Exciting enhancements are coming soon to eCode360! Learn more 🡪
Borough of Emmaus, PA
Lehigh County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[Ord. 1141, 9/19/2016]
The following points of inspection shall be the basis for initial and periodic fire safety inspections.
[Ord. 1141, 9/19/2016]
1. 
Maintenance. Equipment, systems, devices and safeguards required by this code or a previous regulation or code under which the structure or premises was constructed, altered or repaired shall be maintained in good working order. No owner, operator or occupant shall cause any service, facility, equipment or utility which is required under this section to be removed from or shut off from or discontinued for any occupied premises, except for such temporary interruption as necessary while repairs or alterations are in progress. The requirements of this code are not intended to provide the basis for removal or abrogation of fire protection and safety systems and devices in existing structures. Except as otherwise specified herein, the owner or the owner's designated agent shall be responsible for the maintenance of buildings, structures and premises.
[Ord. 1141, 9/19/2016]
1. 
Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table 403.1.
Table 403.1. Fire Protection System Maintenance Standards
System
Standard
Portable fire extinguishers
NFPA 10
Carbon dioxide fire-extinguishing systems
NFPA 12
Halon 1301 fire-extinguishing systems
NFPA 12A
Dry-chemical extinguishing systems
NFPA 17
Wet-chemical extinguishing systems
NFPA 17A
Water-based fire protection systems
NFPA 25
Fire alarm systems
NFPA 72
Water-mist systems
NFPA 750
Clean-agent extinguishing systems
NFPA 2001
[Ord. 1141, 9/19/2016]
Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the Fire Code Official upon request.
[Ord. 1141, 9/19/2016]
Any device that has the physical appearance of life safety or fire protection equipment but that does not perform that life safety or fire protection function shall be prohibited.
[Ord. 1141, 9/19/2016]
A safe, continuous and unobstructed path of travel shall be provided from any point in a building or structure to the public way. Means of egress shall comply with the International Fire Code.
[Ord. 1141, 9/19/2016]
Exit signs shall be kept illuminated at all times of occupancy. Emergency lighting shall be kept operable at all times.
[Ord. 1141, 9/19/2016]
Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the Fire Code Official.
[Ord. 1141, 9/19/2016]
Fire escapes shall be kept in working order and free from obstructions to immediate use at all times.
[Ord. 1141, 9/19/2016]
Fire escapes shall be kept free of corrosion, rust and scale, and shall be kept coated with paint or other approved surface coating.
[Ord. 1141, 9/19/2016]
An approved load test shall be completed at five-year intervals. The load test shall be designed to prove that the fire escape can support the dead load plus a minimum of 100 pounds per square foot.
[Ord. 1141, 9/19/2016]
1. 
Fire-Resistance-Rated Assemblies. The required fire-resistance rating of fire-resistance-rated walls, fire stops, shaft enclosures, partitions and floors shall be maintained.
2. 
Opening Protectives. Required opening protectives shall be maintained in an operative condition. All fire and smoke-stop doors shall be maintained in operable condition. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable.
[Ord. 1141, 9/19/2016]
1. 
Electrical facilities, panelboards, cabinets, wiring, and other such components shall meet the code guidelines set forth below:
A. 
Abatement of Electrical Hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used.
B. 
Illumination. Illumination shall be provided for service equipment areas, motor control centers and electrical panelboards.
C. 
Working Space and Clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1,981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.
Exception: where other dimensions are required or allowed by NFPA 70.
[Ord. 1141, 9/19/2016]
Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating "electrical room" or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident.
[Ord. 1141, 9/19/2016]
1. 
Multiplug adapters and power taps, such as cube adapters, unfused plug strips or any other device not complying with NFPA 70 shall be prohibited.
A. 
Power Tap Design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL1363.
B. 
Power Supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
C. 
Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors, or under doors or floor coverings, or be subject to environmental or physical damage.
[Ord. 1141, 9/19/2016]
1. 
Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. Extension cords shall not be longer than 12 feet unless in use as a temporary power supply.
A. 
Power Supply. Extension cords shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved multiplug extension cords, shall serve only one portable appliance.
B. 
Ampacity. The ampacity of the extension cords shall not be less than the rated capacity of the portable appliance supplied by the cord.
C. 
Maintenance. Extension cords shall be maintained in good condition without splices, deterioration or damage.
D. 
Grounding. Extension cords shall be grounded when serving grounded portable appliances.
[Ord. 1141, 9/19/2016]
Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Panelboards shall have all openings closed in an approved manner per the NEC.
[Ord. 1141, 9/19/2016]
Electrical motors shall be maintained free from excessive accumulations of oil, dirt, waste and debris.
