Unless otherwise specifically stated, the provisions of this article shall apply to all structures hereafter erected, except as may be otherwise provided by state law; Article XVI I, Multiple Dwellings; § 86-16B(3), Required means of egress for converted institutional buildings; and Article XIII, Special Occupancies.
A. 
Kinds of required exits. Every structure hereafter erected shall have such means of egress consisting of interior or exterior stairways, fire towers, horizontal exits, ramps or passageways, including the necessary hallways and doorways as may be hereinafter required.
B. 
Required exits from rooms. Every room having an occupancy of more than 75 persons shall have at least two doorways, remote from each other, leading to an exit or exits.
C. 
Required exits from the ground floor. Every floor area having direct exit to a street and occupied by more than 40 persons shall have at least two means of exit.
D. 
Required exits from floor areas. Every floor area above or below the ground floor shall have at least one interior stairway or fire tower connected thereto. Every such floor area shall have at least one additional exit when it exceeds 2,500 square feet in area.
E. 
Required exits from places of public assembly.
(1) 
The means of egress from dance halls, cabarets, ballrooms, banquet halls, restaurants, exhibition halls and other places of public assembly shall comply with the following requirements:
(a) 
Two separate exits or stairways at least 44 inches in width shall be required for occupancies of 500 persons or less.
(b) 
When the occupancy exceeds 700 persons, there shall be at least four such exits or stairways.
(2) 
Where there are two exits or stairways, they shall be on opposite sides of the space. Where there are three exits or stairways, the third shall be remote from the other two. But every point within the space shall be within 100 feet of an exit or stairway. All but one such exit or stairway shall be separately enclosed and lead into a place readily accessible to the street.
F. 
Number of occupants.
(1) 
The dimensions and capacity of exits shall be proportioned to the number of persons to be accommodated. When the number of persons to be accommodated by the exits is not stated in the application for a permit or is not otherwise fixed, it shall be assumed for every floor area to be:
(a) 
One person for every six square feet in dance halls, lodge rooms and places of assembly.
(b) 
One person for every 10 square feet in restaurants.
(c) 
One person for every 15 square feet in courtrooms, classrooms in schools and colleges and rooms in public buildings not otherwise provided for.
(d) 
One person for every 25 square feet in stores, markets, lodging houses and reading rooms.
(e) 
One person for every 50 square feet in offices and showrooms.
(f) 
One person for every 100 square feet in hospitals, asylums, hotels, furnished room houses and other residence buildings.
(g) 
One person for every 150 square feet in warehouses and garages.
(h) 
As required by the Labor Law in factories and workrooms.
(2) 
For occupancies not herein specified, the Superintendent of Buildings shall, by rule, establish the ratio to be assumed.
(3) 
It shall be unlawful to occupy a floor area by a greater number of persons than that for which exits have been provided in accordance with this article.
G. 
Location of exits. Exits shall be so located that no point in any floor area served by them shall be more than 100 feet distant along the line of travel from the exit, except that when any floor area is subdivided into small areas, such as rooms in hotels and office buildings, the distance from the door to any such room along an unobstructed hallway to an exit shall be not more than 125 feet. Where more than one exit is required to any floor area, the exits shall be placed remote from each other. Where more than two exits are required, they shall be located in such a manner as to contribute to the rapid exit of the occupants.
H. 
Stairway exits. Every required stairway exit shall lead, either directly or through a passageway or hallway, to a street. In structures more than two stories high above curb level with flat roofs, all stairways shall lead to the roof. In structures more than three stories high above the curb level when there are two or more required stairways, at least two shall continue to the roof, provided that in the case of roofs having a pitch exceeding a one-foot rise in four feet, such stairways shall lead to a communicating hallway in the top story.
I. 
Boiler room ladders. Every structure, except private dwellings, in which steam boilers or apparatus using or producing steam, gas or vapor are placed below the curb level shall have stationary iron ladders or stairs from such story leading directly to a manhole through the sidewalk or other outside exit, unless the exit is provided by an enclosed stairway or a horizontal exit. When the room containing the boiler and mechanical equipment is more than 300 square feet in area or when the boiler is a high-pressure boiler, two means of exit shall be provided. Required exit doors from high-pressure boiler rooms shall open outwardly.
