Exciting enhancements are coming soon to eCode360! Learn more 🡪
City of Hornell, NY
Steuben County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
A. 
Required. Plans and specifications of plumbing work, together with an application signed by the owner or his agent for a permit, must be submitted to the Inspector of Plumbing for approval, and a permit must be obtained before any part of the building or work is commenced.
B. 
Contents. There shall be a separate plan for each building, public or private, accompanied by specifications describing the drainage of said building on blanks prescribed and furnished for this purpose, showing the size and kind of pipe, traps, closets, fixtures, etc., to be used, the same to be examined and placed on file in the office of the Department or Board of Health.
C. 
Preparation. Plans must be made by the architect or engineer where one is employed.
Application for a change in plans or work in the building must be made, in writing, by the plumber, duly signed by the owner or his agent, and a written permit obtained from the Board of Health before any part of the change is commenced.
If any work done under the provisions of this chapter shall necessitate trench or street cuts, the person performing such work shall furnish to the city a security bond in the amount required by the city.
Any owner wishing to install plumbing in his own residence only shall obtain permission from the Plumbing Inspector[1] to do such work, file proper plans and pay the regular fees and comply with the requirements of this chapter; and in such event, the word "owner" shall be substituted for the word "plumber" throughout the chapter.
[1]
Editor's Note: The original words "Plumbing Board" have been changed to "Plumbing Inspector" at the request of the city, in accordance with L.L. No. 2-1994.
Where a public sewer is accessible in a street, alley, easement or thoroughfare to a building or premises abutting thereon, the liquid wastes from any plumbing system in said building shall be discharged into the public sewer unless otherwise prohibited.
Where the liquid wastes from any plumbing system are not discharged into a public sewer, such wastes shall be so treated or disposed of as not to endanger any water supply that is or may be used for drinking or domestic purposes or so as not to create any nuisance or unsanitary condition.
No septic tank shall be located less than 20 feet from an occupied building, except by special permission of the Plumbing Inspector or the Board of Health, nor shall a septic tank be located within or under a building, nor shall a septic tank be connected to a sewer.
A. 
Discharge into public sewer. Corrosive or harmful wastes and wastes at a temperature higher than 140° F. shall not be discharged into a public sewer.
B. 
Discharge into plumbing system. Such wastes shall not be discharged into a plumbing system to which water closets, bathtubs, lavatories or other household plumbing fixtures are connected. The plumbing system designed to receive such wastes shall be of a material capable of resisting the destructive action of such wastes.
C. 
Use of cooling device. Where fixtures discharge wastes at a temperature higher than 140° F., they shall be provided with a satisfactory cooling device.
A. 
Discharge into sewers prohibited. No explosive or flammable matters shall be discharged into any sewer.
B. 
Intercepting tank or pit required. Cleaning establishments, buildings used for housing or repairing automobiles, gasoline and oil service stations and other buildings or establishments where gasoline, oils, calcium carbide or other explosives or flammable materials are stored, sold or handled, the drains from which are connected to the public sewers, must be provided with an approved intercepting pit or tank so constructed, located and maintained as to prevent the entrance into the sewer of such explosive or flammable matter. Such intercepting tank or pit shall be approved by the Plumbing Inspector or the Board of Health.
A. 
Grades of horizontal piping. All horizontal piping shall be run in practical alignment and at a uniform grade of not less than 1/8 inch per foot and shall be supported or anchored at intervals not to exceed 10 feet. All stacks shall be supported at their bases, and all pipes shall be rigidly secured.
B. 
Changes in direction. All changes in direction shall be made by the appropriate use of forty-five-degree wyes, half-wyes, long-sweep quarter bends or sixth-, eighth- or sixteenth-bends, except that sanitary tees or offsets may be used on vertical stacks and short quarter-bends may be used in soil and waste lines where the change in direction of flow is from the horizontal to the vertical. Tees and crosses may be used in vent pipes.
C. 
Prohibited fittings. No T's or Y's shall be used on horizontal soil or drain lines. The drilling and tapping of house drains, soil, waste or vent pipes and the use of saddle hubs and bands are prohibited.
D. 
Dead ends. In the installation of any drainage system, dead ends shall be avoided.
E. 
Offsets in mains. Offsets in the mains of all stacks shall be avoided, but when unavoidable, they shall be made with fittings as described in Subsection B.
F. 
Stack; pipe supports.
(1) 
All freestanding stacks shall be thoroughly supported on concrete or masonry piers at their base, and those 40 feet or more in height shall also be provided with footrests at their bases and also with floor or supports at intervals of 10 feet.
(2) 
The pipe supports, according to their location, shall be made either with heavy iron posts, hangers, wall brackets or steel fittings or concrete or masonry piers, provided that no brick pier shall be less than eight inches square. The use of pipe hooks shall be prohibited for larger than one-and-one-half-inch pipes.
G. 
Protection of pipes against breakage and corrosion. All pipes passing under or through walls shall be protected from breakage. All pipes passing through or under cinder concrete or other corrosive material shall be protected against external corrosion.
If required, suitable toilet facilities should be provided for the use of workmen during the construction of any building. These toilet facilities shall be maintained in a sanitary condition.
A. 
Freedom from defects required. All materials used in any drainage or plumbing system or part thereof shall be free from defects.
B. 
Material to be stamped or marked. Each length of soil, pipe, fittings and device used in a plumbing or drainage system shall be stamped or indelibly marked with the weight or quality thereof and the maker's mark or name.
C. 
New materials. Any other material than that specified in this chapter which the Board of Overseers approves as being equally efficient may be permitted.[1]
[1]
Editor's Note: The words "Examining Board of Plumbers" have been changed here and throughout this chapter to "Board of Overseers," where applicable, at the request of the city, in accordance with L.L. No. 2-1994.
D. 
Vitrified clay pipe. All vitrified clay pipe shall conform to the American Society for Testing and Materials, Standard Specifications for Clay Sewer Pipe, Serial Designation C 13-24.
