Exciting enhancements are coming soon to eCode360! Learn more 🡪
City of Hudson, NY
Columbia County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
Potable water is water from a public or private water supply system or source which is accepted by the proper governing authority as suitable for human consumption.
No potable water, when such use is specifically approved by proper administrative authority, may be used for flushing water closets, urinals and other purposes not requiring potable water, provided only that such water shall not be readily accessible for drinking purposes. All piping conveying nonpotable water shall be adequately and durably identified by a distinctively colored paint so that it is readily distinguished from piping carrying potable water.
Potable and nonpotable water supplies shall be distributed through a system entirely independent of each other, and any cross-connection between such supplies is prohibited.
No cross-connection or interconnection of pipes, valves or other devices which connect the water lines of the City to and with pipes or fixtures supplied with water from any other source shall be made or permitted at any time except in strict compliance with the rules and regulations of the Board of Public Works and not until a signed permit has been issued by the Superintendent of said Board.
Wherever possible, water service and house sewer should be laid in separate trenches. Where they must be laid in the same trench, the water pipe shall be laid on a bench or on solidly tamped backfill at least 12 inches above the top of sewer pipe.
The water distributing system shall be protected against backflow, preferably by having the outlet end from which the water flows spaced a distance from flood-level rim of the receptacle into which the water flows sufficient to provide a minimum required air gap as defined in American Standard for Air Gaps in Plumbing Systems (ASA, A40-4, 1942). Where it is not possible to provide a minimum air gap, the fixture shall be equipped with an accessibly located backflow preventer, complying with the American Standard Backflow Preventers in Plumbing Systems (ASA, A40.6), installed between the control valve and the fixture or outlet.
Where it is not possible to provide a minimum air gap or backflow preventer, as may be in the case in connections to cooling jackets, condensers or other industrial or special appliances, then the governing authority shall require a separate tank supply or such other means of protection as may be practicable and desirable.
All nonpressure, potable water supply tanks shall be properly covered to prevent entrance of foreign material into water supply. Soil or waste lines shall not be permitted to pass directly over such tanks or over manholes in pressure tanks.
All piping, tanks, appliances and devices subject to freezing temperature shall be effectively protected against freezing.
If the discharge or waste from pressure tanks, boilers and relief valves is connected by piping to the drainage system, it shall be connected as an indirect waste.
Materials for water distributing pipes and tubing within a building shall be of brass, copper, galvanized wrought iron or steel, lead or cast iron, galvanized malleable iron fittings. Copper water tube and soldered fittings shall conform to ASA Specifications H23.1-1947 and A40.3-1941.
Piping material that has been used for other than potable water supply shall not be used in a potable water supply system.
When selecting the material and size of pipe for water supply, due consideration shall be given to the action of the water on the interior of the pipe and of the soil, fill or other material on the exterior of the pipe.
A. 
All water services shall be of Type K copper and the minimum size shall be 3/4 of an inch, with inverted stop-waste cocks for curb cock and house stop. Curb box shall be of an approved type, and only flared fitting shall be used.
B. 
All other water services and water mains will be allowed only with the approval of the Commissioner of Public Works.
Where flush valves are used or other devices requiring relatively high rates of flow of water, the water service pipe must be designed to supply this flow.
Separate stopcocks or valves, always accessible, shall be placed at the foot of each riser line, and, in multiple dwellings or commercial buildings, a valve to control each dwelling unit.
All water pipes shall be so graded or pitched that the entire system or parts thereof can be drained. The formation of traps and sags shall be avoided where possible, or provisions made for draining.
Supply lines taken from pressure or gravity tanks shall be valved at or near their source.
Individual controls shall be provided for all water closets and for any fixture isolated from a group.
[Amended 12-12-1973]
House tanks shall only be allowed with the approval of the Commissioner of Public Works as to where required, design, as to inlet and air gap, contamination and valves, and shall not be allowed to be connected directly to any drainage system. Inlet and outlet valves shall be of the same size.
All plumbing fixtures shall be provided with an adequate supply of water for flushing so that they may not become foul, unsanitary or dangerous to health. Every water closet or pedestal urinal shall have an approved tank or valve of at least six gallons flushing capacity for water closets and at least two gallons for urinals, and shall be adjusted to prevent the waste of water.
The minimum size of water supply pipes to fixtures shall be as follows:
Fixture
Pipe Size
(inches)
Water closet and urinal tanks
 3/8
Flush valves for water closets, siphon-jet, blowout and pedestal urinals
1
Lavatories
 1/2
Bathtubs
 1/2
Shower stalls
 1/2
Sinks
 1/2
Laundry tubs
 1/2
Combination sink and tray
 1/2
Service sink
 1/2
Flushing rim sinks
 3/4
Drinking fountains
 3/8
Sill cocks
 1/2
Hot water boilers
 1/2
Self-closing devices shall be provided with air chambers or shock absorbers.
Where circulating hot water supply systems are installed, the hot water pipes should be covered with approved insulating material.
A suitable pressure relief valve shall be installed on the hot water storage tank or at some point in the hot water supply system. Such relief valve shall be so located that there is no shutoff valve between the heating boiler or device and the relief valve.
An approved temperature relief valve conforming to the requirements of the American Standard Listing Requirements for Relief and Automatic Gas Shut-Off Valves for Use on Water Heating Systems. (ASA, Z21.22) shall be installed on the hot water storage tank to prevent the storage of hot water at a temperature higher than boiling point at atmospheric pressure.
Any relief valve that meets the specifications of the National Board of Casualty and Surety Underwriters shall be considered acceptable. All relief waste from valves shall be run as an indirect waste.
All water service pipes shall be run in such manner with enough slack and play to allow for the working of the ground, and each corporation cock shall have a brick house protection.
All service pipes shall be protected from frost and shall be at least four feet underground. If less, they shall be wrapped with felt and tar paper securely fastened with brass bands or copper wire.
All new water service pipes shall be tested in the presence of the Inspector.
All excavations for water services and sewers shall be backfilled in street and sidewalk areas with gravel.
Where there is danger of contamination of the water supply, or where such contamination actually develops, the fixtures, apparatus or piping shown to be responsible for the condition shall be altered or replaced to conform to the requirements of this chapter.
Wherever the supply to a fixture is introduced into such fixture below the overflow level, such supply shall be provided with an approved vacuum breaker which will prevent the siphoning of water from such fixture into the supply piping.
Direct water supply piping connections to sterilizers are prohibited. The water piping for sterilizers shall not be connected directly with any drainage system; such waste piping shall discharge above an open, water-supplied, trapped and vented fixture.
Under no condition shall used pipe be used on any part of the water system.