The California Building Code adopted in Section 15.03.010 is modified, amended and/or supplemented as follows:
A.
Delete Appendices A, B, C, D, E, F, G, H, K, L, M, N, O and P.
B.
Amend Section 101.1 to read as follows:
101.1 Title. These regulations shall be known as the Lompoc Building Code, hereinafter referred to as "this code."
C.
Amend Section 101.4 to read as follows:
101.4 Referenced codes. The other codes specified in Sections 101.4.1 through 101.4.8 and referenced elsewhere in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference.
D.
Add Section 101.4.9 Section 101.4 to read as follows:
101.4.9 Electrical. The provisions of the California Electrical Code shall apply to the installation of electrical systems, including alterations, repairs, and replacement of electrical equipment, appliances, fixtures, fittings and appurtenances thereto.
E.
Amend 103.1 to read as follows:
103.1 Creation of enforcement agency. The Building and Safety Division is hereby created and the official in charge thereof shall be known as the building official. The function of the agency shall be the implementation, administration and enforcement of provisions of this code.
F.
Add Subsection 104.6.1 to the Section 104.6 to read as follows:
104.6.1 Citations. The building official, or duly authorized agent, is granted the authority as provided in Section 836.5(a) of the California Penal Code to issue citations for violations of this code.
G.
Amend Section 105.2, Work exempt from permit. Building exemptions 1, 2 and 4 only, to read as follows:
105.2 Work exempt from permit. Exemptions from permit requirements of this code shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of this code or any other laws or ordinances of this jurisdiction. Permits shall not be required for the following:
Building:
1. | One-story detached residential accessory structures used as tool and storage sheds, playhouses, and similar uses, provided that the floor area does not exceed 120 square feet (11 m2). It is permissible that these structures still be regulated by the Wildland-Urban Interface Code, despite being exempt from permit. |
2. | Fences not over 7 feet (2134 mm) high, excluding masonry and concrete and not enclosing or obstructing in any way the means of egress. |
4. | Retaining walls and non-retaining walls, including masonry and concrete free- standing walls, that are not over 4 feet (1219 mm) in height measured from the bottom of the footing to the top of the wall, unless supporting a surcharge or impounding Class I, II or IIIA liquids. |
H.
Amend Section 105.3.2 to read as follows:
105.3.2 Time limitation of application. An application for a permit for any proposed work shall be deemed to have been abandoned 365 days after the date of filing, unless a permit has been issued; except that the building official is authorized to grant one or more extensions of time for additional periods not exceeding 180 days each. If the application is accepted less than 180 days before the effective date of the next edition of the triennial California Building Standards Code, the application will expire 180 days after the effective date of the next edition of the triennial California Building Standards Code. An extension shall be requested in writing and justifiable cause demonstrated. No extension of time granted by the building official shall extend the application for more than 180 days beyond the effective date of the next edition of the triennial California Building Standards Code. In order to renew action on an application after expiration, the applicant shall resubmit plans and pay a new plan review fee.
I.
Add Section 109.2.1 to Section 109.2 to read as follows:
109.2.1 Plan review fees. When submittal documents are required by Section 107.1, a plan review fee shall be paid at the time of submitting the submittal documents for plan review. Said plan review fee shall be in accordance with the schedule as established by the applicable governing body.
The plan review fees specified in this section are separate fees from the permit fees specified in Section 109.2 and are in addition to the permit fees.
Where submittal documents are incomplete or changed so as to require additional plan review, or where the project involves deferred submittal items as defined in Section 107.3.4.1, an additional plan review fee may be charged at a rate established by the applicable governing authority.
J.
Add Sections 109.4.1 and 109.4.2 to Section 109.4 to read as follows:
109.4.1 Investigation. Whenever any work for which a permit is required by this code has been commenced without first obtaining said permit, a special investigation shall be made before a permit may be issued for such work.
109.4.2 Fee. An investigation fee, in addition to the permit fee, shall be collected whether or not a permit is then or subsequently issued. The investigation fee shall be equal to the amount of the permit fee required by this code. The payment of such investigation fee shall not exempt any person from compliance with all other provisions of this code nor from any penalty prescribed by law.
K.
Delete the exception to Section 110.3.6.
L.
Amend Section 502.1 and add Section 502.1.1 to read as follows:
502.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 4 inches (102 mm) high for single family residential buildings and 8 inches (203.2 mm) for R-1, R-2 and non-residential buildings, with a minimum stroke of 0.5 inch (12.7 mm), unless otherwise required to be greater in height or of reflective material as determined by the fire code official during the jurisdiction's development review process for a specific project. Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address identification shall be maintained.
502.1.1 Directories. When required by the fire code official, complexes with multiple buildings may be required to provide directories, premises maps and directional signs. The scale, design and location of directory signs shall be approved by the fire code official and may be required to be illuminated.
