(a) 
All connections to room or space heaters should be of iron, aluminum, brass or copper pipe and fittings. Flexible connections, when used, shall bear the stamp of approval of the National Board of Fire Underwriters of the A.G.A.
(b) 
No soft seat valves will be approved and all valve stems shall be properly packed in such manner as to prevent leakage. A stop cock shall be installed in the line serving heating appliances at the time the appliance is installed and said stop cock shall be accessibly located within 2' of the appliance and in the same room as the appliance. A stop cock shall be installed at the floor line or baseboard on all cook stove openings before final inspection of the installation.
(1965 Code, sec. 15-192)
(a) 
Furnaces generally.
All floor furnaces, central heating units, suspended heating units, insert type wall furnaces such as Panelray and all controls shall be approved by A.G.A. or the National Board of Fire Underwriters. All controls on boilers shall be approved by the A.G.A.
All floor furnaces, central heating units, suspended heating units, and boilers used for heating equipped with manually operated or automatic temperature controls shall be equipped with safety pilot controls that will shut off the gas to the main burner in the event the pilot is extinguished or blown out.
All heating units with a fan to furnish heated air to various rooms in a house or building shall be equipped with a heat limit control switch located in the discharge side of duct and as near the heating units as possible. In the event of fan or motor failure, the heat limit control switch will act as a limiting protection device. Such heat limit control shall be such type that it cannot be set above 2500 F. The safety pilot shall be connected so that a failure in pilot will shut off gas supply to main burner.
No heating unit or controls shall be placed in a closet, room or any other enclosed space without providing ventilating openings as required by A.G.A. at both top and bottom of enclosure equivalent to 12 square inches each for appliances having 40,000 Btu input or less, and 1 square inch additional per 1000 Btu input shall be provided both top and bottom for appliances having more than 40,000 Btu input. Inlet and outlet ducts shall be connected to heating units located in such enclosed spaces. All heating supply ducts shall be constructed of metal in all residential or buildings of frame construction, and shall extend from the heating unit to the grill openings. All return air ducts shall extend from the heating units through the wall or floor of the room in which the heating unit is installed, and ducts shall be of metal.
A gas fired unit heater with propeller fan attached shall not be used as an insert type of duct heater. A unit heater shall not be attached to a warm air duct system unless listed by A.G.A. for such installation.
All heating appliances equipped with a gas regulator or a gas operated diaphragm valve shall have a relief or vent line installed from the regulator or diaphragm valve back to the main burner of the appliance.
(b) 
Duct furnaces.
The heating unit shall be listed as a duct furnace by the A.G.A. The unit shall be equipped with the following controls: pressure regulator, approved automatic heat limit control that cannot be set higher than 250° F., and safety pilot burner control. The controls shall be installed so that the main burner gas supply will shut off in event of overheating, safety pilot failure or motor or belt failure.
The heat exchanger shall be highly resistant to acid, corrosion, and moisture. The heating unit shall be installed on the discharge side of the blower. The blower used with the unit shall have sufficient capacity to deliver the required volume of air against the combined static resistance of the unit and the duct system.
When installed in connection with a cooling system, the heating unit shall be installed in a bypass duct around the cooling system with slide type dampers on each side of the heating unit. Removable inspection plates not less than 6" wide and 23 [sic] the height of the duct in size shall also be installed on each side of the heating unit.
The heating unit shall be installed at least 3' from any wall or ceiling or any other combustible material, and at least 1' above the floor and shall be accessible on all sides at all times. Deviation from this requirement will not be permitted except by written approval from the chief plumbing inspector.
(c) 
Attic furnaces.
A heating unit installed in an attic space shall be approved as an attic furnace by the A.G.A. and the units shall be equipped with controls as specified for duct furnaces. The heating units shall be installed at least 1' from any ceiling or roof. There shall be at least 3' clearance on the control and access side of the furnace. The area where an attic furnace is located shall be floored and shall extend a distance not less than 3' from all sides of the unit. A means of access shall be provided with a permanent ladder or stairway and with an unobstructed passage to the service side of the furnace.
(d) 
Below the floor heating units.
The heating unit shall be approved as a below the floor heating unit by the A.G.A. The unit shall be equipped with controls and shall be accessible as specified for attic furnaces. There shall be at least 3' horizontal clearance on control and access side of unit.
(1965 Code, sec. 15-193)
(a) 
All water heaters installed shall be approved by the A.G.A. and their stamp of approval shall be plainly marked on such heaters. The temperature and pressure valve, safety pilot and thermostat shall be approved by the A.G.A. All gas fired water heating boilers and storage type water heaters shall be equipped with a thermostat and separate pilot burner; the burner shall be equipped with a safety gas control which will shut off the main burner gas supply if the pilot should be extinguished. In addition to the thermostat all such water heaters shall be equipped with a temperature and pressure relief valve set so that water will be released from the heater when the pressure exceeds 125 pounds per square inch, or when the temperature exceeds 200 degrees F. This valve shall be so constructed that it will require manual attention to replace the fuse, link or plug. This valve shall be placed in the hot water line, not more than 4" from the hot water outlet of the heater and shall be accessible at all times. The relief line from said relief valve shall be run independently to the outside of the building and turned down so as to discharge on the ground, and it shall be of galvanized pipe or hard temper copper of not less than 3/8" size. The discharge end of said relief line shall not be more than 2' above the ground, so as to protect anyone passing from being scalded. No water heater shall be placed more than 4'6" above the floor, of the room or closet in which the hot water heater, is located.
(b) 
Boilers used as water heaters shall be tested and approved by the state boiler inspector whose certificate of approval shall be filed in the office of the city plumbing inspector. Such boilers shall be equipped with all safety devices and controls listed above.
(c) 
Electric water heaters and controls shall be approved by the Underwriters’ Laboratories, Inc., and the heaters shall be provided with temperature and pressure relief valve as described for gas water heaters.
(d) 
Water heaters equipped for burning liquid fuel shall be provided with controls as required for gas fired water heaters.
(1965 Code, sec. 15-194)
All persons are prohibited from connecting pipes whereby high pressure steam boilers may be supplied with water direct from the water supply system. All such boilers shall be provided with a tank or other receptacle of sufficient capacity to provide an emergency supply of water in case the water supply is shut off. The steam exhaust from a pressing machine or any other apparatus that has a steam exhaust shall discharge into a suitable receiver that has been vented above the building and is trapped and wasted indirectly to an open fixture or floor drain that is trapped and vented as provided herein. The steam exhaust from a number of presses or machines may discharge into a heater or manifold before entering this receiver.
(1965 Code, sec. 15-195)
(a) 
All water wasted after use as a cooling medium for refrigerant in refrigerating apparatus or waste from any air conditioning apparatus shall not be directly connected into any waste, soil or sewer of a plumbing system but shall be discharged at least 3" above the overflow level of a suitable receptacle or fixture for such waste. Such receptacle shall be properly trapped and vented as herein provided. Potable water shall not be used in refrigerating or air conditioning apparatus, unless the water supply thereto shall be provided with a suitable backflow preventer or air-relief device located at least 6" above the top of any chamber or basin in which water may be contained, sprayed or circulated.
(b) 
No water-consuming air conditioning or refrigerating apparatus of any type shall be placed on any building where said apparatus will project over any street, sidewalk or public alley or thoroughfare.
(c) 
Water shall not be discharged on roofs unless the stormwater leaders serving the roof are connected to the city storm sewer or storm drainage system. Any such water discharge which results in water reaching a street, street gutter, alley or any public or private premises is prohibited.
(d) 
The drain from the cooling tower shall be indirectly connected to a fixture or trap that is properly wasted and vented. Louvers on cooling towers shall be so constructed and maintained as to prevent water from being blown away from or out of the cooling tower structure. Circulating pumps for air conditioning systems shall not be placed on the roof of a building unless the pump is equipped with a mechanical seal or packless stuffing box. Circulating pumps for air conditioning systems shall not be placed on the side of a building or in an alley. All new installations and a replacement in existing air conditioning apparatus and systems shall be made to comply with the requirements of this article.
(1965 Code, sec. 15-196)