J. 
Designation of required means of egress.
(1) 
The location of each required means of egress on every floor of every structure shall be clearly and legibly indicated by exit signs, and, where required to serve their purpose adequately, such signs shall be placed at an angle with the exit doorway. Exit signs shall be of a type and size approved by the Superintendent of Buildings.
(2) 
In long corridors, in open floor areas and in all other situations where the location of the means of egress may not be readily discernible or understood by the occupants, directional signs shall be provided and maintained to serve as guides from all portions of the floor or corridor.
K. 
Lighting of required means of egress. All stairways, fire towers, hallways, passageways and other required means of egress, together with all areas to which the public has access, shall be equipped with adequate artificial lighting facilities. Such lighting facilities shall be used when adequate natural light is unavailable.
L. 
Effect of change in occupancy or use upon exits. Structures changed from one class of use or occupancy to another shall comply with the requirements for means of egress which apply to the use or occupancy, but the Superintendent of Buildings may, in his discretion, approve such other means of egress as, in his judgment, will accomplish the same purpose when strict compliance with the provisions of this article is impractical.
M. 
Inadequate exits for existing structures. Every existing structure which is unprovided with exit facilities, as prescribed in this section, and in which exit facilities are, in the opinion of the Superintendent of Buildings, inadequate for the safety of the occupants shall be provided with such means of egress consisting of fire escapes or such other means of egress or fire protection as he shall direct. If the owner or agent of any structure affected by an order issued under this section shall, after service has been made upon him and within seven days, Sunday and holidays excluded, file a written appeal with the Superintendent of Buildings, the Superintendent shall request the Village Board to appoint a board of survey upon whose findings a new order shall be based and issued.
N. 
Alterations affecting exits. The alteration of any structure hereafter erected in such a manner as to reduce the means of egress to less than is required under the provisions of this section is forbidden. Additional means of egress installed in any structure shall conform to the requirements of this section unless such means of egress are installed in conformity with the requirements of Subsection M, Inadequate exits for existing structures.
A. 
Width of exit doorways. The aggregate clear width of doorways serving as an exit from any room or floor area to a hallway, stairs or other means of exit shall be not less than 36 inches for the first 50 persons to be accommodated thereby and six inches additional for each additional 50 persons or fraction thereof. The aggregate clear width of doorways serving as an exit from any stairway, hallway or passageway shall be not less than the required width for such stairway, hallway or passageway. No single exit doorway shall have a clear width of less than 30 inches, provided that when the total number of persons to be accommodated exceeds 50, the clear width shall be not less than 36 inches.
B. 
Hanging of exit doorways.
(1) 
Doors to stairs and fire tower enclosures and from rooms and areas occupied by more than 50 persons shall open in the direction of egress for the full width of the door.
(2) 
Doors serving as required means of egress shall open outwardly and be so hung and arranged that when opening or opened, they shall not reduce the width of the hallways or passageways or the required width of stairs or stair landings or other means of egress. The maximum projection beyond the building line for doors opening directly on the street shall be 18 inches.
(3) 
in no case shall the swing of a door opening on a stairway overlap the top step.
C. 
Exit door fastenings. The fastenings on doors serving as required means of egress shall be such that the doors may be readily opened from the inside without the use of keys, except that the use of draw bolts in places of assembly is forbidden. This requirement shall not apply to the doors of rooms where persons are under legal restraint.
D. 
Operating devices.
(1) 
Self-closing and automatic doors and windows on required means of egress shall be equipped with such devices as may be required under the conditions of operating to close and maintain in a closed condition the doors and windows to which they are attached.
(2) 
Self-closing and automatic doors and windows and their operating devices shall at all times be maintained in working order, and no such door or window shall be so obstructed, held or blocked open as to interfere with or prevent its operating as a self-closing or automatic fire or smoke cutoff.
