Exciting enhancements are coming soon to eCode360! Learn more 🡪
City of Fall River, MA
Bristol County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
[Amended 7-15-2008 by Ord. No. 2008-40]
For as long as the City retains ownership of the Watuppa Reservoir Company or any fractional interest therein, the care, custody, management and responsibilities of such interest shall reside with the Watuppa Water Board of the City.
It shall be unlawful for any person to injure any public conduit, pipe or reservoir connected with the City waterworks, or to break and enter such conduit, pipe or reservoir, or to, without license from the Watuppa Water Board, turn on or off or cause to be drawn off the water in any public water pipe, conduit or reservoir, or make any opening or connection with such pipe, conduit or reservoir, or remove the cover of any hydrant, except in case of fire or by order of the Chief of the Fire Department.
The Watuppa Water Board may refuse to turn on and may shut off the water from the premises of any person who shall violate or permit any other person to violate the provisions of this article.
The City water shall not be used through the hydrants or standpipes in the yards of persons engaged in manufacturing for any other purpose than that of extinguishing fires, or of being opened by the insurance inspector to ascertain if the water is on and the hydrants and pipes are in working order, unless the Watuppa Water Board allows the water to be otherwise used. All such hydrants and appliances shall be open to the inspection of the agents of the Water Board at all times.
A. 
All plumbing work, other than work done by the Watuppa Water Board, done in the construction and repair of all water pipes and fixtures by means of which water is distributed by the City, whether such pipes or fixtures belong to the City or not, shall be done by a plumber licensed by the commonwealth.
B. 
No person shall perform any labor in the nature of plumbing upon or in connection with any water pipes or fixtures by means of which water is furnished or distributed by the City, whether such pipes or fixtures are owned by the City or not, except under the authority of the license granted by the commonwealth under MGL c. 142.
[Added 8-22-2000 by Ord. No. 2000-20]
As used in §§ 74-256 through 74-258, unless the context indicates otherwise, the following words shall have the meanings indicated:
AIR GAP SEPARATION
The method of preventing backflow through the use of an unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture, or other device and the flood level rim of the receptacle. Air gap shall be at least double the diameter of the supply pipe measured vertically above the flood rim of the vessel; in no case less than one inch.
APPROVED BACKFLOW PREVENTION DEVICE or DEVICE
A method to prevent backflow approved by the department for use in the state.
ATMOSPHERIC VACUUM BREAKER
An approved backflow device used to prevent backsiphonage which is not designed for use under static line pressure.
BACKFLOW
The flow of water or other liquids, mixtures or substances into the distribution pipes of a potable water supply from any source other than the intended source.
BACKFLOW PREVENTER WITH INTERMEDIATE ATMOSPHERIC VENT
A device having two independently operating check valves separated by an intermediate chamber with a means for automatically venting it to the atmosphere, in which the check valves are force loaded to a normally closed position and the venting means is force loaded to a normally open position.
BACKPRESSURE
Pressure created by mechanical means or other means which causes water or other liquids or substances to flow or move in a direction opposite to that which is intended.
BACKSIPHONAGE
A form of backflow due to reduced or subatmospheric pressure within a water system.
BAROMETRIC LOOP
A loop of pipe rising at least 35 feet, at its topmost point, above the highest fixture it supplies.
CERTIFICATION EXAMINATION
An examination approved by the department for the purpose of testing competence in all areas of cross-connection control and backflow prevention device testing.
CERTIFIED BACKFLOW PREVENTION DEVICE TESTER
An individual who holds a valid state backflow prevention device tester's certificate issued by the department.
CONTAMINANT
Any physical, chemical, biological or radiological substance or matter in water.
CROSS-CONNECTION
Any actual or potential connection between a distribution pipe or potable water from a public water system and any waste pipe, soil pipe, sewer, drain, or other unapproved source. Without limiting the generality of the foregoing, the term "cross-connection" shall also include any bypass arrangements, jumper connections, removal section, swivel or changeover connection and other temporary or permanent connection through which backflow can or may occur.
DESIGN DATA SHEET
Plans for each installation of a reduced pressure backflow preventer or double check valve assembly and anti-siphon pressure-type vacuum breakers or for each change to any such device already installed, describing and showing the details of the specific installation.
DOUBLE CHECK VALVE ASSEMBLY
A backflow prevention device which incorporates an assembly of check values with shut-off valves at each end and appurtenances for testing.
HEALTH HAZARD
An actual or potential threat of contamination to the potable water in a public water system which, in the opinion of the department or its designee, would endanger health.
