This chapter shall be known as, referred to, and cited as the
"Fire Prevention, Protection and Control Code" or the "Fire Protection
Code" and is hereinafter referred to as "this chapter."
It is the intent of this chapter:
A.Â
To provide the City of Burlington (municipality) with comprehensive
regulations to improve public safety by attempting to control, limit,
restrict and/or eliminate fire hazards.
B.Â
To improve life safety for residents, occupants, employees, firefighters,
and frequenters of places of employment and public buildings.
C.Â
To regulate the installation, use and maintenance of equipment; regulating
the use of structures, occupancies and open areas.
D.Â
To require the removal and/or reduction of fire hazards; establishing
the responsibilities and procedures for code enforcement; and to set
the minimum standards for compliance and achievement of these objectives.
E.Â
To protect property from the hazards of fire and explosion by establishing
minimum standards for the use, operation, maintenance and inspection
of buildings, structures and premises.
A.Â
The provisions of this chapter shall apply to all public buildings
and places of employment.
B.Â
Exceptions.
(1)Â
The
following buildings and uses are not public buildings or places of
employment and are not subject to the provisions of this chapter:
(a)Â
One- and two-family dwellings, except where specifically included,
as provided in this section and this chapter.
(b)Â
Buildings used exclusively for farming as described in § 102.04(3),
Wis. Stats.
(c)Â
Buildings used primarily to house livestock.
(d)Â
Temporary buildings used for construction purposes only, not to exceed
two stories in height and not used as living quarters.
(e)Â
Buildings owned by the federal government.
(2)Â
Nothing
contained in this chapter shall be construed as applying to the transportation
of any article or thing shipped in conformity with the regulations
prescribed by the Interstate Commerce Commission, or as applying to
the military forces of the United States.
C.Â
The provisions of this chapter shall apply equally to new structures,
including additions, and to change of use, change of occupancy, change
of occupants, renovations of, alterations of, remodeling of and/or
modifications to existing structures and existing conditions, except
that existing conditions not in strict compliance with the terms of
this chapter shall be permitted to continue where the exceptions do
not constitute a distinct hazard to life or adjoining property, as
determined by the authority having jurisdiction (AHJ), or have been
superseded by this chapter.
D.Â
The provisions of this chapter apply equally to the property owner
and/or occupant.
F.Â
If any conflicts exist between this chapter and any NFPA code and/or
standard and/or state code, the most restrictive, as determined by
the AHJ, shall be enforced by the AHJ.
G.Â
Where the AHJ finds that an existing building, because of current
occupancy or a change in occupancy, constitutes a hazard to its occupants
or adjoining property, the AHJ may order compliance with the provisions
of this chapter. A hazard shall be determined by the existence of
one or more of the following conditions:
(1)Â
Any building which by reason of its construction or highly combustible
occupancy and/or contents involves a hazard to its occupants or, in
the judgment of the AHJ, constitutes a fire menace, e.g., paint shop
and other occupancies involving processing, mixing, storing, and dispensing
of volatile liquids or solids.
(2)Â
Non-fire-resistive characteristics of a structure.
(3)Â
Accumulation of flammable or combustible materials of any kind.
(4)Â
Lack of accessibility to the premises for firefighting equipment.
(5)Â
Substantial number of fire calls or complaints on the premises.
(6)Â
Traffic patterns for pedestrian ingress and egress which require
protection under this section.
(7)Â
Insufficient ventilation system.
(8)Â
Lack of an internal communication system, or due to the size or type
of building making regular Fire Department radio communication inoperable,
the building owner is required to install a repeater system or something
comparable to assist radio communications.
(9)Â
Number, characteristics and movement of employees which require protection
under this section.
H.Â
Additions to or change of use of renovated, altered, remodeled or
modified buildings.
(1)Â
The provisions of this chapter shall apply to all existing structures, public buildings and places of employment that are additions to, changes of use of, renovations of, alterations of, remodeling of and/or modifications to existing structures and existing conditions. Note: § 155-3H(2) also applies.
(3)Â
If any addition is made to an existing building and/or structure
that currently has a fire sprinkler, fire suppression, fire control
or fire alarm system installed, the addition shall comply completely
with this chapter.
(4)Â
If any addition is made to an existing building and/or structure
that currently has a fire sprinkler, fire suppression, fire control
or fire alarm system installed, the addition shall have a fire sprinkler,
fire suppression, fire control or fire alarm system installed.
(5)Â
If the use of and/or contents of any existing building is changed
and becomes more hazardous as determined by the AHJ, the building
shall be brought into compliance with this chapter.
(6)Â
Those portions, elements, systems or components of existing buildings
and structures to be renovated, altered, remodeled or modified on
or after the effective date of the rules under this chapter, and where
the alteration, modification or the addition affects a building element
or component relating to subject matters regulated by this chapter,
shall be designed, constructed and maintained in accordance with the
applicable rules of this chapter as the rules exist on one of the
following:
(a)Â
The date plans for the alteration or modification are conditionally
approved by the AHJ.
(b)Â
The date the local building permit is issued.
(c)Â
The date the replacement is initiated, where § 155-3H(6)(a) and (b) do not apply.
(7)Â
Any change in occupancy or change of use of any premises. Any owner,
agent or occupant making a change in occupancy or use of any premises,
or occupying a previously vacant space, excluding any private dwelling,
shall be required to obtain a safety inspection by the Fire Department
prior to the new tenant taking occupancy of any building or structure
that was previously vacated or any change in occupancy or change of
use of any existing building or structure or portion thereof.
(a)Â
The owner, agent or occupant of a building shall schedule an
appointment with the Fire Inspector for an inspection of the building
and/or occupied space(s).
(b)Â
Any violations of this chapter, including all applicable codes
and/or standards adopted by reference, or other portion of the City
of Burlington Municipal Code observed at the time of inspection, shall
be corrected prior to the new tenant taking occupancy or any change
of use taking place.
(c)Â
The Fire Department is authorized to require a consultation
and/or inspection fee for this inspection.
I.Â
System submittal requirements. Any time that an automatic fire sprinkler,
fire protection, fire alarm, fire control, fire extinguishing and/or
fire suppression system and/or any portion thereof is to be installed,
altered, or added on to, or has appliances removed, plans shall be
submitted to the AHJ for review, permitting and conditional approval.
(1)Â
All plans for automatic fire sprinkler, fire protection, fire alarm,
fire control, fire extinguishing, and/or fire suppression systems
and/or any portion thereof must meet or exceed the applicable NFPA
requirements and the AHJ's requirements. Also see specific requirements
in each system type section.
(2)Â
Plans and all equipment data and manuals shall be submitted for review
and conditional approval to the AHJ prior to a permit being issued.
(3)Â
A minimum of three copies of each plan, specification, equipment
data and manuals and all calculations required by the AHJ shall be
submitted. Two copies of each may be retained by the AHJ.
(4)Â
An AutoCAD electronic file of the plans shall also be submitted to
the AHJ with each submittal and upon the completion of each project
with the as-built conditions.
(5)Â
Complete and accurate as-built drawings and revised hydraulic calculations
must be resubmitted for the AHJ's review and approval for all
fire sprinkler systems that utilize CPVC piping prior to any piping
being concealed.
(6)Â
A completed permit application must accompany all plan submittals.
(7)Â
The permit application must be signed by the individual assuming
complete responsibility for the submitted system(s).
(8)Â
The permit application for all fire sprinkler and standpipe systems
must be signed by an individual who holds a valid Wisconsin automatic
fire sprinkler contractor's license.
(9)Â
The appropriate permit, inspection and/or plan review fees must be
submitted with each permit application.
(10)Â
Plans will not be reviewed until all fees have been received
by the municipality.
(11)Â
All fire protection systems must meet or exceed all applicable
State of Wisconsin codes, City of Burlington local Code and all applicable
requirements of NFPA codes and/or standards.
(12)Â
Conditional approval of any fire protection submittal and/or
portion of any fire protection submittal is not intended to imply
waiver or modification of any requirements of any applicable code,
standard, regulation and/or law.
(13)Â
Conditional approval of any fire protection submittal and/or
portion of any fire protection submittal does not grant waiver to
and/or modify any requirements of any applicable code, standard, regulation,
requirement and/or law.
(14)Â
In granting any conditional approval, the City of Burlington
and/or the City of Burlington Fire Department reserve(s) the right
to require changes or additions should conditions arise making them
necessary for code compliance.
(15)Â
As set forth in § 101.12(2) Wis. Stats., nothing in
any review and/or conditional approval shall relieve the designer
of the responsibility for designing a safe building, structure, or
component.
(17)Â
All fire protection, fire control, fire suppression, fire alarm
and/or fire extinguishing system, plan and/or submittal reviews are
based on information provided.
(18)Â
All fire protection, fire control, fire suppression, fire alarm
and/or fire extinguishing system plan and/or submittal reviews are
done for general code compliance only.
(19)Â
Fire protection, fire control, fire suppression, fire alarm
and/or fire extinguishing system plan and/or submittal reviews do
not relieve or limit the responsibility and/or liability of the contractor(s),
architect, engineer, designer or any other responsible party for the
system(s) reviewed.
(20)Â
The City of Burlington and/or the City of Burlington Fire Department
or any of its agents and/or firm or persons hired by the City of Burlington
and/or the City of Burlington Fire Department to review plans are
not responsible for and do not accept any responsibility and/or liability
for the system(s) indicated on any plans and/or submittals reviewed.
(21)Â
The conditional approval of any fire protection, fire control,
fire suppression, fire alarm and/or fire extinguishing system, plan
and/or submittal by the City of Burlington Fire Department and/or
their authorized representative(s) shall not be construed as an assumption
of any design responsibility by the City of Burlington Fire Department
and/or their authorized representative(s).
A.Â
The following permits are required, and the Fire Department is responsible
for issuance upon submission of an acceptable application:
(1)Â
Fireworks permits.
(2)Â
Open burning permits.
(3)Â
Bonfire permits.
(4)Â
Blasting permits.
(5)Â
Construction/installation and/or modification permits for any portion
of the modification of any fire protection, fire alarm, fire detection,
fire suppression, or fire control system.
(6)Â
Operational permit for high-piled storage.
B.Â
A permit must be obtained prior to the start of installation and/or
alteration of any portion of a fire protection, fire alarm, fire control,
and/or fire suppression system.
C.Â
An operational permit issued by the AHJ is required to use a building
or a portion thereof as a high-piled combustible storage area exceeding
500 square feet.
D.Â
Permits will only be issued after the required fire protection, fire
alarm, fire control, and/or fire suppression system plans and specifications
have been reviewed and conditionally approved by the AHJ.
E.Â
Permits for the installation and/or alteration of fire sprinkler
and/or standpipe systems and/or any portion thereof will only be issued
to individuals who hold a valid automatic fire sprinkler contractor's
license.
F.Â
Any contractor that begins installation and/or alteration of any
system regulated by this chapter prior to obtaining the required permit
will be charged a triple permit fee.
G.Â
Anyone that begins installation and/or alteration of any system regulated
by this chapter prior to obtaining the required permit will be charged
a triple permit fee.
H.Â
Any change in use or occupancy shall require a new permit.
I.Â
Permit described. A permit, as specified and/or required by this
chapter, shall constitute permission to maintain, store or handle
materials or conduct processes which produce conditions hazardous
to life or property or install equipment used in connection with such
activities and/or for the installation and/or alteration of any portion
of a fire protection, fire alarm, fire control, and/or fire suppression
system. Such a permit shall not take the place of any other license
or permit required by law.
J.Â
A permit shall be valid for a stated or indefinite period as may
be specified thereon as determined by the AHJ to be reasonably necessary
to promote safety in the permitted activity.
K.Â
A permit shall not be transferable.
L.Â
Inspection. Before a license, occupancy permit or other permit for
the conducting of a business, trade, occupation or calling may be
issued by the municipality or its departments under other chapters
or provisions of this Municipal Code, the AHJ shall inspect and conditionally
approve the receptacles, vehicles, buildings or storage places to
be used.
M.Â
Location of permit. Permits and licenses subject to the issuing,
inspection or approval authority of the Fire Department or the AHJ
under this chapter shall, at all times, be kept on the premises designated
therein and be subject to inspection by the AHJ.
N.Â
Certificates of occupancy. The AHJ shall have dual authority with
the Building Inspector in the issuance of certificates of occupancy
for multifamily residences, public buildings, places of employment,
commercial structures, places of public assembly and schools to the
extent that the AHJ shall inspect and have approval authority over
proposed occupancies to ensure compliance with this chapter.
O.Â
Plans. A copy of structural or applicable plans for all proposed
construction of multifamily residences, commercial and industrial
buildings and installations or upgrades of above- and below-ground
tanks as required by Ch. Comm 10, Wis. Adm. Code,[1] shall be submitted to the AHJ for review.
[1]
Editor's Note: See now Ch. SPS 305, Wis. Adm. Code.
P.Â
Building permits. Building permits shall be issued only for those
buildings which conform to the provisions of this chapter.
Q.Â
The AHJ shall review and conditionally approve or deny all plans
submitted to the Fire Department under this chapter within 14 working
days of submission and, upon a denial, shall within such time mail
to the applicant a written statement setting forth the fact of such
denial and the reasons therefor. If the AHJ denies a plan, the Building
Inspection Department shall not issue a permit. The applicant may
appeal the decision of the AHJ to the Zoning Board of Appeals within
30 days of the date of the written denial. Plans not returned to the
Building Inspection Department stamped "denied" or "conditionally
approved" within 14 working days of submission to the AHJ shall be
considered conditionally approved.
R.Â
Whenever the applicant shall claim that the provisions of this section
do not apply to the structure in question or that the intent and meaning
of this section have been misconstrued or wrongly interpreted by the
AHJ, the applicant may appeal such decision of the AHJ to the Zoning
Board of Appeals within 30 days of the date of the decision.
A.Â
The AHJ may request that the Building Inspector issue a stop-work
order upon any permit issued, subject to the inspection and approval
authority of this chapter, where the AHJ finds that any of the conditions
for issuance have not been maintained or where there has been any
false statement or misrepresentation of any material fact made in
the application or plans upon which the issuance was based.
B.Â
If the AHJ determines requirements of this chapter are not complied
with, the AHJ may issue a stop-work order on any project or portion
thereof.
C.Â
No work may begin on installation of a fire sprinkler, fire alarm,
fire control, fire suppression, or fire extinguishing system or any
portion thereof until plans have been submitted and reviewed by the
City of Burlington Fire Department or its designee and a permit and
conditional approval has been obtained from the City of Burlington
Fire Department. A stop-work order may be given to any contractor,
owner or agent who has begun work on any system without conditionally
approved plans and permits. All fees will be tripled, and a special
inspection fee as set by the Common Council will be charged by the
Fire Department. An inspection of all work completed at the time of
the stop-work order will be performed after plans have been conditionally
approved. Should any discrepancy exist from the conditionally approved
plans and the actual installation, it shall be corrected prior to
a start-work release being issued.
A.Â
All fire sprinkler, fire control, fire extinguishing, fire suppression
and fire alarm systems shall be inspected by the AHJ prior to having
any of their parts covered up or concealed in any manner whatsoever.
B.Â
The AHJ shall be given a minimum of a seventy-two-hour notice prior
to any system inspection.
C.Â
The AHJ shall witness all tests of fire sprinkler, fire control,
fire extinguishing, and fire suppression systems, fire alarm systems,
fire alarm initiating devices, notification appliances, and any other
required system requiring an operational test.
D.Â
The AHJ shall be given a minimum of a seventy-two-hour notice prior
to any system witness test.
E.Â
All testing for any reason that requires the use of a pressure gauge
shall be done using a liquid-filled gauge that is new or has been
calibrated and certified within six months of any test the AHJ requires.
The certification shall be acceptable to the AHJ.
A.Â
The AHJ and/or its authorized representative may, at all reasonable
hours, enter any place of employment and/or public building within
its jurisdiction for the purposes of making any inspection or investigation
which, under the provision of this article, it shall deem necessary.
B.Â
The AHJ shall inspect, or cause to be inspected, all places of employment
and public buildings as often as may be necessary, but not less than
once a year.
C.Â
The purpose of any inspection and/or investigation is to determine
if any violations of the provisions or intent of this chapter and/or
the codes or standards adopted by reference exist and to order corrections
of the violations observed.
D.Â
The AHJ, upon the complaint of any person or whenever it shall deem
necessary, shall inspect any place of employment and/or public building
and premises within its jurisdiction.
E.Â
Any owner or occupant of any place of employment and/or public building who refuses to permit, prevents, or interferes with entry into or upon the premises by anyone authorized by the AHJ shall be guilty of violating this chapter and shall be subject to a penalty as set forth in § 155-55.
F.Â
Exception: The interiors of individual dwelling units will not be
inspected unless an inspection is specifically requested by the owner
or occupant and/or as allowed by Wisconsin state statutes.
G.Â
Inspection warrants. The Fire Chief or Fire Inspector may obtain
a special inspection warrant as provided under § 66.0119,
Wis. Stats., when necessary in his opinion for the purpose of making
an inspection or investigation of any building or premises where the
owner has either failed to respond to previous orders for entry or
has refused entry.
A.Â
The Fire Chief or anyone the Fire Chief has designated as the AHJ
shall enforce the provisions of this chapter.
B.Â
Whenever any AHJ or any designee of the Fire Department shall discover
fire hazards as listed below, he or she shall order such conditions
or materials removed or remedied in such manner as may be specified
or in a manner acceptable to the AHJ:
(1)Â
Dangerous or unlawful amounts of flammable, combustible or explosive
material as determined by the AHJ.
(2)Â
Hazardous conditions arising from defective or improperly installed
equipment for handling or using flammable, combustible or explosive
material.
(3)Â
Dangerous accumulations of rubbish, waste paper, boxes, shavings,
or other highly flammable materials as determined by the AHJ.
(4)Â
Accumulations of dust, grease, or waste materials in air-conditioning
systems, exhaust ducts or vent hoods.
(5)Â
Obstructions to or in fire escapes, stairs, passageways, doors, or
windows, liable to interfere with the operation of the Fire Department
or egress of occupants. This includes snow.
(6)Â
Any building, structure, or premises which for want of repairs, lack
of exit facilities, fire alarm apparatus or fire extinguishing equipment
or by reason of age or dilapidated condition, or from any cause, creates
a fire hazard.
C.Â
The AHJ may use any means in documentation of any inspections and/or
conditions, including but not limited to the use of photographing,
video and/or electronic equipment.
A.Â
Whenever there is a change in occupancy or the agent(s) (manager,
shift supervisor, after-hours emergency contact, etc.) of that occupancy,
the owner or their duly authorized agent shall submit the changes
in writing to the Fire Department within five working days. The information
shall consist of the following:
B.Â
Whenever a change in the service company for the alarm system has
occurred within the occupancy, the owner or authorized agent shall
submit the changes in writing to the Fire Department within five working
days. The information shall consist of the following:
C.Â
No change can be made in the use or occupancy of any building or
structure, or any space within a building, structure, or space of
a building or structure either in a different division of the same
occupancy group or in a different occupancy group, unless the building
or structure complies with this chapter's requirements for the
new division of occupancies, as these requirements exist. This subsection
does not apply to an approved temporary use or to a new use that will
be less hazardous, based on life and/or fire risk, than the existing
use.
D.Â
An inspection by the Fire Department shall be required for any new
occupancy or change of occupancy.
The AHJ may allow a building or portion of a building to be
used temporarily in a manner that differs from the approved use for
the building or space, or may approve a temporary building to be used
by the public, subject to all of the following provisions:
A.Â
The AHJ shall determine the time frame within which the temporary
use is permitted, based on the extent hazards are created by the temporary
use.
B.Â
The AHJ shall determine maximum occupancy load.
C.Â
The AHJ shall determine any fire protection and/or control devices
and life safety provisions that may be needed.
Unless otherwise expressly stated, the following terms shall,
for the purpose of this chapter, have the meaning indicated in this
section. Additional definitions applicable to this chapter are contained
in the applicable NFPA codes and/or standards.
A steel key vault, mounted on the exterior of a building,
that contains keys, floor plans, maps or other items as required by
the AHJ, for access to all portions of the building.
Any place that receives at any time for compensation four
or more adults for care and supervision for less than 24 hours a day.
Similar to a CBRF, except that it is licensed for five or
fewer tenants.
An automatic or manual alarm notification summoning the Fire
Department to the location of an alarm indicating fire.
A unit containing one or more indicator lamps, alphanumeric
displays, or other equivalent means in which each indication provides
status information about a circuit, condition, or location.
Acceptable to the AHJ.
An agency accepted or acceptable to the AHJ, which may include
the following: Underwriters' Laboratories, Inc., the National Institute
of Standards and Technology, the American Gas Association laboratories
or other nationally recognized testing authorities.
Group A occupancies include, among other, the use of a building
or structure, or a portion thereof, for the gathering together of
persons for purposes such as civic, social or religious functions,
recreation, food or drink consumption or awaiting transportation.
A room or space used for assembly purposes by fewer than 50 persons
and accessory to another occupant shall be included as a part of that
occupancy. Assembly occupancies shall include the following:
A-1: assembly uses, usually with fixed seating, intended for
the production and viewing of performing arts or motion pictures.
A-2: assembly uses intended for food and/or drink consumption.
A-3: assembly uses intended for worship, recreation or amusement
and other assembly uses not classified elsewhere in Group A.
A-4: assembly uses intended for viewing of indoor sporting events
and activities with spectator seating.
A-5: assembly uses intended for participation in or viewing
outdoor activities.
A notification appliance that alerts by the sense of hearing.
The Fire Chief of the City of Burlington Fire Department,
or any designee of the Fire Chief, to enforce this chapter and the
laws of the State of Wisconsin, as designated in Ch. Comm 14, Wis.
Adm. Code,[1] pertaining to the prevention of fires and public safety,
and/or conditionally approving equipment installation, and/or procedures
as outlined in NFPA standards, codes and/or recommended practices.
A device which functions without human intervention and is
actuated as a result of predetermined temperature rise, rate of rise
of temperature, combustion products or smoke density.
A system which automatically detects a fire condition and
actuates notification appliances throughout the protected premises
and actuates a fire alarm signal device to a UL-listed central station
for fire service that is acceptable to the AHJ.
A device designed to detect specific products of fire: smoke,
heat or both.
An integrated system of underground and/or overhead piping
designed in accordance with fire protection standards. The system
includes a suitable water supply. The portion of the system above
ground is a network of specially sized or hydraulically designed piping
installed in a structure or area, generally overhead, and to which
automatic sprinklers are connected in a systematic pattern. The system
is usually activated by heat from a fire and discharges water in the
fire area.
An approved system of devices and equipment which automatically
detects a fire and discharges an approved fire-extinguishing agent
onto or in the area of fire.
The quantity of water at a specific pressure that can be
used by the Fire Department for firefighting purposes and/or used
by an automatic fire sprinkler, standpipe, fire control or fire suppression
system.
That portion of a building that is partly or completely below
grade plane. A basement shall be considered as a story.
A building arranged or used as lodging for compensation,
with or without meals, not occupied as a single-family unit.
A recreational fire larger than three feet in diameter or
larger than three feet tall, used to mark a public event, victory
celebration or similar occurrence.
The Bureau of Fire Prevention is made up of the following
personnel: the Fire Chief, the Fire Marshal and/or Fire Inspectors,
or any other designee of the Chief.
Group B occupancy includes, among others, the use of a building
or structure, or a portion thereof, for office, professional or service-type
transactions, including storage of records and accounts.
The upper surface of a space, regardless of height. Areas
with a suspended ceiling would have two ceilings, one visible from
the floor, and one above the suspended ceiling.
A standard that is an extensive compilation of provisions
covering a broad subject matter or that is suitable for adoption into
law independently of other codes and standards.
All materials not classified as "noncombustible" are considered
combustible. This property of a material does not relate to its ability
to structurally perform under fire exposure. The degree of combustibility
is not defined by standard fire test procedures.