E. 
Revolving doors.
(1) 
Revolving doors, to be acceptable as exit doors, shall have a width equal to that required for an acceptable swinging door, the width, in the case of such a door with rigid braces, being the width of a single wing, and the width, in the case of such a door in which the wings may be readily released from one another by pressure so they may swing independently, being the aggregate clear width of the two openings on each side of the central shaft.
(2) 
Revolving doors shall not be used as exit doors in public buildings or institutional buildings nor shall they be used as exit doors in buildings occupied as stores where more than 75 persons are likely to be congregated, unless there are also exit doors of the swinging type having an aggregate width of at least 50% of the required width of exit doors and there is at least one swinging door adjacent to each revolving door.
When serving as an exit from or in connection with one or more stairways, the clear width of any hallway or passageway shall be not less than the aggregate required clear width of all stairs leading to it. The clear width of every hallway or passageway leading to an exit shall be not less than 44 inches for the first 50 persons to be accommodated thereby and six inches additional for each additional 50 persons or fraction thereof. When the number of persons to be accommodated thereby is less than 50, the clear width of such hallway or passageway may be reduced two inches for each 10 persons less than 50.
No horizontal exit shall be deemed satisfactory under this article unless the floor area on either side of such horizontal exit is sufficient to hold the joint occupancy of both floor areas, allowing not less than 3 1/2 square feet of clear floor space per person, and at least one interior stairway or fire tower conforming to the requirements of this article is provided on each side of such horizontal exit. When vestibules or open-air balconies are used, they shall conform to the requirements for vestibules or open-air balconies or fire towers. When bridges are used, they shall be constructed of incombustible material. All doorways or windows opening on such vestibules, balconies or bridges shall be equipped with self-closing fire doors or automatic fire windows. Where there is a difference in level between the connected floor areas, gradients shall be provided of not more than one foot in 10 feet.
A. 
Width of interior stairs. No stairs or stairway required by this article as an exit shall have an unobstructed width of less than 44 inches throughout its length, except that handrails may project not more than 3 1/2 inches into such width. The aggregate width of stairs in any story of the structure shall be such that the stairs or stairway may accommodate at one time the total number of persons ordinarily occupying or permitted to occupy the largest floor area served by such stairs or stairways on the basis of one person for each full 22 inches of stair width and 1 1/2 treads on the stairs and one person for each 3 1/2 square feet of floor area on the landings and halls within the stairway, provided that the number of persons to be accommodated within the stairway may be assumed at 1/2 of such total number when a horizontal exit is provided, in accordance with this article, and at 1/4 of such total number when the building is equipped with a sprinkler system and a horizontal exit is provided.
B. 
Dimensions of treads and risers. The treads and risers of stairs shall be so proportioned that the product of the tread, exclusive of nosing, and the riser, in inches, shall be not less than 70 nor more than 75, but risers shall not exceed 7% inches in height and treads, exclusive of nosing, shall not be less than 9 1/2 inches wide. Treads and risers shall be of uniform width and height in any one flight. The use of winders is prohibited, except for stairs of an ornamental character having a width of not less than five feet. The treads of winders, exclusive of the nosings, shall have a width of not less than seven inches at any point nor more than 10 inches average width.
C. 
Stair landings. No flight of stairs shall have a vertical rise of more than 12 feet between floors and landings, provided that in stairs serving as an exit from places of assembly, such vertical rise shall not exceed eight feet. The distance between risers on landings in straight runs of stairs shall be not less than 44 inches.
D. 
Handrails.
(1) 
Required exit stairs shall have walls or well-secured balustrades or guards on both sides with handrails on both sides. Required handrails on the rake of stairs shall be between 30 and 34 inches high from the tread to the top of the rail measured in line with the riser. Balustrades on the level shall be at least 34 inches from the floor or landing level to the top of the rail.
(2) 
A minimum unobstructed finger clearance of one inch shall be maintained at all points. When the width of a flight of stairs serving as a means of egress is 88 inches or more, an intermediate handrail shall be provided. This handrail shall be continuous between landings, shall be substantially supported and shall terminate at the upper end in a newel or standard at least six feet high. The ends of handrails shall be turned back against walls or newels and finished without projections which would act as obstructions.
E. 
Space under stairs. The space under any stairs, except in one- or two-family dwellings, built in whole or in part of combustible materials shall be left entirely open and kept clear and free from encumbrance.
F. 
Materials for required stairs. Stairs and stairways serving an exit shall be constructed of incombustible material or assemblies throughout, except in frame and non-fireproof structures 40 feet or less in height and occupied by at most 50 persons above the first story. The treads and landings shall be constructed and maintained in such manner as to prevent persons from slipping thereon.
G. 
Strength of required stairs. Stairs, platforms, landings and stair halls shall be of sufficient strength to safely sustain a live load of at least 100 pounds per square foot.
H. 
Support for treads and landings. When treads, landings or platforms in required stairways are of slate, marble, stone or composition, they shall be supported for their entire length and width by a solid steel plate of suitable thickness and securely fastened.
A. 
Fire-resistive ratings for enclosures.
(1) 
Required stairways in all Class 1 Fireproof Structures shall be enclosed with partitions or walls having a fire-resistive rating of at least three hours.
(2) 
All Class 2 Fire-Protected Structures, all Class 3 Nonfireproof Structures and all Class 6 Heavy Timber Structures, except residence buildings of three stories and a basement or less in height and in other structures not over four stories or 40 feet in height, shall be enclosed with walls or partitions having a fire-resistive rating of at least two hours, except as otherwise prescribed in this section.
(3) 
Interior required stairways, which are not required to be enclosed in walls having a minimum fire-resistive dating of at least two hours, shall be enclosed with fire-resistive partitions having a rating of at least one hour.
(4) 
All doors opening on required stairways shall have fire-resistive rating of at least 3/4 hour and shall be self-closing and normally closed. The fastening open of any such door is prohibited.
B. 
Openings and stair enclosures.
(1) 
The opening of pipe, elevator or other shafts, chases, panel boards, toilet rooms, slop sinks, closets or openings, other than exit doorways with fireproof self-closing doors, into the enclosures of required stairways or crossovers in connection with them is forbidden, except that where approved, automatic fire windows may be installed in the exterior walls of such enclosures and, except elevator shafts, on the ground floor.
(2) 
In structures not more than five stories or 65 feet in height, window openings or door openings in required stairways may be provided with nonfireproof windows or doors, provided that such stairways are distant not less than 30 feet from the nearest lot line, unless otherwise prescribed elsewhere in this code.
C. 
Ornamental stairways. Unenclosed service or ornamental stairways may be constructed under the following conditions:
(1) 
Such stairways shall be so placed as not to obstruct or interfere with the function or use of the required means of egress nor to be a part of such means of egress.
(2) 
Not more than two adjoining stories in any structure may be connected by an open well, unenclosed stairway or escalator.
A. 
Where permitted as required means of egress under § 86-36M, exterior stairways shall be constructed of incombustible materials and conform in other respects, except as to enclosures, to the requirements for interior stairs.
B. 
Such exterior stairs shall be connected to each story which they serve by means of self-closing fire doors or by automatic fire windows with a clear exit opening not less than three feet in height and 30 inches in width, and the window and door openings on the course of, below or within 10 feet horizontally of such exterior stairways shall be equipped with self-closing fire doors or automatic fire windows. Such stairways shall be protected throughout to a height of five feet with netting made of wire at least 0.135 inches in diameter (No. 10 United States steel wire gauge) and having a maximum mesh of 1 1/4 inches or with other rigid guards.
A. 
Fire towers required. At least one required means of egress in every public and business building 75 feet or more in height shall be a fire tower.
B. 
Construction and arrangement.
(1) 
interior stairways constructed and arranged as follows shall be known as "fire towers."
(2) 
The enclosing walls shall be of incombustible materials or assemblies having a fire-resistive rating of at least four hours and be without openings, except for doors serving as means of egress.