IN-PLANT PROTECTION
The location of approved backflow prevention devices in a manner which provides simultaneous protection of the public water system and the potable water system within the premises.
INSPECTION
An on-site inspection and survey by a qualified individual to determine the existence and location of cross-connections and/or the physical examination and testing of an installed backflow prevention device to verify that the backflow prevention device is functioning properly.
INSPECTION AND MAINTENANCE REPORT FORM
A report form designated by the department which is to be used by certified testers to record all pertinent testing information.
OWNER
Any person maintaining a cross-connection installation or owning or occupying premises on which cross-connections can or do exist.
OWNER'S AGENT
Any person or body designated by the owner to act as his representative.
POTABLE WATER
Water from any source which has been approved for human consumption by the department.
PRESSURE VACUUM BREAKER
An approved backflow prevention device designed to prevent only backsiphonage and which is designed for use under static line pressure; example: lawn sprinkler.
REDUCED PRESSURE BACKFLOW PREVENTER
A. 
An approved backflow prevention device incorporating:
(1) 
Two or more check valves;
(2) 
An automatically operating differential relief valve located between the two checks;
(3) 
Two shut-off valves; and
(4) 
Necessary appurtenances for testing.
B. 
The reduced pressure backflow preventer is designed to operate so that:
(1) 
The pressure in the zone between the two checks valves is maintained at a value less than the pressure on the public water system side of the device;
(2) 
At cessation of normal flow, the pressure in the zone between the two check valves is maintained at a value less than the pressure on the public water system side of the device; and
(3) 
In the case of leakage of either check valves, the differential relief valve shall operate to maintain reduced pressure in the zone by discharging to the atmosphere.
TESTING
All backflow devices in the City shall have test fittings on all backflows set up for testing purposes, which is one-quarter-inch threaded male hose connection.
[Added 8-22-2000 by Ord. No. 2000-20; amended 7-15-2008 by Ord. No. 2008-40]
A. 
Purpose. The department's purpose in establishing a comprehensive distribution protection program is to prevent the contamination of drinking water to the last free-flowing outlets or consumer's tap. For this reason, the department strongly advocates the elimination of all cross-connections. The installation of backflow prevention devices does not eliminate a cross-connection. The installation of backflow prevention devices is a solution when replumbing or repiping is not feasible. All cross-connection protection devices shall be approved and permitted in accordance with 310 CMR 22.22, as set forth at 310 CMR 22.22(4) and 310 CMR 22.22(7)(b). Each owner of such device shall apply for and be issued a permit by the department.[1]
[1]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions).
B. 
Maintenance of a cross-connection.
(1) 
No physical cross-connection shall be maintained between the distribution system of a public water system, the water of which is being used for drinking, domestic or culinary purposes, and the distribution system of any water source not approved by the department as being of safe, sanitary quality, unless said connection has been approved by the department and a permit has been issued by the department in accordance with 310 CMR 22.22.
(2) 
Subject to applicable laws and regulations, public water systems shall have the authority to terminate any water service connection to any facility where cross-connections are found to be in noncompliance with 310 CMR 22.22. The supplier shall deny water service to any premises where cross-connections exist until corrective action is taken. If necessary, water service shall be disconnected for failure to test or maintain backflow prevention devices in a manner acceptable to the supplier. If it is found that the backflow prevention device has been removed or bypassed or otherwise rendered ineffective, water service shall be discontinued unless corrections are made immediately.
(3) 
The public water system shall establish a time for completion of necessary corrections or removal of actual or potential cross-connections, taking into consideration the degree of hazard involved and the time required to obtain and to install the needed equipment. The public water system shall use every means at its disposal to obtain voluntary compliance. However, if proper protection has not been provided after a reasonable period of time (following legal notification and subject to applicable laws and regulation), the public water system shall physically separate the public water supply from the on-site piping system in such a manner that the two systems cannot again be connected by an unauthorized person.
C. 
Owners' responsibilities. The owner of any cross-connection protection device shall:
(1) 
Apply for, obtain and comply with all necessary approvals and permits from the public water system and/or the department for the maintenance of cross-connections as specified in 310 CMR 22.22, including the permit issued by the department for each cross-connection protection device;
(2) 
Have suitable arrangements made so that the inspections can be made during regular business hours;
(3) 
Maintain a spare parts kit and any special tools required for the removal and reassembly of devices;
(4) 
Provide the necessary labor for inspection and testing by the certified backflow prevention device testers;
(5) 
Overhaul, repair or replace within 14 days of the initial inspection date, and retest pursuant to 310 CMR 22.22(13)(e), any device which fails a test or is found defective;[2]
[2]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions).