E. 
Cast-iron pipe.
(1) 
Quality. All cast-iron pipe and fittings shall conform to the American Society for Testing and Materials, Standard Specifications for Cast-Iron Soil Pipe and Fittings, Serial Designation A 74-18.
(2) 
Coating. All cast-iron pipe and fittings for underground use shall be coated with asphaltum or coal tar pitch.
(3) 
Soil pipe and fittings. All soil pipe and fittings used are to be of a weight known as "standard," except in buildings over three stories high, then all soil pipe and fittings used shall be of a weight known as "extra heavy."
F. 
Wrought iron pipe. All wrought iron pipe shall conform to the American Society for Testing and Materials, Standard Specifications for Welded Wrought Iron Pipe, Serial Designation A 72-27, and shall be galvanized.
G. 
Steel pipe. All steel pipe shall conform to the American Society for Testing and Materials, Standard Specifications for Welded and Seamless Steel Pipe, Serial Designation A 53-27, and shall be galvanized.
H. 
Brass and copper pipe. Brass and copper pipe shall conform, respectively, to the Standard Specifications of the American Society for Testing and Materials for Brass Pipe, Standard Sizes, for Copper Pipe Standard Sizes, for Copper Pipe and Fittings Standard Sizes and for Copper Tubing, Serial Number, brass pipe, B 43-58, tube, B135-58, copper drainage tube, D.W.V. B 306-59, and water tube, K-L-M-B 88-58, respectively.
I. 
Lead pipe; diameter and weights. All lead pipe shall be of the best quality of drawn pipe of not less weight per linear foot than as follows:
(1) 
Lead soil, waste, vent or flush pipes, including bends and traps (extra light):
Internal Diameter
(inches)
Weight Per Foot
1
2 pounds
1 1/4
2 pounds 8 ounces
1 1/2
3 pounds 8 ounces
2
4 pounds
3
4 pounds 12 ounces
4
6 pounds
J. 
Sheet lead. Sheet lead shall weigh not less than four pounds per square foot.
K. 
Sheet copper or brass. Sheet copper or brass shall be not lighter than No. 18 Brown and Sharp gauge, except that for local interior ventilating pipe, it shall be not lighter than No. 26 Brown and Sharp gauge.
L. 
Galvanized sheet iron. Galvanized sheet iron shall be not lighter than the following Brown and Sharp gauges:
(1) 
No. 26 for two- to twelve-inch pipe.
(2) 
No. 24 for thirteen- to twenty-inch pipe.
(3) 
No. 22 for twenty-one- to twenty-six-inch pipe.
M. 
Fittings.
(1) 
Plain screwed fittings. Plain screwed fittings shall be of cast-iron, malleable iron or brass of standard weight and dimensions.
(2) 
Drainage fittings. Drainage fittings shall be of cast-iron, malleable iron or brass, with a smooth interior waterway, with threads tapped out of solid metal.
(3) 
Malleable and cast-iron fittings. All malleable and cast-iron fittings shall be galvanized.
(4) 
Fittings for copper tubing. All fittings for copper tubing shall be brass and shall have a smooth interior waterway reamed out of solid material for the inserting of copper tubing.
N. 
Brass caulking ferrules; weights and dimensions. Brass caulking ferrules shall be of the best quality red cast brass, with weights and dimensions in accordance with the following table:
Pipe size
(inches)
Actual Inside Diameter
(inches)
Length
(inches)
Weight
2
2
4
1 pound
3
3
4
1 pound 8 ounces
4
4
4
2 pounds 4 ounces
O. 
Soldering nipples. Soldering nipples shall be of brass pipe, iron size or of heavy, cast red brass not less than the following weights:
Diameter
(inches)
Weight
1 1/4
6 ounces
1 1/2
8 ounces
2
14 ounces
2 1/2
1 pound 6 ounces
3
2 pounds
4
3 pounds 8 ounces
P. 
Floor flanges for water closets. Floor flanges for water closets shall be not less than 3/16 inch thick and of brass or cast-iron.
Q. 
Blowoff pipes. Blowoff pipes from boilers or heating plants shall be of cast-iron, wrought iron or steel.
A. 
Joints and connections to be gas- and watertight. All joints and connections mentioned under this section shall be made permanently gas- and watertight.
B. 
Vitrified pipe joints. All joints in vitrified clay pipes between vitrified clay pipe and metal shall be yarned and poured with hot jointing material.
C. 
Caulked joints. All caulked joints shall be firmly packed with oakum or hemp and shall be secured only with pure lead not less than one inch deep, well caulked, and no paint, varnish or putty will be permitted until after the joint is tested.
D. 
Screw joints. All screw joints shall be American Standard screw joints, and all burrs or cuttings shall be removed.
E. 
Cast-iron joints. Cast-iron joints may be either caulked or screw joints made in the approved manner.
F. 
Wrought iron, steel or brass to cast-iron joints. The joints may be either screwed or caulked joints made in the approved manner.
G. 
Lead pipe joints. Joints in lead pipe or between lead pipe and brass or copper pipes, ferrules, soldering nipples, bushings or traps, in all cases on the sewer side of the trap and in concealed joints on the inlet side of the trap, shall be full-wiped joints, with an exposed surface of the solder to each side of the joint of not less than 3/4 inch and a minimum thickness at the thickest part of the joint of not less than 3/8 inch. Except in concealed and inaccessible positions, other types of joints may be permitted if approved by the Board of Overseers.[1]
[1]
Editor's Note: The words "Examining Board of Plumbers" have been changed here and throughout this chapter to "Board of Overseers," where applicable, at the request of the city, in accordance with L.L. No. 2-1994.
H. 
Sweat joints. Sweat joints shall be made by means of carrying the liquefied solder around the entire surface between the pipe and fittings by capillary attraction. Copper tubing is to be cut square so as to butt square against the shoulder of the fitting.
I. 