Wisconsin Department of Commerce.
Any area in a building that can be accessed by more than
one person at one time. This does not include areas within a dwelling
unit.
A community facility where five or more adults who are not
related to the operator or administrator and who do not require care
above intermediate level nursing care reside and receive care, treatment
or services that are above the level of room and board, but that include
no more than three hours of nursing care per week per resident.
An approval of plans, calculations, submittals and/or specifications
by the AHJ based upon information provided to the AHJ, including,
but not limited to, any changes required by the AHJ to the above-mentioned
plans, submittals and/or specifications. Conditional approval of any
submittal and/or portion of any submittal does not grant waiver to
and/or modification of any requirements of this chapter, or any other
applicable code, standard, regulation and/or law. The conditional
approval of any automatic fire sprinkler, suppression or fire alarm
system submittal by the AHJ shall not be construed as an assumption
of any design responsibility by the AHJ, municipality, any individual
employed by the municipality and/or any agent(s) for the municipality.
A company, individual or agency hired by the Fire Department
or municipality to provide advice to the Fire Department on fire and/or
life-safety-related issues. Consultants may provide services which
could include, but are not limited to, plan reviews of fire sprinkler,
fire alarm, fire control, fire suppression, and fire extinguishing
systems, witness tests and/or conduct inspections.
Any place which receives at any one time for compensation
four or more children under the age of seven years, for care and supervision,
for less than 24 hours a day or more than 10 days a month, without
the attendance of a parent, relative or legal guardian.
A single unit providing living facilities for one or more
persons, including permanent provisions for living, sleeping, eating,
cooking and sanitation. For the purpose of this chapter, "dwelling
unit" includes apartments and condominiums but does not include hotel
and motel rooms, guest suites, dormitories, boarding rooms, or sleeping
rooms in nursing homes.
Group E occupancy includes, among others, the use of a building
or structure, or a portion thereof, by six or more persons at any
one time for educational purposes through the 12th grade.
Group F occupancy includes, among others, the use of a building
or structure, or a portion thereof, for assembly, disassembly, fabricating,
finishing, manufacturing, packaging, repair or processing operations
that are not classified as Group H occupancy.
The initiation or transmission of a signal, message or other
notification of an event of fire when no such danger exists. Further
defined as:
MALICIOUS ALARMA false alarm of fire deliberately sounded by someone in order to inconvenience the Fire Department.
ACCIDENTAL ALARMAn alarm set off and transmitted through accidental operation of an automatic or manual fire alarm device.
GOOD INTENT FALSE ALARMAn alarm that turns out to be false but was reported in good faith.
Two or more individuals who are related to each other by
blood, marriage, adoption or legal guardianship. For purposes of this
chapter, a group of not more than four persons, not necessarily related
by blood or marriage, living together in a single living unit will
be considered equivalent to a single family.
An automatic or manual alarm notification summoning the Fire
Department to the location of an alarm indicating fire.
A device connected to a fire alarm to signal either a fire
or trouble condition. Fire alarm annunciation devices include visible
notification appliances, strobes, audible notification appliances,
horn/strobes, horns, bells, and/or annunciator panels.
A device connected to a fire alarm system that causes a trouble,
supervisory and/or alarm signal to be initiated. Fire alarm initiating
devices could include: manual pull stations, smoke, heat, flame, ionization,
or photoelectric detectors, spark detectors, water flow, low air,
low temperature, low water, or supervisory switches.
A system or portion of a combination system that consists
of components and circuits arranged to monitor and annunciate the
status of the fire alarm or supervisory signal-initiating devices
to activate notification appliances throughout the protected premises
and to initiate the appropriate response to those signals.
A system designed and constructed with the intent of controlling
or limiting a fire. Fire control systems may be automatic or nonautomatic.
Fire control systems could include automatic fire sprinkler systems,
standpipe systems, chemical agent systems, fire hydrants and/or any
other system acceptable to the AHJ.
A part of a sprinkler, standpipe, deluge and/or combination
system to be used by the Fire Department to pump additional water
into the system(s) it is connected to.
Any combination of a fire door, frame, hardware, and other
accessories that together provide a certain degree of fire protection
to the opening.
That property of materials or their assemblies that prevents
or retards the passage of excessive heat, hot gases or flame under
conditions of use. Materials are tested as prescribed in Section 703
of the International Building Code (IBC), as adopted by § Comm
61.05, Wis. Adm. Code, and amended by § Comm 62.0703, Wis.
Adm. Code.[2]
A fire-resistance-rated wall having protected openings, which
restricts the spread of fire and extends continuously from the foundation
to or through the roof, with sufficient structural stability under
fire conditions to allow collapse of construction on either side without
collapse of the wall.
Anything manufactured, processed or packaged for exploding,
emitting sparks or combustion which does not have any other use and
includes those items set forth in § 167.10(1)(m) and (n),
Wis. Stats.
The total square footage of the sums of all basement, floor
levels, balconies and mezzanines.
The area for basements and floor levels shall be measured from
the outside perimeter of the outside walls.
The area for mezzanines shall be determined from the product
of the length of the mezzanine multiplied by the width of the mezzanine.
For the purpose of determining square footage, fire division
walls will not be accepted as outside walls or area dividers.
Buildings that are in close proximity to each other will have
their building square footage added together to arrive at the total
square footage.
For the purpose of determining close proximity, the following
will hold true:
For the purpose of determining square footage, a firewall which
has a fire resistance rating of not less than four hours and which
subdivides or separates a building to restrict the spread of fire,
including a three-foot parapet wall, is an approved area divider.
That level of a building on a sloping or multilevel site
which has a floor line at or not more than three feet above exit discharge
grade for at least 1/2 of the required exit discharges.
Every person, other than an employee, who may go in or be
in a place of employment or public building under circumstances which
render such person other than a trespasser. Such term includes a pupil
or student when enrolled in or receiving instruction at an educational
institution.
A reference plane representing the average of finished ground
level adjoining the building exterior walls. Where the finished ground
level slopes away from the exterior walls, the reference plane shall
be established by the lowest points within the area between the building
and the lot line or, where the lot line is more than six feet from
the building, between the building and a point six feet from the building.
Group H occupancy includes, among others, the use of a building
or structure, or a portion thereof, that involves the manufacturing,
processing, generation or storage of materials that constitute a physical
or health hazard in quantities in excess of those found in Tables
307.7(1) through 307.7(4) of the International Building Code.
H-1: buildings and structures which contain materials that pose
a detonation hazard.
H-2: buildings and structures which contain materials that pose
a deflagration hazard or a hazard from accelerated burning.
H-3: buildings and structures which contain materials that readily
support combustion or pose a physical hazard.
H-4: buildings and structures which contain materials that are
health hazards.
H-5: semiconductor fabrication facilities and comparable research
and development areas in which hazardous production materials are
used and the aggregate quantity of materials is in excess of those
listed in Tables 307.7(1) and 307.7(2) of the International Building
Code.
Any material or combination of materials which may cause
or significantly contribute to an increase in mortality or an increase
in serious irreversible or incapacitating reversible illness or which
may pose a substantial present or potential hazard to human health
or the environment because of its quantity, concentration or physical,
chemical or infectious characteristics. This term includes, but is
not limited to, products that are explosive, toxic, corrosive, or
flammable, irritants, strong sensitizers, pesticides or a biological
hazard.
The vertical distance from the grade plane to the average
height of the highest roof surface.
A fire hazard typical of that produced by fires in combustible
high-piled storage, flammable/combustible liquid storage, tire storage
and other special occupancies.
Group 1 occupancy includes, among others, the use of a building
or structure, or a portion thereof, in which people having physical
limitations because of health or age are harbored for medical treatment
or other care or treatment, or in which people are detained for penal
or correctional purposes or in which the liberty of the occupants
is restricted. Institutional occupancies are classified as I-1, I-2,
I-3 or I-4, as described in the International Building Code.
Included in a list published by a nationally recognized testing
laboratory, inspection agency, or other organization concerned with
product evaluation, that maintains periodic inspection of production
of listed equipment or materials and whose listing states either that
the equipment or materials meet nationally recognized standards or
has been tested and found suitable for use in a specified manner.
A system or portion of a combination system that consists
of components and circuits arranged to initiate the notification appliances
and appropriate response to those signals only after a person manually
activates the fire alarm system.
Group M occupancy includes, among others, building and structures,
or a portion thereof, for the display and sale of merchandise, and
involves stock of goods, wares or merchandise incidental to such purposes
and accessible to the public.
An intermediate level or levels between floor and ceiling
of any story with an aggregate floor area of not more than 1/3 of
the area of the room or space in which the level or levels are located.
Buildings and structures of an accessory character and miscellaneous
structures not classified in any specific occupancy shall be constructed,
equipped and maintained to conform to the requirements of this chapter
commensurate with the fire and life hazard incidental to their occupancy.
A building or portion thereof containing three or more dwelling
units, such as tenements, apartments or rooming houses. Row houses
with firewalls extending from the basement to the underside of the
roof separating each living unit are not considered multifamily for
the purpose of this chapter.
The City of Burlington.
The National Fire Protection Association.
A portion of a building or structure that people do not have
access to.
A material which, in the form in which it is used, meets
one of the requirements listed below. Materials used adjacent to or
in contact with heat-producing appliances, warm air ducts, plenums
and chimneys shall be classified as noncombustible only on the basis
of Subsection A. Noncombustible does not apply to the flame-spread
characteristics of interior finish or trim materials. No material
shall be classified as noncombustible building construction material
which is subject to increase in combustibility or flame-spread classification
(FSC) beyond the limits herein established through the effects of
age, moisture or other atmospheric conditions. (See flame spread rating
in the Wisconsin Administrative Code.)
Materials which pass the test procedure of ASTM E-136 for noncombustibility
of elementary materials when exposed to a furnace temperature of 1,382°
F. for a minimum period of five minutes and do not cause a temperature
rise of the surface or interior thermocouple in excess of 54°
F. above the furnace air temperature at the beginning of the test
and which do not flame after exposure of 30 seconds.
Materials having a structural base of noncombustible material as defined in Subsection A, with a surfacing not more than 1/8 inch thick which has a flame-spread classification (FSC) not greater than 50 when tested in accordance with the method of test for surface burning characteristics of building materials (ASTM E-84).
For the purpose this chapter, normal access routes are defined
as pavement, sidewalks, streets, driveways and paths leading to a
building that are clear and maintained year round. The normal access
route does not include grass, parking stalls, ditches, hills, shrubs,
flower beds, fences, walls or any other area not typically used for
ingress to or egress from a building.
A fire alarm system component such as a bell, horn, speaker,
light, or text display that provides audible, tactile, visible outputs
or any combination thereof that is acceptable to the AHJ.
The person or persons who physically reside, work or are
present anywhere in a facility, building and/or structure.
The spaces of a facility that can be occupied or used by
the facility occupants as part of the building function or to support
building operations and maintenance. This includes, but is not limited
to, storage areas, mechanical and electrical equipment areas, walk-in
closets or janitor's rooms, restrooms, conference rooms, and
individual offices.
Terms not defined herein used in this chapter shall be as
defined in the International Fire Code Section 202 and/or NFPA codes
and standards that are adopted in this chapter by reference.
Includes his or her duly sworn agent or attorney, a purchaser,
devisee, fiduciary or person having a vested or contingent interest
in the property in question.
A form completed by the owner(s), or the owner's authorized
agent, of a building or structure where a fire sprinkler system is
going to be installed that provides the sprinkler contractor with
information required to properly design a fire sprinkler system.
A permit as specified and/or required by this chapter shall
constitute permission to maintain, store or handle materials or conduct
processes which produce conditions hazardous to life or property or
install equipment used in connection with such activities and/or for
the installation and/or alteration of any portion of a fire protection,
fire alarm, fire control, and/or fire suppression system. Such a permit
shall not take the place of any other license or permit required by
law. A permit shall be valid for a stated or indefinite period as
may be specified thereon as determined by the AHJ to be reasonably
necessary to promote safety in the permitted activity. A permit shall
not be transferable. Any change in use or occupancy shall require
a new permit.
