Exciting enhancements are coming soon to eCode360! Learn more 🡪
City of Creve Coeur, MO
St. Louis County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[R.O. 2008 § 6-16; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A certain document, a copy of which is on file in the office of the City Clerk, such copy being marked and designated as the "International Building Code, 2015," Sixth Edition, including "Appendix H — Signs," as published by the International Code Council, Inc., is hereby adopted as the Building Code of the City of Creve Coeur, Missouri, for the control of building and structures as herein provided; and each and all of the regulations, provisions, penalties, conditions, and terms of the International Building Code, 2015, Sixth Edition, are hereby referred to, adopted and made a part hereof, as if fully set out in this Article, with the additions, insertions, deletions, and changes, prescribed in this Article.
[R.O. 2008 § 6-17; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Throughout the International Building Code, 2015, Sixth Edition, wherever the terms "name of jurisdiction" or "local jurisdiction" appear, it shall be deemed to mean "City of Creve Coeur, Missouri." Likewise, wherever the terms "department of building inspection" or "department of building safety" appear, it shall be deemed to mean "Creve Coeur Building Division." Wherever the term "code" appears, it shall mean the International Building Code, 2015, Sixth Edition, as amended in this Article.
[R.O. 2008 § 6-19; Ord. No. 4076 §1, 5-14-2007; Ord. No. 5110 §1, 10-26-2009; Ord. No. 5165 §3, 12-13-2010; Ord. No. 5235 §1, 12-12-2011; Ord. No. 5310 §1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 1 of the International Building Code, 2015, Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection or clause number in the code is hereby enacted and added thereto.
1. 
101.4.2 Mechanical. The provisions of the St. Louis County Mechanical Code, as adopted by the City, shall apply to the installation, alterations, repairs and replacement of mechanical systems, including equipment, appliances, fixtures, fittings and/or appurtenances, including ventilating, heating, cooling, air-conditioning and refrigeration systems, incinerators and other energy-related systems. All references to the International Mechanical Code shall be interpreted as references to the adopted St. Louis County Mechanical Code.
2. 
101.4.3 Plumbing. The provisions of the St. Louis County Plumbing Code, as adopted by the City shall apply to the installation, alteration, repair and replacement of plumbing systems including equipment, appliances, fixtures, fittings and appurtenances, and where connected to a water or sewage system. All references to the International Plumbing Code shall be interpreted as references to the adopted St. Louis County Plumbing Code.
3. 
101.4.7 Existing buildings. The provisions of Chapter 34 Existing Structures of this code shall apply to matters governing the repair, alteration, change of occupancy, addition to and relocation of existing buildings. All references made to the International Existing Building Code shall be interpreted as references to Chapter 34 Existing Structures of this code.
4. 
102.7 Matters not provided for. Any requirements that are essential for the structural, fire or sanitary safety of an existing or proposed building or structure, or for the safety of the occupants thereof, which are not specifically provided for by this code, shall be determined by the Building Official.
5. 
104.1.1 Rule-making authority. The Building Official shall have authority, as necessary in the interest of public health, safety and general welfare, to adopt and promulgate rules and regulations to interpret and implement the provisions of this code, to secure the intent thereof and to designate requirements applicable because of local climatic or other conditions. Such rules shall not have the effect of waiving structural or fire performance requirements specifically provided for in this code or of violating accepted engineering practice involving public safety.
6. 
104.6.1 Interference with Building Official. No person shall hinder, obstruct, resist, fail to provide entry at reasonable times, or otherwise interfere with the Code Official in the performance of his/her official duties.
7. 
104.6.1.1 Disasters. In the event of a disaster such as a windstorm, tornado, flood, fire, earthquake, bomb blast or explosion, the Building Official is authorized to deputize Missouri Structural Assessment and Visual Evaluation (SAVE) Volunteer Inspectors certified by the Missouri State Emergency Management Agency (SEMA) to conduct emergency post-disaster safety evaluations of buildings.
8. 
105.1.1 Annual permit. [Delete this Section in its entirety]
9. 
105.1.2 Annual permit records. [Delete this Section in its entirety]
10. 
105.2 Work exempt from permit. Exemptions from permit requirements of this code shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of this code or any other laws or ordinances of this jurisdiction. Permits shall not be required for the following:
Building:
1.
Retaining walls which are not over thirty (30) inches in height measured from the top of the proposed finished grade at the non-retained side of the wall to the top of the wall, unless supporting a surcharge or impounding Class I, II or III-A liquids.
2.
Painting, carpeting and similar finish work.
3.
Prefabricated swimming pools accessory to a Group R-3 occupancy which have a maximum water depth of twenty-four (24) inches (610 mm), a maximum water volume of five thousand (5,000) gallons (18,925 L) and are installed entirely above ground.
Electrical:
Any work exempted from permits by the Electrical Code.
Gas:
Any work exempted from permits by the Mechanical Code.
Mechanical:
Any work exempted from permits by the Mechanical Code.
Plumbing:
Any work exempted from permits by the Plumbing Code.
11. 
105.5 Expiration. Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within one hundred eighty (180) days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of one hundred eighty (180) days after the time the work is commenced, or after one (1) year from the date of issuance for tenant improvements, or after two (2) years from the date of issuance for new buildings or building additions if the permit has not otherwise expired. The Building Official is authorized to grant, in writing, one (1) or more extensions of time, for periods not to exceed ninety (90) days each. An extension shall be requested in writing and justifiable cause must be demonstrated.
12. 
105.5.1 Expiration of demolition permits. Demolition work shall be completed within thirty (30) days after the date of issuance of the demolition permit. The Building Official may, after receiving a written request from the applicant, grant one (1) or more thirty-day extensions to this permit if the applicant presents evidence of justifiable cause.
13. 
105.7 Placement of permit and inspection placard. The building permit or copy shall be kept on the site of the work until the completion of the project. An inspection placard shall be posted on the job site in accordance with Section 110.1.1 of this code.
14. 
107.1 General. The application for a permit shall be accompanied by four (4) complete sets of construction documents drawn to scale. The construction documents and site plans shall be prepared and sealed by an architect or an engineer licensed and registered in the State of Missouri to render this service. All construction documents and site plans shall be prepared by the appropriate registered design professional consistent with the professional registration laws of the State of Missouri. All construction documents submitted with an application for a building permit shall bear an original embossed or wet ink seal and an original dated signature of the responsible Missouri registered design professional for each discipline on the front sheet of each discipline within each set of construction documents. In addition, all other sheets of the construction documents, other than the specifications or calculations, shall bear the original embossed or wet ink seal and the original dated signature or the mechanically reproduced seal and dated signature of the responsible Missouri registered design professional. Any addenda or modifications submitted for changes to the construction documents shall also bear the original seal and original dated signature of the responsible Missouri registered design professional. Such changes shall be clearly indicated. The Building Official may waive these requirements when the scope of the work is of a minor nature and does not involve structural alterations.
15. 
107.2.3 Means of egress. The construction documents shall show in sufficient detail the location, construction, size and character of all portions of the means of egress in compliance with the provisions of this code. The construction documents shall designate the number of occupants to be accommodated on every floor, and in all rooms and spaces.
16. 
107.2.5.2 All buildings and structures. For all buildings and structures for all use groups to be constructed, the following additional information shall be shown on the site plan.
A.
The location of all front, side and rear building lines, together with all easements including utilities, drainage and roadways.
B.
The present and proposed finished grades of yards, driveways or walks for drainage in relation to the established first floor elevation including the slope away from the foundation.
C.
The lot number, block (if any), plat or subdivision number, recorded subdivision name, front street and side streets (where applicable) and the north direction arrow.
17. 
107.2.5.3 Private sewage disposal system. The site plan shall indicate the location of a private sewage system when a public sewage system is not available. All technical data and soil data required by the Plumbing Code shall be submitted with the site plan.
18. 
107.2.7 Residential Fire Sprinkler Option Form. An application for permit for a one- or two-family dwelling or residence or townhome shall be accompanied by the City's Residential Fire Sprinkler Option Form signed by the builder and the purchaser affirming that a fire sprinkler system was offered to the purchaser prior to entering into the purchase contract in conformance with Section 903.1 of this code. If there is no purchaser at the time of the permit application submittal, then said signed form shall be submitted as soon as there is a purchaser and prior to the issuance of a certificate of occupancy for the new residence.
19. 
107.3.1 Approval of construction documents. When the Building Official issues a permit, the construction documents shall be approved in writing or by stamp, as "Reviewed for Code Compliance." Two (2) sets of construction documents so approved shall be retained by the Building Official. The other two (2) approved sets shall be returned to the applicant for submittal to the respective fire district for their approval. Upon their approval, the fire district shall return one (1) set of City and Fire District-approved construction documents to the applicant. This set shall be kept at the site of work and shall be open to inspection by the Building Official or a duly authorized representative.
20. 
109.2 Schedule of fees. The fees for plan reviews, issuing permits, making inspections, working overtime, issuing certificates of occupancy, establishing escrow funds and other administrative enforcement activities performed by the Building Department shall be paid in accordance with the fees established in Appendix B to Title IV, Community Development and Public Works Fee Schedule, of the City Code of Ordinances.
21. 
109.2.1 Building Code Board of Appeals filing fee. A filing fee of one hundred fifty dollars ($150.00) shall be paid upon the submittal of the written appeal in order for a quorum of the Building Code Board of Appeals to be notified to convene for the purpose of hearing an appeal of a decision of the Building Official as set forth in Section 113. The filing fee shall be refunded to the applicant if the Board reverses the decision of the Building Official.
22. 
109.3 Building permit valuations. The applicant for a permit shall provide an estimated construction cost for the project at the time of application. The estimated construction cost shall be for the total value of work, including materials, labor, profit and overhead for all structural, architectural, mechanical, electrical and plumbing work, as it relates to the project for which the permit is to be issued. The estimated construction cost shall not include the cost of land or registered design professional fees. If, in the opinion of the Building Official, the estimated construction cost is underestimated on the application, the permit shall be denied, unless the applicant can show detailed estimates to meet the approval of the Building Official. Final building permit valuation shall be set by the Building Official.
23. 
109.4 Work commencing before permit issuance. Where any work for which a permit is required by this code is started, or proceeded with, prior to obtaining said permit, the normal applicable fee shall be doubled and a penalty fee of up to five hundred dollars ($500.00) may be charged by the Building Official. The payment of said doubled fee or penalty shall not relieve any persons from fully complying with the requirements of this code or from other penalties prescribed herein.
24. 
109.6 Refunds. In the case of revocation of a permit no refund shall be granted. Any excess fee for a project that has not been commenced shall be returned to the permit holder upon written request received no later than twelve (12) months after the date the permit was issued, and the permit shall be cancelled. All plan examination fees, permit processing fees, inspection fees and penalties that have been imposed upon the permit holder under the requirements of this code shall be deducted from the refund or paid by the permit holder prior to any refund being granted.
25. 
110.1.1 Inspection placard. Work requiring a permit shall not commence until the permittee or his/her agent posts a City-issued inspection placard at the job site for recording inspections. Failure to maintain this inspection placard will not relieve the permittee of responsibility as provided by this code. When work has progressed to a point of having windows, or when the job is an alteration or addition, the placard shall be attached to the glass in view for recording the balance of inspections required by the code. Absence of inspection placard shall result in the imposition of a penalty fee as set forth in Section 109.2.
26. 
110.1.2 Manufacturer's installation instructions. Manufacturer's installation instructions, as required by this code, shall be available at the job site at the time of inspection.
27. 
110.3 Required inspections. After issuing a building permit, the Building Official shall conduct inspections as set forth in Sections 110.3.1 through 110.3.12 during and upon completion of the work for which a permit has been issued so as to be able to ensure that substantial compliance with this code has occurred. A record of all such inspections and any violations of this code shall be maintained by the Building Official. The owner shall provide for special inspections in accordance with Section 1704.
28. 
110.3.1 Soil and footing inspection. A soil inspection shall be made after excavation for the building or structure is complete and trenches for footings, spread footings, column pads, grade beams, and other types of footings are crumbed, formed, have the reinforcing steel tied in place, and are ready for concrete. A City-approved barrier shall be in place around the excavation until backfilling has occurred. No concrete shall be placed without this inspection.
29. 
110.3.1.1 Lowest floor elevation. Any building or structure permitted to be constructed on property designated as a flood hazard area shall have an elevation certification (as required by Section 1612.5 and prepared and sealed by a registered design professional) which certifies the lowest floor elevation, including the basement, submitted to the Building Official prior to the required foundation inspection. No foundation inspection shall be approved until said submittal is made.
30. 
110.3.2 Foundation inspection. A foundation inspection shall be made after the top of the footing has been cleaned, the foundation forms have been properly set, the reinforcing steel has been cleaned and tied in place, and the proper anchor bolts are on site. A City-approved barrier shall be in place around the excavation until backfilling has occurred. No concrete shall be placed without this inspection.
31. 
110.3.3 Pier inspection. A pier inspection shall be made where special foundations such as drilled and poured-in-place concrete piers, caissons, driven piles of all types, and other extraordinary types of foundations are required. Additional pier inspections shall be made when the Code Official determines the size of the project warrants it. The Code Official may require a special inspector, as set forth in Section 1704, to make these inspections when deemed necessary by the Building Official. Reinforcing steel required in the above cases shall be placed to allow for adequate inspections. A City-approved barrier shall be placed around the excavation until backfilling has occurred. No concrete shall be placed without this inspection.
32. 
110.3.4 Structural concrete slab and under-floor inspection. Structural concrete slab and under-floor inspections shall be made after in-slab or under-floor reinforcing steel and building service equipment, conduit, piping accessories and other ancillary equipment items are in place, but before any concrete is placed or floor sheathing installed, including the sub-floor.
33. 
110.3.5 Framing inspection. A framing inspection shall be made after the plumbing, mechanical, electrical and fire rough-in inspections have been made and approved by those inspection departments and their dated approval signatures have been noted on the posted inspection placard; and after all masonry walls, fireplace chimneys, vents, and all framing (including the floor, wall, and roof structures, fireblocking, bracing and sheathing) are completed. Protection of joints and penetrations in fire-resistance rated assemblies shall not be concealed from view until inspected and approved. No mechanical, electrical, plumbing, or framing systems shall be concealed before this inspection is made and approved by the Code Official.
