The words and terms used in this chapter are defined by the following:
"Approved air-gap separation (air-gap)"means a physical break between the service connection and a receiving vessel on the customer's system. An air-gap separation shall be located as close as possible to the service connection, and all piping between the service connection and the receiving vessel shall be entirely visible unless otherwise approved by the engineer. An air-gap separation shall be at least double the diameter of the supply pipe, measured vertically from the flood rim of the customer's receiving vessel to the supply pipe from the service connection. In no case shall the air-gap separation be less than one inch.
(1) "Approved device"means a backflow-prevention device which is manufactured in full conformance with the standards established by the American Water Works Association (AWWA) entitled "AWWA C506-78 Standards for Reduced-Pressure Principle and Double Check Valve Backflow Prevention Devices" and has completely met the laboratory and field performance specifications of the Foundation for Cross-Connection Control and Hydraulic Research (FCCC&HR) of the University of Southern California.
(2) The AWWA and (FCCC&HR)standards and specifications have been adopted by the Engineer. Only backflow- prevention devices that have been fully tested and granted a certificate of approval by the FCCC&HR laboratory and are listed on the laboratory's current list of "approved devices" shall be installed on customer systems connected to the City potable water system.
"Auxiliary water supply"means any water supply on or available to premises other than potable water supplied by the City water system.
"Backflow"means the flow of water or other liquids, mixtures or substances under pressure from the customer's system into the City potable water system.
"Backflow-prevention device"means an approved device installed to City standards which will prevent backflow or back-siphonage into the City potable water system.
"Back siphonage"means the flow of water or other liquids, mixtures or substances from the customer's system into the City potable water system caused by a reduction or loss of pressure within the City potable water system.
"Certified tester"means:
(1) A person who is certified by the City to perform testing of backflow prevention devices owned by customers of the City and who has completed training and received certification by an American Water Works Association sponsored backflow device testing certification program or the University of Southern California Backflow Prevention Device Testing School. To maintain City certification, a tester shall continually demonstrate competency in performing tests on backflow prevention devices to the Engineer's satisfaction.
Failure to comply with the Engineer's standard shall result in the revocation of City certification. Inactivity on the part of the tester for a period of two years shall result in revocation of City certification;
(2) A service representative of the manufacturer of the backflow-prevention device approved by the Engineer;
(3) All City personnel, as authorized by the Engineer.
"City"means the City of Santa Rosa.
"City potable water system"means the potable water distribution system owned and operated by the City, including the service connection to a potable water main.
"Contamination"means an impairment of the quality of the water supply of the City potable water system by sewage, industrial fluids or waste liquids, compounds or other materials to a degree which creates an actual hazard to the public health through poisoning or through the spread of disease.
"Cross-connection"means an unprotected actual or potential connection between the City potable water system and any source or system within a customer's premises and/or customer's system which contains water or any substance that is not or cannot be approved as a potable water supply. Bypass arrangements, jumper connections, removable sections, swivel and changeover devices, or other devices through which backflow or back-siphonage could occur, shall be considered to be cross-connections.
"Customer"means any person or organization who receives water or water service from the City.
"Customer's system"means the potable water piping system located immediately downstream from a meter. This is the point where the City loses jurisdiction and sanitary control over the water delivered to a customer.
"Engineer"means the Director of Utilities/City Engineer of the City, or a designee.
"Pollution"means an impairment of the quality of the potable water supply of the City.
"Potable water supply"means a water supply which, according to recognized standards and the public health authority having jurisdiction, is safe for human consumption.
"Premises"means a piece of land together with such buildings and appurtenances located thereon.
"Service connection"means the water piping system and/or meter connecting the City potable water system to the customer's system.
(Ord. 2644 § 1, 1987; Ord. 3129 § 2, 1994; Ord. 3845 § 5, 2007)