(6) 
Submit copies of the inspection and maintenance report form as required by the public water system;
(7) 
Maintain on the premises complete records on all devices for the file of said devices, including as-built plans and design data sheets; maintain for seven years the inspection and maintenance report forms for tests conducted by the certified backflow prevention device testers;
(8) 
Make certain that the cross-connection protection device is tested as specified at 310 CMR 22.22(13) or as required by the public water system.[3]
[3]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions).
D. 
Approval and permit required.
(1) 
Installation approval.
(a) 
No person shall install or remove or contract with another person for the installation or removal of any reduced pressure backflow preventer or assembly required by 310 CMR 22.22 unless a design data sheet with plans showing the method of protection of the public water distribution system has been approved by the Watuppa Water Board for the installation of such device.
(b) 
All persons shall obtain approval from the local Plumbing Inspector and the head of the local Fire Department, to the extent required by the State Plumbing Code, 248 CMR 10.09, or MGL c. 148, § 27A, for the initial installation or retrofit for any change in the installation of any air gap separation with tank and pump arrangement, reduced pressure backflow preventer or double check valve assembly.[4]
[4]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions).
(c) 
Prior to the installation of any pressure or atmospheric vacuum breaker backflow preventer with intermediate atmospheric vent, or barometric loop, the plans and specifications for the plumbing work must receive a permit issued pursuant to 248 CMR 10.09 by the local water inspector. For these devices, a letter of approval will be issued under 248 CMR 10.09 and shall constitute installation approval pursuant to 310 CMR 22.22.[5]
[5]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions).
(d) 
All design data sheets and plans for the installation of backflow prevention devices shall be reviewed by a certified cross-connection surveyor as of December 31, 1998.
(2) 
Permit requirement.
(a) 
Any person owning an approved cross-connection protection device shall apply for and obtain a permit by the department for each reduced pressure backflow preventer and double check valve assembly installed on the premises. Departments of the commonwealth and owners of cross-connection protection devices located in delegated public water systems as specified at 310 CMR 22.22(3) shall be exempt from payment of the department's annual permit fee.[6]
[6]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions).
(b) 
The department reserves the right to revoke or suspend any conditional approval and/or permit for cause.
(3) 
Rights of the department. The department reserves the right to revoke any approval or permit for any installation or change in installation of any backflow prevention device which is found to be in noncompliance with 310 CMR 22.22.
E. 
Location of devices.
(1) 
The location of each approved backflow prevention device, with respect to the plumbing on the premises and the service connection to the premises, shall be based upon the degree of existing or potentially existing health hazard and shall conform to the following specific requirements:
(a) 
Approved backflow prevention devices shall be located so that protection of all cross-connections is achieved with a minimum number of devices; and
(b) 
Approved backflow prevention devices shall be located so as to provide in-plant protection;
(c) 
The following types of facilities have been determined to present high health hazard conditions and in-plant protection shall be supplemented by installation of a reduced pressure backflow preventer or an air gap separation at the meter or property line unless otherwise specified by the department or its designee:
[1] 
Nuclear reactors or other facilities where radioactive materials are used;
[2] 
Sewage treatment plants and sewage pumping stations;
[3] 
Piers, docks, marinas, shipyards;
[4] 
Chemical plants;
[5] 
Metal plating industries;
[6] 
Hospitals, mortuaries, medical clinics, dental offices and clinics;
[7] 
Laboratories, except when the department has made a specific determination that no health hazard exists on the premises; and/or
[8] 
Other types of facilities as determined in writing by the department or its designee.
(2) 
If, upon request by the owner of the premises or upon its own initiative, the department or its designee determines that it is unreasonable to locate all cross-connections within the premises, or for economic reasons, then:
(a) 
The public water supply distribution system shall be protected by installation of a reduced pressure backflow preventer or an air gap separation at the meter or property line; and
(b) 
The owner of the premises shall provide a safe alternative supply of potable water, well marked and labeled to all domestic water fixtures on the premises.
F. 
(Reserved)
G. 
Approval of devices for use in the state.
(1) 
Types and models of atmospheric and pressure vacuum breakers and types and model of backflow preventers with intermediate atmospheric vent which may be used in the state for certain low-hazard applications referred to in the State Plumbing Code shall be those meeting the requirements of and approved by, the Board of State Examiners of Plumbers and Gas Fitters. Except as further restricted by the department as provided in 310 CMR 22.22(4), all other backflow prevention devices meeting the requirements of, and approved by, the Board of State Examiners of Plumbers and Gas Fitters may be used in the state.[7]
[7]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions).