34. 
110.3.6 Ceiling cover inspection. A ceiling cover inspection shall be made after the plumbing, mechanical, electrical and fire rough-in inspections have been made and approved by those inspection departments and their dated approval signatures have been noted on the posted inspection placard; and after all masonry walls, fireplace chimneys, vents, ceiling grid and hanger wires, and all framing (including the floor and/or roof structures, fireblocking, bracing and sheathing) are completed. Protection of joints and penetrations in fire-resistance rated assemblies shall not be concealed from view until inspected and approved.
35. 
110.3.7 Gypsum board and plaster. The following ceiling and wall gypsum board or plaster inspections shall be performed as specified:
A)
A lath inspection shall be made after all lathing, interior and exterior, is in place and before any plaster is applied.
B)
A gypsum board inspection shall be made after all gypsum board sheets are in place and properly fastened and before any joint compound is applied over joints and fasteners.
Each layer of a multi-layered fire-resistance rated assembly shall be inspected and approved prior to the next layer being applied. Protection of joints and penetrations in fire-resistance rated assemblies shall not be concealed from view until inspected and approved.
36. 
110.3.8 Fire- and smoke-resistant penetrations. Protection of joints and penetrations in fire-resistance-rated assemblies, smoke barriers and smoke partitions shall not be concealed from view until inspected and approved.
37. 
110.3.9 Energy efficiency inspections. Inspections shall be made to determine compliance with Chapter 13 of this Code and shall include, but not be limited to, inspections for envelope insulation R- and U-values, fenestration U-value, duct system R-value, and HVAC and water-heating equipment efficiency.
38. 
110.3.10 Supplemental inspections. In addition to the inspections specified above, the Building Official is authorized to make or require other inspections or re-inspections of any construction work to ascertain compliance with the provisions of this code, the City's Zoning Code and the City's Code of Ordinances.
39. 
110.3.11 Special inspections. For special inspections, see Section 1704.
40. 
110.3.12 Final inspection. A final building inspection shall be made after the prior required inspections have been completed and the final mechanical, electrical, and plumbing inspections have been made and approved by those inspection departments; and the final fire inspection has been made and approved by the appropriate fire district.
41. 
110.5.1 Duty to request a final inspection and obtain final approval. Upon completion of the work described in the permit application and on the approved construction documents, the permit holder shall request a final inspection and obtain final approval before any occupancy of the building or structure shall occur. Failure of the permit holder to make a timely request for a final inspection and obtain final approval shall constitute a violation of the Building Code, shall subject the permit holder to penalties as set forth in Section 114.4, and shall result in forfeiture to the City of any funds deposited in escrow in connection with the permit if the failure continues after thirty (30) days' written notice sent by certified mail to the last known address of the permit holder, in order to offset at least some of the costs incurred by the City as a result of such continuing failure. The Building Official shall be responsible for sending such notices, including to all permit holders that have failed to make a timely request for a final inspection as of the effective date of these provisions. Unless the permit holder applies in signed writing for segregated investment of its escrow deposit at the time of permit application, an escrow deposit may be invested by the City with other municipal funds and any income derived there from may be used for general revenue purposes at any time. If the permit holder applies by timely signed writing for segregated investment of its escrow deposit, the City shall segregate such funds and invest them in the same manner as allowed for municipal funds, to the extent practicable given the amount of the escrow; however, no return is assured and the City shall have no liability whatsoever other than to pay any income actually derived from such investment in the event of return of such escrow deposit. In the event of a forfeiture of an escrow deposit, any income from segregated investment shall also be forfeited.
42. 
110.7 Coordination of inspections. Whenever in the enforcement of this code or another code or ordinance, the responsibility of more than one (1) Code Official of the jurisdiction is involved, it shall be the duty of the Code Officials involved to coordinate their inspections and administrative orders as fully as practicable. Whenever an inspector from any agency or department observes an apparent or actual violation of some provision of some law, ordinance or code not within the inspector's authority to enforce, the inspector shall report the findings to the Code Official having jurisdiction.
43. 
111.1 Use and occupancy for new buildings. Any building or structure hereafter constructed shall not be used or occupied in whole or in part until the certificate of occupancy shall have been issued by the Code Official. The person in whose name the building permit has been issued pursuant to Section 105 shall obtain the certificate of occupancy and shall prevent the occupancy of any building or structure or part thereof until such certificate is issued to him/her. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction.
44. 
111.1.1 Use and occupancy for existing buildings. Upon written request from the owner or prospective tenant of an existing building or structure, the Code Official shall issue a certificate of occupancy, provided that there are not violations of law, or this code, or orders of the Code Official pending, or which are found to exist upon an inspection of the building, and it has been established after inspection and investigation that the alleged occupancy is also in conformance with the Zoning Ordinance of Creve Coeur, Missouri. This code shall not require the removal, alteration, or abandonment of, or prevent the continuance of, the occupancy of a lawfully existing building or structure, unless such use is deemed to endanger public safety and welfare. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction.
45. 
111.1.2 Use and occupancy for existing residential occupancy. The requirements of Section 111.1.1 shall not be applicable to existing one- and two-family residential buildings and residential structures that were previously issued certificates of occupancy per Section 111.1.
46. 
111.1.3 Required certificate of occupancy. Failure of the owner or tenant of a structure to obtain a certificate of occupancy as required by Sections 111.1 and 111.1.1 shall be deemed a violation of this code and shall subject said owner or tenant to penalties as set forth in Section 114.4.
47. 
111.4 Revocation of the certificate of occupancy. The certificate of occupancy shall always be subject to this code and other laws enforced by the Building Official. Non-compliance with the regulations of this code and other laws enforced by the Building Official shall be deemed a violation subject to the penalties set forth herein, and, in addition, the Building Official shall be empowered to revoke the certificate of occupancy issued for the building in question, until such time as the violations are corrected and the building is in compliance with this code and the Zoning Ordinance of Creve Coeur, Missouri. The issuance of a certificate of occupancy shall not relieve the owner or tenant from compliance with all regulations of this code and other applicable regulations.
48. 
111.5 Permanent address numbers. Every dwelling unit or business structure within the City of Creve Coeur shall have the correct street number(s) permanently affixed on said dwelling unit or business structure so as to be clearly visible from the street in front of the property. The street number(s) shall be a minimum of four (4) inches in height when displayed on a dwelling unit and a minimum of six (6) inches in height when displayed on a business structure. Said street numbers shall be contrasting in color to that of the structure and shall be placed in proximity to the main entrance into the structure. Permanent address numbers shall be permanently affixed on a dwelling unit or a business structure prior to the issuance of a certificate of occupancy.
SECTION 113
BOARD OF APPEALS
49. 
113.1 General. In order to hear and decide appeals of orders, decisions or determinations made by the Building Official relative to the application and interpretation of this code, there is and shall remain a Building Code Board of Appeals. The board shall adopt rules of procedure for conducting its business.
50. 
113.2 Limitations on authority. Any person shall have a right to appeal a decision of the Building Official to the Building Code Board of Appeals. An application for appeal shall be based on a claim that the true intent of this code or the rules legally adopted thereunder have been incorrectly interpreted, the provisions of this code do not fully apply, or an equivalent form of construction is proposed. The board shall have no authority to waive requirements of this code.
51. 
113.3 Time limitation and filing procedure. All appeals shall be filed in writing with the Building Official. A written appeal may not be filed more than thirty (30) days after the affected individuals are notified of the Building Official's decision.
52. 
113.3.1 Filing fee. An application for appeal shall not be filed without full payment of the filing fee as set forth in Section 109.2.1. Said filing fee shall be refunded to the applicant if the Board reverses the decision of the Building Official.
53. 
113.4 Membership of board. The Building Code Board of Appeals shall consist of five (5) regular members, who shall be residents of the City of Creve Coeur, appointed pursuant to Section 4.4(i) of the City Charter for three-year staggered terms. To the extent possible, based on applications submitted to the City, members of the Building Code Board of Appeals should be representative of the following professions or disciplines: registered architects, builder or superintendent of building construction with ten (10) years of experience, structural engineer, code enforcement professional, mechanical engineer, electrical engineer, civil engineer, fire protection engineer, mechanical contractor, electrical contractor, plumbing contractor, fire protection contractor, or other disciplines associated with the building trades or design professions.
54. 
113.4.1 Chair. The Chair of the Building Code Board of Appeals shall be elected annually by the members of the Building Code Board of Appeals.
55. 
113.4.2 Secretary. The City Administrator shall designate a qualified clerk to serve as secretary to the board. The secretary shall file a detailed record of all proceedings in the office of the City Administrator.
56. 
113.4.3 Compensation of members. Members of the Building Code Board of Appeals shall not be compensated for service but shall be reimbursed for actual expenses pursuant to established City policy.
57. 
113.4.4 Code of Ethics for members. All members shall be subject to the City's Code of Ethics.
58. 
113.5 Notice of meeting. The Building Code Board of Appeals shall meet upon notice from the chair, within five (5) calendar days of the filing of a written appeal with the Building Official, or at stated periodic meetings.
59. 
113.6 Open hearing. All hearings before the Building Code Board of Appeals shall be open to the public. Proper public notice shall be given. The appellant, the appellant's representative, the Code Official, and any person whose interests are affected shall be given the opportunity to be heard.
60. 
113.6.1 Procedure. The Board shall adopt and make available to the public through the secretary procedures under which a hearing shall be conducted. The procedures shall not require compliance with strict rules of evidence but shall mandate that only relevant information be received.
61. 
113.7 Quorum. Three (3) members of the Building Code Board of Appeals shall constitute a quorum for the purpose of hearing appeals.
62. 
113.8 Board decision. The Building Code Board of Appeals shall only reverse or modify the decision of the code official by a majority vote of the quorum present and voting. Otherwise, the decision shall be deemed to be upheld.
63. 
113.8.1 Notification of decision. The secretary of the board shall notify the appellant and the Building Official of the decision in writing.
64. 
113.8.2 Administration. The Building Official shall take immediate action in accordance with the decision of the board.
65. 
113.9 Court review. Any aggrieved person, whether or not a previous party of the appeal, shall have the right to apply to the appropriate court for a writ of certiorari to correct errors of law. Application for review shall be made in the manner and time required by law following the filing of the decision of the Building Code Board of Appeals in the office of the City Administrator.
66. 
114.4 Violation penalties. Any person who shall violate a provision of this code, or fail to comply therewith, or with any requirements thereof, shall be guilty of an ordinance violation, punishable by a fine of not more than one thousand dollars ($1,00.00). Each day that a violation continues after due notice has been served shall be deemed a separate offense.
[Ord. No. 5836, 4-24-2023]
67. 
115.1.1 Mud or debris or an excessive amount of surface water on streets and adjacent properties. After a verbal warning to the owner or contractor, the Building Official shall have the authority to issue a stop work order to any project which is causing mud or debris or an excessive amount of surface water to be transferred to any street or adjacent property.
68. 
115.3 Unlawful continuance. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be subject to penalties as set forth in Section 114.4.
SECTION 117
EMERGENCY MEASURES
69. 
117.1 Imminent danger. When, in the opinion of the Building Official, there is imminent danger of failure or collapse of a building or structure or any part thereof which endangers life, or when any structure or part of a structure has fallen and life is endangered by the occupation of the building or structure, the Building Official is hereby authorized and empowered to order and require the occupants to vacate the same forthwith. The Building Official shall cause to be posted at each entrance to such structure a notice reading as follows: "This Structure is Unsafe and its Occupancy has been Prohibited by the Building Official." It shall be unlawful for any person to enter such structure except for the purpose of making the required repairs or of demolishing the same, which work shall be done at such person's own risk.
70. 
117.2 Temporary safeguards. When, in the opinion of the Building Official, there is imminent danger due to an unsafe condition, the Building Official may cause the necessary work to be done in an effort to render such structure temporarily safe, whether or not the legal procedure described herein has been instituted. Neither the City or the Building Official or any other City employee shall be deemed to have guaranteed such security or safety or have any liability related to actions or omissions hereunder.
71. 
117.3 Closing streets. When necessary for the public safety, the Building Official shall temporarily close structures and close, or order the authority having jurisdiction to close, sidewalks, streets, public ways, and places adjacent to unsafe structures, and prohibit the same from being used.
72. 
117.4 Emergency repairs. For the purpose of Section 117, the Building Official shall employ the necessary labor and materials to perform the required work as expeditiously as possible.
73. 
117.5 Costs of emergency repairs. Costs incurred in the performance of emergency work shall be paid by the City on approval from the Building Official. The City Attorney of the jurisdiction shall institute appropriate action against the owner of the premises where the unsafe structure is or was located for purpose of recovering such costs and may cause a special tax lien to be placed against the property for such purposes.
[R.O. 2008 § 6-20; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 2 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number in the code is hereby enacted and added thereto.
1. 
201.3 Terms defined in other codes. Where terms are not defined in this code and are defined in the International Fire Code, International Fuel Gas Code, St. Louis County Mechanical Code, St. Louis County Electrical Code, St. Louis County Plumbing Code, International Energy Conservation Code or International Property Maintenance Code, such terms shall have the meanings ascribed to them as in those codes.
[R.O. 2008 § 6-21; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 3 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-22; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 4 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number in the code is hereby enacted and added thereto.
1. 
415.9.3 Dry cleaning plants. The construction and installation of dry-cleaning plants shall be in accordance with the requirements of this code, the St. Louis County Mechanical Code, the St. Louis County Plumbing Code and NFPA 32. Dry cleaning solvents and systems shall be classified in accordance with the International Fire Code.
[R.O. 2008 § 6-23; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 5 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number in the code is hereby enacted and added thereto.
1. 
501.2 Address identification. New and existing buildings shall be provided with approved address numbers or letters. Each character shall be a minimum of four (4) inches high for dwelling units and six (6) inches high for business structures and a minimum of one-half (1/2) inch wide. They shall be installed on a contrasting background and be plainly visible from the street or road fronting the property. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure.
[R.O. 2008 § 6-24; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 6 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number in the code is hereby enacted and added thereto.
