Exciting enhancements are coming soon to eCode360! Learn more ๐Ÿกช
Butler Area Sewer Authority, PA
Butler County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[HISTORY: Adopted by the Butler Area Sewer Authority 4-18-1995; as revised 1-28-2009. Subsequent amendments noted where applicable.]
[Revised 11/11/2020]
Three copies of plans should be submitted on 24 inches by 36 inches sheets showing plan views to a scale of one inch equals 50 feet and profiles to a scale of one inch equals 50 feet horizontally and one inch equals 10 feet vertically, a North point, a suitable title block, date and the name of the engineer or surveyor and imprint of his registration seal. All public or private easements for sanitary sewers must be labeled, must be adequately described, preferably with metes and bounds descriptions, and be tied to property corners where the easements enter and exit the properties.
[Revised 11/11/2020]
Sewers shall be designed in accordance with the Domestic Wastewater Facilities Manual of the PA Department of Environmental Protection and the construction details and drawings which are a part of these Rules and Regulations.[1]
[1]
Editor's Note: Said construction details and drawings are included in this Manual as Appendixes 1 through 16.
Construction of sewers will not be permitted until the proper state permits have been obtained.
[Revised 11/11/2020]
Prior to final acceptance of the sewers by the Butler Area Sewer Authority, the developer shall submit one set of complete and final as-constructed ("as-built") drawings of the sanitary sewer system extension to the Authority for review and approval. The information required shall include, but not be limited to, the turning angle and distance between manholes, the top elevation of each manhole, the invert elevation of each pipe entering and leaving each manhole, the exact location of all house sewer connections relative to the nearest manhole downstream, the length of each six-inch lateral, and the location and invert elevation of each inspection tee at the end of each lateral. After the Authority has approved (in writing) the โ€œas-builtโ€ drawings, the developer shall submit complete and final โ€œas-builtโ€ drawings sealed by a Professional Engineer. The โ€œas-builtsโ€ shall be in the form of both 1) reproducible Mylar drawings, and 2) digital GPS coordinates of the manhole centers referenced to the PA State Plane Coordinate System.
Easements shall be recorded in the name of the Butler Area Sewer Authority for all sewers to be constructed outside dedicated street rights-of-way.
The designated Inspector of the Butler Area Sewer Authority shall be given at least 24 hours' notice before construction begins.
(A)ย 
The developer shall agree, in writing, at the time plans are submitted to reimburse the Authority for all costs and fees relative to review and approval of the plans and all costs of inspection of construction of all sanitary sewers. The amount and type of inspection required shall be determined by the Authority during construction.
(B)ย 
No sewers constructed by a developer will be approved for use or accepted by the Authority until said sewers are formally approved by the Authority and the Authority has been reimbursed in full for all costs incurred during construction.
(A)ย 
The developer shall submit a construction schedule showing dates of commencement and completion of the project.
(B)ย 
Prior to the installation of any material or equipment on the project, the developer shall submit to the Authority's representative for approval three copies of all shop drawings, laying schedules, manufacturer specification, certifications and drawings.
(C)ย 
The developer shall indicate his review and approval of all submitted materials with an appropriate stamp and signature.
(A)ย 
All pipe, materials and equipment furnished shall be new and guaranteed by the developer and manufacturers to be free from defect, materials, and workmanship. The developer shall replace any pipe, equipment or materials which prove to be defective or which show undue wear within 18 months after having been placed in satisfactory operation and accepted by the Authority.
(A)ย 
It shall be the developer's responsibility to take whatever measures he deems necessary to protect the facilities from damage due to storm- and floodwaters during the construction stage and until such time as they are formally accepted by the Authority.
(A)ย 
The Authority will obtain the required permit from the Pennsylvania Department of Transportation (to cross or otherwise occupy those streets or roads specifically designated to be a part of the state highway system.) The developer, however, shall conduct all work in accordance with its rules and regulations and in accordance with the laws, rules, and/or regulations of all other authorities having jurisdiction over the required construction work. All permits other than PennDOT shall be obtained and paid for by the developer. Any and all inspection and/or flagmen costs incurred and deemed necessary by the governing agencies at any and all locations where work is performed shall be borne by the developer.
(B)ย 
The use of equipment on state highways and all related construction activities shall comply with the provisions of the Pennsylvania Code, Title 67, Chapter 459, "Occupancy of Highways by Utilities," or latest revision.
(A)ย 
The stipulation regarding traffic shall conform to the authority having jurisdiction over the highway in question. In general, a minimum of one lane of traffic shall be maintained on all streets and roads at all times during construction in order to accommodate the residents of the area as well as emergency fire, ambulance and similar vehicular traffic. To this end, the developer will be permitted to open not more than 100 linear feet of ditch along streets and roads. An adequate number of flagmen shall be utilized to guide traffic along all areas where work is being performed or where hazardous driving conditions prevail.
(B)ย 
Maintenance and protection of traffic on the Pennsylvania Department of Transportation's highway system shall be carried out in accordance with the applicable provisions of Publication 203. The developer shall be required to obtain an approved traffic control plan from the Pennsylvania Department of Transportation when working on state highways.
(C)ย 
The developer must obtain written permission from the respective authority, the local fire and police departments before blocking or closing any street or traveled way.
(A)ย 
Suitable and adequate barricades shall be erected and properly maintained by the developer at all times during the course of construction work to clearly and properly caution and protect traffic and pedestrians from open excavations, unstable fill areas, obstructions and other hazards directly or indirectly resulting from the construction activities. Warning signs, barricades, and handrails shall be erected and sufficient high intensity warning lights shall be appropriately located for use at night and at other times when visibility is poor. Also, if necessary, a watchman or flagman shall be employed to control traffic at such times as the developer's work would interfere with the flow of traffic.
(B)ย 
All barricades, warning lights, warning signs, and handrails shall be maintained throughout the construction contract, including all times overnight, over weekend periods, over holidays, and over all other work shutdown or stoppage periods.
(A)ย 
The developer will not be permitted to use existing sanitary sewer systems as drain lines for the construction work. He shall be responsible for all surface water runoff and/or groundwater tributary to the pipeline and/or trenches constructed and shall supply the necessary dewatering and pumping equipment for handling those flows during construction.
(A)ย 
The developer shall employ a competent survey crew, satisfactory to the Authority's representative, to lay out the work.
(A)ย 
All blasting shall be done by licensed blasters, and the developer shall conform to all federal, state and local laws and regulations regarding transportation, storage and use of explosives.
(A)ย 
The depth of trenches shall be such that the location of the proposed pipes will conform with the lines and grades shown on the plans or as approved by the Authority's representative in the field during construction. The shape of all trenches above and within the pipe zone, the construction methods employed, the general excavation requirements, the general trenching requirements, and the minimum regulations for trench shoring shall conform with the regulations set forth under Subpart P, "Excavations, Trenching and Shoring" published as part of the Safety and Health Regulations for Construction by the United States Department of Labor, as amended. No trenching excavation work shall be performed which is not in accordance with those regulations.
