-producing
device thereon; or manipulate, remove or tamper with, or attempt to
manipulate, remove or tamper with any levers, valves, switches, starting
devices, brakes, pumps or any equipment or protective clothing on,
or a part of, any Fire Department emergency vehicle.
| |||
Section 104.12.8 add a new Section as follows. Insert:
| |||
104.12.8 Damage or injury to Fire Department equipment
or personnel. It shall be unlawful for any person to damage
or deface, or attempt to damage or deface, any Fire Department emergency
vehicle at any time or to injure, or attempt to injure, Fire Department
personnel while performing departmental duties.
| |||
Section 105.1.4.1 add a new Section as follows. Insert:
| |||
105.1.4.1 Permit fees. Permit fees, inspection
fees and fees for the Board of Appeals shall be in accordance with
the fee schedule as established by the City of Clayton, Missouri.
The code official is authorized to establish a refund policy.
| |||
Section 105.3.3 delete existing text. Insert:
| |||
105.3.3 Occupancy prohibited before approval. Except
as specifically provided for temporary occupancy in the building code
adopted by the City, a building, structure or portion thereof, shall
not be used or occupied in whole or in part until all fire protection
devices and equipment protecting the building, structure or portion
to be occupied, have been tested and approved by the code official
charged with enforcing this code. All portions of the means of egress
for the building, structure or portion to be occupied shall be unobstructed
and available for immediate use.
| |||
Section 105.3.8.1 add a new Section. Insert:
| |||
105.3.8.1 Work commencing before permit issuance. If any person commences any work or operation before obtaining the
necessary permits, the permit fee shall be increased to two hundred
percent (200%) of the usual permit fee. If the work or operation to
be permitted is twenty-five percent (25%) or less completed before
the necessary permits are obtained, the permit fee shall be increased
to three hundred percent (300%) of the usual permit fee. If the work
or operation to be permitted is more than twenty-five percent (25%)
but equal to or less than fifty percent (50%) completed before the
necessary permits are obtained, the permit fee shall be increased
to four hundred percent (400%) of the usual permit fee, and if the
work or operation to be permitted is more than fifty percent (50%)
completed before the necessary permits are obtained, the permit fee
shall be increased to five hundred percent (500%) of the usual permit
fee.
| |||
Section 105.5.17 delete Exception. Insert:
| |||
Exceptions:
| |||
1.
|
A permit is not required where a valid permit from the water
company that supplies the system is displayed and an appropriate backflow
prevention device is utilized.
| ||
2.
|
A permit is not required for authorized employees of the water
company that supplies the system or the Fire Department to use or
operate fire hydrants or valves.
| ||
Section 105.5.25.1 add a new Section. Insert:
| |||
105.5.25.1 Asphalt kettles. An operational permit
is required for the operation of asphalt kettles inside or on the
roof of any building or structure.
| |||
Section 105.5.53 add a new section. Insert:
| |||
105.5.53 Premises Identification: An operational
permit is required. The plan shall be submitted and reviewed annually
by August 1 of each year.
| |||
Section 105.5.46a add a new Section. Insert:
| |||
105.5.46 Helicopter landing/lift-off, hoisting and lowering
operations. An operational permit is required for helicopter
landing/lift-off, hoisting and lowering operations in accordance with
the following. Proof of financial responsibility must be submitted
to the code official before a permit is issued.
| |||
The helicopter service or the contractor in charge of a helicopter
landing/lift-off, hoisting or lowering operations shall demonstrate
financial responsibility of liability for damages arising from the
landing/lift-off, hoisting or lowering operation by providing the
code official with proof of insurance or other appropriate financial
responsibility. The amount of financial liability shall be adequate
for the payment of all damages which may be caused either to a person
or persons, or to property by reasons of the permitted operation,
and arising from any actions, or in-actions, of the permit holder,
or the permit holder's employees, agents, contractors or subcontractors.
| |||
Permit applications must include a description of the landing/lift-off
operation or work to be performed and the safety precautions to be
used. Forty-eight (48) hour notice shall be provided before the landing/lift-off,
hoisting or lowering operation is to begin. Notification shall be
made to other jurisdictional agencies as listed below:
| |||
Police department: Written or oral permission must
be obtained from the Clayton Police Department in accordance with
the Clayton Code of Ordinances.
| |||
Housing and Planning department: If mechanical
equipment, machinery or building materials are being removed or installed
on a building or structure, a permit must be obtained from the Clayton
Housing and Planning Department.
| |||
City Manager: When the hours for operation for
the landing/lift-off or erection, demolition, alteration or repair
of any building or structure is to occur other than between the hours
of 7:00 A.M. and 6:00 P.M. on weekdays a permit shall be secured from
the City Manager in accordance with the Clayton Code of Ordinances.
| |||
Exceptions:
| |||
1.
|
Emergency or precautionary landings.
| ||
2.
|
Law enforcement or medical evacuation operations.
| ||
3.
|
Other operations approved by the code official.
| ||
Section 105.5.46b add a new Section. Insert:
| |||
105.5.46b Safety precautions. During all helicopter
landing/lift-off, lifting or lowering operations, the following applicable
safety precautions shall be followed:
| |||
The Fire and Police Departments shall approve landing sites,
if landings are necessary.