Lead to cast-iron, steel or wrought iron joints. Lead to cast-iron, steel or wrought iron joints shall be made by means of a caulking ferrule, soldering nipples or bushing.
J. 
Slip joints and unions. Slip joints will be permitted in trap seals or on the inlet side of the trap. Unions on the sewer side of the trap may be slip joints if not concealed or enclosed.
K. 
Roof joints. The joints at the roof shall be made watertight by use of copper, lead or iron plates or flashings.
L. 
Closet, pedestal, urinal and trap, standard slop sink and floor connections. A brass floor connection shall be wiped or soldered to lead pipe, an iron floor connection shall be caulked to cast-iron pipe or an iron floor connection caulked or screwed to wrought iron pipe and the floor connection bolted to an earthenware trap flange. A metal to earthenware, a metal to metal union or a lead or asbestos gasket, spun-rubber gasket, putty or approved wax seal shall be used to make a tight joint.
M. 
Increasers and reducers. Where different sizes of pipes or pipes and fittings are to be connected, proper size increasers or reducers between the two sizes shall be used.
N. 
Prohibited joints and connections. Any fitting or connection which has an enlargement, chamber or recess with a ledge shoulder or reduction of the pipe area in the direction of the flow on the outlet or drain side of any trap is prohibited. No saddles shall be permitted on waste or vent lines.
O. 
Expansion bolts. Connections of wall hangers, pipe supports or fixture settings with masonry, stone or concrete backing shall be made with expansion bolts without the use of wooden plugs.
A. 
Kinds of traps required.
(1) 
Generally. Every trap shall be self-cleaning. Traps for bathtubs, lavatories, sinks and other similar fixtures shall be of lead, brass, cast iron or of malleable iron, galvanized or porcelain-enameled inside. Galvanized or porcelain-enameled traps shall have a full-bore smooth interior waterway, with threads tapped out of solid metal.
(2) 
Sizes. The minimum size (nominal inside diameter) of trap and waste branch for a given fixture shall be not less than shown in the following table:
Kind of Fixture
Size of Trap and Branch
(inches)
Baths, foot
1 1/2
Baths, shower stall
2
Baths, sitz
1 1/2
Bathtubs
1 1/2
Bidets
1 1/2
Combination fixtures
1 1/2
Drinking fountains
1 1/4
Fountain cuspidors
1 1/4
Floor drains
2
Laundry trays
1 1/2
Lavatories
1 1/4
Sinks, dishwasher
1 1/2
Sinks, hotel or public
2
Sinks, kitchen, residence
1 1/2
Sinks, large hotel or public
2
Sinks, slop, with trap combined
3
Sinks, slop, ordinary
2
Sinks, small, pantry or bar
1 1/4
Urinals, lip
1 1/2
Urinals, pedestal
3
Urinals, stall
2
Urinals, trough
2
Water closets
3
(3) 
Concealed traps. Concealed traps shall be four inches by eight inches tapped according to the list set forth in Subsection A(2) for trap sizes or approved deep seal brass trap.
B. 
Prohibited traps. No form of trap which depends for its seal upon the action of movable parts or concealed interior partitions shall be used for fixtures. Where there is an antisiphon trap already installed, such trap may be replaced with the same type of trap.
C. 
Location and number of traps; double-trap prohibited. Each fixture shall be separately trapped by a water-seal trap placed as near to the fixtures as possible, except that a set of not more than three laundry trays or lavatories or a set of two laundry trays and one sink may connect with a single trap. In no case shall the waste from a bathtub or other fixture discharge into a water closet trap. No fixtures shall be double-trapped.
D. 
House trap and fresh-air inlet. On sanitary house sewers or drains, there shall be placed in such sewer or drain a running trap, which trap shall have two four-inch handholes and which shall be connected to a Y-branch trap placed in the cellar as near as possible to the building or foundation wall. Just ahead of the house trap, a fresh-air inlet shall be connected and run to the outside of the building. The fresh-air inlet shall not be less than four inches and the outside opening of the same shall be left not less than 12 inches above finished grade and not less than eight feet from any window, door or opening; also the opening of the same shall be properly capped to permit free entry of air. Where there is no cellar under the building, the house or building trap is to be placed underground as near as possible to the outside of the building wall.
E. 
Water seal. Each fixture trap shall have a water seal of not less than two inches and not more than five inches, except grease traps.
F. 
Trap cleanouts. Each trap, except those in combination with fixtures in which the trap seal is plainly visible and accessible, shall be provided with an accessible brass trap screw of ample size, protected by the water seal. All concealed traps in floors shall have not less than a four-inch screw cleanout. The cleanout shall be accessible above the floor.
G. 
Trap levels and protection. All traps shall be set true with respect to their water seals and protected from frost and evaporation.
H. 
Pipe cleanouts.
(1) 
Specifications. The bodies of cleanout ferrules shall be made of standard pipe sizes, shall conform in thickness to that required for pipe and fittings of the same metal and shall extend not less than 1/4 inch above the hub. The cleanout cap or plug shall be of heavy brass not less than 1/8 inch thick and shall be provided with a raised nut or recessed socket for removal.
(2) 
Locations and sizes. A cleanout easily accessible shall be placed at the foot of each vertical waste or soil stack and one shall be placed at the end of the Y-branch of the house sewer. One cleanout shall be placed in each of the two handholes in the main house or building trap and also at the end of any horizontal soil or waste line that is over five feet in length. Cleanouts shall be the same size as the waste line up to four inches and not less than four inches for larger lines.
I. 
Manholes. All underground traps and cleanouts of a building, except where cleanouts are extended flush with the floor, and all exterior underground traps shall be made accessible by a manhole with proper cover or with cleanouts carried flush with the finished grade.
J. 
Cleanouts. Any floor or wall connection of fixture traps, when bolted or screwed to the floor or wall, shall be regarded as a cleanout.
K. 
Grease traps and catch basins; use and installation regulated.
