The Fire Prevention Bureau requires the following minimum standards for all rapid entry systems devices required by this article. Devices that do not meet these criteria will be considered noncompliant. This will be considered as not meeting the terms of this article.
A.
Lock and key minimum criteria.
(1)
Locks must have the ability to be master-keyed to the lock code authorized by the Fire Marshal and utilized within the Borough of Leonia.
(2)
Lock cylinders must have a listing in accordance with UL 437, Safety Key Locks.
(3)
System keys must withstand a minimum of fifty-inch-pounds of torque when fully inserted.
(4)
System keys shall be cut using a biaxial pattern similar to the Medco Level 3 or better.
(5)
Vendors must be able to provide official proof of UL listing.
(6)
System keys must be able to be secured in an electronic retention device installed in any Leonia Fire Prevention Bureau or Leonia Fire Department vehicle.
B.
Key vault minimum criteria.
(1)
Key vaults must be listed in accordance with UL 1037, Anti-Theft Devices.
(2)
Key vaults must have a minimum door and wall thickness of 1/4-inch plate steel.
(3)
Key vaults must have a weatherproof gasket seal of Neoprene or better around all openings.
(4)
Key vaults must have a stainless steel dust cap or cover over the lock cylinder.