Exciting enhancements are coming soon to eCode360! Learn more 🡪
Allegheny County, PA
 
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
A. 
General.
(1) 
Vent pipe sizes shall be determined from Table 860-144, on the basis of length and fixture units connected.
Table 860-144
Size and Length of Vents
Size of Vent Pipe In Inches
Maximum developed length in feet
Number of Fixture Units
Branch
Main
Vented Branch or Main
*1 1/4
20 feet
20 feet
2 Units
*1 1/2
30 feet
100 feet
10 Units
2
40 feet
150 feet
24 Units
2 1/2
60 feet
300 feet
40 Units
3
80 feet
400 feet
100 Units
4
140 feet
700 feet
500 Units
5
140 feet
700 feet
1100 Units
6
140 feet
700 feet
1900 Units
8
200 feet
1000 feet
3600 Units
NOTE:
*
No water closets permitted on vent piping less than 2" in diameter.
(2) 
In applying vent sizing table above, for water closets or pedestal urinals, a fixture unit value of eight shall be assigned to all types of such fixtures, whether flush tank or flush valve supplied.
B. 
Minimum diameter of vent piping. No vent pipe shall be less than 1 1/4 inches in diameter.
C. 
Individual vents. The diameter of individual vents shall be based on the size of trap being vented, but not less than the following sizes:
Size of Vent
(inches)
Size of Trap
(inches)
1 1/4
1 1/4
1 1/2
1 1/2 to 2 1/2
2
3 and 4
1/2 their diameter
5 and over
D. 
Relief vents. The diameter of a relief vent shall be at least one-half the diameter of the soil or waste branch served, except as provided for in §§ 860-147E and 860-158.
E. 
Circuit or loop vents. The diameter of circuit or loop vents shall be based on the number of fixture units connected as determined from Table 860-144, "Branch or Main."
F. 
Size of branch vents. Branch vents which are meant to include all parts of the venting system other than the main vent, vent stack, or stack vent shall be sized in accordance within the limits of length and number of fixture units vented as provided for in Table 860-144, Branch or Main, except where other-wise provided for in this chapter. The length of the branch vent for application with Table 860-144 shall be measured from its connection with the furthest fixture drain to its connection to a larger vent, vent stack, stack vent or its terminal in the open air.
Vent pipe and fittings for the venting system shall comply with the provisions of Article V.
The protection of trap seals from siphonage or back pressure shall be accomplished by the appropriate use of soil or waste stacks, vents, revents, back vents, loop vents, circuit or continuous vents, or combination thereof, installed in accordance with the requirements of this Chapter, so that at no time shall the trap be subjected to a pressure differential of more than one inch of water.
A. 
Stack vent required. Every soil or waste stack shall be extended vertically as a stack-vent to the open air above the roof.
B. 
Vent stack required. An attendant vent stack or main vent shall be installed with a soil or waste stack whenever relief vents, back vents, circuit vents, or other branch vents are required in a building of three or more branch intervals.
C. 
Size and length of vent stacks. Vent stacks or main vents shall have a diameter of at least one half that of the soil or waste stack, but not less than one and one half inches in diameter, and shall be of a larger size in accordance with the limits of length and number of fixture units vented as determined from Table 860-144, nor shall they be smaller than the largest branch vent connected thereto. The length of the main or vent stack for application with Table 860-144, shall be the total developed length as follow:
(1) 
From the lowest connection of the vent stack with the soil stack, waste stack, or building drain to the terminal of the vent stack when it terminates separately to the open air.
(2) 
From the lowest connection of the vent stack with the soil stack, waste stack, or building drain to the stack vent plus the length of the stack vent and vent stack when the two are joined with a single extension to the open air.
D. 
Connections at base and top. All main vents or vent stacks shall connect full size at their base to the building drain or to the main soil or waste pipe, at or below the lowest fixture branch. All vent stacks or main vents shall extend undiminished in size above the roof, or shall be reconnected with the main soil or waste stack at least six inches above the flood level of the highest fixture connection with a single extension from the connection through the roof.
E. 
Buildings with five or more branch intervals above an offset.
(1) 
Offsets of more than 45° from the vertical in a soil or waste stack shall be vented by installing a relief vent as a vertical continuation of the lower section of the stack or as a side vent connected to the lower section between the offset and the next lower fixture or horizontal branch connection.
(2) 
The diameter of the offset relief vent shall not be less than the diameter of the main vent to which it connects or of the soil or waste stack, whichever is smaller. (Also see § 860-138D.)
F. 
Vent headers. Stack-vent and vent stacks may be connected into a common vent header at the top of the stacks and then extended to the open air as a direct extension of one stack. This header shall be sized in accordance with the requirements of Table 860-144, the number of units being the sum of all units on all vent stacks connected thereto and the developed length being the longest vent length from the intersection at the base of the most distant stack to the vent terminal in the open air.
