508.1 General. Where required by other sections of this code and in all buildings classified as high-rise buildings by the California Building Code, in buildings greater than 300,000 square feet in area and in Group I-2 occupancies having occupied floors located more than 75 feet above the lowest level of fire department vehicle access, a fire command center for fire department operations shall be provided and comply with Sections 508.1.1 through 508.1.8. |
508.1.1 Location and access. The fire command center shall be located adjacent to the main lobby and shall be accessible from fire department vehicular access or as approved by the fire code official. The room shall have direct access from the building exterior at the lowest level of fire department access. |
508.1.3 Size. The fire command center shall be not less than 200 square feet (19 m2) in area with a minimum dimension of 10 feet (3048 mm). |
Exception: A fire command center solely required because a building is greater than 300,000 square feet in area shall be a minimum of 96 square feet (9 m2) with a minimum dimension of 8 feet (2438mm). |
508.1.6 Required features. The fire command center shall comply with NFPA 72 and shall contain the following features: |
1. | The emergency voice/alarm communication system control unit. |
2. | The fire department communications system. |
3. | Fire detection and alarm system annunciator. |
4. | Annunciator unit visually indicating the location of the elevators and whether they are operational. |
5. | Status indicators and controls for air distribution systems. |
6. | The firefighter's control panel required by Section 909.16 for smoke control systems installed in the building. |
7. | Controls for unlocking stairway doors simultaneously. |
8. | Sprinkler valve and water-flow detector display panels. |
9. | Emergency and standby power status indicators. |
10. | A telephone for fire department use with controlled access to the public telephone system. |
11. | Fire pump status indicators. |
12. | Schematic building plans indicating the typical floor plan and detailing the building core, means of egress, fire protection systems, fire-fighter air-replenishment systems, fire-fighting equipment and fire department access, and the location of fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions. |
13. | An approved Building Information Card that includes, but is not limited to, all of the following information: |
13.1. General building information that includes: property name, address, the number of floors in the building above and below grade, use and occupancy classification (for mixed uses, identify the different types of occupancies on each floor) and the estimated building population during the day, night and weekend; |
13.2. Building emergency contact information that includes: a list of the building's emergency contacts including but not limited to building manager, building engineer and their respective work phone number, cell phone number and e-mail address; |
13.3. Building construction information that includes: the type of building construction including but not limited to floors, walls, columns and roof assembly; |
13.4. Exit access stairway and exit stairway information that includes: number of exit access stairways and exit stairways in building; each exit access stairway and exit stairway designation and floors served; location where each exit access stairway and exit stairway discharges, interior exit stairways that are pressurized; exit stairways provided with emergency lighting; each exit stairway that allows reentry; exit stairways providing roof access; elevator information that includes: number of elevator banks, elevator bank designation, elevator car numbers and respective floors that they serve; location of elevator machine rooms, control rooms and control spaces; location of sky lobby; and location of freight elevator banks; |
13.5. Building services and system information that includes: location of mechanical rooms, location of building management system, location and capacity of all fuel oil tanks, location of emergency generator and location of natural gas service; |
13.6. Fire protection system information that includes: location of standpipes, location of fire pump room, location of fire department connections, floors protected by automatic sprinklers and location of different types of automatic sprinkler systems installed including but not limited to dry, wet and pre-action; |
13.7. Hazardous material information that includes: location and quantity of hazardous material. |
14. | Work table. |
15. | Generator supervision devices, manual start and transfer features. |
16. | Public address system, where specifically required by other sections of this code. |
17. | Elevator fire recall switch in accordance with ASME A17.1. |
18. | Elevator emergency or standby power selector switch(es), where emergency or standby power is provided. |
Exception: A fire command center solely required because a building is greater than 300,000 square feet in area shall comply with NFPA 72 and contain the features set forth in Section 508.1.6 subsections 5, 8, 10, 12, 13 and 14. The features set forth in Section 508.1.6 subsections 1, 2, 3, 4, 6, 7, 9, 11, 15, 16, 17, 18 and 19 shall be required when such building contains systems or functions related to these features. |
508.1.8 Fire command center identification. The fire command center shall be identified by a permanent easily visible sign stating "Fire Dept. Command Center," located on the door to the fire command center. |