| |||
All materials or equipment to be lifted shall be brought as
close as possible to the building or structure site by road vehicles.
| |||
The helicopter shall not carry equipment or materials lifted
to or lowered from a building or structure over pedestrians, spectators,
other buildings or vehicles.
| |||
When the operation involves setting or removing equipment or
materials from or on an occupied building, the top two (2) floors
of the building shall not be occupied by anyone, other than individuals
directly involved with the operation while the hoisting or lifting
operation is in progress.
| |||
All flammable or combustible liquids brought to the site for
refueling helicopters shall be stored, used and dispensed in accordance
with Chapters 11 and 34 of this code.
| |||
A Fire Department safety officer, or Fire Department safety
team, must be present on the site during all helicopter landing/lift-off,
lifting or lowering operations. The safety officer, or safety team,
shall terminate the landing/lift-off or lift if weather conditions
or other variables make the operation unsafe. The safety officer,
or safety team, shall be provided radio communications with the helicopter
pilot in the event safety conditions mandate evasive action.
| |||
Exceptions:
| |||
1.
|
Emergency or precautionary landings.
| ||
2.
|
Law enforcement or medical evacuation operations.
| ||
3.
|
Other operations approved by the code official.
| ||
Section 105.6.25 add a new section. Insert:
| |||
105.6.25 Premises Identification: A construction
permit is required to install premises identification in accordance
with Section 408. Premises identification plans shall be submitted
for review and approval before a permit will be issued. Premises identification
permits shall be issued at no charge.
| |||
Section 109.1 delete existing text. Insert:
| |||
109.1 Board of Appeals. There shall be a Board
of Appeals to hear and decide appeals of orders, decisions or determinations
made by the code official relative to the application and interpretation
of this code. The Board of Appeals shall consist of the Board of Appeals
appointed and serving in accord with the Building Code adopted by
the City and the procedures, rules and regulations governing organization,
operation and procedures of the Board of Appeals under the said Building
Code shall apply to appeals under this code.
| |||
Section 112.4 delete existing text. Insert:
| |||
112.4 Penalties. Any person who shall violate a
provision of this code or shall fail to comply with any of the requirements
thereof or who shall erect, install, alter, repair or do work in violation
of the approved construction documents or directive of the code official,
or of a permit or certificate used under provisions of this code,
shall be guilty of an ordinance violation punishable by a fine of
not more than one thousand dollars ($1,000.00) or by imprisonment
not exceeding ninety (90) days, or both such fine and imprisonment.
Each day that a violation continues after due notice has been served
shall be deemed a separate offense.
| |||
Section 112.4.2 add a new Section as follows. Insert:
| |||
112.4.2 False alarms. In the event of false alarms,
after the second false alarm in any twelve (12) month period, the
alarm user, in lieu of court appearance, may pay to the director of
finance a penalty of fifty dollars ($50.00), and further, after the
third false alarm in any twelve (12) month period, the alarm user,
in lieu of court appearance, may pay to the director of finance a
penalty of one hundred dollars ($100.00). For the fifth and subsequent
false alarms in any twelve (12) month period the penalty shall be
an amount that is double the amount of the prior penalty [e.g., fifth
false alarm, two hundred dollars ($200.00), sixth false alarm, four
hundred dollars ($400.00), etc.] plus court costs of twenty-five dollars
($25.00) for each offense thereafter.
| |||
Section 113.4 delete existing text. Insert:
| |||
113.4 Failure to comply. Any person who shall continue
any work after having been served with a stop-work order, except such
work that a person is directed to perform to remove a violation or
unsafe condition, shall be guilty of an ordinance violation and punished
as provided in Section 112.4 of this code.
| |||
Section 114 add a new Section as follows. Insert:
| |||
SECTION 114 UNSAFE CONDITIONS
| |||
114.1 General. Whenever the code official shall
find in any structure or upon any premises dangerous or hazardous
conditions or materials as follows, the code official shall order
such hazardous conditions or materials to be removed or remedied in
accordance with the provisions of this code:
| |||
1.
|
Hazardous conditions liable to cause or contribute to the spread
of fire in or on said premises or structure or endanger the occupants
thereof;
| ||
2.
|
Conditions that interfere with the efficiency or operation of
any fire protection equipment or system;
| ||
3.
|
Obstructions to or on fire escapes, stairs, passageways, doors
or windows, that are liable to interfere with the egress of occupants
or the operation of the Fire Department in case of fire;
| ||
4.
|
Accumulations of dust or waste material in air-conditioning
or ventilating systems or grease in kitchen or other exhaust ducts;
| ||
5.
|
Accumulations of grease on kitchen cooking equipment, or oil,
grease or dirt upon, under or around any mechanical equipment;
| ||
6.
|
Accumulations of rubbish, waste, paper, boxes, shavings or excessive
storage of any combustible material;
| ||
7.
|
Hazardous conditions arising from defective or improperly utilized
or installed electrical wiring, equipment or appliances;
| ||
8.
|
Hazardous conditions arising from defective or improperly installed
equipment for handling or using combustible, explosive or otherwise
hazardous materials;
| ||
9.
|
Dangerous or unlawful amounts of combustible, explosive or otherwise
hazardous materials;
| ||
10.
|
All equipment, materials, processes or operations that are in
violation of the provisions or intent of this code; and
| ||
11.
|
Vehicles or equipment that impairs or obstructs Fire Department
access to an occupied structure hindering or delaying Fire Department
operations in case of an emergency.
| ||
Section 301.2 delete in its entirety. Insert:
| |||
301.2 Permits. Permits shall be required as set
forth in Section 105.6 for the activities or uses regulated by Sections
303, 306, 307, 308.1.3, 308.1.6, 308.3 and 320.
| |||
Section 303.2 delete in its entirety. Insert:
| |||
303.2 Location. Asphalt (tar) kettles shall not
be located within twenty (20) feet (6,096 mm) of any combustible material,
combustible building surface or any building opening and within a
controlled area identified by the use of traffic cones, barriers or
other approved means. Asphalt (tar) kettles and pots shall not be
utilized inside of a building or structure. Roofing kettles and operating
asphalt (tar) kettles shall not block means of egress, gates, roadways
or entrances.
| |||
Section 303.10 add a new Section as follows. Insert:
| |||
303.10 Permits. Asphalt (tar) kettles shall not
be used inside or on the roof of any building or structure without
first obtaining a permit from the code official.
| |||
Section 303.10.1 add a new Section as follows. Insert:
| |||
303.10.1 Safety precautions. All operations shall
comply with the following safety precautions:
| |||
1.
|
Fired asphalt (tar) kettles shall not be left unattended.
| ||
2.
|
Torches or other flame-producing devices shall be fueled with
LP gases only.
| ||
3.
|
LP gas containers or cylinders shall be stored in accordance
with Chapter 61 of this code and with NFPA 58 listed in Chapter 80
of this code.
| ||
4.
|
Torches, flame-producing devices, containers, cylinders, regulators,
hoses and other equipment must be designed and approved for the specific
purpose intended.
| ||
5.
|
LP gas containers or cylinders shall not be transported to the
roof in elevators or exit stairways that are occupied by non-construction
personnel.
| ||
6.
|
Flames from the torch shall not impinge on combustible "cant
strips" or other combustible structural elements.
| ||
7.
|
A firewatch shall be established and conducted in accordance
with Section 2604.2 of this code. The firewatch person shall be provided
with water hoses connected to an adequate water supply on the premises.
The firewatch person shall remain on the premises and in position
to observe residual fire effects at least one (1) hour after each
use of the torch or flame-producing device.
| ||
8.
|
Before a torching operation begins, the site shall be inspected
and approved by the Fire Department. Where climatic, operational or
construction conditions warrant specific inspections or observations,
a Fire Department employee shall act as an additional firewatch. Inspection
fees for the Fire Department firewatch shall be paid in accordance
with Section 105.1 of this code.
| ||
Section 319.1 delete in its entirety. Insert:
| |||
Section 319.1 add a new Section as follows. Insert:
| |||
319.1 Permit required. Any mobile food preparation
vehicle shall require an operational permit from the fire code official
for each deployment or location prior to placing the vehicle in its
proposed set-up location.
| |||
Exceptions:
| |||
1.
|
A permit is not required from the fire code official if the
vehicle has a current annual fire safety inspection sticker and certification
from the City of St. Louis displayed on the vehicle, although the
fire code official shall have the authority to conduct an inspection
on any food preparation vehicle set-up for operation within their
jurisdiction to ensure compliance with this code.
| ||
2.
|
Mobile food preparation vehicles operating under and in compliance
with a permit obtained under Section 319.2.1.
| ||
319.2.1 Event Permit Required. An event permit
is required from the fire code official for any location where three
(3) or more mobile food preparation vehicles will be set-up or in
operation at any one time on the same property or at the same venue.
The event permit may be issued annually for recurring situations with
approval of the fire code official.
| |||
319.2.2 Separation between vehicles. There shall
be a minimum of ten (10) feet of clear space between any vehicles
as measured from the furthest extent of the vehicle or anything tethered
to the vehicle except for a connection to a public utility (water,
power, etc.).
| |||
319.2.3 Separation from structures. There shall
be a minimum of twenty (20) feet from any mobile food preparation
vehicle and any structure as measured from the furthest extent of
the vehicle or anything tethered to the vehicle (except for a connection
to a public utility) to the outermost edge of the building roof overhang
projected in a vertical plane directly down to the ground surface.
| |||
319.2.4 Failure to obtain permit. The fire code
official shall have the authority to suspend or revoke the occupancy
permit of any commercial occupancy that hosts or otherwise allows
an unpermitted mobile food preparation vehicle to operate on its property
in violation of Section 319.2.
| |||
Section 401.5 delete in its entirety. Insert:
| |||
401.5 Making false report. It shall be unlawful for any person to willfully or maliciously give, turn in, signal, transmit or cause to be made, a false alarm or report that a fire or medical emergency has occurred, or is in progress, by any action or means whatsoever, and said false alarm or report causes the unnecessary movement or use of Fire Department apparatus or personnel, or causes the evacuation of building occupants or the disruption of the building occupant's normal activities. The provisions of Sections 215.800 through 215.930 of Article XVIII of Chapter 215 of the Clayton Code of Ordinances shall also apply to false fire alarms.