1. 
603.1.2 Piping. The use of combustible piping materials shall be permitted when installed in accordance with the limitations of the St. Louis County Mechanical Code and the St. Louis County Plumbing Code.
[R.O. 2008 § 6-25; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 7 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-26; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 8 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-27; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5110 § 2, 10-26-2009; Ord. No. 5235 § 2, 12-12-2011; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 9 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number is hereby enacted and added thereto.
1. 
903.1 General. Automatic sprinkler systems shall comply with this Section. Notwithstanding the provisions of the Building Code and International Building Code, as amended and adopted by the City of Creve Coeur, Missouri, a builder of one- or two-family dwellings or residences or townhouses shall offer to any purchaser, on or before the time of entering into the purchase contract, the option, at the purchaser's cost, to install or equip fire sprinklers in the dwelling, residence or townhouse. Notwithstanding any other provision of law to the contrary, no purchaser of such dwelling, residence or townhouse shall be denied the right to choose or decline to install a fire sprinkler system in such dwelling, residence or townhouse being purchased.
2. 
903.2.6.1 Existing Group I. All skilled nursing and intermediate care facilities not required prior to August 28, 2007, to install and maintain an automatic sprinkler system, shall install and maintain an automatic sprinkler system in accordance with NFPA 13 by December 31, 2012, unless the facility receives an exemption from the State of Missouri Department Of Health and presents evidence in writing from a certified sprinkler system representative or licensed engineer that the facility is unable to install an approved NFPA 13 automatic sprinkler system due to the unavailability of water supply requirements associated with this system.
3. 
903.2.11.3 Buildings more than three (3) stories in height or having an occupied floor level located fifty-five (55) feet or more above the lowest level of fire department vehicle access. An automatic sprinkler system shall be installed throughout all buildings that are more than three (3) stories above the grade plane or have an occupied floor level located fifty-five (55) feet or more above the lowest level of fire department vehicle access.
Exceptions: No changes made.
4. 
[F] 903.3.1.2 NFPA 13 or NFPA 13R sprinkler systems. Where allowed in buildings of Group R, up to and including four (4) stories in height, automatic sprinkler systems shall be installed throughout in accordance with NFPA 13 or NFPA 13R.
5. 
[F] 903.3.1.2.3 Combustible attics. Sprinkler protection shall be provided within attics constructed of or containing combustible materials.
6. 
[F] 903.3.5 Water supplies. Delete the reference to the "International Plumbing Code" and substitute the "St. Louis County Plumbing Code."
7. 
[F] 903.4.1 Monitoring. Alarm, supervisory and trouble signals shall be distinctly different and automatically transmitted to an approved central station, remote supervising station or proprietary supervising station as defined in NFPA 72.
Exceptions: No changes made.
8. 
[F] 903.4.2 Alarms. The fire sprinkler system water flow device(s) shall activate alarm notification appliances, located throughout the entire building, which shall be components of an automatic fire alarm system installed in accordance with the provisions of Section 907 and NFPA 72. Such fire sprinkler water flow devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the fire sprinkler system.
Exception: Alarm notification appliances shall not be required for limited area sprinkler systems.
9. 
907.2.24 Buildings equipped throughout with an automatic sprinkler system. An automatic fire alarm system with alarm notification appliances shall be installed and maintained in all new buildings equipped throughout with an automatic sprinkler system that is designed and installed in accordance with Section 903.3.1.1 or Section 903.1.1.2. An automatic fire alarm system with alarm notification devices shall be installed and maintained in all existing unsprinklered buildings that become equipped throughout with an automatic sprinkler system that is designed and installed in accordance with Section 903.3.1.1 or Section 903.3.1.2. An automatic fire alarm system with alarm notification appliances shall be installed and maintained in all existing sprinklered buildings where the construction costs for the proposed renovation of these buildings exceeds fifty percent (50%) of their appraised values (as established by the St. Louis County Assessor's Office) prior to the proposed renovations occurring. Manual fire alarm boxes are not required unless otherwise required by Sections 907.2.1 through 907.2.23.
10. 
907.6.6 Monitoring. All fire alarm and fire detection systems shall be monitored by an approved central station, remote supervising station or proprietary supervising station as defined in NFPA 72.
Exceptions: No changes made.
[R.O. 2008 § 6-28; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 10 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number is hereby enacted and added thereto.
1. 
1004.1.1 Areas without fixed seating. The number of occupants shall be computed at the rate of one (1) occupant per unit of area as prescribed in Table 1004.1.2. For areas without fixed seating, the occupant load shall not be less than the number determined by dividing the floor area under consideration by the occupant load factor assigned to the function of the space as set forth in Table 1004.1.2 or by the actual number of occupants for whom each occupied space, floor or building is designed, whichever number of occupants is greater. When an intended function is not listed in Table 1004.1.2, the Building Official shall establish a function based on a listed function that most nearly resembles the intended function.
Exception. Delete.
2. 
1010.1.9.11 Stairway doors.
Exception 3. Delete. No changes made to the four (4) other exceptions.
3. 
1013.1 Where required. Amend "Exception 1" to read as follows:
Exceptions:
1.
Exit signs are not required in buildings which require only one (1) exit.
No changes made to the four (4) other exceptions.
4. 
1013.6.1 Graphics. Amend the first sentence of this Section to read as follows: Every exit sign and directional exit sign shall have plainly legible red letters not less than six (6) inches high with the principle strokes of the letters not less than seventy-five hundredths (0.75) inch wide. No other changes made to rest of this Section.
5. 
1015.4 Opening limitations. Required guards shall not have openings which allow passage of a sphere four (4) inches (102 mm) in diameter from the walking surface to the required guard height. Guards shall not have an ornamental pattern that would provide a ladder effect. Angular intermediate balusters shall be installed at an angle forty-five degrees (45°) or greater to an adjacent walking surface or stair tread.
Exceptions 1 through 6. No changes made.
6. 
1015.9 Retaining walls. Guards shall be provided where retaining walls with differences in grade level on either side of the wall in excess of thirty (30) inches (762 mm) are located closer than twenty-four (24) inches (610 mm) to a walk, path, parking lot or driveway on the high side of the retaining wall. If deemed in the interest of public safety by the Building Official per Section 104.12, guards or other approved protective measures shall be provided where retaining walls with differences in grade level on either side of the wall in excess of thirty (30) inches are located twenty-four (24) inches or farther from a walk, path, parking lot or driveway.
7. 
1018.6 Dead ends in aisles. Where more than one (1) exit or exit access doorway is required, the exit access shall be arranged such that there are no dead ends in aisles more than twenty (20) feet in length.
Exceptions:
1.
In occupancies in Use Group B where aisles are bounded by furniture, counters, partitions or similar dividers not more than six (6) feet in height, the length of a dead-end aisle shall not be more than fifty (50) feet.
2.
In occupancies in Use Group B where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the length of dead-end aisles shall not exceed fifty (50) feet.
3.
A dead-end aisle shall not be limited in length where the length of the dead-end aisle is less than two and one-half (2.5) times the least width of the dead-end aisle.
8. 
1028.1 General. Exits shall discharge directly to the exterior of the building. The exit discharge shall be at grade or shall provide direct access to grade. The exit discharge shall not reenter a building. The combined use of Exceptions 1 and 2 below shall not exceed fifty percent (50%) of the number and capacity of the required exits.
Exceptions:
1.
A maximum of fifty percent (50%) of the number and capacity of the exit enclosures is permitted to egress through areas on the level of discharge provided all of the following conditions are met:
1.1.
Discharge of interior exit stairways and ramps shall be provided with a free and unobstructed path of travel to an exterior exit door. This free and unobstructed path of travel shall not have any floor dimension less than ten (10) feet in width or length and shall have a minimum floor area of three hundred (300) square feet with a minimum clear ceiling height of eight (8) feet. This exterior exit door shall be readily visible and identifiable from the point of termination of the exit enclosure.
1.2 and 1.3 No change.
2.
No change.
3.
No change.
[R.O. 2008 § 6-29; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5243 § 3, 2-13-2012; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 11 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number is hereby enacted and added thereto.
1. 
Section 1106.5 Van spaces. For every four (4) or fraction of four (4) accessible parking spaces, at least one (1) shall be a van-accessible parking space. Where accessible parking is provided within or beneath a building, at least one (1) van-accessible parking space shall also be provided within or beneath the building adjacent to the other interior accessible parking spaces.
Exception: No change.
[R.O. 2008 § 6-30; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 12 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number is hereby enacted and added thereto.
1. 
1203.1 General. Buildings shall be provided with ventilation in accordance with the St. Louis County Mechanical Code. Where natural ventilation is permitted by the St. Louis County Mechanical Code, the natural ventilation shall be in accordance with Section 1203.5 of this code.
2. 
1206.3.3 Court drainage. Delete the reference to the "International Plumbing Code" and substitute the "St. Louis County Plumbing Code."
[R.O. 2008 § 6-31; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 13 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-32; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 14 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-33; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 15 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number is hereby enacted and added thereto.
1. 
[P] 1503.4 Roof drainage. Delete the reference to the "International Plumbing Code" and substitute the "St. Louis County Plumbing Code."
[R.O. 2008 § 6-34; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 16 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number is hereby enacted and added thereto.
1. 
1608.2.1 Creve Coeur ground snow loads. Ground snow loads to be used in determining the design snow loads for roofs shall be 20 psf.
2. 
1612.3 Establishment of flood hazard areas. To establish flood hazard areas, the applicable governing body shall adopt a flood hazard map and supporting data. The flood hazard map shall include, at a minimum, areas of special flood hazard as identified by the Federal Emergency Management Agency in an engineering report entitled "The Flood Insurance Study for St. Louis County, Missouri, and Incorporated Areas," dated February 4, 2015, as amended or revised with the accompanying Flood Insurance Rate Map (FIRM) and Flood Boundary and Floodway Map (FBFM) and related supporting data along with any revisions thereto. The adopted flood hazard map and supporting data are hereby adopted by reference and declared to be part of this Section.
3. 
1613.3.1 Acceleration parameters. The earthquake spectral response acceleration at short periods (Ss) shall be 0.48g. The earthquake spectral response acceleration at one-second periods (S1) shall be 0.18g.
[R.O. 2008 § 6-35; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 17 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-35.1; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 18 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number is hereby enacted and added thereto.
1. 
Section 1805.4.3 Drainage discharge. Delete the reference to the "International Plumbing Code" and substitute the "St. Louis County Plumbing Code."
2. 
Section 1805.5 Enclosure of surface water run-off: Surface water run-off concentrated into an enclosed pipe system shall not be discharged closer than ten (10) feet from any property line without prior approval from the Building Official. If this method of discharge causes a drainage nuisance to an adjacent property, an alternate drainage method shall be proposed for approval by the Building Official.
Exception: This Section shall not apply to enclosed pipe storm water systems of twelve (12) inches or greater in diameter that are under the jurisdiction of the City of Creve Coeur or the Metropolitan Sewer District.
3. 
1807.2.4 Guards. Guards shall be provided in accordance with Section 1015.9.
4. 
Section 1809.5 Frost protection. Except where otherwise protected from frost, foundation walls, piers and other permanent supports of buildings and structures shall be protected from frost by one (1) or more of the following methods:
1.
Extending a minimum of thirty (30) inches below the finish grade.
No changes made to methods 2 or 3 or exceptions 1, 2 or 3.
[R.O. 2008 § 6-35.2; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 19 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-35.3; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 20 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-35.4; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 21 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-35.5; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 22 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-35.6; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 23 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-35.7; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 24 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-35.8; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 25 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection or clause number is hereby enacted and added thereto.
1. 
Section 2503.1 Inspection. Lath and gypsum board shall be inspected in accordance with Section 110.3.7.
[R.O. 2008 § 6-35.9; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 26 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-35.10; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 27 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-35.11; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 28 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection or clause number is hereby enacted and added thereto.
1. 
Section 2801.1 Scope. Delete the references to the "International Mechanical Code" and substitute "St. Louis County Mechanical Code."
[R.O. 2008 § 6-35.12; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 29 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection or clause number is hereby enacted and added thereto.
1. 
Section 2901.1 Scope. Delete the references to the "International Plumbing Code" and the "International Private Sewage Disposal Code" and substitute "St. Louis County Plumbing Code."
2. 
Section 2902.1 Minimum number of fixtures. Plumbing fixtures shall be provided in accordance with the St. Louis County Code.
3. 
Table 2902.1 Minimum number of required plumbing facilities. The contents of this Table as amended by the St. Louis County Plumbing Code shall apply.
4. 
Section 2902.1.1 Fixture calculations. Fixture calculations shall be provided in accordance with the St. Louis County Plumbing Code.
5. 
Section 2902.2 Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex in accordance with the St. Louis County Plumbing Code.
6. 
Section 2902.3.2 Location of toilet facilities in occupancies other than covered mall buildings and shopping centers. The requirements of the St. Louis County Plumbing Code shall apply.
7. 
Section 2902.3.3 Location of toilet facilities in covered mall buildings and shopping centers. The requirements of the St. Louis County Plumbing Code shall apply.
8. 
Section 2902.5 Drinking fountain location. Drinking fountains shall be provided in accordance with the St. Louis County Plumbing Code.
9. 
Section 2902.6 Small occupancies. Drinking fountains shall not be required for an occupant load of thirty (30) or fewer.
[R.O. 2008 § 6-35.13; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 30 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-35.14; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 31 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number is hereby enacted and added thereto.
1. 
Section 3102.1 General. Delete the reference to "180 days" and substitute "90 days."
2. 
Section 3103.5 Membrane material. The membrane material for all tents, membrane structures and their appurtenances shall be of: approved non-combustible material as defined in Section 703.4; flame-resistant material as determined in accordance with NFPA 701 listed in Chapter 35; or material treated in an approved manner to render the material flame-resistant.
3. 
Section 3103.6 Certification. An affidavit or affirmation shall be submitted to the Building Official and a copy retained on the premises on which the tent or membrane structure is located. The affidavit shall attest to the following information relative to the flame-resistance of the fabric:
1.
Names and addresses of the owners of the tent or membrane structure.
2.