Includes every place, whether indoors or out or underground,
and the premises appurtenant thereto, where either temporarily or
permanently any industry, trade or business is carried on, or where
any process or operation, directly or indirectly related to any industry,
trade or business, is carried on, and where any person is, directly
or indirectly, employed by another for direct or indirect gain or
profit, but does not include any place where persons are employed
in private domestic service which does not involve the use of mechanical
power or in farming. "Farming" includes those activities specified
in § 102.04(3), Wis. Stats., and also includes the transportation
of farm products, supplies or equipment directly to the farm by the
operator of said farm or employees for use thereon, if such activities
are directly or indirectly for the purpose of producing commodities
for market, or as an accessory to such production. When used with
relation to building codes, "place of employment" does not include
an adult family home, as defined in § 50.01(1), Wis. Stats.,
or, except for the purposes of § 101.11, Wis. Stats., a
previously constructed building used as a community-based residential
facility, as defined in § 50.01(1g), Wis. Stats., which
serves 20 or fewer residents who are not related to the operator or
administrator.
The physical location protected by a fire alarm system.
Any structure, including exterior parts of such building,
such as a porch, exterior platform or steps providing means of ingress
or egress, used in whole or in part as a place of resort, assemblage,
lodging, trade, traffic, occupancy, or use by the public or by three
or more tenants. When used in relation to building codes, "public
building" does not include a previously constructed building used
as a community-based residential facility as defined in § 50.01(1g),
Wis. Stats., which serves 20 or fewer unrelated residents or an adult
family home, as defined in § 50.01(1), Wis. Stats.
A scale commonly used by architects, engineers, designers
and others in the preparation of drawings that is acceptable to the
AHJ.
Any form of written material that shows information pertaining
to a device, system, method or person. Written records are required
whenever tests and/or maintenance of any kind is performed on any
fire alarm, fire control, fire suppression or life safety system or
device.
To remodel, alter, or both, means to change any building
or structure which affects the structural strength, fire hazard, internal
circulation, or exits of the existing building or structure. This
definition does not apply to maintenance, re-roofing, or alterations
to the heating and ventilating or electrical system.
A Fire Department connection that is not attached to the
building or structure that is protected by the system the FDC supplies
and is connected by piping usually installed underground or a piping
method that is acceptable to the AHJ.
Group R occupancy includes, among others, the use of a building
or structure, or portion thereof, for sleeping accommodations when
not classed as an Institutional Group I.
R-1: residential occupancies where the occupants are primarily
transient in nature.
R-2: residential occupancies containing more than two dwelling
units where occupants are primarily permanent in nature.
R-3: residential occupancies where the occupants are primarily
permanent in nature and not classified R-1, R-2 or I, and where buildings
do not contain more than two dwelling units or adult- and child-care
facilities that provide accommodations for five or fewer persons of
any age for less than 24 hours.
R-4: residential occupancies shall include buildings arranged
for occupancy as residential care/assisted living facilities, including
five but not more than 16 occupants, excluding staff.
The space located above the finished ceiling(s) and below
the exterior roof of a structure. This includes but is not limited
to any space that could be defined as an attic.
Any building which has a room or rooms for sleeping, without
permanent provisions for cooking. Rooming house rooms do not include
any room in a one- or two-family dwelling.
Visual observation from the floor and/or ground level of
any system and/or component thereof required by this chapter prior
to being concealed in any way by any means.
A place of abode arranged to accommodate three or more attached
side-by-side or back-to-back living units.
A specific measurement of pressure in pound per square inch
(psi) at a specific rate of water flow that all fire sprinkler, fire
control and water-based fire suppression systems must maintain below
the anticipated available water supply as determined by a water flow
test, a municipality-specified flow and pressure or any other water
supply acceptable to the AHJ.
Indicates a mandatory requirement.
Indicates a recommendation or that which is advised but not
required.
A detached building containing only one dwelling unit and
designed exclusively for use and occupancy by one family.
A horizontally measured dimension relating to the allowable
coverage limits of fire detectors, automatic sprinkler systems, and
fire alarm visual notification devices.
Any area in which a high-challenge fire hazard exists and
any NFPA codes and/or standards contain design criteria, limitations
or requirements that apply specifically to the occupancy.
A document, the main text of which contains only mandatory
provisions using the word "shall" to indicate mandatory requirements
and which is in a form generally suitable for reference by another
standard or code or for adoption into law.
Group S occupancy includes, among others, the use of a building
or structure, or portion thereof, for storage that is not classed
as Hazardous Group H.
S-1 (moderate-hazard storage): buildings occupied for storage
uses which are not classified as S-2.
S-2 (low-hazard storage): building used for storage of noncombustible
material such as products on wood pallets or in paper cartons with
or without single thickness divisions or in paper wrappings. Such
products may have a negligible amount of plastic trim, such as knobs,
handles, or film wrapping.
That portion of a building included between the upper surface
of a floor and the upper surface of the floor or roof next above.
To determine the number of stories in a building, all floors will
be counted, whether they are above grade or below grade, including
basements, sub-basements, and ground floors, but not including penthouses
or mezzanines less than 1/3 of a story.
A notification appliance that alerts by the sense of touch
or vibration.
Fewer than 180 days.
A notification appliance that conveys a stream of audible
information. An example of a textual audible notification appliance
is a speaker that reproduces a voice message.
One of the following, depending on the circumstances:
Throughout, for automatic fire sprinkler systems, means providing
fire sprinkler protection in all areas of a structure as required
by NFPA 13.
Throughout, for automatic fire alarm systems, means installing
detection, audible and visual notification devices in all areas of
the protected premises installed in accordance with NFPA 72.
Throughout, for manual fire alarm systems, means installing
audible and visual notification devices in all areas of the protected
premises installed in accordance with NFPA 72.
A detached building containing not more than two individual
dwelling units which are entirely separated by vertical walls or horizontal
floors, unpierced except for access to the outside or common basement.
Any self-propelled device fueled by flammable or combustible
liquid, or compressed gas, used to transport people or goods.
A notification appliance that alerts by the sense of sight.
A test of an available water supply that indicates the quantity
of water flowing out of a specific orifice, at a specific pressure,
at a specific point in time.
Includes comfort, decency and moral well-being.
All references to "Wisconsin Statutes" or "Wis. Stats." shall
mean the State of Wisconsin statutes as of the adoption of this chapter
as or as they may be amended or renumbered from time to time.
A.Â
The following Wisconsin Administrative Codes in effect on the date
of adoption of this chapter, or as they may be amended or renumbered
from time to time, are adopted by reference, enforced and incorporated
into this chapter as if fully set forth herein:
Comm 3
|
Petition for variance procedures
|
Comm 5
|
Licenses, certification and registration
|
Comm 7
|
Explosive materials
|
Comm 8
|
Mines, pits and quarries
|
Comm 9
|
Manufacture of fireworks
|
Comm 10
|
Flammable and combustible liquids
|
Comm 14
|
Fire prevention
|
Comm 16
|
Electrical
|
Comm 18
|
Elevator code
|
Comm 28
|
Smoke detectors
|
Comm 33
|
Passenger ropeways
|
Comm 34
|
Amusement rides and attractions
|
Comm 35
|
Infectious agents
|
Comm 40
|
Gas systems
|
Comm 41
|
Boilers and pressure vessels
|
Comm 43
|
Anhydrous ammonia
|
Comm 45
|
Mechanical, refrigeration
|
Comm 48
|
Petroleum products
|
Comm 61-65
|
Wisconsin Commercial Building Code
|
Comm 70
|
Historic buildings
|
Comm 71
|
Solar energy systems
|
Comm 75-79
|
Existing buildings
|
Comm 95-98
|
Manufactured homes
|
B.Â
Any violation of the incorporated provisions of any State of Wisconsin
code, law, regulation, standard or any other requirements constitutes
a violation of this chapter.
C.Â
In cases of conflict between local and State of Wisconsin codes,
the most restrictive provisions, as determined by the AHJ, shall govern.
D.Â
Copies of the Wisconsin Department of Commerce codes are available
from:
Wisconsin Department of Administration
Document Sales and Distribution Section
P.O. Box 7840
Madison, WI 53707
1-608-266-3358
|
The latest International Code Council (ICC) publications listed
below and published on or before the effective date of this chapter
are adopted by reference, enforced and incorporated into this chapter
as if fully set forth herein:
A.Â
International Fire Code (IFC), 2006 edition (applies only to sections
specifically referenced in this chapter).
A.Â
The latest National Fire Protection Association (NFPA) codes and
publications published on or before the effective date of this chapter
are adopted by reference, enforced and incorporated into this chapter
as if fully set forth herein:
NFPA 1
|
Uniform Fire Code (applies only to use, maintenance, operation
and testing), 2006 edition
|
NFPA 10
|
Standard for Portable Fire Extinguishers, 2007 edition
|
NFPA 11
|
Standard for Low-, Medium- and, High-Expansion Foam, 2005 edition
|
NFPA 12
|
Standard on Carbon Dioxide Extinguishing Systems, 2008 edition
|
NFPA 13
|
Standard for the Installation of Sprinkler Systems, 2007 edition
|
NFPA 13D
|
Sprinkler Systems in One- and Two-Family Dwellings and Manufactured
Homes, 2007 edition
|
NFPA 13R
|
Sprinkler Systems in Residential Occupancies up to and Including
Four Stories in Height, 2007 edition
|
NFPA 14
|
Standard for the Installation of Standpipes, Private Hydrant,
and Hose Systems, 2007 edition
|
NFPA 15
|
Standard for Water Spray Fixed Systems for Fire Protection,
2007 edition
|
NFPA 16
|
Standard for the Installation of Foam-Water Sprinkler and Foam-Water
Spray Systems, 2007 edition
|
NFPA 17
|
Standard for Dry Chemical Extinguishing Systems, 2002 edition
|
NFPA 17A
|
Standard for Wet Chemical Extinguishing Systems, 2002 edition
|
NFPA 20
|
Standard for the Installation of Stationary Pumps for Fire Protection,
2007 edition
|
NFPA 22
|
Standard for Water Tanks for Private Fire Protection, 2003 edition
|
NFPA 24
|
Standard for the Installation of Private Fire Service Mains
and their Appurtenances, 2007 edition
|
NFPA 25
|
Standard for the Inspection, Testing, and Maintenance of Water-Based
Fire Protection Systems, 2008 edition
|
NFPA 30
|
Flammable and Combustible Liquids Code, 2008 edition
|
NFPA 30A
|
Code for Motor Fuel Dispensing Facilities and Repair Garages,
2008 edition
|
NFPA 30B
|
Code for the Manufacture and Storage of Aerosol Products, 2007
edition
|
NFPA 33
|
Standard for Spray Application Using Flammable or Combustible
Materials, 2007 edition
|
NFPA 34
|
Standard for Dipping and Coating Processes Using Flammable or
Combustible Liquids, 2007 edition
|
NFPA 35
|
Standard for the Manufacture of Organic Coatings, 2005 edition
|
NFPA 36
|
Standard for Solvent Extraction Plants, 2004 edition
|
NFPA 37
|
Standard for the Installation and Use of Stationary Combustion
Engines and Gas Turbines, 2006 edition
|
NFPA 40
|
Standard for the Storage and Handling of Cellulose Nitrate Film,