[Ord. 1141, 9/19/2016]
Temporary wiring for electrical power and lighting installations is allowed for a period not to exceed 90 days. Temporary wiring methods shall meet the applicable provisions of NFPA 70.
Exception: Temporary wiring for electrical power and lighting installations is allowed during periods of construction, remodeling, repair or demolition of buildings, structures, equipment or similar activities.
[Ord. 1141, 9/19/2016]
Where smoking is permitted, suitable noncombustible ashtrays or match receivers shall be provided on each table and at other appropriate locations.
[Ord. 1141, 9/19/2016]
1. 
Storage shall be in accordance with § 7-421, Subsection 1A through F, below.
A. 
General Storage. Storage of material in buildings shall be orderly and stacks shall be stable. Storage of combustible materials shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. Allowing storage next to or on top of furnaces, boilers, water heaters, chimneys and vents, generators, or other heat-producing appliances is prohibited.
B. 
Ceiling Clearance. Storage shall be maintained two feet or more below the ceiling in nonsprinklered areas or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings.
Exception: Storage against walls may be permitted to exceed the height requirement if approved by the Code Official.
Exception: Sprinkler systems requiring a larger clearance from storage to sprinkler head deflectors.
C. 
Means of Egress. Combustible materials shall not be stored in exits or enclosures for stairways or ramps.
D. 
Equipment Rooms. Combustible materials shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms unless specifically authorized by the Fire Code Official.
E. 
Outside Storage. Storage in the open shall not exceed 20 feet in height and shall not be located where a fire in the storage will cause an immediate hazard to a structure, or where the storage is in a location that will increase the risk of fire spread between buildings.
F. 
Inside Storage. Storage shall be confined to approved storage rooms or areas.
Exception: Incidental storage for use in that room or space.
Exception: Storage that is acceptable to the Fire Code Official.
[Ord. 1141, 9/19/2016]
1. 
Commercial cooking systems shall be operated and maintained in accordance with this Part, § 7-422, Subsection 1A through G, below.
A. 
Ventilation System. The ventilation system in connection with hoods shall be operated at the required rate of air movement, and classified grease filters shall be in place when equipment under a kitchen grease hood is used.
B. 
Grease Extractors. Where grease extractors are installed, they shall be operated when the commercial-type cooking equipment is used.
C. 
Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals as required by § 7-422, Subsection 1D through F, in this Part.
D. 
Inspection. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be inspected at intervals specified in Table 422.1.D. or as approved by the Fire Code. Official Inspections shall be completed by qualified individuals.
Table 422.1.D. Commercial Cooking System Inspection Frequency
Type of Cooking Operations
Frequency of Inspection
High-volume cooking operations such as 24-hour cooking, charbroiling or wok cooking
3 months
Low-volume cooking operations such as places of religious worship, seasonal businesses and senior centers
12 months
Cooking operations utilizing solid-fuel-burning cooking appliances
1 month
All other cooking operations
6 months
E. 
Grease Accumulation. If during the inspection it is found that hoods, grease-removal devices, fans, ducts or other appurtenances have an accumulation of grease, such components shall be cleaned.
F. 
Records. Records for inspections shall state the individual and company performing the inspection, a description of the inspection and when the inspection took place. Records for cleanings shall state the individual and company performing the cleaning and when the cleaning took place. Such records shall be completed after each inspection or cleaning, shall be maintained on the premises for a minimum of three years and shall be copied to the Fire Code Official upon request.
G. 
Extinguishing System Service. Automatic fire-extinguishing systems protecting commercial cooking systems shall be serviced as required in this Part, § 7-403, Table 403.1.
[Ord. 1141, 9/19/2016]
Chapter 4 of the 2012 International Fire Code is adopted.
[Ord. 1141, 9/19/2016]
It shall be unlawful to deliberately or through negligence set fire to or cause the burning of combustible material in such a manner as to endanger the safety of persons or property.
[Ord. 1141, 9/19/2016]
Overcrowding or admittance of any person beyond the approved capacity of a building or a portion thereof shall not be allowed. The Fire Code Official, upon finding any overcrowding conditions or obstructions in aisles, passageways or other means of egress, or upon finding any condition which constitutes a life safety hazard, shall be authorized to cause the event to be stopped until such condition or obstruction is corrected.
[Ord. 1141, 9/19/2016]
The Borough Manager shall develop rules and regulations for the development of the Fire Prevention Program with input from all Borough departments, including the Fire Department, having direct knowledge of fire inspections matters. The Fire Inspector shall create an inspection checklist to assure compliance with this Part.