A. 
Extension above roofs. Extension of vent pipes through a roof shall be terminated at least 12 inches above it. Where a roof is to be used for any purpose other than weather protection, the vent shall be at least seven feet above the roof.
B. 
Waterproof flashing. Each vent terminal shall be made watertight with the roof by proper flashing.
C. 
Flag poling prohibited. Vent terminals shall not be used for the purpose of flag poling, TV aerials or similar purposes.
D. 
Location of vent terminal. No vent terminal shall be located directly beneath any door, window, or other ventilating opening of the building or of an adjacent building nor shall any such vent terminal be within ten feet horizontally of such an opening unless it is at least two feet above the top of such opening. Vent terminals shall not terminate under the overhang of a building.
E. 
Extensions through wall. Vent terminals extending through a wall, when approved by the Administrative Authority, shall be at least ten feet horizontally from any adjacent building line and terminate downward. They shall be effectively screened and properly flashed, caulked or otherwise sealed at the wall penetration and shall meet the requirements of Subsection D.
F. 
Extension outside building. No soil, waste, or vent pipe extension shall be run or placed on the outside of a wall of any new building, but shall be carried up inside the building.
A. 
Vent grade. All vent and branch vent pipes shall be so graded and connected as to drain back to the soil or waste pipe by gravity.
B. 
Vertical rise. Where vent pipes connect to a horizontal soil or waste pipe, without the benefit of a proper washout, the vent shall be taken off above the center line of the waste or soil pipe. The vent pipe shall rise vertically, or at an angle not more than 45° from the vertical, to a point at least six inches above the flood-level rim of the fixture it is venting, before offsetting horizontally or before connecting to a branch vent. (Refer to illustration in Chapter 22.[1])
[1]
Editor's Note: The illustrations are on file in the Health Department.
C. 
Height above fixtures. A connection between a vent pipe and a vent stack or stack-vent shall be made at least six inches above the flood-level rim of the highest fixture served by the vent. Horizontal vent pipes forming branch vents, relief vents, or loop vents shall be at least six inches above the flood-level rim of the highest fixture served.
A. 
Distance of trap from vent. Each fixture trap shall have a protecting vent so located that the slope and the developed length in the fixture drain from the trap weir to the vent fitting are within the requirements set forth in Table 860-150A,, "Distance of Fixture Trap from Vent".
Table 860-150A
Distance of Fixture Trap From Vent
Size of Fixture Trap
Distance
Trap to Vent
1 1/4 inches
2 feet
6 inches
1 1/2 inches
3 feet
6 inches
2 inches
5 feet
0 inches
2 1/2 inches
5 feet
0 inches
3 inches
6 feet
0 inches
4 inches and over
10 feet
0 inches
B. 
Trap dip. The vent pipe opening from a soil or waste pipe, except for water closets and similar fixtures, shall not be below the weir of the trap.
C. 
Crown venting limitations. No vent shall be installed within two pipe diameters of the trap weir.
Hydraulic gradient. Fixture drains shall be vented within the hydraulic gradient between the trap outlet and vent connection, but in no case shall the unvented drain exceed the distance provided for in Table 860-150A, "Distance of Fixture Trap from Vent."
A. 
Water closets and pedestal urinals independently connected to soil stack. A single floor set water closet or pedestal urinal independently connected to a soil stack and within the required distance as provided for in Table 860-150A will not require any additional relief. Where two closets, two urinals or any combination thereof are installed on one horizontal branch, they shall be looped or circuit vented as provided for in § 860-156A, "Circuit and Loop Venting of Water Closets and Pedestal Urinals."
B. 
Water closets connected to building drain. A single water closet independently connected to any stack vented portion of the building drain and not over ten feet from such drain will not require a relief vent; where more than ten feet, or where more than one such fixture is located on one branch, there shall be provided a proper size relief or loop vent. No floor set water closet or similar floor level connected fixture shall be connected to the building drain closer than five feet upstream or downstream of a soil or waste stack in buildings of four or more stories.
A single wall hung water closet shall have the three inch soil, or vent stack directly in back of closet, or have a separate two inch vent, and when closets are located above one another, each shall have a separate two inch vent in back of each closet, except the upper most closet will not require a separate two inch vent provided it connects directly to the stack vent. When more than three wall hung water closets are located on one horizontal branch, they shall be provided with a circuit or loop vent as provided for in § 860-156A in addition to the two inch vent directly in back of each closet, but no other relief vents will be required. Wall hung water closets shall have a separate two inch vent in back of each closet, except that two closets back to back may have a common two inch vent.
A. 
Floor drains and similar floor level connected fixtures above basement floor. The minimum size trap for floor drains above basement floor shall be three inches, except emergency floor drains in laundry rooms of single family homes may be two inches and shall be considered as a plumbing fixture, and be properly vented. Floor drains, or showers with a trap size of three or four inches upstream of water closets or similar fixtures may be circuit or loop vented. When floor drains or showers are placed on a common horizontal branch with water closets or similar fixtures and located on the downstream side of such fixtures, they shall be individually vented, or they shall be isolated on their own waste branch and circuit or loop vented. Loop or circuit vents shall be sized as provided in Table 860-144, and they shall vent or take off in front of the last fixture connection, or be washed out by the fixture they serve, or the vent may be washed out by a higher connected fixture.
B. 
Floor drains and similar fixtures connected to building drain. A single floor drain or similar floor-level connected fixture independently connected to any stack vented portion of the building drain and not over ten feet from such drain will not require a relief vent; where more than ten feet, or where more than one such fixture is located on one branch, there shall be provided a proper size relief or loop vent.
Combination of fixtures on one horizontal branch. When two water closets, two floor drains, or two similar floor-level connected fixtures, or any combination of these fixtures are located on one horizontal branch of the building drain, they shall be provided with a proper size relief or loop vent.
A. 
Battery venting. A branch soil to which two but not more than eight water closets or pedestal urinals are connected in a battery, shall be vented by a circuit or loop vent which shall be taken off in front of the last fixture connection of the battery, washed out by the fixture it serves, or the vent may be washed out by a higher connected fixture. In addition, lower floor branches serving more than three water closets or pedestal urinals shall be provided with a relief vent taken off in front of the first fixture connection of the battery, in addition to the required circuit vent. When nine or more water closets are connected in a battery, an additional relief vent will be required, and shall be evenly spaced between the first relief vent and the circuit vent so that there are never more than eight water closets between a relief, circuit or loop vent.
B. 
Dual branches. When water closets or pedestal urinals are located back to back, dual or parallel horizontal branches may be used, provided each branch is separately looped or circuit vented and any other venting requirements as required by Subsection A (refer to illustration located in Chapter 22[1]).
[1]
Editor's Note: The illustrations are on file in the Health Department.
C. 
Fixtures back-to-back in battery. When water closets or pedestal urinals are connected to one horizontal branch through a double wye or a sanitary cross in a vertical position, a common vent for each two fixtures back to back or double connection shall be provided. The common vent shall be installed in a vertical position as a continuation of the double connection. The branch shall be circuit or loop vented as required in Subsection A, but no other relief vents will be required.
D. 
Soil branches to stacks which rise more than one story height. Branches to soil stacks which receive the discharge of water closets and similar fixtures which rise more than one story height shall maintain and continue the size of such branches as a circuit or loop vent. The load of such branches shall not exceed that contained in Article XII, Table 860-133B, Maximum Number of Fixture Units on one Horizontal Branch. (Refer to illustration in Chapter 22.[2])
[2]
Editor's Note: The illustrations are on file in the Health Department.
E. 
Vent connections. When the circuit, loop or relief vent connections are taken off the horizontal branch, the vent branch connection shall be taken off at a vertical angle or from the top of the horizontal branch, or otherwise be adequately washed out by a higher connected fixture drain.
Individual vent as common or dual vent. A common or dual vent is permitted for two fixture traps when installed on a vertical continuous waste and vent, or stack vented when the highest fixture, provided both fixture drains connect with the vertical drain or stack on the same level and within the distance allowed between a trap and its vent.
Soil and waste stacks in building have more than 10 branch intervals shall be provided with a relief or yoke vent at each tenth interval installed, beginning with the top floor. Where an odd number of floors above ten are involved, they shall be equally divided. The size of the relief or yoke vent shall be equal to the size of the vent stack to which it connects. The lower end of each relief or yoke vent shall connect to the soil or waste stack through a wye below the horizontal branch serving that floor, and the upper end shall connect to the vent stack through an inverted wye or tee not less than three feet above the floor level.
A. 
Sizing and venting of sub-drain and sumps. The system of drainage piping below the sewer level shall be size, installed, and vented in a like manner to that of the gravity system. Every sump or receiving tank shall have a vent pipe, which shall be sized according to the number of fixture units draining to sump; and in accordance with Table 860-144 based on branch venting for developed length, but in no case less than two inches in diameter. Sumps receiving the discharge of clear water, such as rain water, sub-soil or seepage drainage will not require a vent.
B. 
Separate vents. Vents from pneumatic ejectors or similar equipment shall be carried separately to the open air as a vent terminal. Such relief pipe shall be of sufficient size to relieve air pressure inside the ejector to atmospheric pressure within ten seconds, but shall not be less than two inches in size.
No vent shall be required for a rain conductor trap, backwater trap, area drain, sub-soil catch basin trap, or any outside drain. For further clarification of venting procedures as outlined in this chapter, refer to illustration in Chapter 22.[1]
[1]
Editor's Note: The illustrations are on file in the Health Department.