2007 edition
|
NFPA 42
|
Code for the Storage of Pyroxylin Plastic, 2002 edition
|
NFPA 45
|
Standard on Fire Protection for Laboratories Using Chemicals,
2004 edition
|
NFPA 51
|
Standard for the Design and Installation of Oxygen-Fuel Gas
Systems for Welding, Cutting, and Allied Processes, 2007 edition
|
NFPA 51A
|
Standard for Acetylene Cylinder Charging Plants, 2006 edition
|
NFPA 51B
|
Standard for Fire Prevention During Welding, Cutting, and Other
Hot Work, 2003 edition
|
NFPA 54
|
National Fuel Gas Code, 2006 edition
|
NFPA 55
|
Standard for the Storage, Use, and Handling of Compressed Gases
and Cryogenic Fluids in Portable and Stationary Containers, Cylinders,
and Tanks, 2005 edition
|
NFPA 58
|
Liquefied Petroleum Gas Code, 2008 edition
|
NFPA 59
|
Utility LP-Gas Plant Code, 2004 edition
|
NFPA 59A
|
Standard for the Production, Storage, and Handling of Liquefied
Natural Gas (LNG), 2006 edition
|
NFPA 61
|
Standard for the Prevention of Fires and Dust Explosions in
Agricultural and Food Processing Facilities, 2008 edition
|
NFPA 68
|
Guide for Venting of Deflagrations, 2007 edition
|
NFPA 69
|
Standard on Explosion Prevention Systems, 2008 edition
|
NFPA 70
|
National Electrical Code®, 2005
edition
|
NFPA 72
|
National Fire Alarm Code, 2007 edition
|
NFPA 75
|
Standard for the Protection of Information Technology Equipment,
2003 edition
|
NFPA 76
|
Standard for the Fire Protection of Telecommunications Facilities,
2005 edition
|
NFPA 80
|
Standard for Fire Doors and Fire Windows, 2007 edition
|
NFPA 82
|
Standard on Incinerators and Waste and Linen Handling Systems
and Equipment, 2004 edition
|
NFPA 85
|
Boiler and Combustion Systems Hazards Code, 2007 edition
|
NFPA 86
|
Standard for Ovens and Furnaces, 2007 edition
|
NFPA 88A
|
Standard for Parking Structures, 2007 edition
|
NFPA 88B
|
Standard for Repair Garages, 1997 Edition
|
NFPA 91
|
Standard for Exhaust Systems for Air Conveying of Vapors, Gases,
Mists, and Noncombustible Particulate Solids, 2004 edition
|
NFPA 92A
|
Standard for Smoke-Control Systems, 2006 edition
|
NFPA 92B
|
Standard for Smoke Management Systems in Malls, Atria, and Large
Spaces, 2005 edition
|
NFPA 96
|
Standard for Ventilation Control and Fire Protection of Commercial
Cooking Operations, 2008 edition
|
NFPA 99B
|
Standard for Hypobaric Facilities, 2005 edition
|
NFPA 99C
|
Standard on Gas and Vacuum Systems, 2005 edition
|
NFPA 101
|
Life Safety Code®, 2006 edition
|
NFPA 101B
|
Code for Means of Egress for Buildings and Structures
|
NFPA 102
|
Standard for Grandstands, Folding and Telescopic Seating, Tents,
and Membrane Structures, 2006 edition
|
NFPA 105
|
Standard for the Installation of Smoke Door Assemblies, 2007
edition
|
NFPA 110
|
Standard for Emergency and Standby Power Systems, 2005 edition
|
NFPA 111
|
Standard on Stored Electrical Energy Emergency and Standby Power
Systems, 2005 edition
|
NFPA 115
|
Standard on Laser Fire Protection, 2003 edition
|
NFPA 160
|
Standard for the Use of Flame Effects Before an Audience, 2006
edition
|
NFPA 170
|
Standard for Fire Safety and Emergency Symbols, 2006 edition
|
NFPA 204
|
Standard for Smoke and Heat Venting, 2007 edition
|
NFPA 214
|
Standard on Water-Cooling Towers, 2005 edition
|
NFPA 221
|
Standard for High Challenge Fire Walls, Fire Walls, and Fire
Barrier Walls, 2006 edition
|
NFPA 230
|
Standard for Fire Protection of Storage, 2003 edition
|
NFPA 232
|
Standard for the Protection of Records, 2007 edition
|
NFPA 241
|
Standard for Safeguarding Construction, Alteration, and Demolition
Operations, 2004 edition
|
NFPA 291
|
Practice for Fire Flow Testing and Marking of Hydrants, 2007
edition
|
NFPA 303
|
Fire Protection Standards for Marine and Boatyards, 2006 edition
|
NFPA 318
|
Standard for the Protection of Semiconductor Fabrication Facilities,
2006 edition
|
NFPA 400
|
Hazardous Chemical Code
|
NFPA 407
|
Standard for Aircraft Fuel Servicing, 2007 edition
|
NFPA 408
|
Standard for Aircraft Hand Portable Fire Extinguishers, 2004
edition
|
NFPA 409
|
Standard on Aircraft Hangars, 2004 edition
|
NFPA 410
|
Standard on Aircraft Maintenance, 2004 edition
|
NFPA 418
|
Standard for Heliports, 2006 edition
|
NFPA 430
|
Code for the Storage of Liquid and Solid Oxidizers, 2004 edition
|
NFPA 432
|
Code for the Storage of Organic Peroxide Formulations, 2002
edition
|
NFPA 434
|
Code for the Storage of Pesticides, 2002 edition
|
NFPA 484
|
Standard for Combustible Metals, 2006 edition
|
NFPA 490
|
Code for the Storage of Ammonium Nitrate, 2002 edition
|
NFPA 495
|
Explosive Materials Code, 2006 edition
|
NFPA 499
|
Recommended Practice for the Classification of Combustible Dusts
and of Hazardous (Classified) Locations for Electrical Installations
in Chemical Process Areas, 2004 edition
|
NFPA 560
|
Standard for the Storage, Handling, and Use of Ethylene Oxide
for Sterilization and Fumigation, 2007 edition
|
NFPA 654
|
Standard for the Prevention of Fire and Dust Explosions from
the Manufacturing, Processing, and Handling of Combustible Particulate
Solids, 2006 edition
|
NFPA 655
|
Standard for Prevention of Sulfur Fires and Explosions, 2007
edition
|
NFPA 664
|
Standard for the Prevention of Fires and Explosions in Wood
Processing and Woodworking Facilities, 2007 edition
|
NFPA 704
|
Standard System for the Identification of the Hazards of Materials
for Emergency Response, 2007 edition
|
NFPA 720
|
Standard for the Installation of Carbon Monoxide (CO) Warning
Equipment in Dwelling Units, 2005 edition
|
NFPA 750
|
Standard on Water Mist Fire Protection Systems, 2006 edition
|
NFPA 780
|
Standard for the Installation of Lightning Protection Systems,
2008 edition
|
NFPA 801
|
Standard for Fire Protection for Facilities Handling Radioactive
Materials, 2003 edition
|
NFPA 804
|
Standard for Fire Protection for Advanced Light Water Reactor
Electric Generating Plants, 2006 edition
|
NFPA 850
|
Recommended Practice for Fire Protection for Electric Generating
Plants and High Voltage Direct Current Converter Stations, 2005 Edition
|
NFPA 853
|
Standard for the Installation of Stationary Fuel Cell Power
Systems, 2007 edition
|
NFPA 1123
|
Code for Fireworks Display, 2006 edition
|
NFPA 1124
|
Code for the Manufacture, Transportation, Storage and Retail
Sales of Fireworks and Pyrotechnic Articles, 2006 edition
|
NFPA 1125
|
Code for the Manufacture of Model Rocket and High Power Rocket
Motors, 2007 edition
|
NFPA 1126
|
Standard for the Use of Pyrotechnics before a Proximate Audience,
2006 edition
|
NFPA 2001
|
Standard on Clean Agent Fire Extinguishing Systems, 2008 edition
|
NFPA 2010
|
Standard for Fixed Aerosol Fire Extinguishing Systems, 2006
edition
|
B.Â
Copies of the National Fire Prevention Association codes and publications
are available from:
National Fire Protection Association
1 Batterymarch Park
Quincy, Massachusetts 02169-7471
Tel: 617-770-3000
Sales/Member Services: 800-344-3555 or 617-770-3000
Fax: 617-770-0700
|
This chapter shall not be construed to affect the responsibility
of any persons owning, operating, or installing equipment for injury
to persons or damage to property caused by any defect therein, nor
shall the municipality, or any person, firm, company or agent(s) for
the municipality, be held as assuming such liability by reason of
any plan, system, submittal review and/or conditional approval, inspection
or reinspection authorized herein or the permit issued herein provided
or by reason of the disapproval or approval of any equipment and/or
system authorized herein.
A.Â
The service of correction orders may be made upon the owner, occupant
or both or any other person responsible for the conditions that violate
any section of this chapter. A copy of the service order can be delivered
personally to the owner or by leaving it with the person in charge
of the premises. Whenever it may be necessary to serve such order
upon the owner of the premises, such an order may be served either
by delivering to and leaving with the person a copy of the order,
or if such owner is absent from the jurisdiction of the AHJ making
the order, by mailing such a copy to the owner's last known post
office address. Any such order may be given verbally, handwritten
on an approved inspection form or typed and delivered to such occupant
personally or by placing such order in a conspicuous place on the
door to the entrance of the premises.
B.Â
Compliance with service of correction orders that include conditions
that are hazardous to life or safety of the occupants shall require
immediate correction. All other violations shall be corrected within
a specified time or date, as the AHJ shall determine.
C.Â
When the owner of any property or person in apparent control of the
property is issued an order by the AHJ and fails to comply with the
order, the municipality may do the work ordered or cause the work
ordered to be done, and the cost of such work shall constitute a special
charge against the property upon which the work is done and shall
be levied against such property pursuant to § 66.0627, Wis.
Stats.
D.Â
No person shall refuse to permit or shall prevent or interfere with
any entry into or upon any building or premises by the AHJ who is
lawfully on the premises or interfere with any such inspection. If
consent to enter onto personal or real properties which are not public
buildings, or to portions of public buildings which are not open to
the public, has been denied, the AHJ shall obtain a special inspection
warrant under § 66.0119, Wis. Stats.
E.Â
Compliance with orders. Any such order given shall forthwith be complied
with by the owner and occupant of such building, structure or premises.
The owner or occupant may, within 24 hours of the receipt of such
order, appeal to the Fire Chief in writing for a review of such order,
who shall thereafter as soon as possible file his decision. Unless
such order is revoked or modified by the Fire Chief, it shall remain
in full force and shall be complied with in the time fixed in said
order. Appeals of orders in conflict with orders of the Department
of Commerce may be made pursuant to § Comm 14.01(7), Wis.
Adm. Code.[1]
[1]
Editor's Note: See now § SPS 314.01(9), Wis. Adm.
Code.
A.Â
The AHJ thereon shall enter upon the records of the Department, and
a signed copy shall be furnished to the applicant of, the particulars
of such variances when granted.
B.Â
The AHJ may require tests as proof of compliance with the intent
of this chapter. Such tests are to be made by an approved agency at
the expense of the person requesting approval of the alternate material
or method of construction.
C.Â
If technical expertise is unavailable within the municipality because
of new technology, processes, products, facilities, materials, design,
operation or use of a building or premises subject to the inspection
of the municipality, the AHJ may require the owner or the person in
possession or control of the building or premises to provide, without
charge to the municipality, a technical opinion and report. The opinion
and report shall be prepared by a qualified engineer, specialist,
laboratory or fire safety organization, acceptable to the AHJ and
the owner, and shall analyze the fire safety properties of the design,
operation or use of the building or premises and the facilities and
appurtenances situated thereon, and prescribe all necessary recommended
changes. The Fire Department may also acquire technical assistance
from a consultant and may charge a fee to the owner or occupant for
the service provided.
A.Â
The AHJ may revoke any permit issued in accordance with this chapter
in any case where the AHJ may find that any of the conditions for
the issuance have not been maintained or where there has been false
statement or misrepresentation of any material fact in the application
or plans on which the issuance was based.
B.Â
The AHJ shall promptly notify the permit holder of the request for
revocation and, if so requested by the permit holder, the effective
date of the revocation shall be deferred pending a hearing before
the Chief of the Fire Department. The decision of the Chief for revocation,
following the hearing, shall be final.
C.Â
All permits and conditional approvals shall automatically expire
two years after the date of the permit or conditional approval, whichever
is later, if the system or equipment has not been completely installed
and tested to the satisfaction of the AHJ.
D.Â
The AHJ may extend a permit and/or conditional approval as required
if requested in writing by the owner or the owner's authorized
representative.
