[Adopted]
A.
Statement of purpose. The purpose of this article
is to safeguard potable water supplies from potential contamination
by preventing backflow from a water user's system into the public
water system, recognizing that there are varying degrees of hazard
and applying the principle that the degrees of protection should be
commensurate with the degrees of hazard. It is the intent of the Village
of New Paltz to comply with the requirements of New York State Sanitary
Code, Part 5, Section 5-1.31 which mandates that the supplier of water
protect its water system in accordance with procedures acceptable
to the New York State Commissioner of Health and to that extent, the
terms, conditions and provisions of the New York State Sanitary Code,
Part 5, Section 5-1.31 and the Cross Connection Control Manual published
by the New York State Department of Health are incorporated in this
article by reference as if more fully stated.
B.
Responsibility of the Superintendent of Public Works,
Code Enforcement Officer and Building Inspector. The Superintendent
of Public Works or his designated agent shall inspect the plumbing
in every building or premises in the Village of New Paltz as frequently
as in his judgment may be necessary to ensure that such plumbing has
been installed in such a manner as to prevent the possibility of pollution
of the water supply of the Village by the plumbing. The Superintendent
of Public Works, Code Enforcement Officer or Building Inspector shall
notify in writing the owner or authorized agent of the owner of any
such building or premises, to correct within a reasonable time any
plumbing installed or existing contrary to or in violation of this
article and which, in his judgment, may tend to cause the pollution
of the Village water supply, or otherwise adversely affect the public
health.
C.
Inspection. The Superintendent of Public Works or
his designated agent shall have the right of entry into any building
during reasonable hours, for the purpose of making inspection of the
plumbing systems installed in such building or premises provided that
with respect to the inspection of any single-family dwelling, consent
to such inspection shall first be obtained from a person of suitable
age and discretion therein or in control thereof.
Unless specifically defined below, words or
phrases used in this article shall be interpreted so as to give them
the meaning they have in common usage and to give this article its
most reasonable application.
The unobstructed vertical distance through the free atmosphere
between the lowest opening from any pipe or faucet supplying water
to a tank, plumbing fixture, or other device and the flood-level rim
of the receptacle.
An assembly of at least two independently acting approved
single check valves, including tightly closing shutoff valves on each
side of the check valve assembly and suitable test cocks plus connections
available for testing the water tightness of each valve.
A check valve that seats readily and completely. It must
be carefully machined to have free-moving parts and assured water
tightness. The face of the closure element and valve seat must be
bronze composition, or other noncorrodible material which will seat
tightly under all prevailing conditions of field use. Pins and bushings
shall be of bronze or other noncorrodible, nonsticking material, machined
for easy, dependable operation. The closure element (e.g., clapper)
shall be internally weighted or otherwise internally equipped to promote
rapid and positive closure in all sizes where this feature is obtainable.
Any water supply approved by the New York State Department
of Health.
Any water source or system other than the potable water supply
that may be available in the building or premises.
The flow of water or other liquids, mixtures, or substances
into the distributing pipes of a potable supply of water from any
source or sources other than its intended source. Backsiphonage is
one type of backflow.
A device or means to prevent backflow.
Backflow resulting from negative pressures in the distributing
pipes of a potable water supply.
A loop of pipe rising at least 35 feet, at its topmost point,
above the highest fixture it supplies.
A self-closing device which is designed to permit the flow
of fluids in one direction and to close if there is a reversal of
flow.
See “pollution.”
The Ulster County Commissioner of Health, his assistants
or authorized deputies acting as, or any other person appointed as,
public health officer of the County of Ulster.
Any physical connection between a potable water supply and
any waste pipe, soil pipe, sewer, drain, or any unapproved source
or system or any potable water supply outlet which is submerged or
can be submerged in waste water and/or any other source of contamination.
(See “backflow” and “backsiphonage.”)
Any pipe that carries waste water or waterborne wastes in
a building drainage system.
The edge of the receptacle from which water overflows.
Any conditions, devices or practices in the water supply
system and its operation which create, or in the judgment of the Superintendent
of Public Works, Code Enforcement Officer or Building Inspector, may
create, a danger to the health and well-being of the water consumer.
An example of a health hazard is a structural defect in the water
supply system, whether of location, design or construction that regularly
or occasionally may prevent satisfactory purification of the water
supply or cause it to be polluted from extraneous sources.
A pressure vessel in which air pressure acts upon the surface
of the water contained within the vessel, pressurizing the water distribution
piping connected to the vessel.
The open end of the water supply pipe through which the water
is discharged into the plumbing fixture.
Installed receptacles, devices, or appliances supplied with
water or that receive or discharge liquids or liquid-borne wastes.
Any arrangement of plumbing, including piping and fixtures,
whereby a cross-connection is created.
Includes the water supply and distribution pipes, plumbing
fixtures, and traps; soil, waste and vent pipes; building drains,
and building sewers including their respective connections, devices,
and appurtenances within the property lines of the premises; and water-treating
or water-using equipment.
The presence of any foreign substance (organic, inorganic,
radiological, or biological) in water that tends to degrade its quality
so as to constitute a hazard or impair the usefulness of the water.
An assembly of differential valves and check valves, including
an automatically opened spillage port to the atmosphere designed to
prevent backflow (referred to herein as "RPZ").
The receiving, nonpressure vessel forming part of the airgap
separation between a potable and an auxiliary supply.
Any pressure less than that exerted by the atmosphere.
A vacuum breaker designed so as not to be subjected to static
line pressure.
A vacuum breaker designed to operate under conditions of
static line pressure.
Water free from impurities in amounts sufficient to cause
disease or harmful physiological effects. Its bacteriological and
chemical quality shall conform to the requirements of the Public Health
Service Drinking Water Standards or to the regulations of the public
health authority having jurisdiction.
Water that is not safe for human consumption or is of questionable
potability.
A.
General. A potable water supply system shall be designed,
installed, and maintained in such manner as to prevent contamination
from nonpotable liquids, solids, or gases being introduced into the
potable water supply through cross-connections or any other piping
connections to the system.
B.
Cross-connections prohibited. Cross-connections between
potable water systems and other systems or equipment containing water
or other substances of unknown or questionable safety are prohibited
except when and where, as approved by the Superintendent of Public
Works, suitable protective devices such as the reduced pressure zoned
backflow preventer or equal are installed, tested, and maintained
to insure proper operation on a continuing basis.
C.
Interconnections. Interconnection between two or more
public water supplies shall be permitted only with the approval of
the Superintendent of Public Works.
D.
Individual water supplies. Cross-connections between
an individual water supply and a potable public supply shall not be
made unless specifically approved by the Superintendent of Public
Works.
E.
Connections to boilers. Potable water connections
to boilers shall be made through an airgap or provided with an approved
backflow preventer.
F.
Prohibited connections to fixtures and equipment. Connection to the potable water supply system for the following is prohibited unless protected against backflow in accordance with Subsection H or as set out herein.
(1)
Bidets.
(2)
Operating, dissection, embalming, and mortuary tables
or similar equipment; in such installation the hose used for water
supply shall terminate at least 12 inches away from every point of
the table or attachments.
(3)
Pumps for nonpotable water, chemicals, or other substances;
priming connections may be made only through an airgap.
(4)
Building drainage, sewer, or vent systems.
(5)
Any other fixture of similar hazard.
G.
Refrigerating unit condensers and cooling jackets.
Except where potable water provided for a refrigerator condenser or
cooling jacket is entirely outside the piping or tank containing a
toxic refrigerant, the inlet connection shall be provided with an
approved check valve. Also, adjacent to and at the outlet side of
the check valve, an approved pressure relief valve set to relieve
at 5 psi above the maximum water pressure at the point of installation
shall be provided if the refrigeration units contain more than 20
pounds of refrigerants.
H.
Protection against backflow and backsiphonage.
(1)
Water outlets. A potable water system shall be protected
against backflow and backsiphonage by providing and maintaining at
each outlet:
(2)
Minimum required airgap.
(a)
How measured. The minimum required airgap shall
be measured vertically from the lowest end of a potable water outlet
to the flood rim or line of the fixture or receptacle into which it
discharges.
(b)
Size. The minimum required airgap shall be twice
the effective opening of a potable water outlet unless the outlet
is a distance less than three times the effective opening away from
a wall or similar vertical surface, in which cases the minimum required
airgap shall be three times the effective opening of the outlet.
(3)
Approval of devices. Before any device for the prevention
of backflow or backsiphonage is installed, it shall have first been
certified by a recognized testing laboratory acceptable to the Board
of Trustees of the Village. Devices installed in a building potable
water supply distribution system for protection against backflow shall
be maintained in good working condition by the person or persons responsible
for the maintenance of the system.