| |||
Section 404.5 add a new section. Insert:
| |||
404.5 Premises Identification: Premises identification
shall be in accordance with Section 408.
| |||
Section 408 add a new section. Insert:
| |||
Section 408 Premises Identification.
| |||
408.1 Where required: New and existing buildings
of Educational Group E shall be identified in accordance with Sections
408.2 through 408.5.
| |||
Exception: Previously approved signage shall be
permitted until [DATE BY WHICH MARKING SHALL BE UPDATED].
| |||
408.2 Zone Identification: Zones shall be identified
in accordance with Sections 408.2.1 through 408.2.4.
| |||
408.2.1 Zone Designation: All occupiable structures
on the premises shall be divided into sections or designated a specific
zone agreeable to the AHJ.
| |||
408.2.2 Zone Color Assignment: The zones shall
be assigned a primary or secondary color. Other colors may be used/added
if approved by the AHJ. (Recommended, not required, assign the zone
with the main entrance RED and proceed clockwise with ORANGE, YELLOW,
GREEN, BLUE, PURPLE).
| |||
408.2.3 Zone Level Consistency: Zone color assignment
shall be consistent on all grades of multilevel structures.
| |||
408.3 Corridors Identification: Corridors inside
of a zone shall be identified by the color assigned per Section 408.2.
| |||
408.3.1 Striping: A solid color representative
of the designated zone shall be applied on the walls on both sides
of the corridor.
| |||
408.3.2 Striping Size and Location: The stripe
shall be no less than four (4) inches AFF and no more than thirty-six
(36) inches AFF and a minimum of four (4) inches (102 mm) in width.
The stripe shall be continuous in length of the corridor and terminate
at the exit or the transition to a different zone. (In corridors with
lockers, displays, or other fixed obstructions an alternative location
may be used as approved.)
| |||
408.3.3 Directional Identification: Colored arrows
representative of the zone shall be provided at intersecting corridors.
The arrow shall be a minimum of one (1) inch in width and eight (8)
inches in length. The arrows shall be affixed to the corridor wall
at least four (4) inches AFF and no more than thirty-six (36) inches
AFF. Other heights may be used as approved.
| |||
408.4 Room and Area Identification: All occupiable
rooms and areas within a zone shall be identified in accordance with
Section 408.4.1 through 408.4.5. with numbers or labels in accordance
with Section 408.2.
| |||
408.4.1 Room and area designation: Rooms and areas
shall be identified by their current known number or known descriptive
name (i.e., gym, library).
| |||
408.4.2 Room and Area Color Assignment: Rooms and
areas shall be assigned the color of the zone they occupy.
| |||
408.4.3 Doors: Doors shall be identified with signage
conforming to Section 408.4.3.1 through 408.4.3.2. Doors shall be
labeled in Arabic numbers and alphabetical letters. Numbers shall
not be spelled out. Where required, doors shall have signage both
inside and out.
| |||
408.4.3.1 Egress/Room side of door: A sign with
the room number in the assigned zone color shall be affixed over the
door and shall be readily visible from inside the room. The numbers
shall be in white on a background of the zone color. Each character
shall be not less than four (4) inches (102 mm) high with a minimum
stroke width of one-half (1/2) inch (13 mm).
| |||
408.4.3.2 Ingress/Corridor side of door. Room numbers
shall be placed above the door and shall be readable from all angles
from the hallway or area to which they open. The numbers shall be
in white on a background of the zone color. Each character shall be
not less than four (4) inches (102 mm) high with a minimum stroke
width of one-half (1/2) inch (13 mm).
| |||
408.4.4 Windows: Signs with the room number in
the designated zone color shall be affixed to the interior surface
of the left most facing window and shall be visible from the exterior
of the building.
| |||
408.4.4.1 Placement: Room numbers shall be placed
on the left-most window when viewed from outside the building.
| |||
408.5 Exterior Door Identification. All doors on
the exterior of a building that provide access into the building shall
be identified in accordance with Section 408.5.1 through 408.5.5.
| |||
408.5.1 Number designation: All exterior doors
shall be numbered in a sequential order starting with the main entrance
(office door/public entrance). The main entrance shall always be No.
1. Subsequent doors shall be numbered in sequential order in a clockwise
manner.
| |||
408.5.2 Number color: The color of the number shall
represent the zone color per Section 408.3. Door numbers shall contrast
with their background.
| |||
408.5.2 Number Size: Door numbers shall be Arabic
numbers and alphabetical letters. Numbers shall not be spelled out.
Each character shall be not less than six (6) inches (152 mm) high
with a minimum stroke width of one-half (1/2) inch (13 mm).
| |||
408.5.3 Number placement: Door number shall be
placed at the top center of the door. Exception: Roll-up doors the
number shall be located between one-half (1/2) and three-fourths (3/4)
of the height of the door adjacent to the door opening.
| |||
408.5.4 Exterior access to corridors: Doors that
provide access directly to a corridor shall be marked with the door
number on a retro-reflective block in the corridor zone color per
Section 408.3.
| |||
408.5.5 Exterior access to rooms: Doors that provide
access directly into a room shall be marked with the room number or
descriptive name per Section 408.4.1 directly below the exterior door
identification number.
| |||
Section 409 add a new Section as follows. Insert:
| |||
409 Firefighter assist plans. An approved pictographic
display (sign, drawing or wall marking) shall be posted within all
enclosed stairways at each floor landing in all new and existing high-rise
buildings. Individual displays, or signs shall show the floor level
number where the graphic is displayed, the configuration of exit access
corridors including all door openings, exit stairways, elevators,
exterior building walls, fire alarm pull stations, fire hoses and
sprinkler valves. The sign shall be located five (5) feet (1,524 mm)
above the floor landing in a position that is readily visible when
the doors are in the open or closed positions.
| |||
Section 503.7 add a new Section as follows. Insert:
| |||
503.7 Street obstructions: No person shall erect,
construct, place or maintain any bumps, humps, fences, gates, chains,
bars, pipes, wood or metal horse or any other type of obstruction
in or upon any fire access road unless approved by the Clayton Fire
Department.
| |||
Section 507.4.1 add a new Section as follows. Insert:
| |||
507.4.1 Water flow tests: Water flow tests shall
be conducted between the hours of 8:00 A.M. and 4:30 P.M., Monday
through Friday.
| |||
Section 507.4.2 add a new Section as follows. Insert:
| |||
507.4.2 Water flow safety factor: A safety factor
shall be applied to all flow tests for fire sprinkler systems. A parallel
curve shall be drawn to the actual flow test curve that has been reduced
by twenty percent (20%) of the static pressure. A sprinkler system
shall not exceed the twenty percent (20%) curve.
| |||
Section 507.6 add a new section as follows. Insert:
| |||
507.6 Public water supply. The fire prevention
code official shall recommend to the chief administrative official
of the municipality the location or relocation of new or existing
fire hydrants and the placement or replacement of inadequate water
mains located upon public property and deemed necessary to provide
an adequate fire flow and distribution pattern. A fire hydrant shall
not be placed into or removed from service until approved by the fire
prevention code official.
| |||
Section 507.6.1 add a new Section. Insert:
| |||
507.6.1 Color coding of public fire hydrants. All
public fire hydrant barrels are to be painted yellow. All fire hydrant
bonnets are to be painted as follows:
| |||
COLOR
|
WATER MAIN SIZE
| ||
Green
|
Twelve (12) inch and larger
| ||
Orange
|
Eight (8) and ten (10) inch
| ||
Red
|
Six (6) inch and smaller
| ||
Section 507.6.2 add a new Section as follows. Insert:
| |||
507.6.2 Color coding of private fire hydrants. All
private fire hydrants shall be painted yellow, including the bonnet.
| |||
Section 604.4.1 add a new Section as follows. Insert:
| |||
604.4.1 Information signs. An approved graphic
display of evacuation routes and written information concerning basic
evacuation procedures, including the location of the exit stairs,
shall be posted in an approved location in all common hallways, in
or near elevator lobbies, on all floor levels of all new and existing
high-rise buildings.
| |||
Section 607.9 add a new Section as follows. Insert:
| |||
607.9 Elevator emergency operations testing. All
elevators that are equipped with emergency elevator operations in
accordance with Rule 211.3 of ASME A17.1, listed in Chapter 80, shall
be tested at least once each year in all phases of emergency functions.
An approved elevator service company shall conduct tests.
| |||
Section 607.10 add a new Section as follows. Insert:
| |||
607.10 Prohibited lockout systems, key-ways and devices. Elevator service shall be provided for Fire Department emergency
access to all floors in all high-rise buildings. The use of security
lockout systems, key operated floor selection buttons or other key-ways
or other devices which are not automatically rendered inoperative
by the fire-sensing devices or the key-operated fire service master
switch is prohibited. Walls, security bars, equipment or storage may
not obstruct access to any building level from any elevator.
| |||
Section 806.1.1 delete in its entirety, including exception.
Insert:
| |||
806.1.1 Restricted occupancies. Natural cut trees
shall be prohibited in Group A, B, E, I-1, I-2, I-3, I-4, M, R-1,
R-2 and R-4 occupancies.
| |||
Exception: Trees located in areas protected by
an approved automatic sprinkler system installed in accordance with
Section 903.3.1.1 or Section 903.3.1.2 shall not be prohibited in
Groups A, B, E, M, R-1 and R-2.
| |||
Section 901.6.2 delete in its entirety. Insert:
| |||
901.6.2 Records. Records of all system inspections,
tests and maintenance (IT&M) required by the referenced standards
shall be maintained on the premises for a minimum of three (3) years.
If the required testing frequency is greater than three (3) years,
records must be kept for the number of years of the testing frequency
plus three (3) years. Upon receipt the building representative or
building owner shall forward all IT&M records to the fire code
official. If applicable the building representative or building owner
can request/direct the IT&M company to forward IT&M records
to the code official upon completion.
| |||
Section 901.6.2.1 delete in its entirety. Insert:
| |||
901.6.2.1 Records information. Accurate logs shall
be maintained indicating the number, location and type of device tested.
Any defect, modification, maintenance, inspection, testing or repair
shall be logged. Initial records shall include the name of the installation
contractor, type of components installed, manufacturer of the components,
location and number of components installed per floor. Records shall
also include the manufacturers' operation and maintenance instruction
manuals. Such records shall be maintained on the premises.
| |||
Section 901.6.3 add a new Section as follows. Insert:
| |||
901.6.3 High-rise standpipe tests. In addition
to the standards listed in Table 901.6.1, standpipe flow tests approved
by the code official shall be conducted in accordance with NFPA 25
listed in Chapter 80 on standpipe systems in all high-rise buildings
every two (2) years. The flow shall not be less than the flow demands
required at the time of installation, or not less than two hundred
(200) GPM at the topmost hose outlet while maintaining a residual
pressure of fifty (50) psi, whichever is the higher demand. At the
time of the test, all control valves, including those inside hose
cabinets, shall also be operated and tested to insure proper operation
of the valves. The results of the tests must be submitted to the code
official and also must be entered into the log book.
| |||
Section 903.3.1.1 add a new Section as follows. Insert:
| |||
903.3.1.1.1 Exempt locations.
| |||
Automatic sprinklers shall not be required in the following
rooms or areas where such rooms or areas are protected with an approved
automatic fire-detection system in accordance with Section 907.2 that
will respond to visible or invisible particles of combustion. Sprinklers
shall not be omitted from a room merely because it is damp, of fire-resistance-rated
construction or contains electrical equipment. Sprinklers are required
in clean agent, halogenated or carbon dioxide extinguishing systems
shall not be considered as an alternative to an automatic sprinkler
system in computer rooms, vaults or other rooms where an automatic
sprinkler system is required.
| |||
Section 903.4.4 add a new Section as follows. Insert:
| |||
903.4.4 Post indicating valves. An above ground
post indicating valve (PIV) is required on all new structures that
require an automatic fire sprinkler suppression system. The private
fire service main to a building shall be provided with a listed post
indicator valve located to control all sources of water supply as
stated in NFPA 24. The valve shall be supervised as listed in Section
903.4.
| |||
Section 903.4.5 add a new Section as follows. Insert:
| |||
903.4.5 Control valves. At the discretion of the
Clayton Fire Marshal additional floor control valves controlling flow
to sprinklers in circulating closed loop systems may be required and
shall comply with NFPA 13.
| |||
Section 907.2.13.1.1 add a new item No. 3 to Section as follows:
Insert:
| |||
3.
|
All enclosed pressurized exit stairways in all new and existing
high-rise buildings shall comply with Section 1023.11. Pressurization
equipment for pressurized stairways shall be activated by smoke detectors
installed on the building side of all stairway doors in an approved
location. ON-AUTO-OFF control switches shall be provided in the Fire
Command Center as required by Section 909.16.
| ||
Section 907.3 delete in its entirety. Insert:
| |||
907.3 Where required — retroactive in existing buildings
and structures. An approved manual, automatic or manual and
automatic fire alarm system shall be installed in existing buildings
and structures in accordance with Sections 1103.7 through 1103.8.3.
Where automatic sprinkler protection is provided in accordance with
Section 903.3.1.1 or Section 903.3.1.2 and connected to the building
fire alarm system, automatic heat detection required by this Section
shall not be required.
| |||
An approved automatic fire-detection system shall be installed
in accordance with the provisions of this code and NFPA 72. Devices,
combinations of devices, appliances and equipment shall be approved.
The automatic fire detectors shall be smoke detectors, except an approved
alternative type of detector shall be installed in spaces such as
boiler rooms where, during normal operation, products of combustion
are present in sufficient quantity to actuate a smoke detector.
| |||
Section 907.7.4 add a new Section as follows. Insert:
| |||
907.7.4 Detector indicators. Smoke detectors or
duct detectors located above a ceiling or behind a wall must be provided
with a remote indicating device in an approved location at the ceiling
or wall to indicate the location of the device.
| |||
Exception: Where approved by the code official.
| |||
Section 907.7.5 add a new Section as follows. Insert:
| |||
907.7.5 Monitoring. All fire alarm and detection
systems shall be monitored by an approved central station as defined
in NFPA 72. A UL certificate or FM placard, in accordance with the
2019 Edition of NFPA 72, Chapter 26, shall be issued by the UL-listed
or FM-approved prime contractor for all newly installed required fire
alarm systems. This regulation shall apply to all newly installed
required fire alarm systems with an installation permit issued on
or after December 1, 2007. An existing required fire alarm system
wherein the control panel and alarm components are to be replaced,
shall be considered newly installed for the purposes of this Section.
The code official shall maintain a listing of local UL-listed or FM-approved
prime contractors. Central station service in full compliance with
the 2019 Edition of NFPA 72, Chapter 26, shall be maintained at the
protected property, so long as the requirement for the fire alarm
system exists.
| |||
Exceptions:
| |||
1.
|
Proprietary and remote station systems where approved by the
code official.
| ||
2.
|
Fire alarm and detection systems in one- and two-family dwellings.
| ||
Section 907.15.1 add a new Section as follows. Insert:
| |||
907.15.1 Fire alarm systems monitoring. Central-station
monitoring centers must be listed by Underwriters Laboratories. Monitoring
information, including company name, address and phone number, method
of transmission and UL listing information shall be provided. Where
deemed necessary by the code official, the UL listing information
shall be provided along with a copy of the UL fire alarm certificate
for the appropriate category (central station, remote station, or
proprietary).
| |||
Section 909.23 add a new Section as follows. Insert:
| |||
909.23 Stairway pressurization systems. Stairway
pressurization systems that supply air to interior exit stairways
to provide a positive pressure in stairways shall be tested annually.
Stairways shall be pressurized to a minimum of fifteen hundredths
(0.15) inches of water column and a maximum of thirty-five hundredths
(0.35) inches of water column in the stairway relative to the pressure
in the building with all stairway doors closed under the maximum anticipated
stack pressure.
| |||
Section 1025.6 add a new Section as follows. Insert:
| |||
1025.6 Exterior floor identification dots. All
new high-rise buildings shall be marked on their exterior with floor
level identification dots. These dots shall be not less than eight
(8) inches in diameter and be of an approved illumination reflective
material. Dots shall identify every fifth floor level of the building,
in relationship to the floor level indicators on the elevator cars.
Dots shall be visible on all faces or sides of the building. Specific
dot locations must be approved by the Fire Department.
| |||
Section 1031.1.1 add a new Section as follows. Insert:
| |||
1031.1.1 Maintenance. The means of egress from
each part of the structure, including exits, stairways, egress doors
and any panic hardware installed thereon, aisles, corridors, passageways
and similar elements of the means of egress, shall at all times be
maintained in a safe condition and available for immediate utilization
and free of all obstructions.
| |||
Section 1103.7.7.1 add a new Section as follows. Insert:
| |||
1103.7.7.1 High-rise buildings. An approved automatic
fire alarm system shall be installed in existing high-rise buildings.
The system shall be monitored in accordance with Section 907.7.5.
The annunciator panel shall be installed in a location approved by
the code official and shall give visual indication of the location
of all alarm zones that may be in alarm. Systems that are upgraded
shall be designed and installed in accordance with the requirements
of Section 907.2.13 of this code.
| |||
Section 1104.26 add a new Section as follows. Insert:
| |||
1104.26 Exterior floor identification dots. All
existing high-rise buildings shall be marked on their exterior with
floor level identification dots. These dots shall be not less than
eight (8) inches in diameter and be of an approved illumination reflective
material. Dots shall identify every fifth floor level of the building,
in relationship to the floor level indicators on the elevator cars.
Dots shall be visible on all faces or sides of the building. Specific
dot locations must be approved by the Fire Department.
| |||
Section 2304.3.8 add a new Section. Insert:
| |||
2304.3.8 Fire suppression system. The dispensing
area (pump islands, canopy and adjacent ground area) shall be provided
with an approved fire suppression system.
| |||
Section 3103.2 delete in its entirety. Insert:
| |||
3103.2 Approval required. Tents and membrane structures
shall be subject to application for permit and inspection from the
fire code official as required under Sections 3103.2.1 and 3013.2.2.
| |||
3103.2.1 Cooking Tents. Tents and membrane structures
of any size in or under which cooking with an open flame device or
appliance (including LP, natural gas, charcoal, other open flame)
shall apply for a permit from the fire code official and provide the
following information at a minimum:
| |||
A.
|
Size of the tent or membrane structure.
| ||
B.
|
Type of fuel source and equipment used.
| ||
C.
|
Appropriate extinguisher(s) based on fuel type.
| ||
D.
|
Smoke/CO removal for charcoal.
| ||
E.
|
Plan view of tent showing its location relative to other structures.
| ||
Exceptions:
| |||
1.
|
Tents used exclusively for recreational camping purposes.
| ||
2.
|
Limited cooking performed solely for demonstration purposes
in a tent less than nine hundred (900) square feet.
| ||
3.
|
Warming of already prepared food without open flame (e.g., crock
pots) in a tent less than nine hundred (900) square feet.
| ||
3103.2.2 Tents Without Cooking. Tents and membrane
structures having an area in excess of nine hundred (900) square feet
(37 m2) shall not be erected, operated
or maintained for any purpose without first obtaining a permit and
approval from the fire code official.
| |||
Exceptions (These exceptions only pertain to this
exemption from Section 3103.2.2 and are not a requirement of all tents):
| |||
1.
|
Tents used exclusively for recreational camping purposes.
| ||
2.
|
Tents open on all sides that comply with all of the following:
| ||
2.1.
|
The aggregate area of multiple tents without cooking placed
side by side without a fire break clearance of twelve (12) feet (3,658
mm), not exceeding nine hundred (900) s.f. (65 m2) total.
| ||
2.2.
|
A minimum clearance of twelve (12) feet (3,658 mm) to all structures
and other tents unless a greater distance is required elsewhere in
the code.
| ||
2.3.
|
A minimum clearance of twelve (12) feet (3,658 mm) to all structures
and other tents unless a greater distance is required elsewhere in
the code.
| ||
Section 5003.5.2 add a new Section as follows: Insert:
| |||
5003.5.2 Hazard sign required. Any occupancy required
by this code and/or State law to provide material safety data sheets,
shall provide visible markings on the outside of buildings, rooms
and containers where hazardous substances are present. These markings
shall be in a location approved by the code official. These markings
shall conform to the NFPA 704 marking system or with other Federal
laws or regulations, or in the case of containers, may as an option
comply with Safety and Health Administration Hazard Communication
Rule, 29 CFR 1910.1200(f). To avoid duplication of markings, marking
requirements of the United States Department of Transportation shall
satisfy the requirements in regard to motor vehicles, rolling stock
and aircraft.
| |||
Section 5003.5.3 add a new Section as follows:
| |||
5003.5.3 Main entrance. Where required by Section
5003.5, all buildings shall have a placard located on the main entry
door a minimum of eighteen (18) inches from the bottom edge of the
door. This placard shall have a minimum dimension of five (5) inches.