(3) 
Access to the stairway shall be provided at each story served by a fire tower through outside balconies or fireproof vestibules at least three feet eight inches in width and having unpierced floors of incombustible materials and provided with substantial guardrailings at least four feet high with no openings greater than eight inches in width.
(4) 
The balconies or vestibules shall be level with the floors of the structure and platforms of the stairs connected by them and shall be separated from the structure and the stairs by self-closing fire doors capable of being opened from both sides without the use of a key.
(5) 
Balconies or vestibules shall open on a street or yard or on a court open vertically to the sky for its full height having a minimum net area of 105 square feet and a minimum dimension of seven feet. The opening from the vestibule to the street, yard or court shall have a minimum area of 18 square feet and a minimum dimension of two feet six inches. Openings in the court walls surrounding an interior fire tower, other than the openings from the vestibules, are forbidden within 15 feet of the balcony, except that self-closing fire windows may be used if at least 10 feet from the balcony, provided that the area of the court is at least 12 feet by 24 feet.
(6) 
Fire towers shall terminate at the grade level and shall exit directly to the street independently of corridors serving other stairways, except when terminating in the ground floor corridor outside of the inner vestibule and within 10 feet of the building line.
(7) 
Doors opening into fire towers may be constructed with observation panels made of polished plate or wire glass one-fourth-inch thick, set with a 3/4 inch rabbet and having a maximum area of 16 square inches. Doors shall be operable from both sides without the use of a key.
(8) 
Fire tower stairs shall comply in all other respects with the requirements of § 86-40, Required stairways.
When fire escapes are used as a means of egress under the provisions of § 86-36M, they shall be constructed of incombustible materials of sufficient strength to safely sustain a superimposed load of 100 pounds per square foot. Fire escapes used as a means of egress shall have balconies at each story at least 36 inches wide in the clear and at least 54 inches long and shall be provided with staircases extending to the ground level with a maximum riser of eight inches and minimum width of treads of eight inches, exclusive of nosings. Fire escape staircases shall be at least 22 inches in width. If fire escapes are located on a street front of a structure, the Superintendent of Buildings may permit the use of a drop ladder or a counterbalanced stair from the lowest balcony, provided that the height of such balcony above the sidewalk immediately below does not exceed 16 feet.
The placing of any obstruction in front of, in or on any required means of egress is forbidden.
A. 
Special egress provision for public safety. Where unusual conditions occur in structures of a public character such as hotels, restaurants, railroad depots, public halls, clubhouses with more than eight sleeping rooms, churches, ball parks, stadiums and other structures of a like nature, used or intended to be used for public assembly, amusement or instruction, and business structures, including department stores, where large numbers of people congregate and where such conditions are not covered by the provisions of either Article VII, Means of Egress, or Article XIII, Special Occupancies, the Superintendent of Buildings shall have power to require the provision of such halls, doors, stairways, seats, passageways, lighting and heating as he shall deem necessary to facilitate egress in case of accident or fire and to furnish adequate protection for the public in such cases.
B. 
Obstruction of aisles and passageways. Aisles, halls, foyers, promenades, vestibules and passageways and other parts of such structures of a public character used as means of egress shall be kept free from camp stools, chairs, sofas and miscellaneous furniture or other obstructions, and no person shall be allowed to stand in or occupy any portion of such spaces during any performance, service, exhibition, lecture, concert, banquet, dance or other public assembly, except when the number of such standees has been included in the number of persons for whom means of egress has been provided from such tiers and when the space occupied by such standees is enclosed with tape or cord or erected and of such material that it can be easily broken by persons passing in a direct line of egress.
C. 
Enforcement of special egress requirements. The Superintendent of Buildings may, at any time, serve a written or printed notice upon the owner, lessee or manager of any such structure of a public character directing any act or thing to be done or provided in or about such structures and their appliances and facilities, such as halls, doors, stairs, passageways, windows, seats, aisles, fire walls, fire apparatus and fire escapes, as he may deem necessary to carry out the purposes of Subsection B above when unusual conditions exist.