A.Â
The Fire Department shall investigate the cause and origin, and circumstances,
of fires occurring within their jurisdiction to determine if the fire
was caused by carelessness or design. Such investigations may begin
immediately upon the occurrence of such a fire, and if it appears
to the officer making such an investigation that such fire is of suspicious
origin and of a significant nature, the Fire Chief shall be notified
of the facts. The AHJ shall notify the proper authorities designated
by law to pursue the investigation of such matters and shall further
cooperate with the authorities in the collection of evidence and in
the prosecution of the case. A member of the fire investigation team
shall file a written report of damage associated with every fire in
a timely manner. It shall contain a statement of all facts relating
to the cause and origin and circumstances of such fire and other information
as may be required.
B.Â
The Municipal Attorney and any other department of the municipality,
upon the request of the Fire Chief, shall assist in the investigation
of any fire that, in the Chief's opinion, is of suspicious origin.
C.Â
Any officer of the Fire Department may cause the arrest of any person
failing to give the right-of-way to the Fire Department in responding
to or investigating an incident.
D.Â
The Fire Chief or officers in command may prescribe certain limits
in the vicinity of any incident within which no persons, excepting
firefighters and police officers and those admitted by order of any
officer of the Fire Department, shall be permitted to enter.
E.Â
The Fire Chief or officers in command shall have the power to cause
the removal of any property whenever it is deemed necessary and prudent
for the preservation of such property. During the progress of any
fire, they shall have the power to cause the removal of all wires
or other facilities and the turning off of all electricity or other
services where the same impedes work of the Fire Department during
the progress of fire.
F.Â
It shall be lawful for any Fire Department personnel, while acting
under the direction of the Fire Chief or officer in command, to enter
premises adjacent to or in the vicinity of a building or other property
that is on fire for the purpose of extinguishing, containing, or searching
for extension of such fire or other exigent circumstances.
G.Â
During the progress of fire, the Fire Chief or officers in command
shall have the power to order the removal or destruction of any property
necessary to prevent the further spread of fire or to ensure that
the fire has not extended to other areas, providing that it is likely
that, unless such property is removed, other property is in danger
of being destroyed by fire.
H.Â
No person shall hinder, resist or obstruct any firefighter in the
discharge of his duties as provided in this section. The person so
offending shall be deemed guilty of resisting firefighters in the
discharge of their duties.
A.Â
Intent. The intent of this section is to require the installation
of automatic fire sprinkler, fire control and/or fire suppression
systems to improve the protection of life and property within the
municipality. It will establish a minimum standard for fire safety
through the standardization of the design, installation, testing and
maintenance requirements for automatic fire sprinkler suppression.
B.Â
Code compliance. All automatic fire sprinkler fire control and/or
fire suppression systems installed, modified, altered and/or repaired
shall comply with this chapter and all of the applicable NFPA codes
and/or standards.
C.Â
Code conflicts. If any conflicts exist between this chapter and any
NFPA code and/or standard, the most restrictive, as determined by
the AHJ, shall be enforced by the AHJ.
D.Â
Working plans. Working plans shall be submitted to the AHJ for review
and conditional approval before any equipment is installed, modified
or remodeled.
E.Â
Deviation from conditionally approved plans shall require permission
of the AHJ.
F.Â
All working plans submitted for conditional approval must be signed
and sealed by at least one of the following:
(1)Â
An architect registered in the State of Wisconsin.
(2)Â
An engineer registered in the State of Wisconsin.
(3)Â
A person who holds a designer of engineering systems permit in the
State of Wisconsin.
(4)Â
The individual who holds a valid automatic fire sprinkler contractor's
license and is responsible for the system installation.
G.Â
Working plans shall be drawn to an indicated scale, on sheets of
uniform size, with a plan of each floor, and shall show those items
from the following list that pertain to the design of the system and
any that NFPA 13 and/or the AHJ may require:
(1)Â
Name of owner.
(2)Â
Name of occupant.
(3)Â
Location, including street address.
(4)Â
Point of compass.
(5)Â
Full height cross section, or schematic diagram, including structural
member information.
(6)Â
Ceiling construction.
(7)Â
Elevation of the sprinklers relative to the ceiling.
(8)Â
Method of protection for nonmetallic piping.
(9)Â
Minimum clearance required from the sprinkler deflectors to the top
of storage.
(10)Â
Location of partitions.
(11)Â
Location of firewalls.
(12)Â
Occupancy class of each area or room.
(13)Â
All storage information, limits and exact configurations shall
be on the working drawings prepared by the automatic fire sprinkler
contractor.
(14)Â
Hazard classification for each protected area.
(15)Â
All special occupancy protection areas.
(16)Â
All storage limits based on the sprinkler system design criteria,
including the following:
(a)Â
The storage high limit for each different commodity class.
(b)Â
The storage arrangement for each different commodity class and/or
special occupancy hazard arrangements, including the following:
[1]Â
Storage method (solid pile, shelf, rack or other).
[2]Â
Minimum aisle widths for all rack storage and where required.
[3]Â
Minimum required clearance from overhead fire sprinkler deflectors.
[4]Â
Minimum required clearance from in-rack fire sprinkler deflectors.
[5]Â
Minimum required transverse flue space.
[6]Â
Minimum required longitudinal flue space.
[7]Â
Pile stability.
[8]Â
Storage array.
[9]Â
Any other information the AHJ deems necessary to determine compliance
with the applicable NFPA code and/or standard.
(c)Â
All special occupancy restrictions and/or limits contained in
the applicable NFPA code and/or standard.
(17)Â
Location and size of concealed spaces.
(18)Â
Location and size of combustible concealed spaces.
(19)Â
Closets.
(20)Â
Attics.
(21)Â
Bathrooms.
(22)Â
Any small enclosures in which no sprinklers are to be installed.
(23)Â
Size of City main in street.
(24)Â
Whether City main in street is dead end or circulating.
(25)Â
Direction and distance to nearest circulating main.
(26)Â
City main water flow test results.
(27)Â
System elevation relative to test hydrant.
(28)Â
Other sources of water supply, with pressure or elevation.
(29)Â
Make, type, model, and nominal K-factor of sprinklers, including
sprinkler identification number.
(30)Â
Temperature rating of all sprinklers.
(31)Â
Total area protected by each system.
(32)Â
Total area protected by each system on each floor.
(33)Â
Number of sprinklers on each riser per floor.
(34)Â
Total number of sprinklers on each wet system.
(35)Â
Total number of sprinklers on each dry pipe system.
(36)Â
Total number of sprinklers on each preaction system.
(37)Â
Total number of sprinklers on each combined dry pipe-preaction
system.
(38)Â
Total number of sprinklers on each deluge system.
(39)Â
Approximate capacity in gallons of each dry pipe system.
(40)Â
Approximate capacity in gallons of each preaction system.
(41)Â
Pipe type and inside diameter.
(42)Â
Nominal pipe size and cutting lengths of pipe (or center-to-center
dimensions).
(43)Â
Location and size of riser nipples.
(44)Â
Type of fittings and joints.
(45)Â
Location of all welds and bends.
(46)Â
The contractor shall specify on drawings any sections to be
shop welded and the type of fittings or formations to be used.
(47)Â
Type and locations of hangers.
(48)Â
Locations of sleeves.
(49)Â
Locations of braces, and methods of securing sprinklers.
(50)Â
All control valves.
(51)Â
All check valves.
(52)Â
All drain valves and pipes.
(53)Â
All test connections.
(54)Â
Make, type, model, and size of alarm valve.
(55)Â
Make, type, model, and size of dry pipe valve.
(56)Â
Make, type, model, and size of preaction.
(57)Â
Make, type, model, and size of deluge valve.
(58)Â
Type and location of alarm bells.
(59)Â
Size and location of standpipe risers.
(60)Â
Size and location of hose outlets.
(61)Â
Size and location of hand hose.
(62)Â
Size and location of monitor nozzles, and related equipment.
(63)Â
Private fire service main sizes, lengths, locations, materials,
point of connection to City main; the sizes, types and locations of
valves, valve indicators, regulators, meters, and valve pits; and
the depth of cover.
(64)Â
Piping provisions for flushing.
(65)Â
Where the equipment is to be installed as an addition to an
existing system, enough of the existing system indicated on the plans
to make all conditions clear to the AHJ.
(66)Â
For hydraulically designed systems, the information on the hydraulic
data nameplate, including the following:
(a)Â
System design requirements, including hazard and/or occupancy
classification.
(b)Â
Design area of water application in square feet or minimum number
of sprinklers designed to operate at one time.
(c)Â
Minimum rate of water application (density), gpm/square foot
or minimum flow rate per sprinkler in gpm.
(d)Â
Area per sprinkler in square feet.
(e)Â
Total water demand requirements as calculated, including allowance
for inside hose, outside hydrants, in-rack sprinklers, water curtains
and exposure sprinklers in gpm.
(f)Â
Limitations (spacing, flow, and pressure) on extended coverage
or other listed special sprinklers.
(67)Â
A graphic representation of the scale used on all plans.
(68)Â
Name and address of installing fire sprinkler contractor.
(69)Â
Phone number of installing fire sprinkler contractor.
(70)Â
State of Wisconsin automatic fire sprinkler contractor's license
number.
(71)Â
Hydraulic reference points shown on the plan that correspond
with comparable reference points on the hydraulic calculation sheets.
(72)Â
The minimum rate of water application (density), the design
area of water application, in-rack sprinkler demand, and the water
required for hose streams both inside and outside.
(73)Â
The total quantity of water and the pressure required noted
at a common reference point for each system.
(74)Â
Who determined the design criteria.
(75)Â
Relative elevations of sprinklers, junction points, and water
supply or reference points.
(76)Â
If the room design method is used, all unprotected wall openings
throughout the floor protected.
(77)Â
Calculation of loads for sizing and details of sway bracing.
(78)Â
The setting for pressure-reducing valves.
(79)Â
Information about backflow preventers (manufacturer, size, type).
(80)Â
Information about antifreeze solution used (type and amount).
(81)Â
Size and location of hydrants, showing size and number of outlets
and if outlets are to be equipped with independent gate valves. Whether
hose houses and equipment are to be provided, and by whom, shall be
indicated.
(82)Â
Static and residual hydrants that were used in flow tests shall
be shown.
(83)Â
Size, location, and piping arrangement of Fire Department connections.
(84)Â
The working plan submittal shall include the manufacturer's
installation instructions for any specially listed equipment, including
descriptions, applications, and limitations for any sprinklers, devices,
piping, or fittings.
(85)Â
The maximum spacing allowed for each type of sprinkler being
used based on the square footage used to determine the minimum flow
rate for the hydraulic calculations.
(86)Â
The size, make, type and model of the backflow device.
(87)Â
Any other information the AHJ deems necessary to be on the working
plans.
(88)Â
The working plan(s) for all specific occupancies shall include
the following:
(a)Â
The specific hazard the system is intended to protect.
(b)Â
The specific NFPA standard and/or code the system design criterion
is contained in.
(c)Â
The specific NFPA standard and/or code section the system design
criteria is contained in.
(d)Â
The maximum storage height of the commodity being protected.
(e)Â
The method of storage rack, solid pile, shelf or other.
(f)Â
The maximum ceiling height in the building and/or structure.
(g)Â
All aisles in the storage area.
(h)Â
All required flue spaces, transverse, longitudinal, and/or between
piles.
(i)Â
Any minimum clearance requirements between commodities.
(j)Â
Any minimum clearance requirements between incompatible commodities
and/or materials.
(k)Â
The required minimum clearance between the sprinkler deflectors
and the top of storage.
(l)Â
All storage information, limits and exact configurations shall
be on the working drawings prepared by the automatic fire sprinkler
contractor.
(89)Â
Water supply capacity information. The following information
shall be included:
(a)Â
Location and elevation of static and residual test gauge with
relation to the riser reference point.
(b)Â
Flow location.
(c)Â
Static pressure, psi (bar).
(d)Â
Residual pressure, psi (bar).
(e)Â
Flow, gpm (L/min).
(f)Â
Date.
(g)Â
Time.
(h)Â
Test conducted by or information supplied by.
(i)Â
Other sources of water supply, with pressure or elevation.