This placard is not required to be lettered or numbered.
| |||
Section 5003.5.4 add a new Section as follows:
| |||
5003.5.4 Other doors. All other doors shall have
a placard with a minimum dimension of ten (10) inches located in an
approved location that identifies the worst hazard category of the
product(s) in that area. This placard shall be provided with numerals
in accordance with Section 5003.6.1.
| |||
Section 5003.6.1 add a new Section as follows:
| |||
5003.6.1 Sign size. The exterior markings of buildings
or site entrances where materials are stored shall have a minimum
signal size of four (4) inches. All numbers/letters shall be reflective.
| |||
Section 5601.1.3 modify as follows: Delete exception No. 4 in
its entirety.
| |||
Section 5601.2.4 delete in its entirety. Insert:
| |||
5601.2.4 Financial responsibility. Before a permit
is issued, as required by Section 5601.2, the applicant shall file
with the jurisdiction a corporate surety bond in the principal sum
of two million dollars ($2,000,000.00) or a public liability insurance
policy for the same amount, for the purpose of the payment of all
damages to persons or property which arise from, or are caused by,
the conduct of any act authorized by the permit upon which any judicial
judgment results. The fire code official is authorized to specify
a greater or lesser amount when, in his or her opinion, conditions
at the location of use indicate a greater or lesser amount is required.
Government entities shall be exempt from this bond requirement.
| |||
Section 5704.2.13.1.4 modify as follows: Delete exception for
item No. 3 in its entirety.
| |||
Section 5704.3.2.3 add a new Section as follows:
| |||
5704.3.2.3 Storage cabinets. Unless otherwise mandated
by this code, all flammable and combustibles must be stored in an
approved flammable liquids storage cabinet. Cabinet doors must be
kept closed.
| |||
Section Appendix D103.6 add a new Section as follows. Insert:
| |||
D103.6.3 Fire lanes. Fire lanes so legally designated
by the Chief of the Fire Department shall be posted with appropriate
signs or markings as specified by the Chief of the Fire Department
and approved by the Board of Aldermen so that the public will be aware
of the existence of such fire lanes. If said fire lanes are marked
by painting them, then they shall be painted red in color. In cases
of fire lanes established on private property, the owner thereof,
shall provide such signs or markings at his expense and in cases of
fire lanes established on public property, the Director of Public
Works shall provide such signs or markings at the expense of the City
of Clayton.
| |||
Section M102 in Appendix M is amended by the insertion and addition
of a new subsection M102.1.1 to read as follows:
| |||
M102.1.1 High-rise residential buildings. High-rise
buildings containing residential R-2 dwelling units which are platted
and constructed as a condominium pursuant to Chapter 448, RSMo., shall
be deemed in compliance with Appendix M when all of the following
conditions are met:
| |||
1.
|
An approved automatic sprinkler system shall be provided within
all common areas on all floors such as storage rooms, equipment rooms,
laundry rooms, assembly areas, stairways, corridors and exits. Automatic
sprinkler systems shall be installed in accordance with Section 903.3.1.1
of the International Fire Code and each floor shall be zoned with
an independent flow device.
| ||
2.
|
The automatic sprinkler system installed on each floor of the
building in the common areas shall be of sufficient design to support
the expansion of the automatic sprinkler system to provide coverage
throughout the entire area of the floor.
| ||
3.
|
The governing associations or entities of the building shall
not prohibit the expansion of the automatic sprinkler system into
individual residential units.
| ||
4.
|
Smoke alarms complying with Section 907.2.11 shall be installed
throughout the building, including within the dwelling units.
| ||
5.
|
An approved fire alarm system complying with Section 907.5 shall
be installed throughout the building.
| ||
6.
|
All fire-rated doors in openings within fire-rated assemblies
throughout the building shall be provided with self-closing devices
in compliance with Section 716.5.9 of the 2015 International Building
Code.
| ||
7.
|
Appliances such as ranges or cook tops located within dwelling
units shall be protected by an approved labeled fire suppression device.
| ||
Section M103.1 in Appendix M is amended and a new Section M103.2
is inserted to read as follows:
| |||
M103.1 Compliance schedule. Except as provided
in Section 103.2, below, building owners shall file a compliance schedule
with the Fire Code Official not later than three hundred sixty-five
(365) days after the first effective date of this code (October 13,
2015). The compliance schedule shall not exceed twelve (12) years
for an automatic sprinkler system retrofit.
| |||
M103.2 Compliance schedule High-rise residential buildings. Those buildings electing to comply with Section 102.1.1 shall file
a compliance schedule with the Fire Code Official not later than one
hundred eighty (180) days after adoption of this code amendment (July
11, 2017). The compliance schedule shall not exceed six (6) years
to obtain full compliance with the requirements of Section 102.1.1.
|