(1) 
Where required. In any building where quantities of grease or oily wastes are discharged, a water-cooled grease trap shall be provided on each fixture through which such wastes are discharged or a grease catch basin shall be installed to intercept such wastes before they enter the house drain or house sewer. Where a grease catch basin is used, each fixture shall be separately trapped as provided in Subsection C above.
(2) 
Installation and protection. Whenever possible, the grease catch basin shall be installed outside of the wall of the building as near as possible to the fixtures from which it receives the discharge. Such a trap or catch basin shall be protected, where necessary, against freezing.
(3) 
Prohibited discharges. No human or fresh animal excrement shall be discharged into a grease catch basin, either directly or through any inlet pipe.
L. 
Location and specifications of grease traps. Where a grease trap is installed, it shall be placed as near as possible to the fixture from which it receives the discharge, and it shall have double the capacity of said fixture. It should be self-cleaning as regards sediment solids but large enough to chill and retain grease until manually cleaned. The outlet leg shall be so vented or installed as to preclude the possibility of self-siphonage.
M. 
Construction and capacity of grease catch basins. A grease catch basin shall be constructed in a watertight and substantial manner of steel, iron, brick, concrete, vitrified clay or masonry. The outlet pipe shall be one size larger than the inlet pipe and in no case less than four inches in diameter. The outlet shall be provided with an inverted bend and cleanout, it shall be submerged at least eight inches, and it shall receive liquid as close to the bottom as possible, and the bottom shall be formed that the sedimented solids will be scoured out at each discharge. The catch basin shall be so vented and installed so as to preclude the possibility of siphoning. The inlet shall enter near the water surface. The catch basin should have a tight masonry, vitrified clay or metal cover, readily removable and accessible for the removal of grease. The capacity of the catch basin should be not less than the maximum hourly inflow, except that for garages the capacity shall not be less than three by four (3 x 4) feet, unless special permission is given by the Board of Health.
N. 
Sand traps and catch basins.
(1) 
Where required; prohibited discharge. Sand traps or catch basins shall be installed on the waste pipe from any fixture or yard, stable, manure pit, cellar, floor or subsoil drain or roof leader or other waste, the discharges from which may contain sand or other gritty or clogging matter. The passing of human excrement through a sand trap or catch basin is prohibited.
(2) 
Design and construction. Sand traps and catch basins, when installed, shall be so designed and placed as to be readily accessible for cleaning. They shall be so constructed in the same general manner as provided for grease catch basins in Subsection M above, except that they shall be at least 20 inches in inside diameter, and where possible, the outlet shall be at least four feet below the surface of the ground. The outlet shall be submerged at least eight inches and shall be not less than 15 inches above the bottom of the basin.
(3) 
Ventilation. Where the waste passing through a sand trap or catch basin may contain foul-smelling matter and said sand trap or catch basin is located within a courtyard or within 12 feet of the outside walls of a building or within a building or said sand trap or catch basin is connected to a pipe or receptacle containing sewage or is connected to a plumbing system in such manner that ventilation through the entering soil pipe is not always possible, said sand trap or catch basin shall be vented with a two-inch vent pipe. Said vent pipe shall be connected to the highest practicable point in the sand trap or catch basin.
O. 
Gasoline and oil traps.
(1) 
Where required; prohibited discharge. A gasoline and oil trap shall be provided on the waste from all garages, automobile wash floors, cleaning establishments or establishments from which gasoline, benzine or other similar substance is discharged. The passing of human or animal excrement through such a trap is prohibited.
(2) 
Construction and capacity. A gasoline and oil trap shall be constructed in the same general manner as provided for a grease catch basin in Subsection M above. The capacity of the gasoline or oil trap shall be not less than twice the maximum hourly inflow.
(3) 
Ventilation. All gasoline and oil traps shall be vented with a four-inch or larger vent pipe leading from the highest practicable point in the trap.
P. 
Floor drains; trapping regulated. All floor drains shall connect into a trap so constructed that it can be readily cleaned and of a size to serve efficiently the purpose for which it is intended. The drain inlet shall be so located that it is at all times in full view. Such drains shall be equipped with an adequate backwater valve.
Q. 
Backwater valves; construction. Backwater valves shall have all bearing parts or balls of noncorrodible metal and be so constructed as to ensure a positive mechanical seal and remain closed except when discharging wastes.
A. 
Distribution of domestic and drinking water supply. The domestic and drinking water supply shall be distributed through a piping system entirely independent of any piping system conveying another water supply.
B. 
Size of water service pipe. The water service pipe of any building shall be of sufficient size to permit a continuous ample flow of water on all floors at a given time.
C. 
Water supply to fixtures.
(1) 
Generally. All plumbing fixtures shall be provided with a sufficient supply of water for flushing to keep them in a sanitary condition. Every water closet or pedestal urinal shall be flushed by means of an approved tank or flush valve of at least four gallons' flushing capacity for water closets and at least two gallons for urinals and shall be adjusted to prevent the waste of water. The flush pipe for water closet flush tanks shall be not less than two inches in diameter, and the water from flush tanks shall be used for no other purpose.
(2) 
Pollution. No plumbing fixtures or device shall be supplied directly from a water supply system through a flushometer or other valve unless such valve is installed in a manner such as to prevent any possibility of polluting the water supply.
(3) 
Interconnection. No plumbing fixture, device or construction shall be installed which will provide an interconnection between a distributing system of water for drinking and domestic purposes and a drainage, soil or waste pipe so as to permit or make possible the backflow of sewage or waste into the water supply system.
D. 
Size of water supply pipe. The minimum size of water service pipes from the curb to the dwelling shall be no smaller than 1/2 inch and to fixtures as follows:
Fixture
Minimum Size
(inches)
Bathtubs
1/2
Flush valves, closets
1
Flush valves, urinals
3/4
Hot-water boilers
1/2
Laundry trays
1/2
Lavatories
3/8
Sill cocks
1/2
Sinks
1/2
Urinals
1/2
Water closet tanks
3/8
E. 
Water supply control. A main shutoff on the water supply line shall be provided between the building wall and the curbline. An accessible shutoff shall be provided on the main supply line just inside the foundation wall which shall control the water supply to the entire building. Accessible shutoffs shall also be provided which shall separately control the water supply for each flat or apartment of a building, for each lawn sprinkler, for each hot-water tank and for each water closet.
F. 
Water supply pipes and fittings; material. All water supply pipes for a plumbing system shall be of galvanized wrought iron or steel, brass, copper or cast iron, with brass or galvanized malleable iron fittings. No pipe or fittings that have been used for other purposes shall be used for distributing water. Joints shall be caulked, screwed, sweat or swedged.
G. 
Protection of water supply. All concealed water pipes and storage tanks and all exposed pipes or tanks subject to freezing temperatures shall be efficiently protected against freezing.
H. 
Relief valves. Wherever a check valve or water meter is installed on the cold water supply pipe between the street main and the hot-water tank, there shall be installed on the hot-water distributing system a suitable relief valve.
I. 
Pumps and hydrants. All pumps and hydrants shall be protected from surface water and contamination.
J. 
High-pressure steam boiler feed. The high-pressure steam boiler shall not be supplied with water directly from public water supply pipes. All such boilers shall be provided with a tank or other receptacle of sufficient capacity to hold not less than six hours' supply for the boiler.
A. 
Water closets, urinals and similar receptacles; materials prescribed.
(1) 
All receptacles used as water closets, urinals or otherwise for the disposal of human excreta shall be vitrified earthenware.
(2) 
Where acid or water contaminated with acid is to be wasted, the fixtures, pipe and fittings in both waste and vent lines and connections to sewers must be of acidproof materials (lead, glass or Dur iron).
B. 
Installation generally. All plumbing fixtures shall be installed free and open in a manner to afford access for cleaning. When practical, all pipes from fixtures shall be run to the wall, and no lead trap or pipe shall extend nearer to the floor than 12 inches unless protected by casing.
C. 
Water closet bowls and traps. Water closet bowls and traps shall be made in one piece and of such form as to hold sufficient quantity of water, when filled to the trap overflow, to prevent fouling of surface and shall be provided with integral flushing rims constructed so as to flush the entire interior of the bowl.
D. 
Frostproof closets. Frostproof closets may be installed only in compartments which have no direct connection with a building used for human habitation or occupancy. The soil pipe between the hopper and the trap shall be three inches in diameter and shall be of lead or cast iron, enameled on the inside.
E. 
Flushing tanks for groups of urinals. A group of urinals on the same floor subject to constant use, as in schools and factories, may be supplied from one tank if provided with an automatic simultaneous flush, provided that each individual urinal shall receive not less than one gallon of water at each flushing and the discharge is of such force as to cleanse each individual bowl at each flush.
F. 
Automatic flushing tanks. All urinals having either intermittent or automatic flushing devices shall be flushed at regular intervals not to exceed 10 minutes each during the hours that such fixtures are in use.
G. 
Construction of urinals. All urinals other than those heretofore prescribed shall be constructed of enameled iron that will not corrode under the action of urine. The lip of all stall urinals must be set below the top of the floor so that all water or urine will drain from the floor to the urinal waste outlet, or a separate floor drain shall be provided for the toilet room.
H. 
Prohibited fixtures. Fixed wooden washtrays or sinks shall not be installed in any building designed or used for human habitation. No new copper-lined wooden bathtubs shall be installed, and an old fixture of this class taken out shall not be reconnected. Pan and valve plungers, offset washouts and other water closets having invisible seals or unventilated space or walls not thoroughly washed at each flush shall not be used. Long hopper closets or similar appliances shall not hereafter be installed. No dry closet or chemical closet shall be installed.
I. 
Shower drains. A shower drain shall be considered a fixture and provided with a strainer.
J. 
Fixture strainers. All fixtures other than water closets and pedestal urinals shall be provided with fixed strong metallic strainers with outlet areas not less than that of the interior of the trap and waste pipe.
K. 
Fixture overflow. The overflow pipe from a fixture shall be connected on the house or inlet side of the trap and shall be so arranged that it may be readily and effectively cleaned.
A. 
Location of fixtures restricted. No trapped plumbing fixtures shall be located in any room or apartment which does not contain a window placed in an external wall of the building or is not provided with a system of ventilation.
B. 
Compartments containing not more than four water closets. Compartments containing not more than four water closets or their equivalent shall be located in an apartment containing windows, of sufficient area to ventilate properly the compartment, placed in the external walls of the building or shall be provided with a mechanical means of ventilation which will change the air at a normal temperature at least six times per hour.
C. 
Compartments containing more than four water closets. Compartments containing more than four water closets or their equivalent shall be located either in an apartment containing windows and provided with a gravity or mechanical system of ventilation which will change the air at normal temperature not less than six times per hour or may be placed in a compartment without windows in the external wall of the building, provided that a mechanical system of ventilation is installed which will change the air at normal temperature not less than six times per hour.
D. 
Size of window or skylight. Every toilet room and every water closet or urinal compartment, unless provided with a suitable system of exhaust ventilation, shall be ventilated directly to the outer air by movable windows or by skylights with fixed or pivoted louvers. Every such toilet room or compartment shall have a window or glass skylight not less than one foot wide and an area of not less than six square feet for one water closet or urinal, and the area of the window or skylight shall be increased by at least one square foot for every additional water closet or urinal.
E. 
Mechanical ventilation systems. If a mechanical system of ventilation is used, such system shall consist of metal or smooth masonry ducts extending from the individual toilet rooms or compartments to a fan or fans of sufficient capacity to exhaust a volume of not less than 30 cubic feet of air per minute for each water closet or urinal, and in no case shall less than six changes of air in the toilet room or compartment be allowed per hour. The exhaust duct shall discharge into the outside air above the room and in such a manner as not to create objectionable odors or a nuisance on the premises or adjacent premises.
F. 
Ventilation from toilet rooms to be separate from other ventilating ducts. Ventilation from toilet rooms shall be separate and distinct and have no connection whatever with the other ventilating ducts in the building.
A. 
Materials.
(1) 
Main or branch soil, waste or vent pipes. All main or branch soil, waste and vent pipes within the building shall be of cast iron, galvanized steel or wrought iron, lead, brass or K copper, except that no galvanized steel or wrought iron pipe shall be used for underground soil or waste pipes.
(2) 
House or building drains. All house or building drains shall be cast iron, with caulked joints (neoprene rings permissible) or Schedule 40 PVC (plastic pipe) ASTM D2665, except for replacement of damaged drains.
[Amended 11-28-1988]
B. 
Demand load of fixtures.
(1) 
The load of fixtures shall be as follows:
Fixture
Occupancy
Type of Supply Control
Load
(in fixture units)
Bathrooms, group
Private
Flush tank for closet
6
Bathrooms, group
Private
Flush valve for closet
8
Bathtubs
Private
Faucet
2
Bathtubs
Public
Faucet
4
Combination fixtures
Private
Faucet
3
Lavatories
Private
Faucet
1
Lavatories
Public
Faucet
2
Shower heads
Private
Mixing valve
2
Shower heads
Public
Mixing valve
4
Showers, separate
Private
Mixing valve
2
Sinks, kitchen
Hotel, restaurant
Faucet
4
Sinks, kitchen
Private
Faucet
2
Sinks, service
Office, etc.
Faucet
3
Urinals
Public
Flush tank
3
Urinals
Public
1-inch flush valve
10
Urinals
Public
3/4-inch flush valve
5
Water closets
Private
Flush tank
2
Water closets
Private
Flush valve
6
Water closets
Public
Flush tank
5
Water closets
Public
Flush valve
10
(2) 
The sizes of individual fixture wastes and vents shall be as follows:
Size
Kind of fixture
Waste
(inches)
Vent
(inches)
Baths, foot
1 1/2
1 1/4
Bath shower stalls
2
1 1/4
Baths, sitz
1 1/2
1 1/4
Bathtubs
1 1/2
1 1/4
Combination fixtures
1 1/2
1 1/4
Drinking fountains
1 1/4
1 1/4
Fountain cuspidors
1 1/4
1 1/4
Floor drains
2
--
Laundry trays
1 1/2
1 1/4
Lavatories
1 1/4
1 1/4
Sinks, dishwasher
2
1 1/4
Sinks, hotel or public
2
1 1/4
Sinks, kitchen, residence
1 1/2
1 1/4
Sinks, slop, ordinary
2
1 1/4
Sinks, slop, with trap combined
3
2
Sinks, small, pantry or bar
1 1/4
1 1/4
Urinals, lip
1 1/2
1 1/4
Urinals, pedestal
3
2
Urinals, stall
3
2
Urinals, trough
2
1 1/4
Water closets
3
2
(3) 
All concealed traps shall be four inches by eight inches, tapped according to wastes and vents of the above schedule.
C. 
Soil and waste stacks.
(1) 
Generally. Every building in which plumbing fixtures are installed shall have a soil or waste stack or stacks extending full size through the roof. Soil and waste stacks shall be as direct as possible.
(2) 
Table of sizes. The required size of a soil or waste stack shall be determined from the distribution and totals of all fixture units connected to the stack in accordance with the following tables, except that no water closet shall discharge into a stack less than three inches in diameter:
Maximum Fixture Units on One Stack
Diameter
(inches)
Maximum Units On Any 1 Stack
1 1/4
2
1 1/2
4
2
10
3
18
4
44
D. 
Inlets for fixture connections for soil and waste stacks and branches. All soil and waste stacks and branches shall be provided with correctly faced inlets for fixture connections.
E. 
Changing soil and vent pipes in existing buildings. In existing buildings where the soil or waste vent pipe is not extended undiminished through or above the roof or where there is a soil or waste vent pipe and the fixture is changed in style or location or is replaced, a soil or waste vent pipe of the size and material prescribed for new work shall be installed.
F. 
Prohibited connections. No soil or waste vent, circuit or loop vent above the highest installed fixture on the branch or main shall thereafter be used as a soil or waste pipe.
G. 
Protection of soil and waste stack. No soil or waste stack shall be installed or permitted outside of a building unless adequate provision is made to protect it from frost.
H. 
Roof extensions. All roof extensions of soil and waste stacks shall be run full size at least one foot above the roof, and when the roof is used for other purposes than weather protection, such extension shall be not less than five feet above the roof.
I. 
Roof terminals. The roof terminal of any stack or vent, if within 12 feet of any door, window, scuttle or air shaft, shall extend at least three feet above the same.
J. 
Terminals in and adjoining high buildings.
(1) 
No soil, waste or vent pipe extension of any new or existing building shall be run or placed on the outside of a wall, but it shall be carried up in the inside of the roof.
(2) 
In the event that a new building is built higher than an existing building, the owner of the new building shall not locate windows within 12 feet of any existing vent stack on the lower building, unless the owner of such new building shall defray the expenses or shall himself make such alteration to conform to § 228-39G.
(3) 
It shall be the duty of the owner of the lower or existing building to make such alteration therein upon the receipt, in advance, of money or security therefor sufficient for the purpose from the owner of the new or higher building or to permit, at the election of the owner of the new or higher building, the making of such alteration by the owner of said new or higher building.
K. 
Future vents. A vent is to be run to basements having no fixtures. Such vent is to be capped and left accessible for future fixtures.
L. 
Vents for protection of fixture traps. Every fixture trap shall be protected against siphonage and back pressure, and air circulation assured by means of a soil or waste stack vent, a continuous waste or vent or a loop or circuit vent. Where it is impossible to vent a future trap as prescribed, crown or side venting may be used.
M. 
Distance of vent from trap seal. No trap shall be placed more than five feet, horizontal developed length, from its vent, except that the distance between the vent and trap may be 15 feet or less on the waste from a surgical operating table, dental cuspidor or other similar fixture. The distance shall be measured along the central line of the waste or soil pipe from the vertical inlet of the trap to the vent opening.
N. 
Main vents. Main vents shall be run as straight as possible and either shall be run full size through the roof or tied in other vents above the highest fixture.
O. 
Size of loop vents and stack vents. Circuit or loop vents and stack vents shall be the same size as branch waste and stack waste. Such vents shall be carried full size through the roof or tied back in the vent or in a vent that is not smaller in size and above any fixtures that said vent is venting. Any other branch waste that is over five feet from the main branch waste shall be vented as heretofore prescribed.
P. 
Size of branch and individual vents. No vent shall be less than 1 1/4 inches in diameter, and in no case shall a branch or main vent have a diameter less than 1/2 that of the soil or waste pipe served. No vents for closets shall be less than two inches.
Q. 
Vent pipe grades and connections. All vent and branch pipes shall be free from drops or sags.
R. 
When circuit and loop vents permitted. A circuit or loop vent will be permitted as follows: A branch or waste pipe to which two and not more than 12 water closets, pedestal urinals, trap-standard slop sinks or shower stalls are connected in the series may be vented by a circuit or loop vent, which shall be taken off in front of the last fixture connection. Where fixtures discharge above such branch, each branch shall be provided with a relief vent, provided that such waste is not run vertically more than three feet.
S. 
Vents not required.
(1) 
No vents will be required on a backwater trap, a subsoil catch basin trap or on a floor drain.
(2) 
No vents will be required where water closets or other fixtures are located on opposite sides of a wall or partition or directly adjacent to each other within the prescribed distance of the highest fixtures, if such fixtures are connected separately and at the same level to the stack and not more than five feet from the stack and no vertical branch waste is over three feet in length. Such fixtures are considered stack-vented. All other fixtures in buildings are to be vented as heretofore described.
(3) 
No vents will be required on laundry traps or sinks in the basement of an old or new building having no vent in the same. The same may be trapped by a four-by-ten-inch drain trap if such location is not over 10 feet from the main waste. The waste line shall be not less than 1 1/2 inches.
(4) 
Any plumbing fixture or fixtures previously set and connected to a sewer through an antisiphon trap may be moved to any new location if such location is not more than 25 feet from the present location, and such plumbing fixture or fixtures may be connected to the sewer through an antisiphon trap.
A. 
Independent systems of plumbing and drainage.
(1) 
Required. The drainage and plumbing system of each new building and of new work installed in an existing building shall be separate from and independent of that of any other building, except as provided below, and every building shall have an independent connection with a public or private sewer, when available.
(2) 
Exception. Where one building stands in the rear of another building or an interior lot and no private sewer is available or can be constructed to the rear building through an adjoining alley, court, yard or driveway, the house drain from the front building may be extended to the rear building and the whole will be considered as one house drain.
B. 
Use of old drains restricted. Old drains may be used in connection with new buildings or new plumbing only when they are found, on examination and test, to conform in all respects to the requirements governing new drains as prescribed in this chapter. If the old work is found defective, the proper administrative authority shall notify the owner to make the necessary changes to conform to this chapter.
C. 
Connections where sewer unavailable. When a sewer is not available, drain pipes from buildings shall be connected with an approved septic tank, leach bed or dry well if the same is approved prior to installation by the Board of Health or the City Engineer.
D. 
Excavations.
(1) 
Generally. Each system of piping shall be laid in a separate trench. Where a double system of drainage is installed, the sanitary and surface house drains may be laid side by side in one trench.
(2) 
Work to be open and uncovered. All excavations required to be made for the installation of a house drainage system or any part thereof within the walls of a building shall be open trench work. All such trenches and tunnels shall be kept open until the piping has been inspected, tested and approved.
E. 
Entry to be below basement or cellar floor. Whenever possible, all house drains shall be brought into the building below the basement or cellar floor.
F. 
Materials for house drains.
(1) 
Underground. The house drain, when underground, shall be of lead, K copper, brass or cast iron.
(2) 
Aboveground. The house drain, when aboveground, shall be of cast iron, galvanized wrought iron or steel, lead, copper or brass of approved standards. (See § 228-36A through I.)
G. 
Location of house drains. No underground house drain shall be laid parallel to or within three feet of any bearing which might be weakened thereby.
H. 
Size of sanitary house drains.
(1) 
The required size of sanitary house drains and horizontal branches shall be determined on the basis of the total number of fixture units drained by them in accordance with the following table:
Sanitary System Only
Diameter of Pipe
(inches)
Maximum Number of Fixture Units
1 1/4
1
1 1/2
3
2
6
3
20
4
30
(2) 
No water closet shall discharge into a drain pipe less than three inches in diameter.
(3) 
Not more than two water closets shall discharge into any three-inch horizontal branch or house drain.
I. 
Combined storm and sanitary sewer systems prohibited. No combination storm and sanitary sewer system will be permitted.
J. 
Drainage below level of main sewer.
(1) 
Artificial lift required. In all buildings in which the whole or part of the house drainage and plumbing system thereof lies below the crown level of the main sewer, sewage or house wastes shall be lifted by approved artificial means and discharged into the house sewer.
(2) 
Use of sumps and receiving tanks required. All house drains below sewer level shall discharge into a watertight sump or receiving tank so located as to receive the sewage by gravity, from which sump or receiving tank the sewage shall be lifted and discharged into the house sewer by pumps, compressed air or any equally efficient method. Such sumps shall be either automatically discharged or be of sufficient capacity to receive the house sewage and wastes for not less than 24 hours.
K. 