H.Â
Installation required. Automatic fire sprinkler systems shall be
installed in all structures where the floor area exceeds the thresholds
established in Table 155-21H of the specific occupancy type and construction
type involved. For the purpose of determining square footage as it
relates to the required installation of fire sprinklers in a building,
firewalls shall not be considered area dividers unless the firewall
is rated at four hours without penetrations and extends a minimum
of three feet above the roof.
Table 155-21H
| |||||
---|---|---|---|---|---|
Occupancy Type
|
Type I
|
Type II
|
Type III
|
Type IV
|
Type V
|
E*
|
All
|
All
|
All
|
All
|
All
|
F-2
|
5,000 SF
|
5,000 SF
|
3,000 SF
|
3,000 SF
|
3,000 SF
|
I-2
|
All
|
All
|
All
|
All
|
All
|
I-3
|
All
|
All
|
All
|
All
|
All
|
I-4
|
All
|
All
|
All
|
All
|
All
|
R-4
|
All
|
All
|
All
|
All
|
All
|
U
|
5,000 SF
|
5,000 SF
|
3,000 SF
|
3,000 SF
|
3,000 SF
|
Note:
| |
* Excludes single-family home day cares.
|
I.Â
Additional automatic fire sprinkler system installations required.
An automatic sprinkler system shall be installed in all:
(1)Â
Parking structures above and below ground with ceilings.
(2)Â
CBRFs (community-based residential facilities).
(3)Â
Adult family homes.
(4)Â
Throughout all dormitories, fraternities and sorority houses.
(5)Â
Throughout every building, new or existing, which by reason of its
construction or combustible occupancy involves a life hazard to its
occupants or in the judgment of the AHJ constitutes a fire menace.
J.Â
Basements and garages are to be designed to protect as a minimum
of for ordinary hazard occupancy.
K.Â
When an automatic fire sprinkler system is required to be installed
by this chapter but not the Wisconsin Department of Commerce, in a
structure that is not currently serviced by a municipal water source,
the following must be complied with:
(1)Â
Any required fire sprinkler system shall be installed in complete
compliance with the appropriate NFPA code(s) and/or standard(s).
(2)Â
Exception: For an automatic water supply for any fire sprinkler system(s)
required to be installed by this chapter but not required by the Wisconsin
Department of Commerce Code, the automatic water supply shall comply
with the following:
(a)Â
The automatic water supply for the automatic fire sprinkler
system(s) shall be conditionally approved by the AHJ.
(b)Â
The fire sprinkler system(s) shall be installed and connected
to a conditionally approved automatic water supply.
(c)Â
The required automatic water supply must be capable of delivering
the required quantity of water at the required pressure as determined
by hydraulically calculating the system demand in accordance with
NFPA 13 for the most hydraulically demanding area.
(d)Â
A letter from a licensed fire protection engineer or a State
of Wisconsin permitted fire protection designer attesting to the ability
of the system to comply with the above requirements shall be required
prior to occupancy.
(3)Â
Within 90 days after a municipal water system becomes available,
the sprinkler system shall be connected to the municipal water supply.
(4)Â
For the purpose of this chapter, an available municipal water supply
shall mean any of the following:
(a)Â
A municipal water main located at or near the streets adjacent
to the property on which the structure that is required to be sprinklered
is located.
(b)Â
A municipal water main located in a utility easement on or near
the property on which the structure that is required to be sprinklered
is located.
(c)Â
A municipal water main located under, at or near the streets
within 1,500 lineal feet of any part of the property the on which
the structure that is required to be sprinklered is located.
(d)Â
A municipal water main located in a utility easement within
1,500 lineal feet of any part of the property on which the structure
that is required to be sprinklered is located.
L.Â
All automatic fire sprinkler, fire control and/or fire suppression
systems shall comply with the following:
(1)Â
Be designed in accordance with the appropriate NFPA standards and/or
codes.
(2)Â
Be designed after a complete and correct owner's certificate,
using a form acceptable to the AHJ, has been obtained from the building
owner.
(3)Â
Be designed to protect the highest hazard present at any time in
the protected area.
(4)Â
Be monitored by a UL-listed central station for fire service that
is acceptable to the AHJ.
(5)Â
Have sprinkler control rooms located with adequate access for Fire
Department, sprinkler maintenance and inspection personnel, and shall
not be located within private dwellings with the exception of NFPA
13D systems.
(6)Â
Have direct access from the exterior to the sprinkler control valve
acceptable to the AHJ.
(7)Â
Have a bell (minimum ten-inch) and strobe installed, located above
the FDC.
(8)Â
The FDC must be located at least 40 feet from all gas meters, electrical
meters and transformers.
(9)Â
The FDC must be installed in a location acceptable to the AHJ, and
must be within 150 feet of a fire hydrant.
(10)Â
Be designed for the hazard being protected or as specifically
specified in this chapter and/or as acceptable to the AHJ.
(11)Â
All automatic fire sprinkler systems' hydraulic designs are
to be based on a maximum of 90% of the available water supply. (A
minimum of a 10% safety margin shall be maintained.)
(12)Â
All sprinkler systems designed shall be based on the most current
water flow test conducted in accordance with NFPA 291 that is acceptable
to the AHJ.
(13)Â
The AHJ must witness all water flow tests.
(14)Â
Have all working drawings with all required hydraulic calculations
prepared by the installing contractor and submitted to the AHJ for
review and conditional approval.
(15)Â
Include a complete and correct owner's certificate with
the approval submittal.
(16)Â
The owner's certificate must contain all information required
by the AHJ.
(17)Â
All storage information, limits and exact configurations shall
be on the working drawings prepared by the automatic fire sprinkler
contractor.
(18)Â
Be conditionally approved prior to any portion of the system
being installed.
M.Â
Maintenance of equipment.
(1)Â
Sprinkler systems which have been installed in compliance with a
permit or order, or because of any law or code, or have been installed
for any other reason, shall be maintained in operative condition at
all times. No owner or occupant shall reduce the effectiveness of
the protection so required; except this provision shall not prohibit
the owner or occupant from temporarily reducing or disconnecting the
protection system when making necessary repairs, alterations or additions
when a permit has been issued or permission has been granted by the
AHJ.
(2)Â
The AHJ shall be notified before repairs, alterations or additions
are started and shall be notified again when the system has been restored
to service.
(3)Â
The AHJ shall determine if a permit and/or a submittal and review
are required for any modifications and/or additions to any system.
(4)Â
The AHJ shall issue a permit and a conditional approval prior to
any modifications and/or additions to any system.
(5)Â
Inspections and maintenance of all systems shall be performed by an approved agent, pursuant to the NFPA procedures and requirements listed in §§ 155-12, 155-13 and 155-14 of this chapter. The property owner/occupant and sprinkler inspector shall immediately notify the Fire Department of any deficiencies found.
(6)Â
A service contract is required for annual service of the sprinkler
system according to NFPA 25. This will be required prior to obtaining
an occupancy permit on all newly constructed and existing buildings.
(7)Â
A service contract is required for the monitoring of systems where
monitoring is required.
(8)Â
The latest annual test report must be posted at the riser or a location
acceptable to the AHJ.
N.Â
Application to existing buildings.
(1)Â
Adult family homes and CBRFs, regardless of number of occupants or
class, must be retrofitted with fire sprinkler protection acceptable
to the AHJ.
(2)Â
Where the AHJ finds that an existing building, because of current
occupancy or a change in occupancy, constitutes a hazard to its occupants
or adjoining property, the AHJ may order compliance with the provisions
of this section. A hazard shall be determined by the existence of
one or more of the following conditions:
(a)Â
Any building which by reason of its construction or highly combustible
occupancy involves a hazard to its occupants or, in the judgment of
the AHJ, constitutes a fire menace, e.g., paint shop and other occupancies
involving processing, mixing, storing, and dispensing of volatile
liquids or solids.
(b)Â
Non-fire-resistive characteristics of a structure.
(c)Â
Accumulation of flammable or combustible materials.
(d)Â
Lack of accessibility to the premises for firefighting equipment.
(e)Â
Substantial number of fire calls or complaints on the premises.
(f)Â
Traffic patterns for pedestrian ingress and egress which require
protection under this section.
(g)Â
Insufficient ventilation system.
(h)Â
Lack of an internal communication system, or due to the size
or type of building making regular Fire Department radio communication
inoperable, the building owner is required to install a repeater system
or something comparable to assist radio communications.
(i)Â
Number, characteristics and movement of employees which require
protection under this section.
(3)Â
Installation of an automatic sprinkler system must be started within
one year from the service of such orders and shall be completed within
180 days after construction has started.
O.Â
Exemptions. At any location where the installation of sprinklers
may cause or increase an occupational hazard as determined by any
governmental authority having jurisdiction over such location or occupation,
the AHJ may waive any requirement to install an automatic fire sprinkler
system or any portion thereof.
P.Â
Remote Fire Department connections.
(1)Â
The AHJ is authorized to require a remote Fire Department connection
(FDC) to be installed for any system and facility for which the AHJ
deems it necessary.
(2)Â
All remote FDCs must be installed in a location that is acceptable
to the AHJ.
(3)Â
All remote FDCs must be installed in a manner that is acceptable
to the AHJ.
(4)Â
All remote FDCs, including all piping, must be tested hydrostatically
and flushed in a manner that is acceptable to the AHJ.
A.Â
Intent. The intent of this section is to require Fire Department
standpipe systems to be installed in structures to help firefighters
effectively extinguish a fire and help reduce property damage and
losses.
B.Â
Where required. Fire Department standpipe systems shall be installed
in the following structures:
(1)Â
Any structure required by the State of Wisconsin statutes or administrative
codes.
(2)Â
In all new structures over two stories in height.
(3)Â
In any structure that exceeds 10,000 square feet in floor area.
(4)Â
In any structure for which the AHJ deems standpipes are necessary
for firefighting purposes.
C.Â
Installation requirements. Fire Department standpipes shall be designed
and installed in accordance with this section. Where any requirement
in this section is more restrictive than any NFPA standard and/or
code and/or state code, the requirements in this section must be complied
with.
(1)Â
The installation of standpipes shall be in accordance with this section
and NFPA 14.
(2)Â
The class and location of standpipes and Fire Department connections
shall be acceptable to the AHJ.
(3)Â
All standpipe systems' hydraulic designs are to be based on a maximum
of 90% of the available water supply. (A minimum of a 10% safety margin
shall be maintained.)
(4)Â
All 2Â 1/2 inch hose valves must have a 2Â 1/2 inch by 1Â 1/2
inch reducer, cap and chain attached.
(5)Â
The location of standpipe hose connections shall be accessible and
shall be located so that all portions of the building are within 100
feet of hose attached to a hose valve. This distance must be measured
using the normal aisles or the path a hose would be laid as determined
by the AHJ.
(6)Â
The locations of all hose valves shall be acceptable to the AHJ.
(7)Â
The AHJ may require additional standpipes and/or hose valves to be
installed.
(8)Â
When required by the AHJ, an approved standpipe shall be installed
as construction progresses to make it available for Fire Department
use in the topmost floors constructed. Temporary standpipes shall
be provided in place of permanent standpipes when required during
the period of construction on buildings required by this chapter.
(9)Â
The location of all Fire Department connections for standpipes shall
be approved by the AHJ.
(10)Â
The Fire Department connections shall be located at least 40
feet from all electrical transformers, gas meters, or propane storage.
(11)Â
Temporary standpipes are required on buildings over two stories
in height.
(12)Â
All manual wet and all automatic standpipes must have water-flow
switches and alarm test connections.
D.Â
Approval requirements. Complete plans and calculations for all standpipes
must be submitted to the Fire Department and conditionally approved
prior to installation of any standpipe.
E.Â
Permit requirement. The Fire Department must issue a permit to install
all standpipes prior to installation.
F.Â
Remote Fire Department connections.
(1)Â
The AHJ is authorized to require a remote Fire Department connection
(FDC) to be installed for any system and facility for which the AHJ
deems it necessary.
(2)Â
All remote FDCs must be installed in a location that is acceptable
to the AHJ.
(3)Â
All remote FDCs must be installed in a manner that is acceptable
to the AHJ.
(4)Â
All remote FDCs, including all piping, must be tested hydrostatically
and flushed in a manner that is acceptable to the AHJ.
A.Â
Intent. The intent of this section is to provide a means for automatic
detection of fire conditions and/or to provide warning notification
throughout all buildings and occupancies built hereinafter, structurally
altered, and/or added to. Fire alarm systems are intended to provide
additional life safety and help reduce property loss through early
detection of fires, providing warning to occupants and automatically
notifying the Fire Department of fire.
B.Â
Installation required. A fire alarm system shall be installed in
all structures where the floor area exceeds the thresholds established
in Table 155-23B of the specific occupancy type and construction type
involved.
Table 155-23B
| |||||
---|---|---|---|---|---|
Occupancy Type
|
Type I
|
Type II
|
Type III
|
Type IV
|
Type V
|
E*
|
All
|
All
|
All
|
All
|
All
|
I-2
|
All
|
All
|
All
|
All
|
All
|
I-3
|
All
|
All
|
All
|
All
|
All
|
I-4
|
All
|
All
|
All
|
All
|
All
|
R-4
|
All
|
All
|
All
|
All
|
All
|
U
|
5,000 SF
|
5,000 SF
|
3,000 SF
|
3,000 SF
|
3,000 SF
|
Note:
| |
* Excludes single-family home day cares; state statutes apply.
|
C.Â
Code compliance. All fire alarm systems installed, modified, altered
and/or repaired shall comply with this chapter and all of the applicable
NFPA codes and/or standards.
D.Â
Code conflicts. If any conflicts exist between this chapter and any
NFPA code and/or standard, the most restrictive, as determined by
the AHJ, shall be enforced by the AHJ.
E.Â
Minimum system requirements. The following minimum system requirements shall be met when any occupancy type exceeds the limits in § 155-23B. Minimum system requirements shall include:
(1)Â
Audible notification appliances shall be installed throughout protected
premises.
(2)Â
Visible notification appliances shall be installed throughout protected
premises, except for the following:
(a)Â
Closets and/or other similar small storage rooms that do not
exceed 50 square feet in floor area and are not normally occupied.
(b)Â
Normally unoccupied crawl spaces.
(c)Â
Normally unoccupied attic spaces.
(d)Â
Any nonaccessible area.
(e)Â
Any area for which the AHJ deems visible notification appliances
are not required.
(3)Â
Manual initiating devices (pull stations) shall be located at all
points of egress, including all exit doors on every floor and/or building
level.
(4)Â
Water flow detection devices shall be connected to the fire alarm
system to specifically activate the notification appliances upon water
flow.
(5)Â
Fire suppression system activation alarms shall be connected to the
protected premises' fire alarm system to specifically activate the
notification appliances upon system activation. This includes but
is not limited to wet chemical, CO2, clean
agent, water mist and dry chemical systems.
(6)Â
Fire control and/or suppression systems' supervisory condition indicators
shall be connected to and monitored by the fire alarm system. This
specifically includes but is not limited to: valve supervisory switches
(tamper switches), high air switches, low air switches, high water
level switches, low water switches, low temperature switches, low
water temperature switches, fire pump condition indicators and/or
any other situation or condition deemed necessary by the AHJ.
(7)Â
Fire alarm systems shall be addressable and capable of indicating
the status of all specific components connected to the system.
(8)Â
All fire alarm systems shall be monitored by a service acceptable
to the AHJ.
(9)Â
Fire alarm annunciators shall be installed in all protected premises.
The number and locations of the fire alarm annunciators installed
shall be acceptable to the AHJ.
(10)Â
As determined by the AHJ, any additional notification and/or
initiation appliances/devices may be required due to size, occupancy
hazards, building construction, and/or occupancy use.
(11)Â
The wiring class and style must be acceptable to the AHJ.
(12)Â
The wiring class and style required will vary depending on the
type of construction, occupancy, building height and/or building size.
F.Â
Submittals for fire alarm systems. Submittals for fire alarm systems are intended to provide basic information consistent with the objective of installing a fully operational, code-compliant fire alarm system and to provide the basis for the record drawings required by NFPA 72. Conditional approval of a fire alarm system submittal and/or any portion thereof is not intended to imply waiver or modification of any requirements of any code or any other applicable criteria. See also § 155-31.
G.Â
Three sets of each fire alarm submittal shall be submitted for conditional
approval. The municipality may retain two copies of each submittal,
and one copy will be returned to the installing contractor.
H.Â
Fire alarm submittals shall include all information required by the
AHJ and include, to an extent commensurate with the extent of the
work being performed, the following:
(1)Â
Shop drawings/plans.
(2)Â
Riser diagrams (except for systems in single-story buildings).
(3)Â
Control panel wiring diagrams.
(4)Â
Point-to-point wiring diagrams.
(5)Â
Typical wiring diagrams.
(6)Â
Specifications.
(7)Â
Battery calculations.
(8)Â
Voltage drop calculations acceptable to the AHJ.
(9)Â
Complete current manufacturers' equipment data sheets, including
all installation and operation manuals for all equipment that will
be used for the system.
I.Â
All shop drawings/plans shall be drawn on sheets of uniform size
to a recognized scale and shall include the following information:
(1)Â
Name of owner and occupant.
(2)Â
Location, including street address.
(3)Â
Device legend.
(4)Â
Date.
(5)Â
Name of the person that designed the fire alarm system.
(6)Â
Name, address, phone number and facsimile number of the company that
designed the fire alarm system.
(7)Â
Name address, phone number and facsimile number of the company that
is going to install the fire alarm system.
(8)Â
Name address and phone number of the fire alarm system monitoring
company.
(9)Â
Name of the control panel manufacturer.
(10)Â
Model number of the control panel.
(11)Â
Control panel wiring diagrams.
(12)Â
Point-to-point wiring diagrams.
(13)Â
Typical wiring diagrams.
(14)Â
Floor identification.
(15)Â
Point of compass.
(16)Â
Graphic scale.
(17)Â
All walls and doors.
(18)Â
All partitions extending to within 18 inches of the finished
ceiling.
(19)Â
Room descriptions.
(20)Â
Fire alarm device/component locations.
(21)Â
Locations of fire alarm primary power connection(s).
(22)Â
Locations of monitor/control interfaces to other systems.
(23)Â
Riser locations.
(24)Â
The location of the electrical panel that has the control panel
circuit breaker.
(25)Â
All ceiling heights.
(26)Â
Type of wiring to be used.
(27)Â
Wire gauge to be used.
(28)Â
Wiring class and style.
J.Â
Fire alarm system riser diagrams shall include the following information:
(1)Â
General arrangement of the system, in building cross-section.
(2)Â
Number of risers.
(3)Â
Type and number of circuits in each riser.
(4)Â
Type and number of fire alarm system components/devices on each circuit,
on each floor or level.
(5)Â
Control panel wiring diagram.
(6)Â
Power supply wiring diagram.
(7)Â
Battery charger wiring diagram.
(8)Â
Annunciator(s) wiring diagram.
K.Â
Wiring diagrams shall be provided and shall include the following
information:
(1)Â
Identification of the control equipment depicted.
(2)Â
Location(s) of control panels.
(3)Â
All field wiring terminals.
(4)Â
Terminal identifications.
(5)Â
All circuits connected to field wiring terminals.
(6)Â
Circuit identifications.
(7)Â
All indicators.
(8)Â
Manual controls.
(9)Â
Full text of all labels.
(10)Â
Field connections to supervising station signaling equipment.
(11)Â
Releasing equipment.
(12)Â
Fire safety control interfaces.
M.Â
Inspections, testing and recordkeeping.
(1)Â
The Fire Department and/or their representative(s) may inspect all
fire alarm system installations. All equipment must be inspected prior
to any equipment being concealed.
(2)Â
All inspections must be scheduled with the Fire Department at least
72 hours in advance and prior to any fire alarm system component being
concealed.
(3)Â
The AHJ may witness all acceptance tests.
(4)Â
Witnessing of all tests must be scheduled with the Fire Department
at least 72 hours in advance of any testing.
(5)Â
Two copies of a completed preliminary fire alarm system record of
completion required by NFPA 72 must be provided to the AHJ prior to
final acceptance.
(6)Â
Permanent records must be provided in accordance with NFPA 72. This
includes the completed fire alarm system record of completion form.
N.Â
Special requirements. On all buildings over four stories in height,
a fire command center for the Fire Department's operations shall be
provided. The fire command center shall comply with NFPA 72 and shall
contain the features required in the International Fire Code and NFPA
1 and NFPA 101. Two-way telephone communication service shall be provided
for the Fire Department's use. This system shall be in accordance
with NFPA 72. The communications system shall operate between the
central control station and every elevator car, every elevator lobby,
and each floor level of exit stairs.
O.Â
Testing. When a fire alarm system and/or connected component is installed
or altered, a fire alarm system performance test shall be conducted.
Once the appropriate plans, permits, and installation work have been
completed, the installing contractor shall contact the AHJ to set
up the witnessing of a performance test to ensure all appliances are
installed and functioning properly. Prior to requesting that the AHJ
witness a performance test, the responsible parties must provide the
AHJ with a completed copy of the record of completion required by
NFPA 72.
P.Â
Maintenance. All devices shall be installed, maintained, and tested
in accordance with NFPA 72 standards. If at any point a fire alarm
fails to pass the annual test set forth in NFPA 72, the building owner
and fire alarm system tester/inspector shall notify the AHJ of the
test results. It shall be the AHJ's determination if that failed
system is to be repaired or upgraded to comply with this chapter.
Q.Â
Fire alarm control panels. Fire alarm control panels shall display
the status of the system components and be installed in a location
acceptable to the AHJ. Adequate access for Fire Department, alarm
maintenance, and inspection personnel shall be maintained. Fire alarm
control panels shall not be located within private dwellings, with
the exception of one- and two-family dwellings.
A.Â
Intent. The intent of this section is to require automatic fire extinguishing
systems in vent hoods and duct systems in all cooking areas to effectively
extinguish fire at its source and reduce property damage and losses.
B.Â
Where required. Automatic fire extinguishing systems shall be installed
in any cooking area required by the State of Wisconsin codes and any
area in which the AHJ has determined a potential fire risk exists.
C.Â
Installation requirements.
(1)Â
All fire extinguishing systems must be submitted to the AHJ for conditional
approval.
(2)Â
All fire extinguishing system submittals must include a dimensional
drawing including the following information:
(a)Â
The owner's name.
(b)Â
The owner's address.
(c)Â
The owner's phone number.
(d)Â
The exhaust hood(s) and duct(s).
(e)Â
The area of the protected surface.
(f)Â
The name of the installing contractor.
(g)Â
The address of the installing contractor.
(h)Â
The phone number of the installing contractor.
(i)Â
The fire extinguishing system equipment manufacturer's
name.
(j)Â
The fire extinguishing system equipment manufacturer's
address.
(k)Â
The fire extinguishing system equipment manufacturer's
phone number.
(l)Â
The fire extinguishing system equipment manufacturer's
model designations.
(m)Â
The name of the extinguishing agent being used.
(n)Â
The size and number of tanks to be installed.
(o)Â
All piping systems, with lengths and sizes.
(p)Â
All nozzles, with the fire extinguishing system equipment manufacturer's
model designations.
(q)Â
The distance of nozzles above the cooking surface.
(r)Â
The location and type of detection devices.
(s)Â
All cooking equipment that is to be protected.
(t)Â
The location of any gas shutoff valves.
(u)Â
The location of manual pull stations.
(v)Â
Copies of the fire extinguishing system equipment manufacturer's
data sheets for all equipment that will be installed, including model
designations, shall be included with the required submittal.
(3)Â
The system shall be provided with automatic fuel shutoff.
(4)Â
A Class K fire extinguisher shall be installed per NFPA 10.
(5)Â
Alarms shall be connected to the fire alarm system per NFPA 72.
(6)Â
Cooking equipment used in processes producing smoke or grease-laden
vapors shall be equipped with an exhaust system that complies with
all the equipment and performance requirements of NFPA 1 and NFPA
96, and all such equipment and performance shall be maintained per
NFPA 96 during all periods of operation of the cooking equipment.