(B)ย 
The shape of the trenches in the "pipe zone" (which shall be construed to be that portion of the trench between the trench bottom and an elevation one foot above the top of the pipe), shall conform to the configuration identified as "typical bedding" on Standard Drawing No. 1.[1] The developer is herein advised that if trench widths in the pipe zone exceed the outside diameter of the pipe plus two feet, and if the Authority's representative determines that such excessive widths will result in structural loadings for which the pipe is not designed, he shall be required to bed the pipe on concrete cradle as directed by the Authority's representative.
[1]
Editor's Note: See Appendix 1, BASA Standard Drawing 1, Pipe Bedding.
(C)ย 
The bottom of all trenches shall be excavated to a depth of 0.5 feet below the bottom of the proposed lines to accommodate the bedding hereinafter specified.
(D)ย 
The depth of trench for pipeline shall be such that pipe in its installed position will comply with the lines and grades shown on the plans or as approved by the Authority's representative in the field during construction. The minimum cover for pipelines conveying liquid shall be four feet unless otherwise indicated on the plans.
(E)ย 
All open excavation in the construction area shall be adequately barricaded and posted with battery-operated warning lights, signs, etc., as required by any local, state or federal regulations.
(F)ย 
All inlets and discharge piping within the area of the manhole excavation shall be properly supported or installed in concrete cradle, and the cradle shall extend a minimum of three feet and as far into the pipe trench as necessary to protect the pipe to where standard trench conditions are reached.
(A)ย 
The developer shall furnish and apply a commercial grade of calcium chloride (meeting the requirements of ASTM D98) and/or water for laying dust caused from excavation or grading operations during construction. Method and rates of application shall be approved by the Authority's representative. He shall also flush streets and highways and mechanically, manually, or otherwise continually maintain those traveled roadways where dust, mud, frozen material, debris, unstabilized fills, stockpiles, or other results of construction of the project are hazardous to traffic both during and after working hours throughout the construction.
(B)ย 
Open trenches located along or across traveled ways shall be made safe for vehicular traffic as soon as possible.
(A)ย 
The developer shall provide and maintain in operation suitable and adequate pumping and/or well point equipment for completely dewatering any and all trench excavations in such as manner as to permit the successful installation of the proposed improvements.
(B)ย 
The developer shall take all necessary precautions to protect all construction against flooding and/or flotation from hydrostatic uplift.
(C)ย 
All water pumped or drained from the construction site shall be properly disposed of by the developer in accordance with all regulations and requirements of all governing authorities, including erosion and sedimentation control activities. No stormwater or surface water shall be disposed of in new or existing sanitary sewer facilities.
(A)ย 
Alignment.
[Added 12/13/2022[1]]
1.ย 
Normally sewers 24 inches or less in diameter shall be laid with straight alignment between manholes. The alignment shall be checked by either using a laser beam or lamping. Compression or chemically welded joints shall be used, and joint deflection or pull shall not exceed the maximum permissible under ASTM pipe or joint standards C-425, C-447 and C-361. Chemically welded pipe joint specifications D-2680 or equivalent shall apply. The specifications shall contain provisions for sewer cleaning equipment which will adequately maintain the flow capacity of the sewers and will prevent damage during the cleaning operation. Reference: DEP Domestic Wastewater Facilities Manual 362-0300-001 / 10/1/97 / Page 18.
[1]
Editor's Note: This resolution also redesignated former Subsections A through E as Subsections B through F, respectively.
(B)ย 
Before any pipe is installed in trenches, it shall be inspected for damage and the inside of the pipe shall be swabbed to remove loose dirt and foreign objects. No damaged pipe will be permitted to be installed.
(C)ย 
All pipe shall be installed to the lines and grades shown on the drawings or as approved by the Authority's representative in the field. No pipes shall be constructed in trenches in which water flows or is pooled, and all pipes shall be carefully handled in the ditch to keep the jointing ends and materials free from dirt during installation. During shutdown periods and at the end of each day, all open ends of pipes shall be suitably plugged to prevent the inflow of water, dirt, foreign objects, etc.
(D)ย 
Sewers shall show, substantially, a full circle of light between manholes.
(E)ย 
Each pipe manufacturer shall furnish a pipe installation manual for the developer and the Authority's representative for each different type of pipe supplied. Each pipe manufacturer shall also furnish a representative to remain on the job site for a sufficient period of time at the start of the job to instruct the developer's personnel and to ensure proper installation of the pipe.
(F)ย 
Flexible couplings furnished under this contract shall be nonshear and designed to resist uneven ground loading shear stress. Flexible couplings shall be fabricated of elastomeric polyvinyl chloride (PVC). All clamps, including the band and housing, shall be stainless steel series 300. Couplings shall be designed to connect any two pipes of dissimilar materials to form a positive seal against inflow and infiltration. Couplings shall be nonshear coupling as manufactured by DFW/HPI Plastics, Inc., or Authority-approved equal.
(A)ย 
All proposed pipeline shall be supported on a crushed limestone material such as (AASHTO) No. 57 or No. 67 stone, [see PennDOT Publication 408, Section 703.2(c), Table C] or similar angular graded material, not to exceed 1ย 1/2 inches, approved by the Authority's representative. Smooth or rounded gravel will not be acceptable. The material shall be placed to a minimum depth of 0.5 feet below the bottom of the pipe and installed to the spring line of the pipe for the full width of the trench. For all types of pipe, said material shall further be required to be placed in the entire pipe zone, defined as all that portion of the trench between the trench bottom and an elevation one foot above the top of the pipe in its installed position. The bedding and backfill material shall then be choked, as required by the Authority's representative, with approved material in sufficient quantities to prevent migrations of the surrounding soils into the bedding and backfill. The material shall be placed in the pipe zone in such a manner as to not disturb, displace, or otherwise misalign the installed pipelines.
(A)ย 
In general, the material excavated during trenching and other construction operations shall be used as backfill between the top of the pipe zone and the bottom of the topsoil or other unimproved surface treatments. Said material shall be used for full depth of trench to the finished ground surface where the ground is unimproved. Where open cuts are located in state roads, streets, driveways, shoulders, alleys, parking lots or under any paved cartway or improved surface area subject to vehicular traffic, the material used above the pipe zone shall be PennDOT No. 2A crushed limestone aggregate [see PennDOT Publication 408, Section 703.2(c), Table C] or similar material as approved by the Authority's representative. The material shall be used for the full depth of trench above the pipe zone to the bottom of the road, street, driveway or shoulder subbase. The entire depth within the backfilled area shall be compacted to provide the minimum percentage of density specified for each area of classification:
1.ย 
Percentage of maximum density and optimum water content requirements. Compact soil to not less than the following percentages of maximum dry density for soils which exhibit a well-defined moisture density relationship, determined in accordance with ASTM D1557, and not less than the following percentages of relative density, determined in accordance with ANSI/ASTM D2049, for soils which will not exhibit a well-defined moisture-density relationship.
(a)ย 
Structures. Compact top 12 inches of subgrade and each layer of backfill or fill at 95% maximum dry density at a moisture content that lies within 3% of the optimum moisture content or 80% relative density.
(b)ย 
Building slabs and steps. Compact top 12 inches of subgrade and each layer of backfill or fill material at 95% maximum dry density at a moisture content that lies within 3% of the optimum moisture content or 80% relative density.
(c)ย 
Lawn or unpaved areas. Compact top six inches of subgrade and each layer of backfill or fill material at 90% maximum dry density at a moisture content that lies within 3% of the optimum moisture content.
(d)ย 
Walkways. Compact top six inches of subgrade and each layer of backfill or fill material at 95% maximum dry density at a moisture content that lies within 3% of the optimum moisture content or 80% relative density.
(e)ย 
Pavements. Compact top 12 inches of subgrade and each layer of backfill or fill material at 95% maximum dry density at a moisture content that lies within 3% of the optimum moisture content or 80% relative density for cohesionless granular materials.
(B)ย 
In the event that the developer desires to employ the use of special vibratory and/or heavy-duty machinery for that purpose, such methods will be approved by the Authority's representative, subject to demonstration by the developer that satisfactory end results can be attained. Flooding of trenches will similarly be considered. In any event, restoration of trench settlements occurring within 18 months after completion of the work shall be the responsibility of the developer at no extra cost to the Authority. Particular care shall be exercised by the developer in backfilling trenches located along or crossing streets, street berms, roadways, parking areas, and other traveled ways, such that the resumption of normal traffic patterns will occur reasonably soon after the pipe in those areas has been installed.
(A)ย 
Where, because of local, county, state, or other regulations, special backfill material is required to be installed in unimproved cut areas, the Authority and/or its representative in the field will specify to the developer the type of said special backfill material and the same shall be obtained, placed, and thoroughly compacted by the developer.
(B)ย 
Where muck, quicksand, soft clay, swampy or other material is encountered in the trench bottom which, in the opinion of the Authority's representative, is unsuitable for pipe foundation subgrade or backfill, such material shall be removed to a depth satisfactory to the Authority's representative. The trench shall then be backfilled to grade with acceptable Authority-approved material, mechanically compacted in successive layers.
(C)ย 
Where sanitary sewers are constructed within engineered structural fills, the developer must provide the Authority written certification from a Pennsylvania Registered Geotechnical Engineer that all fill has been placed and compacted properly within the areas of the sanitary sewer system.
[Added 11/11/2020]
(A)ย 
For all new manholes installed in streets, roads, or other improved surface areas, the entire excavated area around the new manhole shall be backfilled with crushed limestone material such as AASHTO No. 57 or No. 67 stone [see PennDOT Publication 408, Section 703.2(c), Table C], or similar material approved by the Authority's representative. The backfill material shall be installed completely around the manhole from its bottom base up to the bottom of the improved surface area. The stone shall further be required to be placed in the inlet and outlet pipe trench area of the manhole so that its surface forms an approximate 45ยฐ angle with the top of the manhole.
(B)ย 
For all new manholes installed in unimproved surface areas, the entire excavated area around the new manhole shall be backfilled with crushed limestone material such as AASHTO No. 57 or No. 67 stone [see PennDOT Publication 408, Section 703.2(c), Table C] or similar material approved by the Authority's representative. The backfill material shall be installed completely around the manhole from its bottom base up to a point 12 inches above the top of the highest pipe entering the manhole.
(A)ย 
Polyvinyl chloride (PVC) sewer pipe and fittings furnished shall conform to ASTM specifications D3034, or latest revision, SDR 35 (with a cell classification of 12454B). PVC sewer pipe shall be supplied in minimum 12.5-foot lengths except where connections to manholes or main line wye branches are to be made, in which case a shorter length will be permitted to be installed. Joints shall be elastomeric gasket type. Where any portion of the pipe zone of a sewer segment exceeds 18 vertical feet, or where sanitary sewers are constructed within engineered structural fills, the entire run from manhole to manhole must be constructed using C900 PVC (green) or ductile iron pipe, and the sewer easement must be 30 feet in width for the entire run, with the center line of the pipe at least 15 feet from the edge of the sanitary sewer easement, utility easement, or property line.
[Revised 11/11/2020]
(B)ย 
Prior to delivery to the job site, the pipe manufacturer shall submit three notarized copies of certifications to the Authority's representative that the pipe has been manufactured, inspected, and tested according to these specifications and meets all requirements thereof and all pipe delivered shall be so marked. All PVC pipe furnished shall be tested for stiffness and deflection. Not less than one length of pipe out of each 200 lengths furnished, or less that two lengths of each size and strength of pipe furnished, shall be tested. Three notarized copies of all test reports shall also be submitted to the Authority's representative.
(C)ย 
PVC sewer pipe shall be transported, unloaded, handled, and installed in strict accordance with the manufacturer's recommendations by personnel experienced in laying such pipe. The manufacturer shall furnish a representative to remain on the job site for a sufficient period of time at the start of the job to instruct the developer's personnel and to ensure proper construction of the sewer lines.
(D)ย 
After the PVC pipe has been installed for a period of at least 60 days, the trench backfilled and tamped to original ground, and the pipe tested for water tightness, the contractor, at his own expense, may be required to perform a field test to demonstrate that the PVC pipe has not deflected beyond 5% of the diameter of the pipe. The test and results will be approved by the Authority's representative.
(E)ย 
An approved manhole coupling or flexible water stop shall be installed around the pipe when it enters and leaves each manhole, concrete encasement, concrete water stop or anchor, or concrete structure.
(A)ย 
Polyvinyl chloride pipe (PVC) shall be designed, manufactured, and tested in strict accordance with ASTM D2241. Three notarized copies of all test reports shall be submitted to the Authority's representative. The pipe shall be designed for installation in trenches with an average depth of five feet and be pressure rated at 200 psi minimum with minimum standard dimension ratio (SDR) of 21 for both barrel and bell dimensions. Pipe greater than 20 feet in length will not be accepted. Pipe shall bear the National Sanitation Foundation seal of approval and will comply with the requirements for Type 1, Grade 1, (PVC 1120) of ASTM D1874. The joint shall be the push-on type with a rubber O-ring gasket conforming to ASTM D1869.
(B)ย 
Prior to delivery to the job site, the pipe manufacturer shall submit three notarized copies of certification that the pipe has been manufactured, inspected, and tested according to these specifications and meets all requirements thereof and all pipe delivered shall be so marked.
(C)ย 
All pipe supplied shall be made by one manufacturer.
(D)ย 
The weight of any fittings, valve, or various appurtenance required in the control, operation, or maintenance of the system shall not be carried by the PVC pipe. The valve, fitting, etc., must be supported by a concrete cradle.
(E)ย 
All fittings for PVC pressure pipe shall conform in all respects to ANSI specification A21.10, "Cast Iron and Ductile Iron Fittings, two inches through 48 inches for Water and Other Liquids," and shall be at least 250-psi pressure classification. Fittings with wall thickness not conforming to ANSI A21.10 will not be permitted. Joints shall be push-on or mechanical joint, rubber gasket type, in general accord with ANSI specification A21.11. Fittings shall be double cement lined and coated with a standard-thickness bituminous material.
(F)ย 
PVC pressure pipe shall be transported, unloaded, handled, and installed in strict accordance with the manufacture's recommendations by personnel experienced in laying such pipe. The manufacturer shall furnish a representative to remain on the job site for a sufficient period of time at the start of the job to instruct the developer's personnel and to ensure proper construction of the lines.
(A)ย 
A detectable Mylar marking tape shall be installed over all nonmetallic pressure lines by the developer. It shall be inductively locatable and conductively traceable using standard pipe and/or cable locating devices. Care will be taken to ensure that the buried marking tape is Mylar-encased aluminum foil. The detectable marking tape will bear the words CAUTION โ€” FORCE MAIN BURIED BELOW. The printing will be under Mylar so as to be readable through the clear Mylar. Maximum spacing between the continuous warning message shall be 16 inches to 36 inches The tape will be a highly visible color and will be minimum three inches in width. The detectable marking tape will be buried four inches to six inches below finish grade or as close to grade as is practical for optimum detectability. The tape should be placed into backfill and allowed to settle into place in the backfill.
(A)ย 
Location.
[Added 12/13/2022[1]]
1.ย 
Manholes shall be installed at all changes in grade and size, changes in alignment for sewers less than 24 inches in diameter, at all intersections and at distances not greater than 400 feet for sewers 15 inches or less and 500 feet for sewers 18 inches to 30 inches. Greater spacing may be permitted in larger lines where adequate cleaning equipment for such spacing is provided. Cleanouts may be used only for special conditions and shall not be substituted for manholes nor installed at the end of laterals greater than 150 feet in length. The location of manholes in streams should be avoided. All manholes subject to flooding shall be protected with watertight covers. Reference: DEP Domestic Wastewater Facilities Manual 362-0300-001 / 10/1/97 / Page 20-21.
[1]
Editor's Note: This resolution also redesignated former Subsections A through U as Subsections B through Z, respectively.
(B)ย 
All manholes shall consist of either precast concrete base section manholes or cast-in-place concrete base section manholes. All inverts in the manhole must provide a minimum of 0.2 foot of fall through the manhole. However, when sewer pipes' grades are greater than 5%, the grade shall be carried through the manhole.
[Revised 11/11/2020]
(C)ย 
All precast concrete base section manholes shall conform to the details shown on BASA Drawing No. 10 (for sewer 8 inches through 21 inches).[2]
[Revised 11/11/2020]
[2]
Editor's Note: See Appendix 10, BASA Drawing 10, Concrete Manhole for Sewers 8" to 21" Diameter With Precast Base Section.
(D)ย 
All cast-in-place concrete base section manholes shall conform to the details shown on BASA Drawing No. 2 (for sewers 8 inches through 21 inches).[3][Revised 11/11/2020]
Precast Concrete Base Sections:
[3]
Editor's Note: See Appendix 2, BASA Drawing 2, Concrete Manhole for Sewers 8" to 21" Dia. With Cast-in-Place Section.
(E)ย 
The precast concrete base slab and precast concrete base riser sections shall be poured monolithically with the base riser section having a minimum height of two feet above the top of the base and the base slab extending a minimum of six inches beyond the outside diameter of the precast base riser section. The base slab section shall be installed on a twelve-inch-thick (minimum) subbase of (AASHTO) No. 57 or No. 67 [see PennDOT Publication 408, Section 703.2(c), Table C] compacted crushed stone. Prior to installing the subbase stone, the excavated subbase area below the manhole shall be thoroughly and evenly compacted.
(F)ย 
An Authority-approved flexible manhole sleeve shall be installed in the precast base or riser section by the manhole manufacturer for a watertight installation. The flexible watertight sleeve shall be a set a minimum of four inches above the manhole floor. The influent and effluent flexible sleeves shall be set at elevations which will maintain a minimum uniform grade through the manhole equal to the grade of the sewers upstream or downstream of the respective manholes. Manholes shall not be ordered by the developer from the manufacturer until complete field layout of the proposed pipe line is established, staked, and approved by the Authority's representative. This field layout will establish the proper horizontal and vertical alignments on influent and effluent lines of the manholes. No manholes shall be delivered to the site unless and until receipt by the Authority's representative of notarized certification that the manhole base slab is monolithically poured with the vertical base riser section, that the required and specified air entrained concrete is being used, and that all manhole sections and materials meet the appropriate specifications.
(G)ย 
All manholes shall be installed in accordance with the details outlined herein and as may be directed in the field by the Authority's representative. All manholes are subject to final field acceptance by the Authority's representative.
Cast-in-Place Concrete Base Sections:
(H)ย 
The cast-in-place concrete base sections shall be as detailed on the respective drawings, including base reinforcement.
(I)ย 
Joints at the bottom of the precast manhole barrel where connection is made with the precast or cast-in-place concrete base shall be made to produce a watertight installation. The joints in the precast concrete manhole barrels (and between all precast concrete grade rings) shall be filled with two complete rings of a one-inch-diameter approved flexible butyl rubber manhole joint sealant.
(J)ย 
All manholes shall have poured-in-place inverts. No precast or prepoured inverts will be permitted.
(K)ย 
The developer shall carefully form all full pipe depth channels and bench areas in manhole bottoms such that the least amount of turbulence will be caused in the sewage flow. All channels shall be steel trowel finished.
(L)ย 
Frames and covers for all standard manholes shall be fabricated of cast iron and be of uniform quality, free from blowholes, porosity, hard spots, blisters, shrinkage distortion or other defects. They shall be smooth and well-cleaned by shotblasting. Materials used in the manufacture of castings shall conform to ASTM A48, or latest revision, Class 30 or better. All castings shall be manufactured true to pattern and component parts shall fit together in a satisfactory manner. All frames and covers shall have machined bearing surfaces to prevent rocking and rattling. All frames and covers shall receive a factory painting of a manufacturer-recommended black asphaltum or bitumastic coating which shall be smooth and durable with no tendency to scale or chip off. The standard manhole frame and cover shall conform to the details as shown on BASA Drawing No. 3 for a minimum 27 inches frame size.[4] The final setting of manhole castings shall be such that they conform with the existing ground slopes and/or final design elevations and shall be set to exclude surface water. Where manholes are located along creeks or low areas subject to flooding and in areas where they are subject to being covered, the top elevation shall be set above the ground and landscaped as indicated on the contract drawings and/or as directed by the Authority's representative. On each manhole, two complete rings of a one-half-inch-diameter approved flexible butyl rubber joint sealant shall be installed between the bottom of the frame and the top of the concrete of the manhole. Two three-fourths-inch anchor bolts shall be provided for all frames. All outer covers shall be furnished with the lettering "Sanitary Sewer."
[Revised 11/11/2020]
[4]
Editor's Note: See Appendix 3, BASA Drawing 3, Circular Manhole Frame and Cover.
(M)ย 
Ladder bars, furnished for manholes and concrete chambers, shall be designed in accordance with the latest requirements of ASTM C478 and shall generally conform to the configuration and dimensions indicated on Standard Drawing No. 5.[5] Ladder bars to be embedded in cast-in-place concrete structures shall be cast in place at the time of pour.
[5]
Editor's Note: See Appendix 5, BASA Standard Drawing 5, Ladder Bars for Manholes.
(N)ย 
Ladder bars shall be fabricated of gray iron construction (minimum tensile strength: 40,000 psi) or, as alternate, a minimum three-eighths-inch round (minimum) steel step encapsulated with copolymer polypropylene plastics. The steps shall be capable of withstanding the design loading required in ASTM C478 specifications at a temperature of 0ยฐ F. with no structural failure.
(O)ย 
An approved manhole coupling or flexible water stop shall be installed around all pipe where it enters and leaves each manhole.
(P)ย 
Wherever sewers enter manholes such that the influent inverts are in excess of two feet above the main invert of the manhole, drop connections shall be constructed in conformance with the details on BASA Drawing No. 6.[6] Wherever sewers enter manholes such that the influent invert of the sewer is above, but less than two feet above, the manhole bottom, a channeled concrete fillet shall be constructed to prevent the flow from splashing into the manhole. The channeled concrete fillet shall be steel trowel finished. All manhole flow channels shall be steel trowel finished.
[Revised 11/11/2020]
[6]
Editor's Note: See Appendix 6, BASA Drawing 6, Inside Manhole Drop Connection for 6", 8", 10" and 12" Pipes.
(Q)ย 
Manhole eccentric cone sections, precast base sections, flat top sections, and barrel sections shall not have more than two lifting holes per section for handling and installation purposes. After installation, the holes shall be sealed (both inside and outside) and made completely watertight. All sections shall also receive a factory-applied waterproof coating on all exterior surfaces. Materials shall be as recommended by the manhole manufacturer. The Developer shall provide final touch-up coating to maintain complete integrity or repair damaged coated areas.
(R)ย 
All of the above manhole sections shall be handled according to the manufacturer's recommendations so as to avoid chipping, cracking, or breaking. Any section damaged in transporting, handling, or installation shall be replaced.
(S)ย 
Each manhole section supplied shall be plainly marked on the inside of the manhole section to indicate the date of manufacture and the name and/or trademark of the manufacturer.
(T)ย 
Prior to delivery to the job site, the manufacturer shall submit to the Authority's representative three notarized copies of certifications that all manhole sections and materials were manufactured, inspected and tested in accordance with these specifications and meet all of the requirements hereof.
(U)ย 
Prior to delivery to the job site, shop drawing details of all manhole appurtenances shall be submitted to the Authority's representative for approval, including frame and cover, steps, joint sealant, barrel and eccentric cone sections, and precast base sections.
(V)ย 
All concrete utilized for manholes (precast and cast-in-place) shall be in conformance with the concrete section of these specifications, including air entrainment requirements.
(A)ย 
Main line wye branches shall be the prefabricated wye branch type with a six-inch-diameter branch size. Connection fitting shall be utilized as shown on BASA Drawing No. 11.[1] Other construction details shall conform with those shown on that drawing.
[Revised 11/11/2020]
[1]
Editor's Note: See Appendix 11, BASA Drawing 11, Sanitary Service Connections Using Wye Fittings and Saddles.
(B)ย 
All main line wye branches shall be installed so as to direct the flow from the service sewer downstream. The angle between the upstream main line and the service sewer shall not be greater than 60ยฐ, and in no case will 90ยฐ main line wye branch tee connections be permitted.
(A)ย 
All service sewers shall be six-inch-diameter pipe.
(B)ย 
All six-inch-diameter service sewers shall be laid to a uniform grade no less than 1/8 inch per foot and to a straight line. The service sewer shall be terminated with an inspection tee constructed in conformance with the details on BASA Drawing No. 14.[1]
[Revised 11/11/2020]
[1]
Editor's Note: See Appendix 14, BASA Drawing 14, Inspection Tee.
(C)ย 
The service sewers shall be six-inch-diameter pipe and of the same material as the main line sewer. Class of pipe shall be PVC โ€“ SDR 35 ASTM D3034.
(D)ย 
The developer shall furnish to the Authority a separate wye sheet for each service line or lot. (See BASA Drawing No. 12.[2]) Each wye sheet shall include all the information as specified on the drawing, as well as a sketch showing the installation and reference measurements as outlined on the sample. Blank forms of the wye sheet will be supplied by the Authority prior to the start of construction.
[Revised 11/11/2020]
[2]
Editor's Note: See Appendix 12, BASA Drawing 12, Wye Sheet.
(A)ย 
The developer shall furnish all material, equipment, labor, and services to completely install all of the concrete work as hereinafter specified and as indicated on the drawings.
(B)ย 
All concrete, grout and all ingredients thereof, including water, shall be subject to the approval of the Authority's representative. The developer shall notify the Authority's representative at least 24 hours in advance of each concrete pour, and no concrete shall be poured until the excavations and reinforcement have been approved by the Authority's representative. No concrete shall be deposited upon frozen, loose, or otherwise unstable ground. All concrete to be used in this work shall be ready-mix concrete conforming to the requirements of ASTM C94 (latest revision).
(C)ย 
The component materials of the concrete shall meet the following requirements:
1.ย 
Cement. Portland cement shall conform to the Standard Specifications for Portland Cement of the American Society for Testing Materials, serial designation C150, Type II.
2.ย 
Aggregates. Concrete aggregates shall conform to the "Tentative Specifications for Concrete Aggregate," ASTM designation C33, except 10b and 10c will not apply.
(D)ย 
The minimum allowable compressive strength on samples taken from the transportation unit at the point of discharge shall be 4,000 psi in 28 days. The maximum allowable slump shall be four inches and the coarse aggregate shall be ASTM No. 467 or No. 57 (ASTM C33). The concrete mix shall be proportioned in accordance with ANSI/ACI Standard No. 304 and ASTM specification C94, Paragraph 4, Alternate No. 2.
(E)ย 
Placing of concrete shall be done in accordance with ACI Standard 304, or latest revision, Recommended Practice for Measuring, Mixing, and Placing Concrete, Sections V and VI, and all applicable portions of said standards shall apply. No concrete shall be poured in spaces where debris, oil, or water are present. Approval of forms and reinforcement by the Authority's representative shall be obtained before the concrete is placed. All concrete use in manhole bottoms, pavement replacement, pipe cradle or encasement and for similar purposes shall be thoroughly vibrated with approved mechanical vibrating equipment.
(F)ย 
The developer shall take all necessary precautions to ensure that concrete placed during hot or cold weather is not damaged by the extremities of temperature. To this end, he shall place the concrete in accordance with the applicable portions of ACI Standards 305 and 306. No concrete will be accepted which is frozen or damaged due to extremes in weather.
(G)ย 
The developer shall make provision for the installation and casting into the concrete of all sleeves, hatchway or grating frames, pipe, sewers, or other appurtenances indicated on the drawing or described herein.
(H)ย 
An air-entraining admixture shall be added to all concrete (precast and poured-in-place). Admixture shall be added to the concrete to produce a 5% air content. Air content shall not vary more than 1% from the specified amount. All admixtures shall be added to the concrete in strict accordance with the recommendation of the manufacturer.
(A)ย 
All grout utilized shall be durable, nonstaining, nonshrink, nonmetallic grout. The grout shall show no shrinkage in accordance with ASTM C827 prior to initial setting and shall show no shrinkage in the hardened state under ASTM C57, Corps of Engineers specification CRD-C 588 and the field cylinder test. The grout shall conform to ASTM C191 concerning time of initial set. All grouting operations shall be completed in accordance with the recommendations of ACI, CSI, and the manufacturer's published specifications for mixing and placing.
(B)ย 
All grout utilized shall be Five Starยฎ Grout as manufactured by US Grout Corporation, Greenwich, Connecticut; MasterFlow 713 Grout as manufactured by Master Builders, Cleveland, Ohio; or equal. Where nonmetallic grout is nonessential, grout shall be a nonshrink, noncatalyzed, metallic grout such as Embecco 636 Grout, as manufactured by Master Builders, Cleveland, Ohio, or equal.
Special Notice Regarding Testing.
(A)ย 
The developer is hereby informed that construction of sewers beyond an initial 1,000 feet of pipe will not be permitted until satisfactory test results are obtained.
(B)ย 
Should the developer desire to test before completion of service connections, he may do so, but will be required to retest the same line with the completed service connections before final acceptance by the Authority. Subject to unsatisfactory initial test results and at the Authority's option, testing at 1,000-foot maximum increments will be required throughout the project.
(C)ย 
Each section of sewer between manholes, or for longer distances if the Authority's representative shall so direct, shall be cleaned, tested and inspected. All repairs shown to be necessary by the tests are to be made promptly. Broken or cracked pipe shall be replaced and all deposits removed and the sewer left true to line and grade and entirely clean. Each length of sewer is to show a full circle of light from manhole to manhole.
(D)ย 
All sewers shall be tested for leakage, and any section of sewer showing leakage in excess of the amount hereinafter set forth shall be rejected.
(E)ย 
The air test shall be conducted by the developer under the supervision of the Authority's representative and shall be performed with Air-Locยฎ equipment manufactured by Cherne Industrial, Inc., Hopkins, Minnesota, or approved equal.
(F)ย 
The developer may desire to perform an air test for his own purposes prior to backfilling; however, the acceptable air test shall be performed after backfilling has been completed.
(G)ย 
Each section of sewer being tested shall be temporarily sealed off by means of suitable plugs. In addition, all wyes, tees, or ends of lateral stubs shall be sealed with suitable removable caps securely fastened to withstand internal test pressures.
(H)ย 
The procedure and criteria to be used for air testing shall conform to that described by the manufacturer of the respective pipe used and shall be in general conformance with ASTM F-1417.
[Revised 11/11/2020]
(I)ย 
All gauge pressures in the test shall be increased by the amount of groundwater pressure at the crown of the pipe.
(J)ย 
It is essential that the plugs be properly secured and care be exercised in their removal. All plugs shall be blocked and carefully braced to prevent sudden release of compressed air, slippage, or blowout due to internal pressure.
(K)ย 
To protect against injury due to the above-mentioned hazards, no one shall be permitted in the manhole or at the end of the pipe test section during testing.
(L)ย 
The pressurizing equipment shall have a safety gauge which shall limit the loading on the sewer line to 10 psi. In addition, the calibrations on all pressure gauges shall be no greater than 0.10 psi.
(M)ย 
If the pipe installation fails to meet these requirements, the developer shall determine the source or sources of leakage, and he shall repair or replace all defective materials and workmanship, including rebackfilling, compaction, and all surface restoration.
(N)ย 
Immediately following the testing, an amount of not less than 500 gallons of fresh water shall be flushed through the system from the upstream end of each separate branch. After the fresh water has flowed through, the newly constructed pipe shall be internally inspected by the developer using closed-circuit television equipment. A color CCTV video on suitable media shall be supplied to the Authority and shall be complete with audio description, on-screen titling showing manhole numbers, direction of flow, size and type of pipe, date of the inspection, and on-screen footage display accurate to tenths of one foot. In the event any defects are found, they shall be properly repaired by the developer, regardless of the outcome of the air pressure testing done previously. The CCTV video shall become the property of the Authority.
[Revised 11/11/2020]
(A)ย 
All pressure pipelines shall be tested by the developer in a manner satisfactory to and witnessed by the Authority's representative. The developer shall furnish all equipment, apparatus, temporary blocking, pumps, taps and gauges to conduct the following tests:
1.ย 
The section under test shall be filled with water and all air expelled from the line and maintained full of water for a period of not less than 24 hours.
2.ย 
The pressure and leakage tests shall be conducted concurrently, and consist of raising the water pressure (based on the elevation of the lowest point of the section under test and corrected to the gauge elevation) to a pressure in pounds per square inch numerically equal to 1.5 times the normal working pressure or, 50 pounds greater than the normal working pressure of the pipe, whichever is greater, and maintaining such pressure for a period of two hours.
3.ย 
For all piping at the end of the test period, the section test will be accepted if the total leakage is not greater than 10 gallons/inch-diameter/mile/24 hours. Leakage shall be defined as the quantity of water that must be supplied into the newly laid pipe, or any valve section thereof, to maintain pressure within five psi of the specified test pressure after the pipe has been filled with water and the air in the pipeline has been expelled.
4.ย 
If the section fails to pass the pressure and leakage tests, the developer shall do everything necessary to locate, uncover and repair or replace the defective pipe, fittings or joints. Additional test and repairs shall be made until the section passes the specified test.
5.ย 
All visible leaks are to be repaired regardless of whether or not the pipe meets the test requirements.
6.ย 
All testing shall be made from valve to valve (maximum) throughout the system to ensure the proper operation of each valve.
(B)ย 
Manholes shall be tested separately and independently from sewer lines. Leakage tests at manholes shall be made by the contractor and observed by the Authority representative periodically during construction. The test shall be a manhole vacuum test as described herein. Testing shall be in accordance with ASTM C1244, or the latest edition, "Standard Test Method for Concrete Sewer Manholes by Negative Air Pressure (Vacuum) Test."
1.ย 
All lifting holes and exterior joints shall be filled and pointed with an approved nonshrinking mortar grout.
2.ย 
Manholes are to be tested immediately after assembly and after backfilling. No standing water shall be allowed in the manhole excavation which may affect the accuracy of the test.
3.ย 
All incoming and outgoing piping shall be plugged through the use of suitably sized pneumatic plugs in such a manner as to prevent displacement of the plugs while the vacuum is on.
4.ย 
The vacuum head tester assembly shall be installed on the top of the secured frame so that the frame-cone joint is also tested. The manhole tester head assembly shall be circular in shape, properly sized to accommodate the manhole opening diameter.
5.ย 
The testing shall be accomplished by starting the vacuum pump engine and stabilizing the rpm's. The manhole shall then be tested to 10 inches mercury vacuum. The maximum allowable drop will be one inch mercury during 60 seconds.
6.ย 
If the manhole fails the test, necessary repairs shall be made by the contractor by a method and in a manner approved by the Authority, and the vacuum test repeated until the manhole passes the test.
7.ย 
If the manhole joint mastic is displaced during the vacuum test, the manhole shall be disassembled, the seal replaced, and the manhole retested.
(A)ย 
The developer shall be responsible for providing the quantity and quality of water necessary for proper pressure testing of pipe and/or manholes.
(B)ย 
Water supply for gravity sanitary sewer lines, force mains, or other nonpotable water lines shall be free of sand, mud solids, oil, acids, and any other deleterious materials.
(A)ย 
Concrete cradle and encasement, if required, shall be furnished and installed in accordance with Drawing No. 1.[1]
[1]
Editor's Note: See Appendix 1, BASA Standard Drawing 1, Pipe Bedding.
[Revised 11/11/2020]
(A)ย 
Concrete anchors, if required, shall be installed in accordance with BASA Drawing No. 7.[1]
[1]
Editor's Note: See Appendix 7, BASA Drawing 7, Concrete Anchor for Pipe Lines.
(Applicable to all installations and systems approved before September 6, 2005, unless otherwise agreed in writing by the owner and Authority.)
(A)ย 
General.
1.ย 
The grinder pump assemblies shall be Model WGL-20-21, a product of F.E. Myers Company, Ashland, Ohio, as per Myers Specifications 520 pages 7-1 through 7-11, attached hereto subject to the following additions and/or modifications[1] or E/One D-Series Assembly, a product of Environmental One Corporation, as per E/One Specifications found on the manufacturer's website.
[Revised 12/13/2022]
[1]
Editor's Note: Said specifications are on file in the BASA office.
2.ย 
Contractor shall furnish and install a six-inch leveling course of AASHTO No. 57 stone for each basin.
3.ย 
Contractor shall furnish and install a 12-inch-thick precast reinforced concrete pad for each basin and shall anchor each basin to the concrete pad.
4.ย 
Contractor shall backfill each basin excavation with clean sand to a depth of 12 inches below finished grade. The remaining excavation shall be backfilled with clean topsoil.
5.ย 
Basin size shall be 24 inches diameter minimum with an overall depth of eight feet.
6.ย 
The basins shall be certified by the manufacturer as structurally sound for the intended service. Any basin whose walls have cracked, buckled or otherwise shown any sign of damage or disfiguration at any time after backfilling operations have been completed and within the specified warranty period shall immediately be replaced with a completely new base assembly.
7.ย 
The basin shall be anchored to the precast reinforced concrete pad using three-fourths-inch diameter stainless steel bolts.
(B)ย 
Basin piping and valves.
1.ย 
Each basin assembly shall include a PVC antisiphon check valve. The antisiphon valve shall mount horizontally and shall not interfere with pump removal or installation.
2.ย 
A basin inlet hub shall be included but not mounted on the basin. It shall be of such a diameter that the bell end of a six-inch Class 50 ductile iron mechanical joint pipe can fit tightly onto the hub. The contractor shall mount the hub in the field. The contractor shall install a section of six-inch Class 50 ductile iron pipe at the basin inlet hub. The length of the six-inch ductile iron pipe shall be such that it extends not less than one foot past the excavation line and onto undisturbed earth, but in no event shall it be less than 10 feet long. The manufacture shall provide, and the contractor shall install, a one-fourth-inch-thick epoxy painted steel backing plate conforming to the curvature of the basin. The backing plate shall be bolted to the inlet hub from the inside of the basin with four sets of stainless steel bolts, nuts and rubber washers.
3.ย 
The manufacturer shall furnish a factory-installed outlet hub suitable for the bell end of a four-inch Class 50 ductile iron casing pipe. In addition, a one-fourth-inch steel plate shall be molded in the basin wall at the discharge location. The outlet hub shall be bolted to the steel plate with four sets of stainless steel bolts, nuts and rubber washers. The contractor shall install an adequate length of the four-inch casing pipe such that it extends not less than one foot past the excavation line and onto undisturbed earth, but in no event shall it be less than 10 feet long. The contractor shall furnish and install rubber bushings to center the 1ย 1/2-inch discharge pipe inside the four-inch casing pipe.
(C)ย 
Control panel. There shall be a 106 db buzzer in the panel which shall also activate on high water conditions. The buzzer shall sound for three minutes and then automatically silence. The light shall remain on until the alarm condition is satisfied. A screened opening shall be provided in the bottom of the panel so that the alarm can be heard from the outside.
(D)ย 
Level control and alarm switches.
1.ย 
Pump on and off levels shall be controlled by two mercury tube float type switches. The mercury switch shall be sealed in a solid polyurethane float ball. The support wire shall be 16-2SJOW (neoprene jacket) and a weight shall be attached to the cord above the float to hold the switch in place in the basin.
2.ย 
The high water alarm switch shall be the same as the level control switches, except that it shall be a different color than the pump level control switches.
3.ย 
The level controls shall be supported in the basin by a bracket and cord snubber which will give positive support to the controls and allow flexibility in the set levels.
4.ย 
All level controls shall be field-checked by the contractor to assure they are set at the proper elevations.
(E)ย 
Manufacturer's services and testing.
1.ย 
The grinder pump basins shall be installed in strict accordance with the manufacturer's recommendations. The contractor shall provide the services of a qualified manufacturer's representative to supervise the installation of basins as deemed necessary by the Authority's representative.
2.ย 
Before being placed in operation, each basin assembly shall be inspected and approved by a qualified representative of the manufacturer in the presence of the Authority's representative.
(F)ย 
Supplies and spare parts. For each 10 grinder pumps, or fraction thereof, to be furnished on any sewer extension, the following supplies and spare parts, properly packaged and labeled, shall be furnished:
1.ย 
Two complete grinder pumps ready to slide into basin, including discharge check valves, guide brackets, related piping, etc., or cash equivalent at the option of Butler Area Sewer Authority.
2.ย 
One fiberglass in-basin junction box.
3.ย 
One basin cover.
4.ย 
One discharge ball valve.
5.ย 
Twelve O-rings for pump discharge nozzle.
6.ย 
One amber lexan globe.
7.ย 
One upper pump seal and one lower pump seal.
8.ย 
One complete control panel.
9.ย 
Twelve stainless steel bolts and washers for basin covers.
10.ย 
Six of each of the following electrical components.
Fusesย โ€”ย each size.
Bulbsย โ€”ย each size.
Toggle switchesย โ€”ย each type.
11.ย 
One manufacturer's complete operation and maintenance manual.
(G)ย 
Modifications to residential service.
1.ย 
At each home which is to receive a grinder pump assembly, the contractor shall furnish and install an outside grinder pump service switch and alarm panel.
2.ย 
Electrically, the service switch and alarm panel shall be located on the load side of the residential service meter box.
3.ย 
Underground power and control cables from the stand to the grinder pump basin shall be 600 volt, multiconductor, Class "B" stranded insulated copper conductors. Conductor insulation shall be Type XHHW (Cross-linked polyethylene) containing a continuous, impervious metallic sheath with outer PVC jacket. The complete cable shall be suitable for direct burial.
4.ย 
Conduit raceways. Conduit shall be rigid galvanized steel or intermediate metal conduit (IMC). Conduit installed below grade shall be given a heavy coating of bitumastic No. 50 coating compound prior to burial.
5.ย 
The contractor shall install an indicator warning tape which shall be buried 12 inches below grade above all electrical cable runs. The warning tape shall be yellow plastic marker tape as manufactured by Pollard Co., Long Island, New York, or equal. Tape shall read "Caution โ€” Buried Electrical Cable Below."
6.ย 
The complete grinder pump service and alarm electrical systems shall be installed and equipment and material shall be furnished in accordance with the latest edition of the National Electric Code and state and local municipal codes and ordinances.
(Applicable to all installations and systems approved after September 6, 2005.)
(A)ย 
If, and only if, gravity sewer service (basement or first floor only) is not available, the Authority may permit the use of individual grinder pump and associated facilities for sanitary sewage service on the gravity sewer system, provided the title owner of the lot on which the grinder pump is to be installed and used complies with the following requirements:
1.ย 
The titled owner of the lot shall be responsible for all costs associated with the design, administration, permitting, installation, operation, maintenance, repair and replacement of the grinder pump unit, the private pressurized force main, and all associated appurtenances. The private force main shall consist of the portion of the discharge line from the grinder pump to the connection to the pressure sewer system at the public sewer easement or public street right-of-way.
2.ย 
The grinder pump unit shall be equipped with an audible and visual alarm system that will notify the owner/resident when the pump is not operating properly.
3.ย 
The force main connection to the Authority's gravity sewer shall be made directly into an Authority manhole by a cored drilling method with a flexible watertight coupling approved by the Authority. In no case shall the line be installed in a parallel occupancy along a public road or public right-of-way to avoid obtaining a private right-of-way from neighboring properties.
4.ย 
A shutoff valve and cleanout shall be installed at the property line or edge of the sanitary sewer easement in accordance with BASA Drawing No. 16.[1]
[Revised 11/11/2020]
[1]
Editor's Note: See Appendix 16, BASA Standard Drawing 16, Grinder Pump Force Main Cleanout.
5.ย 
The Authority and its duly authorized agent shall have the right of access at all reasonable hours to all parts of any premises connected with the sewer system for the purpose of examining and inspecting the connections and fixtures, or for disconnecting service for proper cause.
6.ย 
The Authority shall have no obligation at any time to own, operate, repair, replace or maintain the private grinder pump and/or private force main. In the event the titled owner fails to properly operate, maintain, repair, or replace the grinder pump and/or private force main, the local municipality shall be responsible for enforcing its local ordinances and using whatever means legally possible to ensure proper operation, maintenance, and repair of the private grinder pump and/or force main.
7.ย 
The titled owner shall record an easement over and through all properties which permits the local Municipality or its duly authorized agent to enter the property and to perform emergency service to the grinder pump and/or force main.
8.ย 
The titled owner shall comply with all other Authority Rules and Regulations and other municipal ordinances as may be amended from time to time.
9.ย 
The titled owner shall enter an agreement with the Authority agreeing to the conditions and requirements cited above. The Authority shall record this agreement in the Butler County Recorder of Deeds Office.
10.ย 
The titled owner shall disclose the requirements of this agreement to any prospective buyers and provide written notice to the Authority prior to any change in ownership of any property served by a grinder pump.
(Applicable for all subdivisions or land development plans approved after September 6, 2005.)
(A)ย 
If, and only if, gravity sewer service (basement or first floor only) is not available, the Authority may permit the use of a pressure sewer system consisting of a common force main and grinder pump units with discharge lines (private force mains) to provide sanitary sewage service for a proposed subdivision or land development. The developer/contractor shall comply with all requirements of Part III, Chapter 29 (titled "Alternative Sewer Systems"), of the "Domestic Wastewater Facilities Manual" as published by the Commonwealth of Pennsylvania Department of Environmental Protection, as well as the following requirements:
1.ย 
Each individual lot within the subdivision or land development shall be served by an individual grinder pump unit.
2.ย 
No force mains shall be installed within any public street right-of-way without the prior written consent and approval of the local municipality or the Pennsylvania Department of Transportation. All force mains shall be installed within private dedicated sanitary sewer or utility easements. The common force main connection to the Authority's gravity sewer shall be made directly into an Authority manhole by core drilling method with a flexible, watertight coupling approved by the Authority.
3.ย 
The pressure sewer system shall be furnished and installed in full accordance with all applicable Authority Rules and Regulations. The pressure sewer system must be designed around a standard grinder pump unit specified by the Authority's Rules and Regulations, and the design of the proposed pressure sewer system must be certified by a registered professional engineer and the manufacturer of the specified grinder pump units.
4.ย 
The titled owner of each lot within the subdivision or land development shall be responsible for the installation of the individual grinder pump units in accordance with all of the requirements specified in ยงย 300-2.33, Subsection (A)1. through 10., except that connection to the common force main shall be made at the service lateral provided by the developer for each individual lot.
5.ย 
The Authority covenants to service and maintain the portion of the pressure sewer system installed within the public sewer easement or public street right-of-way.
6.ย 
The grinder pump units, including the wet well, valves, control panel, electrical system and all appurtenances, and the private force main (as defined in ยงย 300-2.33) shall be totally privately owned, operated, and maintained by the titled owner of the lots.
7.ย 
The Authority shall have no obligation at any time to own, operate, repair, replace or maintain any grinder pump units or the private force mains located outside of the public sewer easement or the public street right-of-way.
8.ย 
The developer shall enter a developer's agreement with the Authority, agreeing to the conditions and requirement cited above.
9.ย 
The developer shall obtain all required state, county and municipal permits applicable to the sanitary sewer system. The Pennsylvania Department of Environmental Protection (DEP) may require that the Authority sign as the applicant on the Water Quality Management Part II Sewer Extension and Pumping Station Permit application (hereinafter the "permit"). Such request is subject to Authority Board approval. Notwithstanding the Authority's designation as the applicant on the permit, the developer acknowledges and understands that the developer will be responsible for all obligations required under the terms of the permit.
10.ย 
The developer shall agree that, should the developer fail to design or construct the pressure system in accordance with this agreement, and/or should such improvements fail to pass Authority's testing and inspection, the Authority may prohibit connection to its sanitary sewer system and will not be obligated to accept sewage from the development. In addition, the developer shall agree that the Authority, at its sole discretion, may request in writing to the DEP that the DEP cancel the Water Quality Management Permit.
[Added 12/13/2022]
(Applicable to all installations and systems approved after December 13, 2022.)
(A)ย 
Sewage pumps or sewage ejector pumps are permitted if, and only if:
1.ย 
Gravity service to basement elevations is not feasible; and
2.ย 
First floor service is available via gravity service.
(B)ย 
Installation.
1.ย 
Reference Chapter 7, Section 712, "Sumps and Ejectors" of the latest adopted International Plumbing Code (IPC) for design and installation requirements.
2.ย 
Reference "BASA Standard Drawing No. 17, Interior Sewage Pump or Sewage Ejector" for additional Authority requirements. Improper design and installation will result in a failed permit inspection until corrected.
3.ย 
In the event that neither the first floor, nor basement, can be serviced via gravity connection, an exterior grinder pump will be required. Reference ยงย 200-1.24, Private Grinder Pump and Force Main Installations, and ยงยงย 300-2.32 and 300-2.33 for more information regarding the installation of an exterior grinder pump.
(C)ย 
Illegal connections.
1.ย 
The connection or presence of any basement seepage, stormwater, surface water, drains, down spouts, roof drainage, or infiltration of ground or subsurface waters into the sanitary sewer system is illegal. Reference your local municipal ordinance and ยงยงย 200-1.19 and 200-1.22 of Authority rules and regulations for further details.