(4)
Installation of devices.
(a)
Vacuum breakers. Vacuum breakers shall be installed
with the critical level at least 6 inches above the flood level rim
of the fixture they serve and on the discharge side of the last control
valve to the fixture. No shutoff valve or faucet shall be installed
beyond the vacuum breaker. For closed equipment or vessels such as
pressure sterilizers the top of the vessel shall be treated as the
flood level rim but a check valve shall be installed on the discharge
side of the vacuum breaker.
(b)
Reduced pressure zone backflow preventer. A
reduced pressure principal-type backflow preventer may be installed
subject to full static pressure.
(c)
Devices of all types. Backflow and backsiphonage
preventing devices shall be accessible, located preferably in the
same room with the fixture they serve. Installation in utility or
service spaces, provided they are readily accessible, is also permitted.
(5)
Tanks and vats below rim supply. Where a potable water
outlet terminates below the rim of a tank or vat and the tank or vat
has an overflow of diameter not less than given in Table 3.85, the
overflow pipe shall be provided with an airgap as close to the tank
as possible.
A.
Toxic or hazardous substances not under pressure.
At the service connection to any premises on which any material dangerous
to health or toxic substance in toxic concentration is not handled
under pressure but is otherwise handled in such manner as to constitute
a cross-connection, the Village water supply shall be protected by
an approved RPZ unless such cross-connection is abated to the satisfaction
of the Superintendent of Public Works and approved by the County Health
Officer.
B.
Nonhazardous substances. At the service connection
to any premises on which a substance that would be objectionable (but
not necessarily hazardous to health) if introduced into the Village
water supply is handled in such a manner as to constitute a cross-connection,
the Village water supply shall be protected by an approved double
check valve assembly.
C.
Sewage and storm drain treatment plants and pumping
stations. At the service connection to any sewage treatment plant
or sewage pumping station, the Village water supply shall be protected
by an airgap separation. The airgap shall be located as close as practicable
to the service connection and all piping between the service connection
and receiving tank shall be entirely visible. If these conditions
cannot be reasonably met, the Village water supply shall be protected
with an approved RPZ providing this alternative is acceptable to both
the Superintendent of Public Works and the County Health Officer.
A final decision in this matter shall be made by the State Health
Department.
D.
Fire systems. At the service connection to any premises
in which a fire protection system is installed, the Village water
supply shall be protected based on the water source and arrangement
of supplies in accordance with the following classification:
(1)
Class 1 - Direct connection from public water mains
only; no pumps, tanks or reservoirs; no physical connections from
auxiliary water supplies; no antifreeze or other additives of any
kind; all sprinkler drains discharging to atmosphere, dry wells, or
other outlets.
Protection: None other than the check valve
required by the National Fire Code.
|
(2)
Class 2 - Same as Class 1, except booster pumps may
be installed in the connections from the street mains.
Protection: None other than the check valve
required by the National Fire Code.
|
(3)
Class 3 - Direct connection from public water supply
main plus one or more of the following: elevated storage tanks; fire
pumps taking suction from aboveground covered reservoirs or tanks;
and pressure tanks.
Protection: Double check valve assembly.
|
(4)
Class 4 - Directly supplied from public mains similar
to Classes 1 and 2, and with an auxiliary water supply on or available
to the premises; or an auxiliary supply may be located within 1,700
feet of the pumper connection.
Protection: Airgap or RPZ.
|
(5)
Class 5 - Directly supplied from public mains, and
interconnected with auxiliary supplies, such as pumps taking suction
from reservoirs exposed to contamination, or rivers and ponds; driven
wells; mills or other industrial water systems; or where antifreeze
or other industrial water systems; or where antifreeze or other additives
are used.
Protection: Airgap or RPZ.
|
(6)
Class 6 - Combined industrial and fire protection
systems supplied from the public water mains only, with or without
gravity storage or pump suction tanks.
Protection: Determined by the Superintendent
of Public Works upon review of certified engineering drawings of the
system prepared at the applicant's expense.
|
E.
Pier and dock hydrants. At the service connection
to any pier or dock hydrant used for supplying vessels at piers or
waterfronts, the Village water supply shall be protected by an approved
RPZ.
F.
Lawn sprinkling systems. At the service connection
to any permanently installed, below-grade lawn sprinkling system,
the Village water supply shall be protected by an approved RPZ assembly.
G.
Others. Examples of other facilities which may require
cross-connection control include, but are not limited to:
(1)
Beverage bottling plants.
(2)
Breweries.
(3)
Food processing plants.
(4)
Chemical plants and plating facilities.
(5)
Film laboratories.
(6)
Hospitals, medical buildings, sanitariums, morgues,
and mortuaries.
(7)
Irrigation systems.
(8)
Laundries and dye works.
(9)
Meat packing plants.
(10)
Metal manufacturing, cleaning and fabricating
plants.
(11)
Radioactive materials production or research
plants.
(12)
Restricted, classified or other facilities closed
to inspection.
(13)
Sewage and storm facilities.
(14)
Building heated by boilers where treatment chemicals
are used.
(15)
Building with certain types of air-conditioning
systems.
(16)
Swimming pools.
(17)
Printing operations.
(18)
Furniture stripping.
It shall be the duty of the water user on any
premises on account of which backflow protective devices are installed,
to have competent inspections made at least once a year, or more often
in instances where successive inspections indicate repeated failure.
Devices shall be repaired, overhauled or replaced at the expense of
the water user whenever they are found to be defective. These tests
shall be performed by a qualified backflow prevention device tester
and all test results will be provided to the water user within 72
hours after the test is made. Records of such tests, repairs and overhaul
shall also be kept and made available to the water user and the local
health department upon request.
All presently installed backflow prevention devices which do not meet the requirements of this article, but were approved devices for the purposes described herein at the time of installation and which have been properly maintained shall, except for the inspection and maintenance requirements under § 207-22 of this article, be excluded from the requirements of these rules as long as the Superintendent is assured that they will satisfactorily protect the Village's water supply. Whenever the existing device is moved from its present location or requires more than minimum maintenance which constitutes a hazard to health, the unit shall be replaced by a backflow prevention device meeting the requirements of this article.
A.
No water service connection to any premises shall
be installed or maintained by the water user, unless the water supply
is protected as required by this article and such other applicable
local, state and federal laws, rules and regulations.
B.
If any person or facility served by a water system
denies access to the premises to the Superintendent of Public Works
or his designated agent for the purposes of determining if protection
to the public water system is necessary, the maximum protection condition
shall be imposed with the requirement that the number of devices shall
equal the number of service lines.
C.
The Superintendent of Public Works or the County Health
Officer may order immediate discontinuance of service without notice
if:
(1)
In his opinion, the water supply of the Village of
New Paltz is being contaminated or is in immediate danger of contamination;
or
(2)
A protective device required by this article has not
been installed or has been removed or bypassed and the consumer cannot
be readily located or refuses to comply. Delivery of water may not
be resumed until the protective device required by this article and
approved by the Superintendent of Public Works has been properly installed,
or until the conditions at the premises causing the contamination
or danger of contamination have been abated or corrected to the satisfaction
of the Superintendent of Public Works or the County Health Officer.
D.
Notwithstanding any other provisions of this chapter
to the contrary, the following penalties shall be applicable for a
violation of the cross-connection control regulations set forth in
this article of the Municipal Code:
(1)
Failure to submit appropriate backflow prevention device plans to
the Village of New Paltz and the Ulster County Health Department within
30 days after the consumer is given notice of the requirements to
install the device: fine set annually by resolution of the Board of
Trustees.
[Amended 10-22-2014 by L.L. No. 13-2014]
(2)
Failure to comply with correction of plans within 30 days of notice
thereof: fine set annually by resolution of the Board of Trustees.
[Amended 10-22-2014 by L.L. No. 13-2014]
(3)
Failure to complete installation of the appropriate backflow prevention
device within 30 days after final approval of plans: fine set annually
by resolution of the Board of Trustees.
[Amended 10-22-2014 by L.L. No. 13-2014]
(4)
Failure to complete installation of the appropriate
backflow prevention device within 15 days after second notice: Termination
of service.
(5)
Failure to at least annually test the backflow prevention device:
fine set annually by resolution of the Board of Trustees or termination
of water service, or both.
[Amended 10-22-2014 by L.L. No. 13-2014]
(6)
Failure to replace or repair a backflow prevention device as required
within 30 days after notice: fine set annually by resolution of the
Board of Trustees or termination of water service, or both.
[Amended 10-22-2014 by L.L. No. 13-2014]