Subsections 903.1, 903.1.1, and 903.2 of the International Fire Code are hereby amended to read as follows:
Section 903.1 General. Automatic sprinkler systems shall comply with this section. |
1. For structures with unknown tenants, the sprinkler density of .39 per 5,600 square feet shall be used for design purposes where required by the Fire Chief. |
Section 903.1.1 Alternative Protection. Alternative automatic fire-extinguishing systems complying with Section 904 shall be permitted in lieu of automatic sprinkler protection where recognized by the applicable standard and approved by the fire code official. |
Section 903.2 Where Required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in this section. |
For provisions on special hazards and hazardous materials, see the fire code. |
Gross floor area defined. For purposes of this chapter, gross floor area shall be as defined in Chapter 10, International Building Code. |
1. All buildings hereinafter constructed as defined by the International Fire Code shall be equipped with a fully automatic sprinkler system designed, installed, maintained and tested per NFPA 13, 13D, 13R, or 25, the edition currently adopted by the city, where the gross floor area or occupant load exceeds those listed below, or the building is 35 feet in height or three or more stories. |
Buildings protected by a fire sprinkler system. Canopies 4 feet or more in width shall be protected by a fire sprinkler system. |
For requirements related to additions, alterations and/or remodels to existing buildings see Section 15.16.020. |
(Ord. 699 § 1, 1995; Ord. 1357 § 1, 2010; Ord. 1462 § 11, 2013; Ord. 1484 § 1, 2014)