M.
Amend Section 903.2.8.1 to read as follows:
903.2.8.1 Group R-3. An automatic sprinkler system installed in accordance with Section 903.3, including Section 903.3.1.3 for Group R-3, shall be provided throughout all buildings with a Group R fire area including all Manufactured, Modular or Mobile single family or Multifamily Homes or sleeping units.
N.
Delete the exception to Section 903.2.10, Item 2.
O.
Add Section 903.2.11.7 to read as follows:
903.2.11.7 Commercial Cannabis activity including manufacturing, farming, processing, distribution or sale. Each cannabis business that includes commercial cannabis activity, as defined by the State of California Business and Professions Code Division 10 and/or the Lompoc Municipal Code shall provide automatic fire sprinklers in accordance with NFPA 13 and the California Fire Code.
Exception:
1.
Retail sales and/or delivery services and incidental storage under 5,000 sq. ft. may request a waiver of automatic sprinkler installation from the Fire Marshal.
P.
Add Section 903.2.22 to Section 903.2 to read as follows:
903.2.22 Fire Sprinklers Required. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided as listed below.
1.
New Construction—For Non-Residential Occupancies. Unless otherwise required in other provisions of this code or State Regulations at a smaller floor area, automatic sprinkler systems shall be installed and maintained in all buildings which have a total building area exceeding 5,000 square feet.
2.
Additions and/or modifications to Existing Buildings—For Non-Residential Buildings. Unless otherwise required in other provisions of this code or State Regulations, when the total building area of the building including the addition(s) is in excess of 5,000 square feet, the entire building (existing and the addition) shall be provided with an automatic fire sprinkler system. Modifications that require addition of an automatic sprinkler system shall include removal, combining or rearrangement of demising or tenant space walls to create a single occupancy or tenant space of 5,000 square feet or greater or changes in occupancy or use when the change of occupancy or use results in a requirement for an automatic sprinkler system as specified in Section 903, including, but not limited to, increased occupant load, multiple fire areas, use of hazardous materials and other increased hazards. Any existing structure that includes a basement used for other than mechanical equipment placement and servicing shall have the floor area of the basement included in the total building square footage for determination of the 5,000 square foot floor area threshold for provision of fire sprinklers. In the event a building or any portion of the building is proposed to be divided into fire areas so as not to exceed the limits of this section, such fire areas shall be constructed in accordance with Section 711 of the Lompoc Building Code.
3.
Additions and/or modifications to Existing Buildings—For Group R Division 3 Residential Buildings. Existing Group R, Division 3 buildings to which additions, alterations, modifications or repairs are made that involve the removal, alteration or replacement to 50 percent or greater of the linear length of walls of the building (exterior plus interior) within a two-year period shall meet the requirements of new construction of this code for purpose of fire sprinkler installation requirements. Alteration also includes the infill of existing openings and the creation of new or expansion of existing openings.
Q.
Add Section 903.2.23 to Section 903.2 to read as follows:
903.2.23 Speculative building defined. Any 'F', 'M', or 'S' occupancy required by this code to be equipped with automatic fire sprinklers in which the tenant is not identified at the time of application for a building permit shall be considered a speculative building.
903.2.23.1 Speculative building, sprinkler system design. Automatic fire sprinkler systems in speculative buildings as defined in Section 903.2.23 with an interior clear height of 12 feet or less shall have a minimum design of 0.20 gallons per minute over a 2,500 square foot design area (D.20/2,500).
903.2.23.2 Speculative building, sprinkler system design. Automatic fire sprinkler systems in speculative buildings as defined in Section 903.2.23 with an interior clear height of more than 12 feet shall be designed as set forth in Section 3206.2.2 of this code (high-piled storage).
R.
Add Section 903.3.11 to Section 903.3 to read as follows:
903.3.11 Exterior locations. Automatic fire sprinklers installed at exterior locations shall be approved corrosion-resistant devices.
S.
Add Section 904.16 to Section 904 to read as follows:
904.16 Wood or wood product fueled cooking. All commercial-type cooking equipment using wood or wood products as fuel shall be protected by an automatic sprinkler system within the hood and the duct work. The water supply may be provided from the building's fire sprinkler system, or the domestic water supply. The minimum water flow calculation shall be 20 gallons per minute (76 lpm) at 7 psi (0.5 bar) for each head. There shall be a separate control valve for the fire sprinkler system protecting the commercial-type cooking equipment.
T.
Amend Section 906.8 to read as follows:
906.8 Cabinets. Cabinets used to house portable fire extinguishers shall not be locked. Cabinets shall be labeled "FIRE EXTINGUISHER" and have all letters capitalized with a minimum height of 1 inch (25.4 mm) reflective white on red background as required by the Fire Code Official.
