Exciting enhancements are coming soon to eCode360! Learn more 🡪
St. Charles County, MO
 
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[1]
Editor’s Note: Former Article VII, Private Sewage Disposal Code, containing Section 500.080, was repealed 7-5-2017 by § 7 of Ord. No. 17-061. See now Section 500.300.
[Ord. No. 17-061 § 7, 7-5-2017; Ord. No. 23-102, 11-13-2023]
St. Charles County hereby adopts the 2020 National Fire Protection Association 70 — National Electric Code, a copy of which shall be deposited in the Office of the County Registrar with this ordinance, with the following amendments by additions, insertions, deletions and changes so that such Sections and Subsections read as follows:
(ARTICLE 90 INTRODUCTION)
90.1(D) Administration of this code. The administration of this code shall be in accordance with Appendix K "Administrative Provisions" of the Building Code adopted in Section 500.100.
(CHAPTER 2 WIRING AND PROTECTION)
(ARTICLE 210 BRANCH CIRCUITS)
210.8(A) Dwelling Units. All 125-volt through 250-volt receptacles installed in the locations specified in 210.8(A)(1) through (A)(11) and supplied by single-phase branch circuits rated one hundred fifty (150) volts or less to ground shall have ground-fault circuit-interrupter protection for personnel.
(1)
Bathrooms.
(2)
Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use.
Exception to (2): For one- and two-family dwellings and townhouses, garage door opener receptacles not installed in a readily accessible location.
(3)
Outdoors.
Exception to (3): Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment shall be permitted to be installed in accordance with 426.28 or 427.22, as applicable.
(4)
Crawl spaces — at or below grade level.
(5)
Basements.
Exception to (5): A receptacle supplying only a permanently installed fire alarm or burglar alarm system shall not be required to have ground-fault circuit-interrupter protection.
Informational Note: See 760.41(B) and 760.121(B) for power supply requirements for fire alarm systems.
Receptacles installed under the exception to 210.8(A)(5) shall not be considered as meeting the requirements of 210.52(G).
(6)
Kitchens — where the receptacles are installed to serve the countertop surfaces.
(7)
Sinks — where receptacles are installed within one and eight-tenths (1.8) m (6 ft) from the top inside edge of the bowl of the sink.
(8)
Boathouses.
(9)
Bathtubs or shower stalls — where receptacles are installed within eight-tenths (1.8) m (6 ft) of the outside edge of the bathtub or shower stall.
(10)
Laundry areas.
Exception to (1) through (3), (5) through (8), and (10): Listed locking support and mounting receptacles utilized in combination with compatible attachment fittings installed for the purpose of serving a ceiling luminaire or ceiling fan shall not be required to be ground-fault circuit-interrupter protected. If a general-purpose convenience receptacle is integral to the ceiling luminaire or ceiling fan, GFCI protection shall be provided.
(11)
Indoor damp and wet locations.
210.12(A) Dwelling Units. All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, or similar rooms or areas shall be protected by any of the means described in 210.12(A)(1) through (6):
Exception: For one- and two-family dwellings and townhouses, protection is not required in laundry areas and similar rooms or areas.
(1)
A listed combination-type arc-fault circuit interrupter installed to provide protection of the entire branch circuit.
(2)
A listed branch/feeder-type AFCI installed at the origin of the branch-circuit in combination with a listed outlet branch-circuit-type arc-fault circuit interrupter installed at the first outlet box on the branch circuit. The first outlet box in the branch circuit shall be marked to indicate that it is the first outlet of the circuit.
(3)
A listed supplemental arc protection circuit breaker installed at the origin of the branch circuit in combination with a listed outlet branch-circuit type arc-fault circuit interrupter installed at the first outlet box on the branch circuit where all of the following conditions are met:
a.
The branch-circuit wiring shall be continuous from the branch-circuit overcurrent device to the outlet branch-circuit arc-fault circuit interrupter.
b.
The maximum length of the branch-circuit wiring from the branch-circuit overcurrent device to the first outlet shall not exceed fifteen and two-tenths (15.2) m (50 ft) for a 14 AWG conductor or twenty-one and three-tenths (21.3) m (70 ft) for a 12 AWG conductor.
c.
The first outlet box in the branch circuit shall be marked to indicate that it is the first outlet of the circuit.
(4)
A listed outlet branch-circuit-type arc-fault circuit interrupter installed at the first outlet on the branch circuit in combination with a listed branch-circuit overcurrent protective device where all of the following conditions are met:
a.
The branch-circuit wiring shall be continuous from the branch-circuit overcurrent device to the outlet branch-circuit arc-fault circuit interrupter.
b.
The maximum length of the branch-circuit wiring from the branch-circuit overcurrent device to the first outlet shall not exceed fifteen and two-tenths (15.2) m (50 ft) for a 14 AWG conductor or twenty-one and three-tenths (21.3) m (70 ft) for a 12 AWG conductor.
c.
The first outlet box in the branch circuit shall be marked to indicate that it is the first outlet of the circuit.
d.
The combination of the branch-circuit overcurrent device and outlet branch-circuit AFCI shall be identified as meeting the requirements for a system combination-type AFCI and shall be listed as such.