(2) 
Only types and models of reduced pressure backflow preventers, double check valve assemblies, and manufactured air gap separation devices which have been specifically evaluated and approved by the department, and included on the list of approved backflow prevention devices maintained by the department, may be used in cross-connection control in the state.
H. 
Installation requirements.
(1) 
Reduced pressure backflow preventers. Reduced pressure backflow preventers may be used to protect against backflow caused by back pressure or backsiphonage and to protect a public water supply system from substances which are hazardous to health only when they are installed in the following manner:
(a) 
For devices installed as in-plant protection, the reduced pressure backflow preventer shall be installed on the owner's side of the water meter on the potable water supply line.
(b) 
Before installing a reduced pressure backflow preventer, all pipelines shall be thoroughly flushed to remove foreign material.
(c) 
Drinking and domestic water lines, lines for safety showers, and lines for eye wash units must be taken off the upstream side of reduced pressure backflow preventers for devices installed as in-plant protection.
(d) 
The reduced pressure backflow preventer shall be located so as to permit easy access and provide adequate and convenient space for maintenance, inspection and testing.
(e) 
The owner of the device shall be able to shut down water lines after reasonable notice during normal business hours to permit necessary testing and maintenance of the device, provided that if it is not possible to meet this requirement a bypass line equipped with an approved type reduced pressure backflow preventer shall be installed.
(f) 
The reduced pressure backflow preventer and shut-off valves must be installed in a horizontal alignment between three feet and four feet from the floor to the bottom of the device and a minimum of 12 inches from any wall, unless the device is approved by the department for vertical installations.
(g) 
Tightly closing valves must be installed in each end of the device and be immediately accessible unless otherwise approved by the department or its designee.
(h) 
The device must be protected from freezing, flooding, and mechanical damage.
(i) 
If the device is to be installed on a hot water line, a device approved for use at the elevated temperature must be used.
(j) 
If a drain is to be provided for the relief valve port, there must be an approved air gap separation between the port and drain line. To be approved, the air gap must be at least twice the internal diameter of the discharge line.
(k) 
Pit installation shall be approved only as provided in 310 CMR 22.22(11)(f).[8]
[8]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions).
(l) 
All water lines shall be color coded according to the State Plumbing Code, except that water filtration plants, pumping stations, sewage treatment plants and sewage pumping stations shall label all water lines in lieu of color coding.
(2) 
Double check valve assemblies. Double check valve assemblies may be used to protect against backflow caused by backpressure or backsiphonage and to protect a public water supply system from substances which may be objectionable, but not hazardous to health, only if they are installed in the following manner:
(a) 
Drinking and domestic water lines, lines for safety showers, and lines for eye wash units must be taken off the upstream side of the double check valve assembly for devices installed as in-plant protection.
(b) 
The double check valve assembly shall be installed with adequate space to facilitate maintenance inspection and testing.
(c) 
The double check valve must be installed horizontally and the top of the double check valve assembly must be between 30 inches and 52 inches from the floor to the bottom of the device and a minimum of 12 inches from any wall, unless otherwise approved by the department.
(d) 
If a water meter is not provided on the upstream side of an approved swing-type double check valve assembly, a three- to five-foot spacer must be installed between the check valves.
(e) 
Tightly closing valves must be installed at each end of the device and be immediately accessible unless otherwise approved by the department or its designee.
(f) 
Double check valve assemblies must be provided with suitable connections and appurtenances for testing.
(g) 
The device must be protected against flooding, freezing and mechanical damage.
(h) 
Pit installations will be approved only as provided in 310 CMR 22.22(11)(f).[9]
[9]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions).
(3) 
Vacuum breakers. Vacuum breakers shall not be used to protect against backflow due to back pressure and shall not be installed as protection for high-hazard conditions as determined by the department or its designee. Vacuum breakers may be used for low health hazards only if they are installed in the following manner:
(a) 
Vacuum breakers must be installed at least six inches above the flood level rim of the fixture they serve. Tightly closing valves must be installed on both sides of the device.
(b) 
Atmospheric vacuum breakers must be installed downstream of the last shut-off servicing the fixture or equipment.
(c) 
Vacuum breakers must not be installed in locations where the device is subject to corrosive fumes, dust or grit.
(d) 
Vacuum breakers must be protected against flooding, freezing and mechanical damage.