Date the fabric was last treated with flame-resistant solution.
3.
Trade name or kind of chemical used in treatment.
4.
Name of person or firm treating the material.
5.
Name of testing agency and test standard by which the fabric was tested.
4. 
Section 3103.7 Label. Membrane structures, tents and canopies shall bear a permanently affixed label that identifies the size and fabric or material type.
5. 
Section 3103.8 Anchorage. All temporary structures shall be anchored to the ground to resist the wind loads prescribed by Section 1609. At the discretion of the Building Official, the anchorage system may be required to be designed by a registered design professional.
6. 
Section 3109.4.1.9 Pool structure as barrier. Where an above-ground pool structure is used as a barrier or where the barrier is mounted on top of the pool structure, and the means of access is a fixed or removable ladder or steps, the ladder or steps shall be surrounded by a barrier which meets the requirements of Sections 3109.4.1.1 through 3109.4.1.8. A removable ladder or steps shall not constitute an acceptable alternative to enclosure requirements.
SECTION 3112 ANTENNAS
7. 
Section 3112.1 Permits required. A building permit is required for roof installations of antennal structures. Such a structure shall be erected so as to not damage the roof covering, and when removed from the roof, the roof covering shall be repaired to maintain weather and water tightness. The installation of any antennal structure mounted on the roof of a building shall not be erected nearer to the lot line than the total height of the antennal structure above the roof, nor shall such structure be erected near electric power lines or encroach upon any street or other public space. The application shall be accompanied by detailed drawings of the structure and methods of anchorage. All connections to the roof structure shall be properly flashed to maintain water tightness. The construction documents shall meet the submittal requirements of Section 107.1.
8. 
Section 3112.2 Dish antennas. An antenna consisting of a radiation element which transmits or receives radiation signals generated as electrical, light or sound energy, and supported by a structure with or without a reflective component to the radiating dish, usually in a circular shape with a parabolic curve design constructed of a solid or open mesh surface, shall be known as a dish antenna.
9. 
Section 3112.2.1 Permits. The approval of the Building Official shall be secured for all dish antenna structures more than two (2) feet in diameter erected on the roof of or attached to any building or structure.
10. 
Section 3112.3 Structural provisions. Antennal structures or dish antennas larger than two (2) feet in diameter shall be subject to the structural provisions of Sections 1608 and 1609. The snow load provisions of Section 1608 shall not apply where the antenna has a heater to melt falling snow.
[R.O. 2008 § 6-35.15; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
Chapter 32 of the International Building Code, 2015 Sixth Edition, is adopted without modification.
[R.O. 2008 § 6-35.16; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 33 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number is hereby enacted and added thereto.
1. 
Section 3302.4 Street and adjacent property cleaning. Mud and debris on streets or adjacent properties caused either directly or indirectly by construction shall be removed immediately. This maintenance shall be performed at all times during construction. The responsibility for ensuring that streets leading to and from and properties adjacent to the construction site are kept clean shall be with the owner of said property. Failure to comply with this Section shall result in the property owner being cited with a violation subject to penalties set forth in Section 114.4 or being served with a stop work order specified in Section 115.0, or both.
2. 
Section 3303.4 Grading and restoration of lot. Where a structure has been demolished or otherwise removed from a lot and construction for the new structure has not begun, the vacant lot shall be filled, graded, and maintained in conformity to the established elevation of the street grade at curb level nearest the point of demolition or excavation. Provisions shall be made to prevent the accumulation of water or damage to any foundations on the premises or adjoining property. If construction activity as authorized by a grading permit or building permit has not commenced within thirty (30) days of the demolition of the structure, said lot shall be re-vegetated with approved vegetation.
3. 
Section 3305.1 Facilities required. Delete the reference made to the "International Plumbing Code" and substitute "St. Louis County Plumbing Code."
[R.O. 2008 § 6-35.17; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 34 of the International Building Code, 2009 Fourth Edition, is inserted as Chapter 34 of the International Building Code, 2015 Sixth Edition, and amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number is hereby enacted and added thereto.
GENERAL
1. 
3401.1 Scope. The provisions of this Chapter shall control the alteration, repair, addition and change of occupancy of existing structures.
Exception: Existing bleachers, grandstands and folding and telescopic seating shall comply with ICC 300-12.
2. 
3401.2 Maintenance. Buildings and structures, and parts thereof, shall be maintained in a safe and sanitary condition. Devices or safeguards which are required by this code shall be maintained in conformance with the code edition under which installed. The owner or the owner's designated agent shall be responsible for the maintenance of buildings and structures. To determine compliance with this Subsection, the Building Official shall have the authority to require a building or structure to be reinspected. The requirements of this Chapter shall not provide the basis for removal or abrogation of fire protection and safety systems and devices in existing structures.
3. 
3401.1.3 Compliance. Alterations, repairs, additions and changes of occupancy to existing structures shall comply with the provisions for alterations, repairs, additions and changes of occupancy in the International Fire Code, International Fuel Gas Code, International Mechanical Code, International Plumbing Code, International Property Maintenance Code, International Private Sewage Disposal Code, International Residential Code and NFPA 70.
4. 
3401.4 Building materials. Building materials shall comply with the requirements of this Section.
5. 
3401.4.1 Existing materials. Materials already in use in a building in compliance with requirements or approvals in effect at the time of their erection or installation shall be permitted to remain in use unless determined by the Building Code Official to be dangerous to life, health or safety. Where such conditions are determined to be dangerous to life, health or safety, they shall be mitigated or made safe.
6. 
3401.4.2 New and replacement materials. Except as otherwise required or permitted by this code, materials permitted by the applicable code for new construction shall be used. Like materials shall be permitted for repairs and alterations, provided no hazard to life, health or property is created. Hazardous materials shall not be used where the code for new construction would not permit their use in buildings of similar occupancy, purpose and location.
SECTION 3402
DEFINITIONS
7. 
3402.1 Definitions. The following words and terms shall, for the purposes of this Chapter and as used elsewhere in the code, have the meanings show herein.
DANGEROUS
Any building or structure or portion thereof that meets any of the conditions described below shall deemed dangerous:
(1)
The building or structure has collapsed, partially collapsed, moved off its foundation or lacks the support of ground necessary to support it.
(2)
There exists a significant risk of collapse, detachment or dislodgment of any portion, member, appurtenance or ornamentation of the building or structure under service loads.
EXISTING STRUCTURE
A structure erected prior to the date of adoption of the appropriate code, or one for which a legal building permit has been issued.
PRIMARY FUNCTION
A primary function is a major activity for which the facility is intended. Areas that contain a primary function, include, but are not limited to, the customer service lobby of a bank, the dining area of a cafeteria, the meeting rooms in a conference center, as well as offices and other work areas in which the activities of the public accommodation or other private entity using the facility are carried out. Mechanical rooms, boiler rooms, supply storage rooms, employee lounges or locker rooms, janitorial closets, entrances, corridors and restrooms are not areas containing a primary function.
SUBSTANTIAL STRUCTURAL DAMAGE
A condition where:
(1)
In any story, the vertical elements of the lateral force- resisting system have suffered damage such that the lateral load-carrying capacity of the structure in any horizontal direction has been reduced by more than twenty percent (20%) from its pre-damage condition; or
(2)
The capacity of any vertical gravity load-carrying component, or any group of such components, that supports more than thirty percent (30%) of the total area of the structure's floor(s) and roof(s) has been reduced more than twenty percent (20%) from its pre-damage condition and the remaining capacity of such affected elements, with respect to all dead and live loads, is less than seventy-five percent (75%) of that required by this code for new buildings of similar structure, purpose and location.
TECHNICALLY INFEASIBLE
An alteration of a building or a facility that has little likelihood of being accomplished because the existing structural conditions require the removal or alteration of a load-bearing member that is an essential part of the structural frame, or because other existing physical or site constraints prohibit modification or addition of elements, space or features which are in full and strict compliance with the minimum requirements for new construction and which are necessary to provide accessibility.
SECTION 3403
ADDITIONS
8. 
3403.1 General. Additions to any building or structure shall comply with the requirements of this code for new construction. Alterations to the existing building or structure shall be made to ensure that the existing building or structure together with the addition are no less conforming with the provisions of this code than the existing building or structure was prior to the addition. An existing building together with its additions shall comply with the height and area provisions of Chapter 5.
9. 
3403.2 Flood hazard areas. For buildings and structures in flood hazard areas established in Section 1612.3, any addition that constitutes substantial improvement of the existing structure, as defined in Section 1612.2, shall comply with the flood design requirements for new construction, and all aspects of the existing structure shall be brought into compliance with the requirements for new construction for flood design.
For buildings and structures in flood hazard areas established in Section 1612.3, any additions that do not constitute substantial improvement or substantial damage of the existing structure, as defined in Section 1612.2, are not required to comply with the flood design requirements for new construction.
10. 
3403.3 Existing structural elements carrying gravity load. Any existing gravity load-carrying structural element for which an addition and its related alterations cause an increase in design gravity load of more than five percent (5%) shall be strengthened, supplemented, replaced or otherwise altered as needed to carry the increased load required by this code for new structures. Any existing gravity load-carrying structural element whose gravity load-carrying capacity is decreased shall be considered an altered element subject to the requirements of Section 3404.3. Any existing element that will form part of the lateral load path for any part of the addition shall be considered an existing lateral load-carrying structural element subject to the requirements of Section 3403.4.
11. 
3403.3.1 Design live load. Where the addition does not result in increased design live load, existing gravity load-carrying structural elements shall be permitted to be evaluated and designed for live loads approved prior to the addition. If the approved live load is less than that required by Section 1607, the area designed for the nonconforming live load shall be posted with placards of approved design indicating the approved live load. Where the addition does result in increased design live load, the live load required by Section 1607 shall be used.
12. 
3403.4 Existing structural elements carrying lateral load. Where the addition is structurally independent of the existing structure, existing lateral load-carrying structural elements shall be permitted to remain unaltered. Where the addition is not structurally independent of the existing structure, the existing structure and its addition acting together as a single structure shall be shown to meet the requirements of Sections 1609 and 1613.
Exception: Any existing lateral load-carrying structural element who demand-capacity ratio with the addition considered is no more than ten percent (10%) greater than its demand-capacity ratio with the addition ignored shall be permitted to remain unaltered. For purposes of calculating demand-capacity ratios, the demand shall consider applicable load combinations with design lateral loads or forces in accordance with Sections 1609 and 1613. For purposes of this exception, comparisons of demand-capacity ratios and calculation of design lateral loads, forces and capacities shall account for the cumulative effects of additions and alterations since original construction.
13. 
3403.4.1 Seismic. Seismic requirements for alterations shall be in accordance with this Section. Where the existing seismic force-resisting system is a type that can be designated ordinary, value of R, 0 and Cd for the existing seismic force-resisting system shall be those specified by this code for an ordinary system unless it is demonstrated that the existing system will provide performance equivalent to that of a detailed intermediate or special system.
SECTION 3404
ALTERATIONS
14. 
3404.1 General. Except as provided by Section 3401.4 or this Section, alterations to any building or structure shall comply with the requirements of the code for new construction. Alterations shall be such that the existing building or structure is no less complying with the provisions of this code than the existing building or structure was prior to the alteration.
Exceptions:
1.
An existing stairway shall not be required to comply with the requirements of Section 1009 where the existing space and construction does not allow a reduction in pitch or slope.
2.
Handrails otherwise required to comply with Section 1009.12 shall not be required to comply with the requirements of Section 1012.6 regarding full extension of the handrails where such extensions would be hazardous due to plan configuration.
15. 
3402.2 Flood hazard areas. For buildings and structures in flood hazard areas established in Section 1612.3, any alteration that constitutes substantial improvement of the existing structure, as defined in Section 1612.2, shall comply with the flood design requirements for new construction, and all aspects of the existing structure shall be brought into compliance with the requirements for new construction for flood design. For buildings and structures in flood hazard areas established in Section 1612.3, any alterations that do not constitute substantial improvements or substantial damage of the existing structure, as defined in Section 1612.2, are not required to comply with the flood design requirements for new construction.
16. 
3404.3 Existing structural elements carrying gravity load. Any existing gravity load-carrying structural element for which an alteration causes and increase in design gravity load of more than five percent (5%) shall be strengthened, supplemented, replaced or otherwise altered as needed to carry the increased gravity load required by this code for new structures. Any existing gravity load-carrying structural element whose gravity load-carrying capacity is decreased as part of the alteration shall be shown to have the capacity to resist the applicable design gravity loads required by this code for new structures.
17. 
3404.3.1 Design live load. Where the alteration does not result in increased design live load, existing gravity load-carrying structural elements shall be permitted to be evaluated and designed for live loads approved prior to the alteration. If the approved live load is less than that required by Section 1607, the area designed for the non-conforming live load shall be posted with placards of approved design indicating the approved live load. Where the alteration does result in increased design live load, the live load required by Section 1607 shall be used.
18. 
3404.4 Existing structural elements carrying lateral load. Except as permitted by Section 3404.5, where the alteration increases design lateral loads in accordance with Section 1609 and 1613, or where the alteration results in a structural irregularity as defined in ASCE 7, or where the alteration decreases the capacity of any existing lateral load-carrying structural element, the structure of the altered building or structure shall be shown to meet the requirements of Sections 1609 and 1613.
Exception: Any existing lateral load-carrying structural element whose demand-capacity ratio with the alteration considered is no more than ten percent (10%) greater than its demand-capacity ratio with the alteration ignored shall be permitted to remain unaltered. For purposes of calculating demand-capacity ratios, the demand shall consider applicable load combinations with design lateral loads or forces per Sections 1609 and 1613. For purposes of this exception, comparisons of demand-capacity ratios and calculation of design lateral loads, forces, and capacities shall account for the cumulative effects of additions and alterations since original construction.
19. 
3404.4.1 Seismic. Seismic requirements for alterations shall be in accordance with this Section. Where the existing seismic force-resisting system is a type that can be designated ordinary, values of R, Ω0 and Cd for the existing seismic force-resisting system shall be those specified by this code for an ordinary system unless it is demonstrated that the existing system will provide performance equivalent to that of a detailed intermediate or special system.
20. 