(5)
If metal raceway, metal wireways, metal auxiliary gutters, or Type MC, or Type AC cable meeting the applicable requirements of 250.118, with metal boxes, metal conduit bodies, and metal enclosures are installed for the portion of the branch circuit between the branch-circuit overcurrent device and the first outlet, it shall be permitted to install a listed outlet branch-circuit-type AFCI at the first outlet to provide protection for the remaining portion of the branch circuit.
(6)
Where a listed metal or non-metallic conduit or tubing or Type MC cable is encased in not less than fifty (50) mm (2 in.) of concrete for the portion of the branch circuit between the branch-circuit overcurrent device and the first outlet, it shall be permitted to install a listed outlet branch-circuit-type AFCI at the first outlet to provide protection for the remaining portion of the branch circuit.
Exception: AFCI protection shall not be required for an individual branch circuit supplying a fire alarm system installed in accordance with 760.41(B) or 760.121(B). The branch circuit shall be installed in a metal raceway, metal auxiliary gutter, steel-armored cable, Type MC or Type AC, meeting the applicable requirements of 250.118, with metal boxes, conduit bodies, and enclosures.
Informational Note No. 1: For information on combination-type and branch/feeder-type arc-fault circuit interrupters, see UL 1699-2011, Standard for Arc-Fault Circuit Interrupters. For information on outlet branch-circuit type arc-fault circuit interrupters, see UL Subject 1699A, Outline of Investigation for Outlet Branch Circuit Arc-Fault Circuit-Interrupters. For information on system combination AFCIs, see UL Subject 1699C, Outline of Investigation for System Combination Arc-Fault Circuit Interrupters.
Informational Note No. 2: See 29.6.3(5) of NFPA 72-2013, National Fire Alarm and Signaling Code, for information related to secondary power-supply requirements for smoke alarms installed in dwelling units.
Informational Note No. 3: See 760.41(B) and 760.121(B) for power-supply requirements for fire alarm systems.
(D)
Branch circuit extensions or modifications — dwelling units, dormitory units, and guest rooms and guest suites. Where branch circuit wiring for any of the areas specified in 210.12(A), (B), or (C) is modified, replaced, or extended, the branch circuit shall be protected by one (1) of the following:
(1)
By any of the means described in 210.12(A)(1) through (A)(6).
(2)
A listed outlet branch-circuit-type AFCI located at the first receptacle outlet of the existing branch circuit.
Exception No. 1: AFCI protection shall not be required where the extension of the existing branch circuit conductors is not more than one and eight-tenths (1.8) m (6 ft) and does not include any additional outlets or devices, other than splicing devices. This measurement shall not include the conductors inside an enclosure, cabinet, or junction box.
Exception No. 2: For one- and two-family dwellings and townhouses, AFCI protection shall not be required where the extension of the existing branch circuit conductors is not more than nine and five-tenths (9.5) m (30 ft) and does not include any additional outlets or devices, other than splicing devices. This measurement shall not include the conductors inside an enclosure, cabinet, or junction box.
(ARTICLE 230 SERVICES)
230.85 Emergency disconnects. Delete Section in its entirety.
(CHAPTER 4 EQUIPMENT FOR GENERAL USE)
(ARTICLE 406 RECEPTACLES, CORD CONNECTORS, AND ATTACHMENT PLUGS (CAPS))
406.12 Tamper-Resistant Receptacles. All 15- and 20-ampere, 125- and 250-volt non-locking-type receptacles in the areas specified in 406.12(1) through (8) shall be listed tamper-resistant receptacles.
(1)
Dwelling units, including attached and detached garages and accessory buildings to dwelling units, and common areas of multifamily dwellings specified in 210.52 and 550.13.
(2)
Guest rooms and guest suites of hotels, motels, and their common areas.
(3)
Child care facilities.
(4)
Preschools and education facilities.
(5)
Business offices, corridors, waiting rooms and the like in clinics, medical and dental offices, and outpatient facilities.
(6)
Subset of assembly occupancies described in 518.2 to include places of awaiting transportation, gymnasiums, skating rinks, and auditoriums.
(7)
Dormitory units.
(8)
Assisted living facilities.
Informational Note No. 1: This requirement would include receptacles identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD 6-2016, Wiring Devices — Dimensional Specifications.
Informational Note No. 2: Assisted living facilities are Institutional Use Group I-1 per IBC 2015.
Exception No. 1 to (1): This shall not apply to one- and two-family dwellings and townhouses.
Exception No. 2 to (1), (2), (3), (4), (5), (6), (7) and (8): Receptacles in the following locations shall not be required to be tamper resistant:
(1)
Receptacles located more than one and seven-tenths (1.7) m (5 1/2 ft) above the floor.
(2)
Receptacles that are part of a luminaire or appliance.
(3)
A single receptacle, or a duplex receptacle for two (2) appliances, located within the dedicated space for each appliance that, in normal use, is not easily moved from one (1) place to another and that is cord-and-plug-connected in accordance with 400.10(A)(6), (A)(7), or (A)(8).
(4)
Non-grounding receptacles used for replacements as permitted in 406.4(D)(2)(a).