[Amended 9-24-2019 by Ord. No. 2019-30]
No building in which an automatic sprinkler system is required in accordance with § 22-78 and no building required to be supervised by 527 CMR or MGL c. 148 shall be connected to the municipal fire alarm system either directly or by another system accepted in accordance with NFPA Standard 72 without a permit for such installation or connection from the head of the Fire Department. Prior to the approval of any such permit, an acceptance and performance test shall be performed by the head of the Fire Department or his designee to ensure performance, reporting and verification requirements in accordance with NFPA Standard 72. The verification process must not take longer than 90 seconds from the time the alarm signal is received at the supervising station until the time that the retransmission of the verified alarm signal is initiated. [NFPA Standard 26.2.3.1(4)] Failure of such test must be remedied, and a re-test passed within seven business days, or no permit shall be issued. Any permit issued must be annually renewed with payment of the required fee. The fees for such permit and annual renewal shall be as provided in Chapter A110, Fee Schedule, of the City Code.