3404.5 Voluntary seismic improvements. Alterations to existing structural elements or additions of new structural elements that are not otherwise required by this Chapter and are initiated for the purpose of improving the performance of the seismic force-resisting system of an existing structure or the performance of seismic bracing or anchorage of existing non-structural elements shall be permitted, provided that an engineering analysis is submitted demonstrating the following:
1.
The altered structure and the altered non-structural elements are no less in compliance with the provisions of this code with respect to earthquake design than they were prior to the alteration.
2.
New structural elements are detailed and connected to the existing structural elements as required by Chapter 16.
3.
New or relocated non-structural elements are detailed and connected to existing or new structural elements as required by Chapter 16.
4.
The alterations do not create a structural irregularity as defined in ASCE 7 or make an existing structural irregularity more severe.
21. 
3404.6 Means of egress capacity factors. Alterations to any existing building or structure shall not be affected by the egress width factors in Section 1005.1 for new construction in determining the minimum egress widths or the minimum number of exits in an existing building or structure. The minimum egress widths for the components of the means of egress shall be based on the means of egress width factors in the Building Code under which the building was constructed, and shall be considered as complying means of egress for any alteration if, in the opinion of the Building Code Official, they do not constitute a distinct hazard to life.
SECTION 3405
REPAIRS
22. 
3405.1 General. Buildings and structures, and parts thereof, shall be repaired in compliance with Section 3401.2. Work on non-damaged components that is necessary for the required repair of damaged components shall be considered part of the repair and shall not be subject to the requirements for alterations in this Chapter. Routine maintenance required by Section 3401.2, ordinary repairs exempt from permit in accordance with Section 105.2, and abatement of wear due to normal service conditions shall not be subject to the requirements for repairs in this Section.
23. 
3504.1.1 Dangerous conditions. Regardless of the extent of structural or non-structural damage, the Building Code Official shall have the authority to require the elimination of conditions deemed dangerous.
24. 
3405.2 Substantial structural damage to vertical elements of the lateral force-resisting system. A building that has sustained substantial structural damage to the vertical elements of its lateral force-resisting system shall be evaluated and repaired in accordance with the applicable provisions of Section 3405.2.1 through 3405.2.3.
25. 
3405.2.1 Evaluation. The building shall be evaluated by a registered design professional, and the evaluation findings shall be submitted to the Code Official. The evaluation shall establish whether the damaged building, if repaired to its predamage state, would comply with the provisions of this code for wind and earthquake loads. Evaluation for earthquake loads shall be required if the substantial structural damage was caused by or related to earthquake effect or if the building is in Seismic Design Category C, D, E or F.
Wind loads for this evaluation shall be those prescribed in Section 1609. Earthquake loads for this evaluation, if required, shall be permitted to be seventy-five percent (75%) of those prescribed in Section 1613. Values of R, W0 and Cd for the existing seismic force-resisting system shall be those specified by this code for an ordinary system unless it is demonstrated that the existing system will provide performance equivalent to that of an intermediate or special system.
26. 
3405.2.2 Extent of repair for compliant buildings. If the evaluation establishes compliance of the predamage building in accordance with Section 3405.2.1, then repairs shall be permitted that restore the building to its predamage state using materials and strengths that existed prior to the damage.
27. 
3405.2.3 Extent of repair for noncompliant buildings. If the evaluation does not establish compliance of the predamage building in accordance with Section 3405.2.1, then the building shall be rehabilitated to comply with applicable provisions of this code for load combinations, including wind or seismic loads. The wind loads for the repair shall be as required by the Building Code in effect at the time of original construction, unless the damage was caused by wind, in which case the wind loads shall be as required by the code in effect at the time of original construction or as required by this code, whichever are greater. Earthquake loads for this rehabilitation design shall be those required for the design of the predamage building, but not less than seventy-five percent (75%) of those prescribed in Section 1613. New structural members and connections required by this rehabilitation design shall comply with the detailing provisions of this code for new buildings of similar structure, purpose and location.
28. 
3405.3 Substantial structural damage to gravity load-carrying components. Gravity load-carrying components that have sustained substantial structural damage shall be rehabilitated to comply with the applicable provisions of this code for dead and live loads. Snow loads shall be considered if the substantial structural damage was caused by or related to snow load effects. Existing gravity load-carrying structural elements shall be permitted to be designed for live loads approved prior to the damage. Non-damaged gravity load-carrying components that receive dead, live or snow loads from rehabilitated components shall also be rehabilitated or shown to have the capacity to carry the design loads of the rehabilitation design. New structural members and connections required by this rehabilitation design shall comply with the detailing provisions of this code for new buildings of similar structure, purpose and location.
29. 
3405.3.1 Lateral force-resisting elements. Regardless of the level of damage to vertical elements of the lateral force-resisting system, if substantial structural damage to gravity load-carrying components was caused primarily by wind or earthquake effects, then the building shall be evaluated in accordance with Section 3405.2.1 and, if noncompliant, rehabilitated in accordance with Section 3404.2.3.
30. 
3405.4 Less than substantial structural damage. For damage less than substantial structural damage, repairs shall be allowed that restore the building to its predamage state using materials and strengths that existed prior to the damage. New structural members and connections used for this repair shall comply with the detailing provisions of this code for new buildings of similar structure, purpose and location.
31. 
3405.5 Flood hazard areas. For buildings and structures in flood hazard areas established in Section 1612.3, any repair that constitutes substantial improvement of the existing structure, as defined in Section 1612.2, shall comply with the flood design requirements for new construction, and all aspects of the existing structure shall be brought into compliance with the requirements for new construction for flood design. For buildings and structures in flood hazard areas established in Section 1612.3, any repairs that do not constitute substantial improvement or substantial damage of the existing structure, as defined in Section 1612.2, are not required to comply with the flood design requirements for new construction.
SECTION 3406
FIRE ESCAPES
32. 
3406.1 Where permitted. Fire escapes shall be permitted only as provided for in Sections 3406.1.1 through 3406.1.4.
33. 
3406.1.1 New buildings. Fire escapes shall not constitute any part of the required means of egress in new buildings.
34. 
3406.1.2 Existing fire escapes. Existing fire escapes shall be continued to be accepted as a component in the means of egress in existing buildings only.
35. 
3406.1.3 New fire escapes. New fire escapes for existing buildings shall be permitted only where exterior stairs cannot be utilized due to lot lines limiting stair size or due to the sidewalks, alleys or roads at grade level. New fire escapes shall not incorporate ladders or access by windows.
36. 
3406.1.4. Limitations. Fire escapes shall comply with this Section and shall not constitute more than fifty percent (50%) of the required number of exits nor more than fifty percent (50%) of the required exit capacity.
37. 
3406.2 Location. Where located on the front of the building and where projecting beyond the building line, the lowest landing shall not be less than seven (7) feet (2,134 mm) or more than twelve (12) feet (3,658 mm) above grade, and shall be equipped with a counterbalanced stairway to the street. In alleyways and thoroughfares less than thirty (30) feet (9,144 mm) wide, the clearance under the lowest landing shall not be less than twelve (12) feet (3,658 mm).
38. 
3406.3 Construction. The fire escape shall be designed to support a live load of one hundred (100) pounds per square foot (4,788 Pa) and shall be constructed of steel or other approved non-combustible materials. Fire escapes constructed of woods no less than nominal two (2) inches (51 mm) thick are permitted on buildings of Type 5 construction. Walkways and railings located over or supported by combustible roofs in buildings of Type 3 and 4 construction are permitted to be of wood not less than nominal two (2) inches (51 mm) thick.
39. 
3406.4 Dimensions. Stairs shall be at least twenty-two (22) inches (559 mm) wide with risers not more than, and treads not less than, eight (8) inches (203 mm) and landings at the foot of stairs not less than forty (40) inches (1,016 mm) wide by thirty-six (36) inches (914 mm) long, located not more than eight (8) inches (203 mm) below the door.
40. 
3406.5 Opening protectives. Doors and windows along the fire escape shall be protected with three-fourths (3/4) hour opening protectives.
SECTION 3407
GLASS REPLACEMENT
41. 
3407.1 Conformance. The installation or replacement of glass shall be as required for new installations.
SECTION 3408
CHANGE OF OCCUPANCY
42. 
3408.1 Conformance. No change shall be made in the use or occupancy of any building that would place the building in a different division of the same group of occupancies or in a different group of occupancies, unless such building is made to comply with the requirements of this code for such division or group of occupancies. Subject to the approval of the Building Official, the use or occupancy of existing buildings shall be permitted to be changed and the building is allowed to be occupied for purposes in other groups without conforming to all the requirements of this code for those groups, provided the new or proposed use is less hazardous, based on life and fire risk, than the existing use.
43. 
3408.2 Certificate of occupancy. A certificate of occupancy shall be issued where it has been determined that the requirements for the new occupancy classification have been met.
44. 
3408.3 Stairways. Existing stairways in an existing structure shall not be required to comply with the requirements of a new stairway as outlined in Section 1011 where the existing space and constructions will not allow a reduction in pitch or slope.
45. 
3408.4 Change of occupancy. When a change of occupancy results in a structure being reclassified to a higher occupancy category, the structure shall conform to the seismic requirements for a new structure of the higher occupancy category. Where the existing seismic force-resisting system is a type that can be designated ordinary, values of R, 0 and Cd, for the existing seismic force-resisting system shall be those specified by this code for an ordinary system unless it is demonstrated that the existing system will provide performance equivalent to that of a detailed, intermediate or special system.
Exceptions:
1.
Specific seismic detailing requirements of this code or Section 1613 for a new structure shall not be required to be met where it can be shown that the level of performance and seismic safety is equivalent to that of a new structure. Such analysis shall consider the regularity, over strength, redundancy and ductility of the structure within the context of the existing and retrofit (if any) detailing provided.
2.
When a change of use results in a structure being reclassified from Occupancy Category I or II to Occupancy Category III and the structure is located in a seismic map area where SDS < 0.33, compliance with the seismic requirements of this code and Section 1613 are not required.
SECTION 3409
HISTORIC BUILDINGS
46. 
3409.1 Historic buildings. The provisions of this code relating to the construction, repair, alteration, addition, restoration and movement of structures, and change of occupancy shall not be mandatory for historic buildings where such buildings are judged by the Building Official to not constitute a distinct life safety hazard.
47. 
3409.2 Flood hazard areas. Within flood hazard areas established in accordance with Section 1612.3, where the work proposed constitutes substantial improvement as defined in Section 1612.2, the building shall be brought into compliance with Section 1612.
Exception: Historic buildings that are:
1.
Listed or preliminarily determined to be eligible for listing in the National Register of Historic Places;
2.
Determined by the Secretary of the U.S. Department of Interior as contributing to the historical significance of a registered historic district or a district preliminarily determined to qualify as an historic district; or
3.
Designated as historic under a State or local historic preservation program that is approved by the Department of Interior.
SECTION 3410
MOVED STRUCTURES
48. 
Section 3410.1 Conformance. Structures moved into or within the City of Creve Coeur shall comply with the provisions of this code for new structures.
Exception: The moved structure may be granted non-conforming status provided all of the following conditions are met:
1.
No change shall be made in the previous use or occupancy of the moved structure.
2.
No addition shall be made to the structure after it is moved.
3.
It can be demonstrated to the Building Official, in writing, that the moved structure's structural strength, means of egress facilities, life safety systems and mechanical, electrical and plumbing systems are in compliance with the building, mechanical, electrical and plumbing codes enforced when the moved structure was originally built.
SECTION 3411
ACCESSIBILITY FOR EXISTING BUILDINGS
49. 
3411.1 Scope. The provisions of Sections 3411.1 through 3411.9 apply to maintenance, change of occupancy, additions, and alterations to existing buildings, including those identified as historic buildings.
Exception: Type B dwelling or sleeping units required by Section 1107 of this code are not required to be provided in existing buildings and facilities being altered or undergoing a change of occupancy.
50. 
3411.2 Maintenance of facilities. A building, facility or element that is constructed or altered to be accessible shall be maintained accessible during occupancy.
51. 
3411.3 Extent of application. An alteration of an existing element, space or area of a building or facility shall not impose a requirement for greater accessibility than that which would be required for new construction.
Alterations shall not reduce or have the effect of reducing accessibility of a building, portion of a building or facility.
52. 
3411.4 Change of occupancy. Existing buildings that undergo a change of group or occupancy shall comply with this Section.
53. 
3411.4.1 Partial change in occupancy. Where a portion of the building is changed to a new occupancy classification, and alterations shall comply with Sections 3411.6, 3411.7 and 3411.8.
54. 
3411.4.2 Complete change of occupancy. Where an entire building undergoes a change of occupancy, it shall comply with Section 3411.4.1 and shall have all of the following accessible features:
1.
At least one (1) accessible building entrance.
2.
At least one (1) accessible route from an accessible building entrance to primary function areas.
3.
Signage complying with Section 1111.
4.
Accessible parking, where parking is being provided.
5.
At least one (1) accessible passenger loading zone, when loading zones are provided.
6.
At least one (1) accessible route connecting accessible parking and accessible passenger loading zones to an accessible entrance.
Where it is technically infeasible to comply with the new construction standards for any of these requirements for a change of group or occupancy, the above items shall conform to the requirements to the maximum extent technically feasible.
55. 
3411.5 Additions. Provisions for new construction shall apply to additions. An addition that affects the accessibility to, or contains an area of, a primary function shall comply with the requirements in Section 3411.7.
56. 
3411.6 Alterations. A building, facility or element that is altered shall comply with the applicable provisions in Chapter 11 of this code and ICC A117.1, unless technically infeasible. Where compliance with this Section is technically infeasible, the alteration shall provide access to the maximum extent technically feasible.
Exceptions:
1.
The altered element or space is not required to be on an accessible route, unless required by Section 3411.7.
2.
Accessible means of egress required by Chapter 10 are not required to be provided in existing buildings and facilities.
3.
The alteration to Type A individually owned dwelling units within a Group R-2 occupancy shall meet the provisions for Type B dwelling unit and shall comply with the applicable provisions in Chapter 11 and ICC A117.1.
57. 
3411.7 Alterations affecting an area containing a primary function. Where an alteration affects the accessibility to, or contains an area of primary function, the route to the primary function area shall be accessible. The accessible route to the primary function area shall include toilet facilities or drinking fountains serving the area of primary function.
Exceptions:
1.
The costs of providing the accessible route are not required to exceed twenty percent (20%) of the costs of the alterations affecting the area of primary function.
2.
This provision does not apply to alterations limited solely to windows, hardware, operating controls, electrical outlets and signs.
3.
This provision does not apply to alterations limited solely to mechanical systems, electrical systems, installation or alteration of fire protection systems and abatement of hazardous materials.
4.
This provision does not apply to alterations undertaken for the primary purpose of increasing the accessibility of an existing building, facility, or element.
58. 
3411.8 Scoping for alterations. The provisions of Sections 3411.8.1 through 3411.8.14 shall apply to alterations to existing buildings and facilities.
59. 
3411.8.1 Entrances. Accessible entrances shall be provided in accordance with Section 1105.
Exception: Where an alteration includes alterations to an entrance, and the building or facility has an accessible entrance, the altered entrance is not required to be accessible, unless required by Section 3411.7. Signs complying with Section 1110 shall be provided.
60. 
3411.8.2 Elevators. Altered elements of existing elevators shall comply with ASME A17.1 and ICC A117.1 Such elements shall also be altered in elevators programmed to respond to the same shall call control as the altered elevator.
61. 
3411.8.3 Platform lifts. Platform (wheelchair) lifts complying with ICC A117.1 and installed in accordance with ASME A18.1 shall be permitted as a component of an accessible route.
62. 
3411.8.4 Stairs and escalators in existing buildings. In alterations, change of occupancy or additions where an escalator or stair is added where none existed previously and major structural modifications are necessary for installation, an accessible route shall be provided between the levels served by the escalator or stairs in accordance with Sections 1104.4 and 1104.5.
63. 
34411.8.5 Ramps. Where slopes steeper than allowed by Section 1010.2 are necessitated by space limitations, the slope of ramps in or providing access to existing buildings or facilities shall comply with Table 3411.8.5
Table 3411.8.5
Ramps
Slope
Maximum Rise
Steeper than 1:10 but not steeper than 1:8
3 inches
Steeper than 1:12 but not steeper than 1:10
6 inches
For SI: 1 inch = 25.4 mm.
64. 
3411.8.6 Performance areas. Where it is technically infeasible to alter performance areas to be on an accessible route, at least one (1) of each type of performance area shall be made accessible.
65. 
3411.8.7 Accessible dwelling or sleeping units. Where Group I-1, I-2, I-3, R-1, R-2 or R-4 dwelling or sleeping units are being altered or added, the requirements of Section 1107 for Accessible units apply only to the quantity of spaces being altered or added.
66. 
3411.8.8 Type A dwelling or sleeping units. Where more than twenty (20) Group R-2 dwelling or sleeping units are being added, the requirements of Section 1107 for Type A units apply only to the quantity of the spaces being added.
67. 
3411.8.9 Type B dwelling or sleeping units. Where four (4) or more Group I-1, I-2, R-1, R-2, R-3 or R-4 dwelling or sleeping units are being added, the requirements of Section 1107 for Type B units apply only to the quantity of the spaces being added.
68. 
3411.8.10 Jury boxes and witness stands. In alterations, accessible wheelchair spaces are not required to be located within the defined area of raised jury boxes or witness stands and shall be permitted to be located outside these spaces where the ramp or lift access restricts or projects into the means of egress.
69. 
3411.8.11 Toilet rooms. Where it is technically infeasible to alter existing toilet and bathing facilities to be accessible, an accessible family or assisted-use toilet or bathing facility constructed in accordance with Section 1109.2.1 is permitted. The family or assisted-use facility shall be located on the same floor and in the same area as the existing facilities.
70. 
3411.8.12 Dressing, fitting and locker rooms. Where it is technically infeasible to provide accessible dress, fitting or locker rooms at the same location as similar types of rooms, one (1) accessible room on the same level shall be provided. Where separate-sex facilities are provided, accessible rooms for each sex shall be provided. Separate-sex facilities are not required where only unisex rooms are provided.
71. 
3411.8.13 Fuel dispensers. Operable parts of replacement fuel dispensers shall be permitted to be fifty-four (54) inches (1,370 mm) maximum measured from the surface of the vehicular way where fuel dispensers are installed on existing curbs.
72. 
3411.8.14 Thresholds. The maximum heights of thresholds at doorways shall be three-fourths (3/4) inch (19.1 mm). Such thresholds shall have beveled edges on each side.
73. 
3411.9 Historic buildings. These provisions shall apply to buildings and facilities designated as historic structures that undergo alterations or a change of occupancy, unless technically infeasible. Where compliance with the requirements for accessible routes, entrances or toilet facilities would threaten or destroy the historic significance of the building or facility, as determined by the applicable governing authority, the alternative requirements of Section 3411.9.1 through 3411.9.4 for that element shall be permitted.
74. 
3411.9.1 Site arrival points. At least one (1) accessible route from a site arrival point to an accessible entrance shall be provided.
75. 
3411.9.2 Multilevel buildings and facilities. An accessible route from an accessible entrance to public spaces on the level of the accessible entrance shall be provided.
76. 
3411.9.3 Entrances. At least one (1) main entrance shall be accessible.
Exceptions:
1.
If a main entrance cannot be made accessible, an accessible non-public entrance that is unlocked while the building is occupied shall be provided; or
2.
If a main entrance cannot be made accessible, a locked accessible entrance with a notification system or remote monitoring shall be provided.
3.
Signs complying with Section 1110 shall be provided at the primary entrance and the accessible entrance.
77. 
3411.9.4 Toilet and bathing facilities. Where toilet rooms are provided at least one (1) accessible family or assisted-use toilet room complying with Section 1109.2.1 shall be provided.
SECTION 3412
COMPLIANCE ALTERNATIVES
78. 
3412.1 Compliance. The provisions of this Section are intended to maintain or increase the current degree of public safety, health and general welfare in existing buildings while permitting repair, alteration, addition and change of occupancy without requiring full compliance with Chapters 2 through 33, or Sections 3401.3, and 3403 through 3409, except where compliance with other provisions of this code is specifically required in the Section.
79. 
3412.2 Applicability. Structures existing prior to September 14, 1953, in which there is work involving additions, alterations or changes of occupancy shall be made to comply with the requirements of this Section or the provisions of Sections 3403 through 3409. The provisions in Sections 3412.2.1 through 3412.2.5 shall apply to existing occupancies that will continue to be, or are proposed to be, in Groups A, B, E, F, M, R, S and U. These provisions shall not apply to buildings with occupancies in Group H or I.
80. 
3412.2.1 Change in occupancy. Where an existing building is changed to a new occupancy classification and this Section is applicable, the provisions of this Section for the new occupancy shall be used to determine compliance with this code.
81. 
3412.2.2 Partial change in occupancy. Where a portion of the building is changed to a new occupancy classification, and that portion is separated from the remainder of the building with fire barriers or horizontal assemblies having a fire-resistance rating as required by Table 508.4 for the separate occupancies, or with approved compliance alternatives, the portion changed shall be made to comply with the provisions of this Section.
Where a portion of the building is changed to a new occupancy classification, and that portion is not separated from the remainder of the building with fire barriers or horizontal assemblies having a fire-resistance rating as require by Table 508.4 for the separate occupancies, or with approved compliance alternatives, the provisions of this Section which apply to each occupancy shall apply to the entire building. Where there are conflicting provisions, those requirements which secure the greater public safety shall apply to the entire building or structure.
82. 
3412.2.3 Additions. Additions to existing buildings shall comply with the requirements of this code for new construction. The combined height and area of the existing building and the new addition shall not exceed the height and area allowed by Chapter 5. Where a fire wall that complies with Section 706 is provided between the addition and the existing building, the addition shall be considered a separate building.
83. 
3412.2.4 Alterations and repairs. An existing building or portion thereof, which does not comply with the requirements of this code for new construction, shall not be altered or repaired in such a manner that results in the building being less safe or sanitary than such building is currently. If, in the alteration or repair, the current level of safety or sanitation is to be reduced, the portion altered or repaired shall conform to the requirement of Chapters 2 through 12 and Chapters 14 through 33.
84. 
3412.2.4.1 Flood hazard areas. For existing buildings located in flood hazard areas established in Section 1612.3, if the alterations and repairs constitute substantial improvement of the existing building, the existing building shall be brought into compliance with the requirement for new construction for flood design.
85. 
3412.2.5 Accessibility requirements. All portions of the buildings proposed for change of occupancy shall conform to the accessibility provisions of Section 3411.
86. 
3412.3 Acceptance. For repairs, alterations, additions and changes of occupancy to existing buildings that are evaluated in accordance with this Section, compliance with this Section shall be accepted by the Building Official.
87. 
3412.3.1 Hazards. Where the Building Official determines that an unsafe condition exists, as provided for in Section 116, such unsafe condition shall be abated in accordance with Section 116.
88. 
3412.3.2 Compliance with other codes. Buildings that are evaluated in accordance with this Section shall comply with the International Fire Code and the International Property Maintenance Code.
89. 
3412.4 Investigation and evaluation. For proposed work covered by this Section, the building owner shall cause the existing building to be investigated and evaluated in accordance with the provisions of this Section.
90. 
3412.4.1 Structural analysis. The owner shall have a structural analysis of the existing building made to determine adequacy of structural systems for the proposed alteration, addition or change of occupancy. The analysis shall demonstrate that the building with the work completed is capable of resisting the loads specific in Chapter 16.
91. 
3412.4.2 Submittal. The results of the investigation and evaluation as required in Section 3412.4, along with proposed compliance alternatives, shall be submitted to the Building Official.
92. 
3412.4.3 Determination of compliance. The Building Official shall determine whether the existing building, with the proposed addition, alteration or change of occupancy, complies with the provisions of this Section in accordance with the evaluation process in Sections 3412.5 through 3412.9.
93. 
3412.5 Evaluation. The evaluation shall be comprised of three (3) categories: fire safety, means of egress and general safety, as defined in Sections 3412.5.1 through 3412.5.3.
94. 
3412.5.1 Fire safety. Included within the fire safety category are the structural fire resistance, automatic fire detection, fire alarm and fire suppression system features of the facility.
95. 
3412.5.2 Means of egress. Included within the means of egress category are the configuration, characteristics and support features for means of egress in the facility.
96. 
3412.5.3 General safety. Included within the general safety category are the fire safety parameters and the means of egress parameters.
97. 
3412.6 Evaluation process. The evaluation process specified herein shall be followed in its entirety to evaluate existing buildings. Table 3412.7 shall be utilized for tabulating the results of the evaluation. References to other Sections of the code indicate that compliance with those Sections is required in order to gain credit in the evaluation herein outlined. In applying this Section to a building with mixed occupancies, where the separation between the mixed occupancies does not qualify for any category indicated in Section 3412.6.16, the score for each occupancy shall be determined and the lower score determined for each section of the evaluation process shall apply to the entire building.
Where the separation between mixed occupancies qualifies for any category indicated in Section 3412.6.16, the score for each occupancy shall apply to each portion of the building based on the occupancy of the space.
98. 
3412.6.1 Building height. The value for building height shall be the lesser value determined by the formula in Section 3412.6.1.1 Chapter 5 shall be used to determine the allowable height of the building, including allowable increases due to automatic sprinklers as provided for in Section 504.2. Subtract the actual building height in feet from the allowable and divide by twelve and one-half (12 1/2) feet. Enter the height value and its sign (positive or negative) in Table 3412.7 under Safety Parameter 3412.6.1, Building Height, for fire safety, means of egress and general safety. The maximum score for a building shall be 10.
99. 
3412.6.1.1 Height formula. The following formulas shall be used in computing the building height value.
500-99.tif
100. 
3412.6.2 Building area. The value for building area shall be determined by the formula in Section 3412.6.2.2. Section 503 and the formula in Section 3412.6.2.1 shall be used to determine the allowable area of the building. This shall include any allowable increases due to frontage and automatic sprinklers as provided for in Section 506. Subtract the actual building area in square feet from the allowable area and divide by one thousand two hundred (1,200) square feet. Enter the area value and its sign (positive or negative) in Table 3412.7 under Safety Parameter 3412.6.2, Building Area, for fire safety, means of egress and general safety. In determining the area value, the maximum permitted positive value for area fifty percent (50%) of the fire safety score as listed in Table 3412.8, Mandatory Safety Scores.
101. 
3412.6.2.1 Allowable area formula. The following formula shall be used in computing allowable area:
500-101.tif
102. 
3412.6.2.2 Area formula. The following formula shall be used in computing the area value. Determine the area value for each occupancy floor area on a floor-by-floor basis. For each occupancy, choose the minimum area value of the set of values obtained for the particular occupancy.
500-102.tif
103. 
3412.6.3 Compartmentation. Evaluate the compartments created by fire barriers or horizontal assemblies which comply with Sections 3412.6.3.1 and 3412.6.3.2 and which are exclusive of the wall elements considered under Sections 3412.6.4 and 3412.6.5. Conforming compartments shall be figured as the net area and do not include shafts, chases, stairways, walls or columns. Using Table 3412.6.3, determine the appropriate compartmentation value (CV) and enter that value into Table 3412.7 under Safety Parameter 3412.6.3, Compartmentation, for fire safety, means of egress and general safety.
Table 3412.6.3
Compartmentation Values
Categoriesa
Occupancy
a Compartment size equal to or greater than 15,000 square feet
b Compartment size of 10,000 square feet
c Compartment size of 7,500 square feet
d Compartment size of 5,000 square feet
e Compartment size of 2,500 square feet or less
A-1, A-3
0
6
10
14
18
A-2
0
4
10
14
18
A-4, B, E, S-2
0
5
10
15
20
F, M, R, S-1
0
4
10
16
22
For SI: 1 square foot = 0.093 m2.
a.
For areas between categories, the compartmentation value shall be obtained by linear interpolation.
104. 
3412.6.3.1 Wall construction. A wall used to create separate compartments shall be a fire barrier conforming to Section 707 with a fire-resistance rating of not less than two (2) hours. Where the building is not divided into more than one (1) compartment, the compartment size shall be taken as the total floor area on all floors. Where there is more than one (1) compartment within a story, each compartmented area on such story shall be provided with a horizontal exit conforming to Section 1026. The fire door serving as the horizontal exit between compartments shall be so installed, fitted and gasketed that such fire door will provide a substantial barrier to the passage of smoke.
105. 
3412.6.3.2 Floor/ceiling construction. A floor/ceiling assembly used to create compartments shall conform to Section 712 and shall have a fire-resistance rating of not less than two (2) hours.
106. 
3412.6.4 Tenant and dwelling unit separations. Evaluate the fire-resistance rating of floors and walls separating tenants, including dwelling units, and not evaluated under Sections 3412.6.3 and 3412.6.5. Under the categories and occupancies in Table 3412.6.4, determine the appropriate value and enter that value in Table 3412.7 under Safety Parameter 3412.6.4, Tenant and Dwelling Unit Separations, for fire safety, means of egress and general safety.
Table 3412.6.4
Separation Values
Occupancy
Categories
a
b
c
d
e
A-1
0
0
0
0
1
A-2
-5
-3
0
1
3
A-3, A-4, B, E, F, M, S-1
-4
-3
0
2
4
R
-4
-2
0
2
4
S-2
-5
-2
0
2
4
107. 
3412.6.4.1 Categories. The categories for tenant and dwelling unit separations are:
1.
Category a - No fire partitions; incomplete fire partitions; no doors; doors not self-closing or automatic closing.
2.
Category b - Fire partitions or floor assemblies with less than a 1-hour fire-resistance rating or not constructed in accordance with Sections 708 or 711 respectively.
3.
Category c - Fire partitions with a 1-hour or greater fire-resistance rating constructed in accordance with Section 708 and floor assemblies with a 1-hour but less than 2-hour fire-resistance rating constructed in accordance with Section 711, or with only one (1) tenant within the floor area.
4.
Category d - Fire barriers with a 1-hour but less than 2-hour fire-resistance rating constructed in accordance with Section 707 and floor assemblies with a 2-hour or greater fire-resistance rating constructed in accordance with Section 711.
5.
Category e - Fire barriers and floor assemblies with a 2-hour or greater fire-resistance rating and constructed in accordance with Sections 707 and 711, respectively.
108. 
3412.6.5 Corridor walls. Evaluate the fire-resistance rating and degree of completeness of walls which create corridors serving the floor and constructed in accordance with Section 1020. This evaluation shall not include the wall elements considered under Sections 3412.6.3 and 3412.6.4 Under the categories and groups in Table 3412.6.5, determine the appropriate value and enter that value into Table 3412.7 under Safety Parameter 3412.6.5, Corridor Walls, for fire safety, means of egress and general safety.
Table 3412.6.5
Corridor Wall Values
Occupancy
Categories
a
b
ca
da
A-1
-10
-4
0
2
A-2
-30
-12
0
2
A-3, F, M, R, S-1
-7
-3
0
2
A-4, B, E, S-2
-5
-2
0
5
a.
Corridors not providing at least one-half (1/2) the travel distance for all occupants on a floor shall use Category b.
109. 
3412.6.5.1 Categories. The categories for corridor walls are:
1.
Category a - No fire partitions; incomplete fire partitions; no doors; or doors not self-closing.
2.
Category b - Less than 1-hour fire-resistance rating or not constructed in accordance with Section 708.4.
3.
Category c - 1-hour to less than 2-hour fire-resistance rating, with doors conforming to Section 716 or without corridors as permitted by Section 1020.
4.
Category d - 2-hour or greater fire-resistance rating, with doors conforming to Section 716.
110. 
3412.6.6 Vertical openings. Evaluate the fire-resistance rating of exit enclosures, hoistways, escalator openings and other shaft enclosures within the building, and openings between two (2) or more floors. Table 3412.6.6(1) contains the appropriate protection values. Multiply that value by the construction type factor found in Table 3412.6.6(2). Enter the vertical opening value and its sign (positive or negative) in Table 3412.7 under Safety Parameters 3412.6.6, Vertical Openings, for fire safety, means of egress, and general safety. If the structure is a one-story building or if all the unenclosed vertical openings within the building conform to the requirements of Section 713, enter a value of 2. The maximum positive value for this requirement shall be 2.
111. 
3412.6.6.1 Vertical opening formula. The following formula shall be used in computing vertical opening value.
VO
=
PVxCF
(Equation 34-4)
VO
=
Vertical opening value
PV
=
Protection value [Table 3412.6.6(1)]
CF
=
Construction type factor [Table 3412.6.6(2)]
Table 3412.6.6(1)
Vertical Opening Protection Value
Protection
Value
None (unprotected opening)
-2 times number floors connected
Less than 1 hour
-1 times number floors connected
1 to less than 2 hours
1
2 hours or more
2
Table 3412.6.6(2)
Construction-Type Factor
Type Of Construction
IA
IB
IIA
IIB
IIIA
IIIB
IV
VA
VB
Factor
1.2
1.5
2.2
3.5
2.5
3.5
2.3
3.3
7
112. 
3412.6.7. HVAC Systems. Evaluate the ability of the HVAC system to resist the movement of smoke and fire beyond the point of origin. Under the categories in Section 3412.6.7.1, determine the appropriate value and enter that value into Table 3412.7 under Safety Parameter 3412.6.7, HVAC Systems, for fire safety, means of egress and general safety.
113. 
3412.6.7.1 Categories. The categories for HVAC systems are:
1.
Category a - Plenums not in accordance with Section 602 of the International Mechanical Code.
-10 points
2.
Category b - Air movement in egress elements not in accordance with Section 1020.5.
-5 points
3.
Category c - Both categories a and b are applicable.
-15 points
4.
Category d - Compliance of the HVAC system with Section 1020.5 and Section 602 of the International Mechanical Code.
0 points
5.
Category e - Systems servicing one (1) story; or a central boiler/chiller system without ductwork connecting two (2) or more stories.
5 points
114. 
3412.6.8 Automatic fire detection. Evaluate the smoke detection capability based on the location and operation of automatic fire detectors in accordance with Section 907 and the International Mechanical Code. Under the categories and occupancies in Table 3412.6.8, determine the appropriate value and enter that value into Table 3412.7 under Safety Parameter 3412.6.8, Automatic Fire Detection, for fire safety, means of egress and general safety.
Table 3412.6.8
Automatic Fire Detection Values
Occupancy
Categories
a
b
c
d
e
A-1, A-3, F, M, R, S-1
-10
-5
0
2
6
A-2
-25
-5
0
5
9
A-4, B, E, S-2
-4
-2
0
4
8
115. 
3412.6.8.1 Categories. The categories for automatic fire detection are:
1.
Category a - None.
2.
Category b - Existing smoke detectors in HVAC systems and maintained in accordance with the International Fire Code.
3.
Category c - Smoke detectors in HVAC systems. The detectors are installed in accordance with the requirements for new buildings in the International Mechanical Code.
4.
Category d - Smoke detectors throughout all floor areas other than individual sleeping units, tenant spaces and dwelling units.
5.
Category e - Smoke detectors installed throughout the floor area.
116. 
3412.6.9 Fire alarm systems. Evaluate the capability of the fire alarm system in accordance with Section 907. Under the categories and occupancies in Table 3412.6.9, determine the appropriate value and enter that value into Table 3412.7 under Safety Parameter 3412.6.9, Fire Alarm Systems, for fire safety, means of egress and general safety.
Table 3412.6.9
Fire Alarm System Values
Occupancy
Categories
a
ba
c
d
A-1, A-2, A-3, A-4, B, E, R
-10
-5
0
5
F, M, S
0
5
10
15
a.
For buildings equipped throughout with an automatic sprinkler system, add 2 points for activation by a sprinkler waterflow device.
117. 
3412.6.9.1 Categories. The categories for fire alarm systems are:
1.
Category a - None.
2.
Category b - Fire alarm system with manual fire alarm boxes in accordance with Section 907.3 and alarm notification appliances in accordance with Section 907.4.
3.
Category c - Fire alarm system in accordance with Section 907.
4.
Category d - Category c plus a required emergency voice/alarm communications system and a fire command center that conforms to Section 403.4.5 and contains the emergency voice/alarm communications system controls, fire department communication system controls and any other controls specific in Section 911 where those systems are provided.
118. 
3412.6.10 Smoke control. Evaluate the ability of a natural or mechanical venting, exhaust or pressurization system to control the movement of smoke from a fire. Under the categories and occupancies in Table 3412.6.10, determine the appropriate value and enter that value into Table 3412.7 under Safety Parameter 3412.6.10, Smoke Control, for means of egress and general safety.
Table 3412.6.10
Smoke Control Values
Occupancy
Categories
a
b
c
d
e
f
A-1, A-2, A-3
0
1
2
3
6
6
A-4, E
0
0
0
1
3
5
B, M, R
0
2a
3a
3a
3a
4a
F, S
0
2a
2a
3a
3a
3a
a.
This value shall be 0 if compliance with Category d or e in Section 3412.6.8.1 has not been obtained.
119. 
3412.6.10.1 Categories. The categories for smoke control are:
1.
Category a - None.
2.
Category b - The building is equipped throughout with an automatic sprinkler system. Openings are provided in exterior walls at the rate of twenty (20) square feet (1.86m2) per fifty (50) linear feet (15,240 mm) of exterior wall in each story and distributed around the building perimeter at intervals not exceeding fifty (50) feet (15,240 mm). Such openings shall be readily openable from the inside without a key or separate tool and shall be provided with ready access thereto. In lieu of operable openings, clearly and permanently marked tempered glass panels shall be used.
3.
Category c - One (1) enclosed exit stairway with ready access thereto, from each occupied floor of the building. The stairway has operable exterior windows and the building has opening in accordance with Category b.
4.
Category d - One (1) smokeproof enclosure and the building has opening in accordance with Category b.
5.
Category e - The building is equipped throughout with an automatic sprinkler system. Each floor area is provided with a mechanical air-handling system designed to accomplish smoke containment. Return and exhaust air shall be moved directly to the outside without recirculation to other floor areas of the building under fire conditions. The system shall exhaust not less than six (6) air changes per hour from the floor area. Supply air by mechanical means to the floor area is not required. Containment of smoke shall be considered as confining smoke to the fire area involved without mitigation to other floor areas. Any other tested and approved design which will adequately accomplish smoke containment is permitted.
6.
Category f - Each stairway shall be one (1) of the following: a smokeproof enclosure in accordance with Section 1023.11; pressurized in accordance with Section 909.20.5, or shall have operable exterior windows.
120. 
3412.6.11 Means of egress capacity and number. Evaluate the means of egress capacity and the number of exits available to the building occupants. In applying this Section, the means of egress are required to conform to the following Sections of this code: 1003.7, 1004, 1005.1, 1014.2, 1006.3, 1026.1, 1028.2, 1029.2, 1029.3, 1029.4 and 1030 [except that the minimum width required by this Section shall be determined solely by the width for the required capacity in accordance with Table 3412.6.11(1)]. The number of exits credited is the number that is available to each occupant of the area being evaluated. Existing fire escapes shall be accepted as a component in the means of egress when conforming to Section 3406. Under the categories and occupancies in Table 3412.6.11(2), determine the appropriate value and enter that value into Table
Table 3412.6.11(1)
Egress Width Per Occupant Served
Occupancy
Without Sprinkler System
With Sprinkler Systema
Stairways
(inches per occupant)
Other egress components (inches per occupant)
Stairways
(inches per occupant)
Other egress components
(inches per occupant)
Occupancies other than those listed below
0.3
0.2
0.2
0.15
Hazardous: H-1, H-2, H-3 and H-4
Not Permitted
Not Permitted
0.3
0.2
Institutional: I-2
Not Permitted
Not Permitted
0.3
0.2
For SI: 1 inch = 25.4 mm.
a.
Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
121. 
3412.7 under Safety Parameter 3412.6.11, Means of Egress Capacity, for means of egress and general safety.
Table 3412.6.11(2)
Means Of Egress Values
Occupancy
Categories
aa
b
c
d
e
A-1, A-2, A-3, A-4, E
-10
0
2
8
10
B, F, S
-1
0
0
0
0
M
-3
0
1
2
4
R
-3
0
0
0
0
a.
The values indicated are for buildings six (6) stories or less in height. For buildings over six (6) stories above grade plane, add an additional -10 points.
122. 
3412.6.11.1 Categories. The categories for Means of Egress Capacity and number of exits are:
1.
Category a - Compliance with the minimum required means of egress capacity or number of exits is achieved through the use of a fire escape in accordance with Section 3406.
2.
Category b - Capacity of the means of egress complies with Section 1004 and the number of exits complies with the minimum number required by Section 1022.
3.
Category c - Capacity of the means of egress is equal to or exceeds one hundred twenty-five percent (125%) of the required means of egress capacity, the means of egress complies with the minimum required width dimensions specified in the code and the number of exits complies with the minimum number required by Section 1022.
4.
Category d - The number of exits provided exceeds the number of exits required by Section 1022. Exists shall be located a distance apart from each other equal to not less than that specified in Section 1007.
5.
Category e - The area being evaluated meets both Categories c and d.
123. 
3412.6.12 Dead ends. In spaces required to be served by more than one (1) means of egress, evaluate the length of the exit access travel path in which the building occupants are confined to a single path of travel. Under the categories and occupancies in Table 3412.6.12, determine the appropriate value and enter that value into Table 3412.47 under Safety Parameter 3412.6.12, Dead Ends, for means of egress and general safety.
Table 3412.6.12
Dead-End Values
Occupancy
Categoriesa
a
b
c
A-1, A-3, A-4, B, E, F, M, R, S
-2
0
2
A-2, E
-2
0
2
a.
For dead-end distances between categories, the dead-end value shall be obtained by linear interpolation.
124. 
3412.6.12.1 Categories. The categories for dead ends are:
1.
Category a - Dead end of thirty-five (35) feet (10,670 mm) in non-sprinklered buildings or seventy (70) feet (21,340 mm) in sprinklered buildings
2.
Category b - Dead end of twenty (20) feet (6,096 mm); or fifty (50) feet (15,240 mm) in Group B in accordance with Section 10204, exception 2.
3.
Category c - No dead ends; or ratio of length to width (l/w) is less than 2.5:1.
125. 
3412.6.13 Maximum exit access travel distance. Evaluate the length of exit access travel to an approved exit. Determine the appropriate points in accordance with the following equation and enter that value into Table 3412.7 under Safety Parameter 3412.6.13, Maximum Exit Access Travel Distance, for means of egress and general safety. The maximum allowable exit access travel distance shall be determined in accordance with Section 1016.1
126. 
3412.6.14 Elevator control. Evaluate the passenger elevator equipment and controls that are available to the fire department to reach all occupied floors. Elevator recall controls shall be provided in accordance with the International Fire Code. Under the categories and occupancies in Table 3412.6.14, determine the appropriate value and enter that value into Table 3412.47 under Safety Parameter 3412.6.14, Elevator Control, for fire safety, means of egress and general safety. The values shall be zero for a single-story building.
Table 3412.6.14
Elevator Control Values
Elevator Travel
Categories
a
b
c
d
Less than 25 feet of travel above or below the primary level of elevator access for emergency fire-fighting or rescue personnel
-2
0
0
+2
Travel of 25 feet or more above or below the primary level of elevator access for emergency fire-fighting or rescue personnel
-4
NP
0
+4
For SI: 1 foot = 304.8 mm.
127. 
3412.6.14.1 Categories. The categories for elevator controls are:
1.
Category a - No elevator.
2.
Category b - Any elevator without Phase I or II recall.
3.
Category c - All elevators with Phase I or II recall as required by the International Fire Code.
4.
Category d - All meet Category c; or Category b where permitted to be without recall; and at least one (1) elevator that complies with new construction requirements serves all occupied floors.
128. 
3412.6.15 Means of egress emergency lighting. Evaluate the presence of and reliability of means of egress emergency lighting. Under the categories and occupancies in Table 3412.6.15, determine the appropriate value and enter that value into Table 3412.7 under Safety Parameter 3412.6.15, Means of Egress Emergency Lighting, for means of egress and general safety.
Table 3412.6.15
Means Of Egress Emergency Lighting Values
Number Of Exits Required By Section 1014
Categories
a
b
c
Two or more exits
NP
0
4
Minimum of one exit
0
1
1
129. 
3412.6.15.1 Categories. The categories for means of egress emergency lighting are:
1.
Category a - Means of egress lighting and exit signs not provided with emergency power in accordance with Chapter 27.
2.
Category b - Means of egress lighting and exit signs provided with emergency power in accordance with Chapter 27.
3.
Category c - Emergency power provided to means of egress lighting and exit signs which provides protection in the event of power failure to the site or building.
130. 
3412.6.16 Mixed occupancies. Where a building has two (2) or more occupancies that are not in the same occupancy classification, the separation between the mixed occupancies shall be evaluated in accordance with this Section. Where there is no separation between the mixed occupancies or the separation between mixed occupancies does not qualify for any of the categories indicated in Section 3412.6.16.1, the building shall be evaluated as indicated in Section 3412.6 and the value for mixed occupancies shall be zero. Under the categories and occupancies in Table 3410.6.16, determine the appropriate value and enter that value into Table 3412.7 under Safety Parameter, 3412.6.16,
Table 3412.6.16
Mixed Occupancy Valuesa
Occupancy
Categories
a
b
c
A-1, A-2, R
-10
0
10
A-3, A-4, B, E, F, M, S
-5
0
5
a.
For fire-resistance ratings between categories, the value shall be obtained by linear interpolation.
Mixed Occupancies, for fire safety and general safety. For buildings without mixed occupancies the value shall be zero.
131. 
3412.6.16.1 Categories. The categories for mixed occupancies are:
1.
Category a - Occupancies separated by minimum 1-hour fire barriers or minimum 1-hour horizontal assemblies, or both.
2.
Category b - Separations between occupancies in accordance with Section 508.4.
3.
Category c - Separations between occupancies having a fire-resistance rating of not less than twice that required by Section 508.3.3.
132. 
3412.6.17 Automatic sprinklers. Evaluate the ability to suppress a fire based on the installation of an automatic sprinkler system in accordance with Section 903.3.1.1. "Required sprinklers" shall be based on the requirements of this code. Under the categories and occupancies in Table 3412.6.7, determine the appropriate value and enter that value into Table 3412.7 under Safety Parameter 3412.6.17, Automatic Sprinklers, for fire safety, means of egress divided by two (2) and general safety.
Table 3412.6.17
Sprinkler System Values
Occupancy
Categories
a
b
c
d
e
f
A-1, A-3, F, M, R, S-1
-6
-3
0
2
4
6
A-2
-4
-2
0
1
2
4
A-4, B, E, S-2
-12
-6
0
3
6
12
133. 
3412.6.17.1 Categories. The categories for automatic sprinkler system protection are:
1.
Category a - Sprinklers are required throughout; sprinkler protection is not provided, or the sprinkler system design is not adequate for the hazard protected in accordance with Section 903.
2.
Category b - Sprinklers are required in a portion of the building; sprinkler protection is not provided, or the sprinkler system design is not adequate for the hazard protected in accordance with Section 903.
3.
Category c - Sprinklers are not required; none are provided.
4.
Category d - Sprinklers are required in a portion of the building; sprinklers are provided in such portion; the system is one which complied with the code at the time of installation and is maintained and supervised in accordance with Section 903.
5.
Category e - Sprinklers are required throughout; sprinklers are provided throughout in accordance with Chapter 9.
6.
Category f - Sprinklers are not required throughout; sprinklers are provided throughout in accordance with Chapter 9.
134. 
3412.6.18 Standpipes. Evaluate the ability to initiate attack on a fire by making a supply of water available readily through the installation of standpipes in accordance with Section 905. Required standpipes shall be based on the requirements of this code. Under the categories and occupancies in Table 3412.6.18, determine the appropriate value and enter that value into Table 3412.7 under Safety Parameter 3412.6.18, Standpipes, for fire safety, means of egress and general safety.
3412.6.18
Standpipe System Values
Occupancy
Categories
aa
b
c
d
A-1, A-3, F, M, R, S-1
-6
0
4
6
A-2
-4
0
2
4
A-4, B, E, S-2
-12
0
6
12
a.
This option cannot be taken if Category a or b in Section 3412.6.17 is used.
135. 
3412.6.18.1 Standpipe. The categories for standpipe systems are:
1.
Category a - Standpipes are required; standpipe is not provided, or the standpipe system design is not in compliance with Section 905.3.
2.
Category b - Standpipes are not required; none are provided.
3.
Category c - Standpipes are required; standpipes are provided in accordance with Section 905.
4.
Category d - Standpipes are not required; standpipes are provided in accordance with Section 905.
136. 
3412.6.19 Incidental accessory occupancy. Evaluate the protection of incidental accessory occupancies in accordance with Section 509.4.1. Do not include those where this code requires suppression throughout the buildings, including covered mall buildings, high-rise buildings, public garages and unlimited area buildings. Assign the lowest score from Table 3412.6.19 for the building or floor area being evaluated and enter that value into Table 3412.7 under Safety Parameter 3412.6.19, Incidental Accessory Occupancy, for fire safety, means of egress and general safety. If there are no specific occupancy areas in the building or floor area being evaluated, the value shall be zero.
Table 3412.6.19
Incidental Accessory Occupancy Area Valuesa
Protection Provided
Protection Required By Table 508.2.5
None
1 Hour
AFSS
AFSS with SP
1 Hour and AFSS
2 Hours
2 Hours and AFSS
2 Hours and AFSS
-4
-3
-2
-2
-1
-2
0
2 Hours, or 1 Hour and AFSS
-3
-2
-1
-1
0
0
0
1 Hour and AFSS
-3
-2
-1
-1
0
-1
0
1 Hour
-1
0
-1
0
0
0
0
1 Hour, or AFSS with SP
-1
0
-1
0
0
0
0
AFSS with SP
-1
-1
-1
0
0
-1
0
1 Hour or AFSS
-1
0
0
0
0
0
0
a.
AFSS = Automatic fire suppression system; SP = Smoke partitions (See Section 508.2.5).
Note: For Table 3412.7, see next page.
137. 
3412.7 Building score. After determining the appropriate date from Section 3412.6, enter those data in Table 3412.7 and total the building score.
138. 
3412.8 Safety scores. The values in Table 3412.8 are the required mandatory safety scores for the evaluation process listed in Section 3412.6.
Table 3412.8
Mandatory Safety Scoresa
Occupancy
Fire Safety
(MFS)
Means of Egress
(MME)
General Safety
(MGS)
A-1
16
27
27
A-2
19
30
30
A-3
18
29
29
A-4, E
23
34
34
B
24
34
34
F
20
30
30
M
19
36
36
R
17
34
34
S-1
15
25
25
S-2
23
33
33
a.
MFS = Mandatory Fire Safety;
MME = Mandatory Means of Egress;
MGS = Mandatory General Safety.
139. 
3412.8 Evaluation of building safety. The mandatory safety score in Table 3412.8 shall be subtracted from the building score in Table 3412.7 for each category. Where the final score for any category equals zero or more, the building is in compliance with the requirements of this Section for that category. Where the final score for any category is less than zero, the building is not in compliance with the requirements of this Section.
140. 
3412.9.1 Mixed occupancies. For mixed occupancies, the following provisions shall apply:
1.
Where the separation between mixed occupancies does not qualify for any category indicated in Section 3412.6.16, the mandatory safety scores for the occupancy with the lowest general safety score in Table 3412.8 shall be utilized (see Section 3412.6.)
2.
Where the separation between mixed occupancies qualifies for any category indicated inspection 3412.6.16, the mandatory safety scores for each occupancy shall be placed against the evaluation scores for the appropriate occupancy.
Table 3412.7
Summary Sheet — Building Code
Existing occupancy:
Proposed occupancy:
Year building was constructed:
Number of stories: _____ Height in feet:
Type of construction:
Area per floor:
Percentage of open perimeter increase: _____%
Completely suppressed:
Yes_____
No _____
Corridor wall rating: __________
Compart-mentation:
Yes _____
No _____
Required door closers:
Yes _____ No _____
Fire-resistance rating of vertical opening enclosures:
Type of HVAC system:
, serving number of floors:
Automatic fire detection:
Yes _____
No _____
Type and location: __________
Fire alarm system:
Yes _____
No _____
Type: __________
Smoke control:
Yes _____
No _____
Type: __________
Adequate exit routes:
Yes _____
No_____
Dead ends:
__________ Yes _____ No _____
Maximum exit access travel distance:
Elevator controls:
Yes _____ No _____
Means of egress emergency lighting:
Yes _____
No _____
Mixed occupancies: Yes _____ No _____
SAFETY PARA-METERS
FIRE SAFETY (FS)
MEANS OF EGRESS (ME)
GENERAL SAFETY (GS)
3412.6.1
Building Height
3412.6.2
Building Area
3412.6.3
Compartmentation
3412.6.4
Tenant and Dwelling Unit Separations
3412.6.5
Corridor Walls
3412.6.6
Vertical Openings
3412.6.7
HVAC Systems
3412.6.8
Automatic Fire Detection
3412.6.9
Fire Alarm Systems
3412.6.10
Smoke Control
****
3412.6.11
Means of Egress Capacity
****
3412.6.12
Dead Ends
****
3412.6.13
Maximum Exit Access Travel Distance
****
3412.6.14
Elevator Control
3412.6.15
Means of Egress Emergency Lighting
****
3412.6.16
Mixed Occupancies
****
3412.6.17
Automatic Sprinklers
÷ 2 =
3412.6.18
Standpipes
3412.6.19
Incidental Accessory Occupancy
Building score — total value
3412.6.1
Building Height
3412.6.2
Building Area
3412.6.3
Compartmentation
3412.6.4
Tenant and Dwelling Unit Separations
3412.6.5
Corridor Walls
3412.6.6
Vertical Openings
3412.6.7
HVAC Systems
3412.6.8
Automatic Fire Detection
3412.6.9
Fire Alarm Systems
3412.6.10
Smoke Control
****
3412.6.11
Means of Egress Capacity
****
3412.6.12
Dead Ends
****
3412.6.13
Maximum Exit Access Travel Distance
****
3412.6.14
Elevator Control
3412.6.15
Means of Egress Emergency Lighting
****
3412.6.16
Mixed Occupancies
****
3412.6.17
Automatic Sprinklers
÷2 =
3412.6.18
Standpipes
3412.6.19
Incidental Accessory Occupancy
Building score — total value
****
No applicable value to be inserted.
[R.O. 2008 § 6-35.18; Ord. No. 4076 § 1, 5-14-2007; Ord. No. 5310 § 1, 7-8-2013; Ord. No. 5690, 4-13-2020]
A. 
Chapter 35 of the International Building Code, 2015 Sixth Edition, is amended as set forth herein. Each Section, Subsection, or clause of the code that numerically corresponds to one of the following numbered provisions is hereby deleted where so noted or amended to read as set forth below. Each provision set out below without a corresponding Section, Subsection, or clause number is hereby enacted and added thereto.
B. 
This Chapter lists the standards that are referenced in various Sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the Section or Sections of this document that reference the standard. The application of the referenced standards shall be as specified in Section 102.4.
ICC — International Code Council, Inc.
500 New Jersey Ave., NW
6th Floor
Washington, DC 20001
Standard reference number
Title
Referenced in Code Section number
DELETE: IEBC-15
International Existing Building Code
DELETED
DELETE: IMC-15
International Mechanical Code
ADD: Mechanical Code
St. Louis County Mechanical Code
No changes made to referenced Code Sections
DELETE: IPC-15
International Plumbing Code
ADD: Plumbing Code
St. Louis County Plumbing Code
No changes made to referenced Code Sections
NFPA — National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
Standard reference number
Title
Referenced in Code Section number
ADD: 70-14
National Electrical Code/St. Louis County Electrical Code
No changes made to referenced Code Sections
ADD: 701-10
Standards Methods of Fire Tests for Flame-propagation of Textiles and Films
ADD: 3103.5