Venting of ejectors. The soil or waste pipe leading to an ejector or other appliance for raising sewage or other waste matter to the street sewer shall be extended full size through the roof independently from the vent pipes of the gravity drainage system.
L. 
Motors, compressors and air tanks. All motors, air compressors and air tanks shall be located where they are open for inspection and repair at all times. The air tanks shall be so proportioned as to be of equal cubical capacity to the ejectors connected therewith, in which there shall be maintained an air pressure of not less than two pounds for each foot of height the sewage is to be raised.
M. 
Ejectors for subsoil drainage below sewer level. When subsoil catch basins are installed below the sewer level, an automatic device for raising water or an automatic water ejector provided with a ball float attached to the main water supply shall be used.
N. 
Exhaust blowoffs and sediment and drip pipe connections. The exhaust blowoff and sediment or drip pipe from a high-pressure steam boiler shall not connect directly with any sewer, drain, soil or waste pipe. Such pipes shall discharge into the top and above the line of discharge of a suitable closed tank or condenser made of wrought or cast iron, provided with a relief pipe of at least three inches in diameter extending to the outer air above the roof.
O. 
Hot-water discharges prohibited. Water heated to over 140° F. shall not be allowed to enter any street sewer, drain or lateral. When blowoff tanks discharge water at a higher temperature, they shall be provided with a cooling device.
P. 
Elevators, lifts or pressure machines; use of intermediate tank required. All direct-connected hydraulic elevators, lifts or pressure machines shall be provided with an intermediate tank of sufficient capacity as to discharge its waste without pressure into any sewer, drain, soil or waste pipe. Such tank shall be trapped, and where there is danger of back pressure from the sewer, there shall be placed on its outlet side a sewer or backwater valve.
A. 
Drainage of yards, areas and roofs. All roofs and paved areas, yards, courts and courtyards shall be drained into the stormwater sewerage system. Where there are no storm sewers, available drains may empty into dry wells of cesspools.
B. 
Size of leaders.
(1) 
No inside leader shall be of less size than the following:
Area of Roof
(square feet)
Leader
(inches)
Up to 90
1 1/2
91 to 270
2
271 to 810
2 1/2
811 to 1,800
3
1,801 to 3,600
4
3,601 to 5,500
5
5,501 to 9,600
6
(2) 
Storm drain systems shall be measured as follows:
Diameter of Pipe
(inches)
Maximum Drained Roof Area
(square feet)
3
865
4
1,860
5
3,325
6
5,315
8
11,115
10
19,530
12
31,200
14
42,600
C. 
Inside conductors.
(1) 
When placed within the walls of any building or run in an inner or interior court of ventilating pipe shaft, all conductors or roof leaders shall be constructed of cast iron or galvanized wrought iron or steel pipe.
(2) 
Roof drains shall be of cast brass or iron having a proper strainer and clamping device, either tapped for an iron pipe or with a spicket end for caulking.
D. 
Prohibited uses of conductors, soil, waste or vent pipes. Conductor pipes shall not be used as soil, waste or vent pipes, nor shall any soil, waste or vent pipes be used as conductors. No main sewer trap or fresh air inlet shall be required for roof drains or waste.
No waste pipe from a refrigerator or icebox floor drain, soda water fountain, bar fixture or any other receptacle where food is stored or cooked shall connect directly with any house drain, soil or waste pipe. Such waste pipes shall in all cases empty into an open sink that is properly supplied with water connected, trapped and vented the same as other fixtures or into a cellar floor drain, but their ends must be left open. Such waste connections shall not be located in inaccessible or unventilated cellars.
Pipes from a water supply tank or exhaust from a water lift shall not be directly connected with any house drain, soil or waste pipe. Such pipe shall discharge upon the roof or be trapped into an open fixture or shall discharge in the same manner as for refrigerator wastes.
Wastes from hydraulic motors, hydraulic elevators or other machinery discharging large quantities of water shall be detained in a receiving tank of sufficient size and so connected as to prevent the discharge of the wastes under pressure.
The waste pipe from any fixture such as a bubbling fountain, aquarium overflow or fixture of similar nature, the waste from which is practically clear water, may discharge untrapped into an open fixture floor drain or gutter as provided for refrigerator drains. The waste pipes from such fixtures need not be trapped unless connected to the plumbing system or to a conduit or tank containing sewage. When trapped, such waste pipes shall be properly vented.
Waste pipes in dye houses, bottling works, creameries, laundries and similar establishments, where the wastes are highly diluted, may discharge directly onto a nonabsorbent floor provided with an adequate number of floor drains, which drains must be connected to a catch basin. The waste pipes discharging directly upon the floor need not be trapped. Gutters that can be easily cleaned and kept in efficient operating condition may be provided for collecting and conducting waste to floor drains, equipped, where necessary, with a suitable screen for arresting the coarser materials that would otherwise enter the system.
A. 
Construction. Swimming pools shall be of watertight construction. Inside surfaces shall be of smooth, nonabsorbent material with rounded corners, and nonskid floors and shall be constructed so as to be easily cleaned. Pools shall be provided with a valve so that the pool can be drained in 12 hours.
B. 
Drainage. Swimming pools and wading pools which have overflow connections located at an elevation below street level shall have their drainage outlets connected to a sanitary system by means of an indirect waste pipe. Such drainage outlets shall include pool drains, scum-gutter drains, backwash outlets from the pool and water filters and floor drains which serve walks around pools. When such drainage piping is below the grade of building sewers, any existing circulation pump for pool water may be used for pumping the waste to an elevation suitable for gravity discharge into a fixture approved for such use.
C. 
Connections between public or private water supply and minimum-flow line. There shall be no physical connection between a public or private water supply system and the minimum-flow line of a pool, unless such connection is installed to prevent siphonage in the water supply system.
D. 
Cleanliness. The bottom and sidewalls of artificial pools shall be kept reasonably free from sediment, dirt and leaves.
E. 
Protection. All pools are to be fenced or adequate safety protection provided.