Exceptions:
1.
Where portable fire extinguishers subject to malicious use or damage are provided with a means of ready access.
2.
In Group I-3 occupancies and in mental health areas in Group I-2 occupancies, access to portable fire extinguishers shall be permitted to be locked or to be located in staff locations provided the staff has keys.
3.
In new construction, fire extinguishers shall be located within recessed or semi recessed cabinets. In existing occupancies, fire extinguishers shall be located within recessed or semi-recessed cabinets when required by the Fire Code Official. All fire extinguishers in cabinets shall be mounted so that their tops are no more than 48 inches (1,219 mm) above the floor with the brackets or hangers included with the fire extinguishers.
U.
Amend Section 907.3.1 in Section 907.3 to read as follows:
907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature, and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is installed. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the California Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. The reset switch for the duct detectors shall be in an accessible location acceptable to the Fire Marshal.
Exception: In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
V.
Amend Section 907.6.6 in Section 907.6 to read as follows:
907.6.6 Monitoring. Fire alarm systems required by this chapter or by the California Fire Code shall be monitored by an approved central station service listed by Underwriters Laboratory for receiving fire alarms in accordance with NFPA 72 and this section. The central station shall contact and notify the police/fire dispatch center immediately on notification of an alarm and prior to making contact with the protected premises.
Exception: Monitoring by a central station is not required for:
W.
Amend Section 912.2.1 in Section 912.2 to read as follows:
912.2.1 Visible location. Fire department connections shall be located on the front access side of buildings, fully visible and recognizable from the street or nearest point of fire department vehicle access or as otherwise approved by the fire chief or his/her designee. The location of fire department connections shall be approved and installed as follows:
1.
Within 40 feet from an approved roadway or driveway and arranged so that hose lines can be readily attached to the inlets without interference from any nearby objects including buildings, fences, posts, plantings, or other fire department connections or otherwise approved by the fire chief or his/her designee.
2.
Within 50 feet from an approved hydrant.
3.
Inlet height shall not be less than 18 inches or more than 48 inches above grade.
4.
Guard posts or other approved means shall be required to protect fire department inlet connections from vehicular damage.
X.
Add Section 1506.4 in Section 1506 to read as follows:
1506.4 Wood shake and shingle roof covering limitations. Wood shake or shingle roof coverings shall not be installed on any building. A roof covering shall not be applied over existing wood shakes or shingles.
Exception: A wood shake or wood shingle system listed as a Class A-rated roof covering complying with Section 1505.2 of this code.
Y.
Amend Section 3201.1 to read as follows:
3201.1 Scope. The provisions of this chapter and Chapter 12.12 of the Municipal Code shall govern encroachment of structures into the public right-of-way.
Z.
Amend Section 3201.3 to read as follows:
3201.3 Other laws. The provisions of this chapter shall not be construed to permit violation of other laws or ordinances regulating the use and occupancy of public property. The projection of any structure or portion thereof into a right-of-way shall be subject to an encroachment permit issued by the City of Lompoc, State of California, or other agency having jurisdiction over the public right-of-way.
AA.
Amend Section 3201.4 to read as follows:
3201.4 Drainage. Drainage water collected from a roof, awning, canopy or marquee, and condensate from mechanical equipment shall not flow over a public walking surface unless specifically approved by the City Engineer.
BB.
Amend Section 3202.2 to read as follows and delete Sections 3202.2.1, 3202.2.2 and 3202.2.3:
3202.2 Encroachments above grade and below 8 feet in height. Encroachments into the public right-of-way above grade and below 8 feet (2,438 mm) in height shall be prohibited. Doors, windows, and stairs shall not open or project into the public right-of-way.
CC.
Amend Section 3202.3.1 in Section 3202.3 to read as follows:
3202.3.1 Awnings, canopies, marquees, roof overhangs, roof projections, and signs. Awnings, canopies, marquees, roof overhangs, roof projections, and signs shall be constructed so as to support applicable loads as specified in Chapter 16. Roof overhangs or projections shall not be used for human occupancy. Awnings, canopies, marquees, roof overhangs, roof projections and signs with less than 15 feet (4,572 mm) clearance above the sidewalk shall not extend into or occupy more than two-thirds the width of the sidewalk measured from the building to the face of curb. Stanchions or columns that support awnings, canopies, marquees, and signs shall not be located on the public right-of-way.
DD.
Amend Section 3202.3.2 and add exception to read as follows:
3202.3.2 Windows, balconies, architectural features, and mechanical equipment. Where the vertical clearance above grade to projecting windows, architectural features or mechanical equipment is more than 8 feet (2,438 mm), 1 inch (25 mm) of encroachment is permitted for each additional 1 inch of clearance above 8 feet (2,438 mm), but the maximum encroachment shall be 4 feet (11,219 mm).
Exception: For windows and architectural features projecting over a public sidewalk, the minimum vertical clearance may be 8 feet (2,438 mm) for the maximum encroachment length of 4 feet (11,219 mm) and the maximum projection shall be not less than 2 feet (610 mm) from the face of curb.
EE.
Add Appendix Sections J101.3 and J101.4 in Section J101 to read as follows:
J101.3 Hillsides. The term hillside area is defined as all properties with slopes of 10 percent or more. No grading shall commence on slopes greater than 30 percent, including but not limited to access roads and driveways unless approved by the Planning Commission or the City Council. The hillside development regulations of the city zoning ordinance and General Plan/Local Coastal Plan Policy CO-10 shall apply in addition to the standards and procedures set forth in this code for all properties in this category.
J101.4 Approval for building construction. Prior to commencement of any building construction, pursuant to a building permit for the graded site, a benchmark shall be provided to verify that the building site is graded in conformance with the approved grading plan. No building construction shall be started until the building official or city engineer has verified that the rough grading conforms to the approved plan, including any interim or permanent erosion control measures deemed necessary.
FF.
Amend Appendix Section J103.2 and add Appendix Sections J103.3 and J103.4 to read as follows:
J103.2 Exempted work. A grading permit shall not be required for the following:
1.
Grading in an isolated, self-contained area, provided there is no danger to the public, and that such grading will not adversely affect adjoining properties.
2.
Excavation for construction of a structure permitted under this code.
3.
Cemetery graves.
4.
Refuse disposal sites controlled by other regulations.
5.
Excavations for wells, or trenches for utilities.
6.
Mining, quarrying, excavating, processing, or stockpiling of rock, sand, gravel, aggregate, or clay controlled by other regulations, provided such operations do not affect the lateral support of, or significantly increase stresses in, soil on adjoining properties.
7.
Exploratory excavations performed under the direction of a registered design professional.
8.
An excavation which does not exceed fifty cubic yards and: (1) is less than 2 feet (610 mm) in depth; or (2) does not create a cut slope greater than 5 feet (1,524 mm) in height and steeper than 1 unit vertical to 2 units horizontal.
9.
A fill less than 1 foot (305 mm) in depth and placed on natural terrain with a slope flatter than 1 unit vertical to 5 units horizontal, not intended to support structures, on any one lot and does not obstruct a drainage course.
10.
A fill less than 3 foot (38.3 mm) in depth and placed on natural terrain with a slope flatter than 1 unit vertical to 5 units horizontal, not intended to support structures, that does not exceed 50 cubic yards (38.3 m3) on any one lot and does not obstruct a drainage course.
Exemption from the permit requirements of this appendix shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of this code or any other laws or ordinances of this jurisdiction. |
J103.3 Early grading. A grading permit shall not be issued prior to issuance of a building permit for the project unless:
1. | Approval of a tentative subdivision or tract map, use permit, planning permit or similar authorization has been granted; and |
2. | Related street and utility grades have been established and approved; and |
3. | A surety bond in accordance with Section J103.4 is deposited to guarantee restoration of the site to a natural or other condition acceptable to the building official should the project not proceed to completion. |
J103.4 Bonds. The building official may require bonds in such form and amounts as may be deemed necessary to ensure that the work, if not completed in accordance with the approved plans and specifications, will be corrected to eliminate hazardous conditions or restore a graded site to the original condition. In lieu of a surety bond, the applicant may file a cash bond or instrument of credit with the building official in an amount equal to that which would be required in the surety bond.
The city engineer may require that bonds be posted to recover the full costs of any damage to public right-of-way which may occur because of the peculiar nature or large scope of the project, such as transportation of fill or heavy equipment on local streets not designed to accommodate the traffic.
GG.
Amend Appendix Section J104.2 in Section J104 to read as follows:
J104.2 Site plan requirements. In addition to the provisions of Section 107, a grading plan shall show the existing grade and finished grade in contour intervals of sufficient clarity to indicate the nature and extent of the work and show in detail that it complies with the requirements of this code. The plans shall show the existing grade on adjoining properties in sufficient detail to identify how grade changes will conform to the requirements of this code. The plans shall show existing drainage conditions and drainage devices and all proposed changes thereto. The plans shall include the location and dimension of all trees on the site to remain and to be removed which are 3 inches (76.2 mm) in diameter or larger at the trunk, measured at 4.5 feet (1.37 m) above ground level. A preservation plan shall be submitted for all trees to remain. The plans shall indicate where excess material, rocks, or rubble will be disposed of.
HH.
Add Appendix Section J110.3 in Section J110 to read as follows:
J110.3 Other standards. Erosion control measures shall conform to the following standards and approval processes: