A certain document, a copy of which is on file in the office of the city secretary of the city, being marked and designated as the International Residential Code, 2021 edition, including appendix, as published by the International Code Council, be and is hereby adopted as the residential code of the city for regulating and governing the construction, alteration, movement, enlargement, replacement, repair, equipment, location, removal and demolition of detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories in height with separate means of egress as herein provided; providing for the issuance of permits and collection of fees therefor, and each and all of the regulations, provisions, penalties, conditions and terms of said residential code on file in the office of the city are hereby referred to, adopted, and made a part hereof, as if fully set out in this article, with the additions, insertions, deletions and changes, if any, adopted by the city.
(Ordinance 2017-04-06 adopted 4/10/17; Ordinance 2025-03-15 adopted 3/24/2025)
The residential code adopted in this article shall be subject to the exceptions and amendments to the International Residential Code, 2021 edition, which shall herein after read as follows:
The following sections, paragraphs, and sentences of the 2021 International Residential Code are hereby amended as follows: Standard type is text from the IRC. Underlined type is text inserted. Lined through type is deleted text from IRC. A triple asterisk identifies a new or revised amendment with the 2021 code.
The energy provisions in IRC Chapter 11 is deleted in its entirety.
Reference the 2021 IECC for energy code provisions and recommended amendments.
**Section R101.1 Title, is amended as follows:
101.1 Title.
These provisions shall be known as the Residential Code for One- and Two-family Dwellings of Lancaster, Texas, and shall be cited as such and will be referred to as "this code."
**Section R112 Board of Appeal, is deleted in its entirety and replaced with the following:
Any appeal of orders, decisions or determinations made by the building official relative to the application and interpretation of this code shall be heard by the City's Property Standards and Appeals Board as provided for by the City's Code of Ordinances.
**Section R102.4; change to read as follows:
R102.4 Referenced codes and standards. The codes, when specifically adopted, and standards referenced in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections R102.4.1 and R102.4.2. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference made to NFPA 70 or the Electrical Code shall mean the Electrical Code as adopted.
**Section R103 and R103.1 amend to insert the Department Name
DEPARTMENT OF BUILDING SAFETY THE BUILDING INSPECTIONS DEPARTMENT]
R103.1 Creation of enforcement agency. The Department of Building Safety. The City of Lancaster Building Inspections Department is hereby created and the official in charge thereof shall be known as the building official.
**Section R104.10.1 Flood Hazard areas; delete this section.
**Section R105.3.1.1 & R106.1.4; delete these sections.
**Section R110 (R110.1 through R110.5); delete the section.
***Section R202; change definition of "Townhouse Unit" to read as follows:
TOWNHOUSE UNIT. A single-family dwelling unit separated by property lines in a townhouse that extends from foundation to roof and that has a yard or public way on not less than two sides.
***Table R301.2(1); fill in as follows; delete remainder of table Manual J Design Criteria and footnote N:
GROUND SNOW LOAD
WIND DESIGN
SEISMIC DESIGN CATEGORYf
A
SUBJECT TO DAMAGE FROM
WINTER DESIGN TEMPe
ICE BARRIER UNDER-LAYMENTh
FLOOD HAZARDSg
AIR FREEZING INDEXi
MEAN ANNUAL TEMPj
SPEEDd
(MPH)
Topographic Effectsk
Special Wind RegionL
Windborne Debris Zonem
Weatheringa
Frost Line Depthb
Termitec
5 lb/ft
115 (3 secgust)/76 fastest mile
No
No
No
Moderate
6"
Very Heavy
22° F
No
Local Code
150
64.9° F
**Section R112 Board of Appeal, is deleted in its entirety and replaced with the following:
Any appeal of orders, decisions or determinations made by the building official relative to the application and interpretation of this code shall be heard by the City's Property Standards and Appeals Board as provided for by the City's Code of Ordinances.
**Section R113 Violations, is amended by replacing section 113.2 and 113.3 with the following:
113.2 Notice of Violation. The building official may, but is not required to, serve a notice of violation or order upon the person responsible for the erection, construction, alteration, extension, repair, moving, removal, demolition or occupancy of a building or structure in violation of the provisions of this code, or in violation of a permit or certificated issued under the provisions of this code. Such notice may direct the discontinuance of the illegal action or condition an the abatement of the violation.
113.3 Prosecution of violation. The building official, any code enforcement officer, or any law enforcement official of the City may issue a citation regarding any violation of this code, regardless of whether a notice has been previously issued. Any of these persons may also request the legal counsel of the jurisdiction to institute an appropriate proceeding at law or in equity to restrain, correct, or abate such violation, or to require the removal or termination of the unlawful occupancy of the building or structure in violation of the provisions of this code or of the order or direction made pursuant thereto.
**Section R302.1; add exception #6 to read as follows:
Exceptions: {previous exceptions unchanged}
6.
Open non-combustible carport structures may be constructed when also approved within adopted ordinances.
**Section R302.3; add exception #3 to read as follows:
Exceptions:
1.
{existing text unchanged}
2.
{existing text unchanged}
3.
Two-family dwelling units that are also divided by a property line through the structure shall be separated as required for townhouses.
***Section R302.2.6; delete exception #6:
Exceptions: {previous exceptions unchanged}
6.
Townhouse units protected by a fire sprinkler system complying with Section P2904 or NFPA 13D.
**Section R302.5.1; change to read as follows:
R302.5.1 Opening protection. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood doors not less than 13/8 inches (35 mm) in thickness, solid or honeycomb core steel doors not less than 13/8 inches (35 mm) thick, or 20-minute fire-rated doors. Equipped with a self closing or automatic closing device.
**Section R303.3, exception; amend to read as follows:
Exception: {existing text unchanged} Spaces containing only a water closet or water closet and a lavatory may be ventilated with an approved mechanical recirculating fan or similar device designed to remove odors from the air.
Section R3073; amend to read as follows:
***R307.3 Blocking. Required at one toilet at grade level. Blocking per Sec. R307.4 and Figure 307.4, shall be installed at rear wall and one wall adjacent to toilet at the lowest living level where a toilet is provided.
Section R307.4; amend to read as follows:
***R307.4 Blocking. Blocking may be 1/2" plywood or equivalent or 2 x solid wood blocking flush with wall.
006 Blocking.tif
**Section R313.2 One and Two Family Dwellings; delete this section and subsection in their entirety.
***Section R315.2.2 Alterations, repairs and additions; amend to read as follows:
Exception:
1.
[existing text remains]
2.
Installation, alteration or repairs of all electrically powered mechanical systems or plumbing appliances.
**Section R322 Flood Resistant Construction; deleted section.
***Section 327.1.1; add to read as follows:
Section 327.1.1 Adjacency to Structural Foundation. Depth of the swimming pool and spa shall maintain a ratio of 1:1 from the nearest building foundation or footing of a retaining wall.
Exception: A sealed engineered design drawing of the proposed new structure shall be submitted for approval.
**Section R401.2; amended by adding a new paragraph following the existing paragraph to read as follows.
Section R401.2. Requirements. {existing text unchanged} . . .
Every foundation and/or footing, or any size addition to an existing post-tension foundation, regulated by this code shall be designed and sealed by a Texas-registered engineer.
**Section R602.6.1; amend the following:
R602.6.1 Drilling and notching of top plate. When piping or ductwork is placed in or partly in an exterior wall or interior load-bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 Ga) and 1 1/2 inches (38) mm 5 inches (127 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) having a minimum length of 1 1/2 inches (38 mm) at each side or equivalent. Fasteners will be offset to prevent splitting of the top plate material. The metal tie must extend a minimum of 6 inches past the opening. See figure R602.6.1. {remainder unchanged}
**Figure R602.6.1; delete the figure and insert the following figure:
006 Figure R602. 6.1.tif
**Add section R703.8.4.1.2 Veneer Ties for Wall Studs; to read as follows:
R703.8.4.1.2 Veneer Ties for Wall Studs. In stud framed exterior walls, all ties may be anchored to studs as follows:
1.
When studs are 16 in (407 mm) o.c., stud ties shall be spaced no further apart than 24 in (737 mm) vertically starting approximately 12 in (381 mm) from the foundation; or
2.
When studs are 24 in (610 mm) o.c., stud ties shall be spaced no further apart than 16 in (483 mm) vertically starting approximately 8 in (254 mm) from the foundation.
**Section R902.1; amend and add exception #5 to read as follows:
R902.1 Roofing covering materials. Roofs shall be covered with materials as set forth in Sections R904 and R905. Class A, B, or C roofing shall be installed. in designated by law as requiring their use or when the edge of the roof is less than 3 feet from a lot line. {remainder unchanged}
Exceptions:
1.
{text unchanged}
2.
{text unchanged}
3.
{text unchanged}
4.
{text unchanged}
5.
Non-classified roof coverings shall be permitted on one-story detached accessory structures used as tool and storage sheds, playhouses, and similar uses, provided the floor area does not exceed (area defined by jurisdiction).
**Chapter 11 [RE] - Energy Efficiency is deleted in its entirety; reference the 2021 IECC for energy code provisions and recommended amendments.
**Section M1305.1.2; change to read as follows:
M1305.1.2 Appliances in attics. Attics containing appliances shall be provided . . . {bulk of paragraph unchanged} . . . side of the appliance. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm by 762 mm), and large enough to allow removal of the largest appliance. As a minimum, for access to the attic space, provide one of the following:
1.
A permanent stair.
2.
A pull down stair with a minimum 300 lb (136 kg) capacity.
3.
An access door from an upper floor level.
Exceptions: [remaining text unchanged]
**Section M1411.3; change to read as follows:
M1411.3 Condensate disposal. Condensate from all cooling coils or evaporators shall be conveyed from the drain pan outlet to an approved place of disposal a sanitary sewer through a trap, by means of a direct or indirect drain. {remaining text unchanged}
**Section M1411.3.1, items 3 and 4; add text to read as follows:
M1411.3.1 Auxiliary and secondary drain systems. {bulk of paragraph unchanged}
1.
{text unchanged}
2.
{text unchanged}
3.
An auxiliary drain pan. . . {bulk of text unchanged}. . . with Item 1 of this section. A water level detection device may be installed only with prior approval of the building official.
4.
A water level detection device. . . {bulk of text unchanged}. . . overflow rim of such pan. A water level detection device may be installed only with prior approval of the building official.
**Section M1411.3.1.1; add text to read as follows:
M1411.3.1.1 Water-level monitoring devices. On down-flow units . . .{bulk of text unchanged}. . . installed in the drain line. A water level detection device may be installed only with prior approval of the building official.
**M1503.6 Makeup Air Required; amend and add exception as follows:
M1503.6 Makeup air required. Where one or more gas, liquid or solid fuel-burning appliance that is neither direct-vent nor uses a mechanical draft venting system is located within a dwelling unit's air barrier, each exhaust system capable of exhausting in excess of 400 cubic feet per minute (0.19 m3/s) shall be mechanically or passively provided with makeup air at a rate approximately equal to the difference between exhaust air rate and 400 cubic feet per minute. Such makeup air systems shall be equipped with not fewer than one damper complying with Section M1503.6.2.
Exception: Makeup air is not required for exhaust systems installed for the exclusive purpose of space cooling and intended to be operated only when windows or other air inlets are open. Where all appliances in the house are of sealed combustion, power-vent, unvented, or electric, the exhaust hood system shall be permitted to exhaust up to 600 cubic feet per minute (0.28 m3/s) without providing makeup air. Exhaust hood systems capable of exhausting in excess of 600 cubic feet per minute (0.28 m3/s) shall be provided with a makeup air at a rate approximately to the difference between the exhaust air rate and 600 cubic feet per minute.
**Section M2005.2; change to read as follows:
M2005.2 Prohibited locations. Fuel-fired water heaters shall not be installed in a room used as a storage closet. Water heaters located in a bedroom or bathroom shall be installed in a sealed enclosure so that combustion air will not be taken from the living space. Access to such enclosure may be from the bedroom or bathroom when through a solid door, weather-stripped in accordance with the exterior door air leakage requirements of the International Energy Conservation Code and equipped with an approved self-closing device. Installation of direct-vent water heaters within an enclosure is not required.
**Section G2408.3 (305.5) Private Garages; delete this section in its entirety.
**Section G2415.2 (404.2) CSST; add a second paragraph to read as follows:
Both ends of each section of medium pressure gas piping shall identify its operating gas pressure with an approved tag. The tags are to be composed of aluminum or stainless steel and the following wording shall be stamped into the tag:
"WARNING: 1/2 to 5 psi gas pressure - Do Not Remove"
**Section G2415.12 (404.12) and G2415.12.1 (404.12.1); change to read as follows:
G2415.12 (404.12) Minimum burial depth. Underground piping systems shall be installed a minimum depth of 12 inches (305 mm) 18 inches (457 mm) below grade, except as provided for in Section G2415.12.1.
G2415.12.1 (404.12.1) Individual Outdoor Appliances; delete in its entirety.
**Section G2417.1 (406.1); change to read as follows:
G2417.1 (406.1) General. Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested to determine that the materials, design, fabrication, and installation practices comply with the requirements of this code. The permit holder shall make the applicable tests prescribed in Sections 2417.1.1 through 2417.1.5 to determine compliance with the provisions of this code. The permit holder shall give reasonable advance notice to the building official when the piping system is ready for testing. The equipment, material, power and labor necessary for the inspections and test shall be furnished by the permit holder and the permit holder shall be responsible for determining that the work will withstand the test pressure prescribed in the following tests.
**Section G2417.4; change to read as follows:
G2417.4 (406.4) Test pressure measurement. Test pressure shall be measured with a monometer or with a pressure-measuring device designed and calibrated to read, record, or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Mechanical gauges used to measure test pressure shall have a range such that the highest end of the scale is not greater than five times the test pressure.
**Section G2417.4.1; change to read as follows:
G2417.4.1 (406.4.1) Test pressure. The test pressure to be used shall be no less than 3 psig (20 kPa gauge), or at the discretion of the Code Official, the piping and valves may be tested at a pressure of at least six (6) inches (152 mm) of mercury, measured with a manometer or slope gauge, irrespective of design pressure. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. For tests requiring a pressure of 3 psig, diaphragm gauges shall utilize a dial with a minimum diameter of three and one half inches (3 1/2"), a set hand, 1/10 pound incrementation and pressure range not to exceed 6 psi for tests requiring a pressure of 3 psig. For tests requiring a pressure of 10 psig, diaphragm gauges shall utilize a dial with a minimum diameter of three and one-half inches (3 1/2"), a set hand, a minimum of 2/10 pound incrementation and a pressure range not to exceed 20 psi. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.48 kPa) (1/2 psi) and less than 200 inches of water column pressure (52.2 kPa) (7.5 psi), the test pressure shall not be less than ten (10) pounds per square inch (69.6 kPa). For piping carrying gas at a pressure that exceeds 200 inches of water column (52.2 kPa) (7.5 psi), the test pressure shall be not less than one and one-half times the proposed maximum working pressure.
Diaphragm gauges used for testing must display a current calibration and be in good working condition. The appropriate test must be applied to the diaphragm gauge used for testing.
**Section G2417.4.2; change to read as follows:
G2417.4.2 (406.4.2) Test duration. The test duration shall be held for a length of time satisfactory to the Building Official, but in no case for be not less than 10 fifteen (15) minutes. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure (3.48 kPa), the test duration shall be held for a length of time satisfactory to the Building Official, but in no case for less than thirty (30) minutes.
**Section G2420.1 (406.1); add section G2420.1.4 to read as follows:
G2420.1.4 Valves in CSST installations. Shutoff valves installed with corrugated stainless steel (CSST) piping systems shall be supported with an approved termination fitting, or equivalent support, suitable for the size of the valves, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration but in no case greater than 12-inches from the center of the valve. Supports shall be installed so as not to interfere with the free expansion and contraction of the system's piping, fittings, and valves between anchors. All valves and supports shall be designed and installed so they will not be disengaged by movement of the supporting piping.
**Section G2420.5.1 (409.5.1); add text to read as follows:
G2420.5.1 (409.5.1) Located within the same room. The shutoff valve. . . {bulk of paragraph unchanged}. . . in accordance with the appliance manufacturer's instructions. A secondary shutoff valve must be installed within 3 feet (914 mm) of the firebox if appliance shutoff is located in the firebox.
**Section G2421.1 (410.1); add text and Exception to read as follows:
G2421.1 (410.1) Pressure regulators. A line pressure regulator shall be . . . {bulk of paragraph unchanged}. . . approved for outdoor installation. Access to regulators shall comply with the requirements for access to appliances as specified in Section M1305.
Exception: A passageway or level service space is not required when the regulator is capable of being serviced and removed through the required attic opening.
**Section G2422.1.2.3 (411.1.3.3) Prohibited locations and penetrations; delete exception 1 and exception 4.
**Section G2445.2 (621.2); add exception to read as follows:
G2445.2 (621.2) Prohibited use. One or more unvented room heaters shall not be used as the sole source of comfort heating in a dwelling unit.
Exception: Existing approved unvented room heaters may continue to be used in dwelling units, in accordance with the code provisions in effect when installed, when approved by the Building Official unless an unsafe condition is determined to exist as described in International Fuel Gas Code Section 108.7 of the Fuel Gas Code.
**Section G2448.1.1 (624.1.1); change to read as follows:
G2448.1.1 (624.1.1) Installation requirements. The requirements for water heaters relative to access, sizing, relief valves, drain pans and scald protection shall be in accordance with this code.
**Section P2603; add to read as follows:
P2603.3 Protection against corrosion. Metallic piping, except for cast iron, ductile iron and galvanized steel, shall not be placed in direct contact with steel framing members, concrete or cinder walls and floors or other masonry. Metallic piping shall not be placed in direct contact with corrosive soil. Where sheathing is used to prevent direct contact, the sheathing shall have a thickness of not less than 0.008 inch (8 mil) (0.203 mm) and the sheathing shall be made of approved material plastic. Where sheathing protects piping that penetrates concrete or masonry walls or floors, the sheathing shall be installed in a manner that allows movement of the piping within the sheathing.
**Section P2603.5.1 Sewer Depth; change to read as follows:
P2603.5.1 Sewer depth. Building sewers that connect to private sewage disposal systems shall be a minimum of [number] inches (mm) below finished grade at the point of septic tank connection. Building sewers shall be a minimum of 12 inches (304 mm) below grade.
***Section P2604; add to read as follows:
P2604.2.1 Plastic sewer and DWV piping installation. Plastic sewer and DWV piping installed underground shall be installed in accordance with the manufacturer's installation instructions. Trench width shall be controlled to not exceed the outside the pipe diameter plus 16 inches or in a trench which has a controlled width equal to the nominal diameter of the piping multiplied by 1.25 plus 12 inches. The piping shall be bedded in 4 inches of granular fill and then backfilled compacting the side fill in 6-inch layers on each side of the piping. The compaction shall be to minimum of 85 percent standard proctor density and extend to a minimum of 6 inches above the top of the pipe.
** Section P2801; change to read as follows:
P2801.6 Required pan. Where a storage tank-type water heater or a hot water storage tank is installed in a location where water leakage from the tank will cause damage, the tank shall be installed in a pan constructed of one of the following:
1.
Galvanized steel or aluminum of not less than 0.0236 inch (0.6010 mm) in thickness.
2.
Plastic not less than 0.036 inch (0.9 mm) in thickness.
3.
Other approved materials.
A plastic pan beneath a gas fired water heater shall be constructed of material having a flame spread index of 25 or less and a smoke developed index of 450 or less when tested in accordance with ASTM E84 or UL 723.
**Section P2801.6.1; change to read as follows:
Section P2801.6.1 Pan size and drain. The pan shall be not less than 1 1/2 inches (38 mm) in depth and shall be of sufficient size and shape to receive all dripping or condensate from the tank or water heater. The pan shall be drained by an indirect waste pipe having a diameter of not less than 3/4 inch (19 mm). Piping for safety pan drains shall be of those materials listed in Table P2906.5. Multiple pan drains may terminate to a single discharge piping system when approved by the administrative authority and permitted by the manufactures installation instructions and installed with those instructions. {existing text unchanged}
** Section P2804.6.1; change to read as follows:
Section P2804.6.1 Requirements for discharge piping. The discharge piping serving a pressure relief valve, temperature relief valve or combination thereof shall:
1.
Not be directly connected to the drainage system.
2.
Discharge through an air gap located in the same room as the water heater.
3.
Not be smaller than the diameter of the outlet of the valve served and shall discharge full size to the air gap.
4.
Serve a single relief device and shall not connect to piping serving any other relief device or equipment.
Exception: Multiple relief devices may be installed to a single T & P discharge piping system when approved by the administrative authority and permitted by the manufactures installation instructions and installed with those instructions.
5.
Discharge to the floor, to the pan serving the water heater or storage tank, to a waste receptor an approved location or to the outdoors.
[remainder unchanged]
**Section P2902.5.3; change to read as follows:
P2902.5.3 Lawn irrigation systems. The potable water supply to lawn irrigation systems shall be protected against backflow by an atmospheric-type vacuum breaker, a pressure-type vacuum breaker, a double-check assembly or a reduced pressure principle backflow preventer. A valve shall not be installed downstream from an atmospheric vacuum breaker. Where chemicals are introduced into the system, the potable water supply shall be protected against backflow by a reduced pressure principle backflow preventer.
**Section P3003.9; change to read as follows:
P3003.9.2 Solvent cementing. Joint surfaces shall be clean and free from moisture. A purple primer that conforms to ASTM F 656 shall be applied. Solvent cement not purple in color and conforming to ASTM D 2564, CSA B137.3, CSA B181.2 or CSA B182.1 shall be applied to all joint surfaces. The joint shall be made while the cement is wet and shall be in accordance with ASTM D 2855. Solvent cement joints shall be permitted above or below ground.
Exception: A primer is not required where both of the following conditions apply:
1.
The solvent cement used is third party certified as conforming to ASTM D 2564
2.
The solvent cement is used only for joining PVC drain, waste, and vent pipe and fittings in not pressure applications in sizes up to and including 4 inches (102mm) in diameter.
**Section P3111 Combination waste and vent systems; delete this section in its entirety.
**Section P3112.2 Vent Connection; delete and replace with the following:
P3112.2 Installation. Traps for island sinks and similar equipment shall be roughed in above the floor and may be vented by extending the vent as high as possible, but not less than the drainboard height and then returning it downward and connecting it to the horizontal sink drain immediately downstream from the vertical fixture drain. The return vent shall be connected to the horizontal drain through a wye-branch fitting and shall, in addition, be provided with a foot vent taken off the vertical fixture vent by means of a wye-branch immediately below the floor and extending to the nearest partition and then through the roof to the open air or may be connected to other vents at a point not less than six (6) inches (152 mm) above the flood level rim of the fixtures served. Drainage fittings shall be used on all parts of the vent below the floor level and a minimum slope of one-quarter (1/4) inch per foot (20.9 mm/m) back to the drain shall be maintained. The return bend used under the drain-board shall be a one (1) piece fitting or an assembly of a forty-five (45) degree (0.79 radius), a ninety (90) degree (1.6 radius) and a forty-five (45) degree (0.79 radius) elbow in the order named. Pipe sizing shall be as elsewhere required in this Code. The island sink drain, upstream of the return vent, shall serve no other fixtures. An accessible cleanout shall be installed in the vertical portion of the foot vent.
(Ordinance 2017-04-06 adopted 4/10/17; Ordinance 2025-03-15 adopted 3/24/2025)