All required passenger and freight elevators in all buildings
and structures hereinafter constructed, except one- and two-family
residential occupancies, shall:
A. Provide at least one elevator to all floors of such a size and arrangement
to accommodate a twenty-four-inch by eighty-five-inch ambulance stretcher
in the horizontal, open position.
B. The elevator arranged to accommodate an ambulance stretcher shall
be identified by the Star of Life. This symbol shall not be less than
three inches in height and shall be placed on both sides of the hoistway
door frame.
Prior to, and as a condition of, obtaining an occupancy permit,
the owner of all buildings, except one- and two-family units, shall
supply the Fire Department with an 8 1/2-inch by eleven-inch
site plan which includes the following:
A. Location(s) of gas and electrical shutoffs.
B. Location(s) of high pile storage.
C. Location of Fire Department connection and sprinkler control valve.
D. Dimensions of the structure in feet.
E. Location of the standpipe(s).
G. Apartments, suites, or unit numbers.
H. Location of all hydrants on the site and surrounding streets.
I. Location of alarm panels.
J. Location of access box(es).
K. Special fire protection and area covered: heat vents, FM 200 systems,
etc.
L. Special construction features: skylights, blowout walls, etc.
M. Floor plans, including roof access points.
The Fire Department shall conduct plan reviews and approvals
of fire-safety-related elements prior to construction of any public
buildings and/or places of employment.
All structures that have automatic sprinkler systems:
A. Shall have sprinkler control rooms located with adequate access for
Fire Department, sprinkler maintenance and inspection personnel.
B. Shall not be located within private dwellings, with the exception
of NFPA 13D systems.
C. Shall have direct access from the exterior to the sprinkler control
valve(s) that is acceptable to the AHJ.
Entry key override switches shall be required on any exit door
at any location which uses a card reader entry system and/or a magnetic
door lock security system.