(e) 
Atmospheric vacuum breakers shall not be used under conditions of static line pressure. Pressure vacuum breakers may be used under conditions of static line pressure.
(4) 
Barometric loops. Barometric loops may be used only to protect against backsiphonage, and shall be approved for use only when no health hazard exists and when backpressure is not possible.
(5) 
Air gap separation. Air gap separation may be used to protect against backflow caused by back pressure or backsiphonage and to protect a public water supply system from substances which are hazardous to health and shall be approved for use only when installed in the following manner: The minimum air gap must be twice the diameter of the effective opening of the inlet pipe above the flood level rim of the receptacle being fed, but in no case shall it be less than one inch.
(6) 
Pit installation. No devices shall be installed in pits except as specifically approved by the Fire Department, its designee or the public water system in cases of unique circumstances, and pits must comply with all OSHA standards, where applicable, for work in confined spaces and then only as follows:
(a) 
The pit interior shall be a minimum of 10 feet long, six feet wide, and must have a clear height 6 1/2 feet high;
(b) 
The pit must be watertight;
(c) 
The pit opening and manhole cover must be at least 30 inches in diameter;
(d) 
The foothold inserts must be of steel, aluminum or other material approved by the department, must be a maximum of 12 inches apart and must be installed so that the top foothold is within 12 inches of the manhole cover and the bottom foothold is within 12 inches of the pit floor.
(e) 
An adequate drain must be installed, and the drain line shall not be connected to a sewer;
(f) 
The pit floor shall be pitched to the drain; and
(g) 
If built in a roadway, the top of the pit must be adequately reinforced.
I. 
Inspection, surveying, testing and overhauling of devices.
(1) 
All cross-connection surveys and/or backflow prevention device tests shall be conducted by a person who is a state-certified cross-connection surveyor. All backflow prevention device tests shall be conducted by a certified backflow prevention device tester in accordance with 310 CMR 22.22. A person holding a combination certification may conduct a cross-connection survey and/or backflow prevention test.
(2) 
Within 14 calendar days after the installation of devices in accordance with plans reviewed and approved by the reviewing authority, the owner or owner's agent shall notify the public water system to arrange for the inspection of the installation.
(3) 
Reduced pressure backflow preventers, double check valve assemblies, pressure -type vacuum breakers and air gap separations may be inspected and tested by the department, its designee or the public water system at any time.
(4) 
The public water system is responsible to ensure that each reduced pressure backflow preventer will be inspected semiannually in accordance with the public water system's approved cross-connection program plan, as provided for in 310 CMR 22.22(3)(b). If the supply is used less than six months of the year, these devices shall be inspected and tested once each year. Each double check valve assembly shall be tested annually. Each test shall be conducted by a certified backflow prevention device tester and recorded on the department's inspection and maintenance report form. Copies of the inspection forms shall be submitted to the public water system and the owner.
(5) 
Devices which fail the test or are found to be defective shall be overhauled, repaired, or replaced and retested within 14 calendar days of the failure or from the discovery of the defect. The repair work must be done by a plumber licensed by the state to the extent required by 248 CMR 2.04(3). No person shall overhaul, repair, or replace a device on a fire system without approval from the head of the local Fire Department pursuant to MGL c. 148, § 27A.
(6) 
No two routine tests for reduced pressure backflow preventers required by 310 CMR 22.22 shall be conducted within five months of each other without the written approval of the department, its designee or the public water system.
(7) 
The owner or owner's agent must maintain on the premises a spare parts kit and any special tools required for removal and reassembly of devices which are to be tested. The presence of these materials must be recorded on the inspection and maintenance report form.
(8) 
The owner or owner's agent must provide labor on the premises as necessary to allow inspection and testing of devices by the department, the supplier of water, or certified backflow prevention device testers.
(9) 
The owner or owner's agent shall notify the public water system in writing, no later than 30 days prior to the removal from service of any permitted device, and such notification shall include the reason for removal and must indicate if the cross-connection has been eliminated.
(10) 
The owner or owner's agent shall notify the public water system in writing no later than 30 days prior to a change in ownership. Notification must include, at a minimum, the name and address of the new owner as well as documentation with proof of change in ownership.
(11) 
If the public water system deems necessary, it may test a device more frequently to ensure proper cross-connection control.
J. 
Right of entry. All owners or operators of private homes, commercial, industrial or institutional premises served by a public water supply system shall authorize agents and employees of the Watuppa Water Board, upon presentation of their credentials, to enter their premises without a warrant for the purpose or inspection and surveying their water systems for cross-connections and assuring compliance with 310 CMR 22.22, whether or not the Watuppa Water Board has evidence that the system is in violation of an applicable legal requirement.
K. 
Enforcement.
(1) 
Whoever maintains a cross-connection without a permit, or after revocation of the permit to maintain such connection, and whoever maintains a cross-connection without installing the appropriate backflow prevention device required by 310 CMR 22.22 and by the reviewing authority shall be:
(a) 
Punished by a fine of not more than $25,000 for each day such violation occurs or continues, or by imprisonment for not more than one year, or both such fine and imprisonment; or
(b) 
Subject to a civil penalty not to exceed $25,000 per day for each day that each violation occurs or continues.
(2) 
Any violation of 310 CMR 22.22 shall be subject to the administrative penalty provisions of 310 CMR 5.00.
(3) 
Upon due notice to the person maintaining the connection, the department may revoke any permit whenever in the opinion of the department the cross-connection or the maintenance thereof no longer complies with 310 CMR 22.00.
(4) 
In order to ensure the delivery of a fit and pure water supply, the department may issue a written order, pursuant to MGL c. 111, § 160A, requiring a supplier of public water to cease supplying water to any premises if one or more cross-connections are maintained in violation of the requirements of 310 CMR 22.22, or requiring any person to take such actions as are reasonable and necessary to prevent or to eliminate cross-connections.[10]
[10]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions).
Key:
AG
=
Air Gap Separation
AVB
=
Atmospheric Vacuum Breaker
BFPAV
=
Backflow Preventer with Intermediate Atmospheric Vent
DCVA
=
Double Check Valve Assembly
RPBP
=
Reduced Pressure Backflow Preventer
Acceptable Types of Backflow Preventers
Type of Hazard on Premises
AG
RPBP
DCVA
AVB
BFPAV
Comments
1.
Sewage treatment plant
X
X
2.
Sewage pumping station
X
X
3.
Food processing
X
X
X*
*If no health hazard exists
4.
Laboratories
X
X
X*
*If no health hazard exists
5.
Sinks with hose threads on inlets
X
X
X
6.
Hospitals, mortuaries, clinics
X
X
7.
Plating facilities
X
X
8.
Irrigation systems**
X
X
X*
Each case should be evaluated separately
*If no backpressure is possible
**Pressure vacuum breakers can be installed if no health hazard exists and backpressure is not possible.
9.
Systems of equipment using radioactive material
X
X
10.
Submerged inlets
X
X
X*
*If no health hazard exists and no back pressure in possible
11.
Dockside facilities
X
X
12.
Valved outlets or fixtures with hose attachments
X
X
X*
X**
Each case should be evaluated individually
*If no health hazard exists
**If no health hazard exists and no backpressure is possible
13.
Commercial laundries and dry cleaners
X
X
14.
Commercial dish-washing machines
X
X
X*
*If no health hazard exists
15.
High- and low-pressure boilers
X
X
If chemicals are added
16.
Low-pressure heating boilers
X
Residential and small commercial, having no chemicals added
17.
Photo processing equipment
X
X
18.
Reservoirs — Cooling tower recirculating systems
X
X
19a.
Fire protection systems: any system with a pumper connection within 1,700 feet of an unapproved supply available and accessible for Fire Department use, unless otherwise indicated in writing by the local Fire Department(s) pre-fire plan of the facility
X
X
X
19b.
Any system with a pumper connection serviced by a fire department(s) that use(s) or does not specifically prohibit, in accordance with DEP policies and guidelines, the use of corrosion inhibitors or chemical additives in the tanks of their fire trucks, or where the water purveyor, based on a written statement from the local fire department(s), cannot be assured of the potability of the input to the pumper connection
X
X
X
19c.
Any system with a pumper connection that normally requires the use of chemical extinguishing agents, unless otherwise indicated in writing by the Fire Department(s)
X
X
19d.
Any system maintained at a facility with unusually complex piping systems, unless otherwise indicated in writing by the Fire Department(s)
X
X
19e.
Any system which incorporates storage tanks or fire pumps taking suction from covered tanks or reservoirs
X
X
19f.
Any system incorporating connections to chemical extinguishing agents, antifreeze, or auxiliary water suppliers
X
X
20.
Solar energy systems
X
X
X*
Residential and small commercial having no chemicals or only USP Glycenne added to water
21.
Single-jacketed heat exchangers*
X
X
*Each case should be evaluated individually
[1]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions).