Exciting enhancements are coming soon to eCode360! Learn more 🡪
Village of Freeport, NY
Nassau County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
All building materials shall be of quality to meet the intent of the Building Code and shall conform to such specifications consistent with its requirements as may be promulgated by the Superintendent of Buildings or, in the absence of such specifications, to well recognized standards for the materials in question.
A. 
Quality of masonry materials.
(1) 
Brick. All brick shall be sound, hard, well-burnt brick. Secondhand brick may be used subject to the approval of the Superintendent of Buildings as to condition and quality, but in all cases they shall be thoroughly cleaned before being used and shall be whole and good, hard, well-burnt brick.
(2) 
Concrete hollow tile blocks. Hollow building blocks of concrete shall be made of portland cement and suitable aggregates in such proportion as to develop an ultimate crushing strength of 700 pounds per square inch of gross area and tested as laid in the wall. For partitions, fireproofing and furring, when unexposed to the weather, solid or hollow concrete budding block or tile having a minimum ultimate compressive strength of 300 pounds per square inch of gross area, tested as laid in the wail, may be used, provided that such units shall be marked on the face with two readily discernible parallel grooves to indicate that they are units for partition, fireproofing or furring purposes.
(3) 
Terra cotta hollow tile blocks. Structural clay tile for bearing walls or for walls wholly or partly exposed to the weather shall at least comply with the standard specifications of the American Society for Testing Materials, D, C34-34T for medium tile. The minimum thickness of a single shell or the minimum aggregate thickness of a double shell shall be one inch. With double shell tiles, the maximum width of void between shells shall be 5/8 inch. For partitions, fireproofing or furring, when unexposed to the weather, structural clay tile shall comply with the standard specifications of the American Society for Testing Materials, D, C56-34T and shall have exterior shells of not less than 5/8 inch overall thickness and webs of not less than 1/2 inch overall thickness.
(4) 
Gypsum block or tile. Gypsum block or tile shall comply with the standard specifications of the American Society for Testing Materials, D, C42-33 and may contain a maximum of 12 1/2% by weight of combustible matter measured dry.
B. 
Mortar and other concrete materials.
(1) 
Sand. Sand shall be clean, sharp, coarse and siliceous and free from salt, lime, clay or other foreign materials.
(2) 
Lime. Quick lime and hydrated lime shall conform to the standard specifications of the American Society for Testing Materials.
(3) 
Cement. Portland cements shall conform with the standard specifications of the American Society for Testing Materials. Nothing herein contained shall be construed to prohibit the use of cements of other types which may be approved by the Superintendent of Buildings.
C. 
Mortar proportions.
(1) 
Cement mortar. Cement mortar shall be composed of one part of cement and not more than three parts of sand, to which may be added at most 15% of the cement content in hydrated lime or lime putty.
(2) 
Cement-lime mortar. Cement-lime mortar shall be composed of one part of cement, one part of lime putty or hydrated lime and a maximum of six parts of sand.
(3) 
Lime mortar, Lime mortar shall be composed of one part of lime putty or hydrated lime and a maximum of three parts of sand. Cement may be added to lime mortar replacing equal volumes of lime, provided that adequate methods of mixing are used so that the cement gauging will be uniformly distributed.
D. 
Quality of materials for reinforced concrete.
(1) 
Aggregates. Concrete aggregate shall consist of natural sands and gravels, crushed rock or other hard durable material that may be approved by the Superintendent of Buildings. Aggregates shall be free from strong alkali or organic material.
(2) 
Plain concrete proportion. Plain concrete shall be mixed in the proportions of at least one part of cement to a total of seven parts of separate volumes of fine and coarse aggregate, measured dry, and maximum of 8 1/2 United States gallons of water, including that contained in the aggregate, per sack of cement. Such concrete shall develop a strength of at least 1,500 pounds per square inch at the age of 28 days.
(3) 
Reinforced concrete proportions. Concrete shall be mixed in the proportions of at least one part of cement to a total of 5 1/2 parts of separate volumes of fine and coarse aggregate measured dry, and a maximum of 7 1/2 United States gallons of water, including that contained in the aggregate, per sack of cement. Such concrete shall develop a strength of at least 1,750 pounds per square inch at the age of 28 days.
(4) 
Metal reinforcing. Metal reinforcement shall conform to the standard specifications of the American Society for Testing Materials for billet steel concrete reinforcement bars of intermediate or structure steel, grade D, A15-33, or for rail-steel concrete reinforcement bars, D, A16-33.
(5) 
Structural steel used in reinforced concrete. Structural steel used in reinforced concrete shall conform to the requirements of the standard specifications of the Americans Society for Testing Materials for structural steel for buildings, D, A9-34.
(6) 
Wire used in reinforced concrete. Wire for concrete reinforcement shall conform to the requirements of the standard specifications of the American Society for Testing Materials for cold-drawn steel wire for concrete reinforcement, D, A82-34.
(7) 
Identification of metal reinforcement. All reinforcing bars shall be rolled with raised symbols or letters to identify both the manufacturing mill and the grade of steel. All bundles or rolls of cold-drawn steel wire reinforcement and on-fourth-inch rounds shall be securely tagged so as to identify the manufacturer and the grade of steel.
E. 
Iron and steel.
(1) 
Cast iron. Cast iron shall be of good foundry mixture producing a clean, rough, gray iron. It shall conform to the standard specifications of the American Society for Testing Materials, D, A48-32T, for medium gray iron castings. Casting shall be free from serious blowholes, cinder spots and cold shuts.
(2) 
Cast steel. Steel castings for building construction shall be made of open hearth steel and shall be practically free from blowholes. They shall conform to the standard specifications of the American Society for Testing Materials, D, A27-24, for medium or soft steel castings.
(3) 
Structural steel. All medium structural steel for building construction shall conform to the standard specifications of the American Society for Testing Materials, D, A9-34, as to chemical and physical properties, inspection, marking and tests. Structural rivet steel shall comply with the standard specifications of the American Society for Testing Materials, D, A141-33.
(4) 
Use of special steels. Alloy and high carbon steels may be used in accordance with the rules of the Superintendent of Buildings as approved by the Board of Trustees.
(5) 
Working stresses for special steel. The maximum allowable working stresses in tension for special steels shall be 30% of the minimum ultimate strength, and other stresses may be proportioned to the corresponding allowable stresses for the structural steel specified in § 86-53D, Structural steel.
(6) 
Inspection of special steels. All special steel shall be inspected and accepted by an inspection bureau of known reputation, acceptable to the Superintendent and, when required, in the presence of a representative of the Superintendent. An affidavit shall be filed with the Superintendent by the inspecting bureau to the effect that the steel, as accepted, is the class of steel required and that it conforms in all respects to these requirements. Such inspection shall be at the expense of the owner.
F. 
Quality and size of lumber and timber.
(1) 
The grades and quality of lumber and timbers used structurally shall conform to the basic provisions of American lumber standards as contained in Simplified Practice Recommendations, R 16-29 Lumber, Fourth Edition, Bureau of Standards, United States Department of Commerce Publications, effective July 1, 1929, except that studding posts compression members and similar load-bearing members shall be at least equal to the commercial grade of No. 2 common dimension.
(2) 
Beams, girders, joists, rafters, truss members in tension and flexure, planks and similar load-bearing members less than five inches in normal thickness shall be of a grade at least equal to No. 1 common dimension.
(3) 
Lumber, five inches thick, and timber shall be at least equal to the lowest commercial grade for which working stresses are indicated under tables showing allowable working stresses for wood beams, girders and similar structural purposes.
(4) 
The net size of all lumber and timbers used structurally shall be sufficient to safely sustain their combined live and dead loads within the allowable working stresses fixed by this code. See especially § 86-53F, Lumber and timbers.
(5) 
Lumber for load-carrying purposes shall not be used that is smaller in width and thickness than 1/4 inch scant of the nominal or commercial description of size, except that American lumber standard dressed sizes, when seasoned, shall be accepted.
(6) 
Computations to determine the required sizes in design shall be based upon the net cross-sectional area or actual sizes, and these sizes shall be shown on the plans.
(7) 
Wood floor and roof beams, joists, rafters and framing lumber shall be at least two inches in nominal thickness, except that no floor or roof beams of structures within the fire limits may be less than three inches in nominal thickness, and the depths of beams, joists and girders shall in no case exceed six times such thickness.
(8) 
All sheathing of exterior walls on frame buildings, all subfloors wherever used and all roof boarding shall be not less than 3/4 inch net thickness and shall be No. 2 common grade or better and dressed two sides.
A. 
When required. New structural material or structural material not otherwise provided for in this article shall be subjected to such tests to determine its character and quality as the Superintendent of Buildings shall direct. Appliances and devices required by any of the provisions of this chapter and new methods of construction shall be subjected to such tests to determine their efficiency as the Superintendent of Buildings may direct. Such tests as may be required under this section shall be described in rules promulgated by the Superintendent of Buildings.
B. 
Conduct of tests. All tests shall be conducted under the supervision of the Superintendent of Buildings or his authorized representative. Laboratory tests shall be conducted at a testing laboratory of recognized standing. Duly authenticated tests by a competent person or laboratory may be accepted by the Superintendent of Buildings in lieu of tests under his supervision. So far as is practicable, test procedure shall be prescribed in rules duly promulgated by the Superintendent of Buildings.
C. 
Approval. Any material, appliance or method of construction meeting the requirements of this article or the specifications authorized thereunder shall be approved within a reasonable time after the completion of the tests. All such approvals and the conditions under which they are issued shall be reported and kept on file in the office of the Superintendent of Buildings and open to public inspection.
D. 
Conditions attached to approvals. Materials, appliances or methods of construction which have been tested and approved shall be used and installed in accordance with the terms of the approval. So far as is practicable, all materials and appliances for which approvals have been issued shall have a distinctive brand mark for identification impressed on or otherwise attached to them. It shall be unlawful to use any such brand mark or any other material or appliance than that for which the approval was issued.
E. 
Additional tests. The Superintendent of Buildings may require tests to be repeated if there is any reason to believe that a material or appliance no longer conforms to the specifications on which its approval was based.
F. 
Tests on completed work. If there is reason to question the safety of a structure or part thereof while in the course of construction or before a certificate of occupancy has been issued, the Superintendent may require the owner or builder to make load tests or other suitable tests to determine the acceptability of the construction. Such tests shall be made under the supervision of the Superintendent of Buildings and shall show that the construction in question will safely sustain a load equal to twice the live load prescribed in this article.
G. 
Rejection. Any material, appliance or method of construction failing to conform to the requirements of this code or rules adopted thereunder shall not be used.
For the purpose of estimating dead loads, in the absence of more definite information, the weights of building materials, in pounds per cubic foot, shall be assumed to be as follows:
Building Materials
Weight
(pounds per cubic foot)
Brickwork
120
Concrete, stone
144
Concrete, cinder, used for floor arches or slabs
108
Concrete, cinder, used for filling
60
Hollow concrete block masonry
108
Cinder block masonry
84
Gypsum block
48
Hollow tile wall-bearing
60
Hollow tile, partition
54
Plaster, mortar
96
Granite, bluestone and marble
170
Limestone
56
Sandstone
144
Oak
50
Long leaf yellow pine
44
Douglas fir and short leaf yellow pine
36
Spruce, hemlock and white pine
30
A. 
General load requirements. Structures and all parts thereof shall be of sufficient strength to safely support their imposed live loads in addition to their own dead load, provided that all structures shall be designed for at least the minimum live loads specified in this code, and that the Superintendent of Buildings shall have the authority to fix live loads for structures not covered by the provisions of this code.
(1) 
Allowance for partition loads. A uniformly distributed load of 20 pounds per square foot shall be added to the dead loads of floors in office and public buildings where partitions are not definitely located in the design, and in other buildings subject to shifting of partitions, without reference to arrangement of floor beams or girders. The weight of definitely located partitions shall be included in the calculation of dead loads.
(2) 
Temporary supports. Every temporary support placed or under any structure or part thereof during the erection, finishing, alteration or repairing of such structure or part thereof shall be of sufficient strength to safely carry the load to be supported thereby.
B. 
Live loads.
(1) 
Live loads to be posted. The live loads for which any and every floor may be designed shall be clearly shown in the application and on the plans before any permit to erect is issued. See also § 86-52, Posting floor capacities.
(2) 
Residences and sleeping quarters. For private dwellings, multiple dwellings, bedroom floors in hotels and clubhouses, private and ward room floors in hospitals, dormitories and similar occupancies, including corridors, the minimum live load shall be taken as 40 pounds per square foot uniformly distributed.
(3) 
Office space. For office floors, including corridors, the minimum live load shall be taken as 50 pounds per square foot uniformly distributed. Provisions shall be made in designing office floors for a load of 2,000 pounds placed upon a space of 2 1/2 square feet whenever this load, upon an otherwise unloaded floor, would produce stresses greater than the 50 pound distributed load.
(4) 
Places of assembly other than theaters and hails. For classrooms with fixed seats, including aisles and passageways between seats, churches with fixed seats and reading rooms, the minimum live load shall be taken as 60 pounds per square foot uniformly distributed.
(5) 
Theaters and assembly hails. For the seating space in theaters and assembly hails with fixed seats, including the passageway between seats, except as provided in Subsection B(6) below, the minimum live load shall be taken as 75 pounds per square foot uniformly distributed.
(6) 
Public spaces. For aisles, corridors not otherwise provided for above, hails, lobbies, public space in hotels and public structures assembly halls without fixed seats, theater stages, cabarets, barrooms, art galleries and museums, stores, restaurants, skating rinks, grandstands, gymnasiums, dance halls, dining rooms, lodge rooms, laboratories in school and college buildings, stairways, fire escapes and exit passageways and other spaces where groups of people are likely to assemble, the minimum live load shall be taken as 100 pounds per square foot uniformly distributed. This requirement shall not apply to such spaces in private dwellings for which the minimum live load shall be taken as in Subsection B(5) above.
(7) 
Industrial or commercial occupancies. In designing floors for industrial or commercial purposes other than previously mentioned, the live load shall be assumed as the maximum caused by the use which the structure or part of the structure is to serve. The following loads, in pounds per square foot uniformly distributed, shall be taken as the minimum live loads permissible for the occupancies listed, and loads at least equal shall be assumed for uses similar in nature to those listed in this section. Floors to be used for:
(a) 
The display and sale of light merchandise and where incidental factory work does not utilize more than 25% of the floor area: 75 pounds per square foot.
(b) 
Factory work, wholesale stores, storage and stock rooms in libraries: 120 pounds per square foot.
(c) 
Stables: 75 pounds per square foot.
(d) 
Garages for passenger cars only: 75 pounds per square foot. When there is floor area sufficient for the accommodation of two or more cars, the design of floors for such garages shall make provision for a concentrated load of 2,000 pounds at any one point.
(e) 
Garages for all types of vehicles.
[1] 
Garages for all types of vehicles, other than private passenger cars exclusively, shall use:
[a] 
For floor construction: 175 pounds per square foot.
[b] 
For beams, columns and girders: 175 pounds per square foot.
[2] 
The design of floors for such garages shall also make provision for the heaviest concentrated loads to which the floors may be subjected, but in all cases these loads shall be assumed as at least 6,000 pounds concentrated at any point.
(f) 
Trucking spaces and driveways within the limits of a structure: 175 pounds per square foot. The design of floors for such trucking spaces shall also make provision for the heaviest concentrated loads to which they may be subjected, but in all cases these loads shall be assumed as at least 24,000 pounds concentrated at any point on a beam or girder.
(8) 
Moving loads. For structures carrying live loads which cause shock and vibration, a proper percentage shall be added to the live-load stress to provide for dynamic effects.
(9) 
Roof loads.
(a) 
Roofs having a rise of four inches or less per foot of horizontal projection shall be designed to safely carry a vertical live load of not less than 40 pounds per square foot of horizontal projection to any or all slopes.
(b) 
Roofs having a rise of more than four inches and not more than 12 inches per foot of horizontal projection shall be designed to safely carry a vertical live load of not less than 30 pounds per square foot of horizontal projection.
(c) 
Roofs having a rise of more than 12 inches per foot of horizontal projection shall be designed to safely carry a wind force, acting normal to the roof surface, on one slope at a time, of 30 pounds per square foot of such surface.
(10) 
Sidewalk loads. For public sidewalk area between the curb and building lines, the live load shall be taken at 300 pounds per square foot.
(11) 
Yard and court loads. For yards and courts inside the building line, the live loads shall be taken at not less than 150 pounds per square foot.
(12) 
Reduction of live loads.
(a) 
In structures intended for storage purposes, all columns, piers or walls and foundations may be designed for 85% of the full assumed live load. In buildings intended for other uses, the assumed live load used in designing all columns, piers or walls and foundations may be as follows:
[1] 
One hundred percent of the live load on the roof.
[2] 
Eighty-five percent of the live load on the top floor.
[3] 
Eighty percent of the live load on the next floor below.
[4] 
Seventy-five percent of the live load on the next floor below, and on each successive lower floor, corresponding decreasing percentages, provided that in all cases at least 50% of the live load shall be assumed.
(b) 
Girders, except in roofs and as specified in Subsection B(12)(c) below, carrying a designed floor load, the equivalent of 200 square feet or more of floor area, may be designed for 85% of the specified live loads.
(c) 
In designing trusses and girders which support columns and for determining the area of footings, the full dead loads, plus the live loads shall be taken with reduction figured as permitted above.
(13) 
Safes restricted. No safe shall be placed on a stair landing or in a stair hall nor shall its weight be carried by any beam which also carries the floor of any landing or stair hall.
A. 
General requirements for wind pressure. All structures shall be designed to resist a horizontal wind pressure on all surfaces exposed to the wind, allowing for wind in any direction, of not less than 15 pounds per square foot for those portions less than 40 feet above the ground and of not less than 30 pounds per square foot for those portions more than 40 feet above ground, provided that the wind pressure on signs, tanks, towers and stacks shall be assumed as 30 pounds per square foot for any height.
B. 
Stability. The overturning moment due to wind pressure shall not exceed 80% of the moment of stability of the structure, unless the structure is securely anchored to the foundation.
C. 
Allowable stresses.
(1) 
For combined stresses due to wind and other loads, the working stresses prescribed in this article may be increased 33 1/3%, provided that the section thus found is not less than that required by the dead load and live loads alone.
(2) 
For members carrying wind stresses only, the permissible working stresses may be increased 33 1/3%.
A. 
New and altered buildings. The live load for which each floor or part of a floor of a business building or storage building hereafter erected or altered is designed and approved by the Superintendent of Buildings shall be conspicuously posted in that part of the story to which it applies.
B. 
Existing buildings.
(1) 
In every business building or storage building now existing in which heavy materials are kept or stored or machinery is introduced, the live load that each floor will safely sustain shall be estimated by the owner or occupant or by a competent person employed by the owner or occupant. Such estimate shall be filed with the Superintendent of Buildings and, if found satisfactory and approved by him, shall be posted as provided for new buildings.
(2) 
If the Superintendent of Buildings shall have cause to doubt the correctness of said estimate, he is empowered to revise and correct the same and, for the purpose of such revision, the officers and employees of the Department of Buildings may enter any building and remove so much of any floor or other portion of the structure as may be required to make necessary measurements and examination. Any expense necessarily incurred in removing any floor or other portion of a structure for the purpose of making the examination herein provided for shall be paid by the Treasurer upon the requisition of the Board of Trustees. Such expense shall be a charge against the person or persons by whom or on whose behalf said estimate was made, provided that such examination proves the floor or other portion of the structure of insufficient strength to safely sustain the estimated live load.
C. 
Loading restricted. No person shall place or cause or permit to be placed on any floor of a building or on any part of a structure a greater load than the approved safe load.
A. 
General requirements.
(1) 
Computations. Every structure hereafter erected and all new construction in the alteration of an existing structure shall be so designed and constructed that the working stresses fixed in this section are not exceeded. In using these stresses, the effects of all loads and conditions of loading and the influence of all forces affecting the design and strength of the several parts shall be taken into account.
(2) 
Permissible working stresses. Higher stresses than herein specified may be used, but only if it is clearly established by test or other satisfactory evidence that material of a higher grade or a superior workmanship than the accepted standard is to be employed. The use of higher stresses, however, shall not be allowed until a statement giving the reasons for such permission, together with the facts and circumstances on which it is based, is placed on file and made a part of the official record of the permit.
(3) 
Working stresses not specified. For materials permitted in the construction of structures which are not provided for in this section, the Superintendent of Buildings shall, by rule, establish working stresses.
B. 
Stone and masonry.
(1) 
Natural stone masonry.
(a) 
The maximum allowable compressive stresses for masonry of natural stone with dressed or cut beds, due to combined live and dead loads, expressed in pounds per square inch of gross cross-sectional area are given in the following table:
Kind
Mortar Cement
(pounds per square inch)
Cement-Lime Mortar
(pounds per square inch)
Lime Mortar
(pounds per square inch)
Granite
800
640
400
Gneiss
750
600
375
Limestone
500
400
250
Marble
500
400
250
Bluestone
400
300
175
Sandstone
300
250
150
(b) 
The maximum allowable compressive stress for other natural cut stone masonry and for all uncut stone masonry shall be 140 pounds per square inch of gross cross-sectional area in cement mortar and 110 pounds in cement-lime mortar.
(2) 
Masonry. The working stresses, in pounds per square inch, in masonry in compression shall be taken as follows:
When Laid in
Portland Cement Mortar
(pounds per square inch)
Cement-Lime Mortar (pounds per square inch)
Lime Mortar (pounds per square inch)
Brickwork
250
150
100
Hollow building blocks
Gross area:
Concrete cells vertical,
80
70
Concrete cells horizontal,
30
25
Terra cotta cells vertical,
120
100
Terra cotta cells horizontal
70
60
Plain concrete masonry (1 to 7 mix)
400 pounds per square inch
Grout, neat portland cement in thin layers under bases only
1,000 pounds per square inch
Grout, (1 1/2 mix)
600 pounds per square inch
C. 
Reinforced concrete.
(1) 
Concrete. The allowable working stresses, in pounds per square inch, and the ratio (n) for concrete mixed in the proportions as specified in § 86-47D(3), 1:5 1/1 mix, shall be taken as follows:
Flexure: FC
Designation
Description
Allowable Working Stresses
(pounds per square inch)
S1
Extreme fiber stress in bending
650
S2
Extreme fiber stress in compression adjacent to supports
750
Shear: V
S3
Beams without web reinforcement and without special anchorage of longitudinal steel
40
S4
Beams without web reinforcement but with special anchorage of longitudinal steel
60
S5
Beams with properly designed web reinforcement but without special anchorage of longitudinal steel
100
S6
Beams with properly designed web reinforcement and with special anchorage of longitudinal steel
150
S7
Flat slabs at distance (d) from edge of column capital or drop panel
60
S8
Footings where longitudinal bars are without special anchorage
40
S9
Footings where longitudinal bars have special anchorage
60
Bond: U
In beams, slabs and one-way footings:
S10
Plain bars
80
S11
Deformed bars
100
In two-way footings:
S12
Plain bars
60
S13
Deformed bars
75
Bearing: FC
S14
Direct
500
Axial compression: FC
S15
In columns
500
S16
In pedestals
500
S17
Ratio (n)
15
(2) 
Steel reinforcement. The maximum allowable working stresses, in pounds per square inch, for reinforcing steel shall be as follows:
Description
Allowable Working Stress
(pounds per square inch)
Rail steel bars in tension
fs 16,000
Structural steel grade billet steel in tension
fs 18,000
Cold-drawn steel wire in tension
fs 20,000
Web reinforcement
fv 16,000
Steel bars in compression
nfc
(3) 
Controlled concrete. When concrete is used of a mixture, the strength of which at the age of 28 days shall be 2,200 pounds per square inch or more, the product shall be known as controlled concrete." The allowable working stresses shall be based on the ultimate compressive strength of the concrete (fc), as determined by test, and for which the proportions of water to cement ratios shall be fixed by the Superintendent of Buildings. All field tests of concrete, tests of materials, load tests and other tests deemed necessary by the Superintendent of Buildings shall be made without expense to the Village. The maximum allowable working stresses, in pounds per square inch, shall be as follows:
Flexure: FC
Designation
Description
Allowable Working Stresses (f'c)
S1
Extreme fiber stress in compression
0.40
S2
Extreme fiber stress in compression adjacent to supports of continuous or fixed beams or slabs or of rigid frames
0.45
Shear: V
S3
Beams without web reinforcement and without special anchorage of longitudinal steel
0.02
S4
Beams without web reinforcement but with special anchorage of longitudinal steel
0.03
S5
Beams with properly designed web reinforcement but without special anchorage of longitudinal steel
0.06
S6
Beams with properly designed web reinforcement with special anchorage of longitudinal steel
0.09
S7
Flat slabs at distance (d) from edge of column capital or drop panel
0.03
S8
Footings where longitudinal bars are without special anchorage
0.02
S9
Footings where longitudinal bars have special anchorage
0.03
Bond: U
In beams, slabs and one-way footings:
S10
Plain bars
0.04
S11
Deformed bars
0.05
In two-way footings:
S12
Plain bars
0.03
S13
Deformed bars
0.0375
Where special anchorage is provided, § 86-61I, double these values in bond may be used.
Bearings: FC
S14
Direct bearing
0.30
Axial compression: FC
S15
In columns
0.25
S16
In pedestals
0.30
S17
Ratio (n)
30,000
D. 
Structural steel, All parts of structures shall be so proportioned that the sum of the maximum static stresses, in pounds per square inch, shall be within the following:
(1) 
Tension stresses. Rolled steel on net section: 18,000 pounds per square inch.
(2) 
Compression stresses.
(a) 
Rolled steel on short lengths or where lateral deflection is prevented: 18,000 pounds per square inch.
(b) 
On gross section of columns:
with a maximum of 15,000 pounds per square inch in which "L" is the unsupported length of the column and "r" is the corresponding least radius of gyration of the section, both in inches.
(c) 
For main compression members, the ratio L to r shall be within 120, and for bracing and other secondary members, the ratio shall be 200.
(3) 
Bending stresses.
(a) 
On extreme fibers of rolled shapes and built-up sections, net section if lateral deflection is prevented: 18,000 pounds per square inch.
(b) 
When the unsupported length, "L," exceeds 15 times "b," the width of the compression flange, the stress, in pounds per square inch, in the latter shall be within:
The laterally unsupported length of beams and girders shall be within forty times "b," the width of the compression flange.
(c) 
On extreme fibers of pins, when the forces are assumed as acting at the center of gravity on the pieces: 27,000 pounds per square inch.
(4) 
Shearing stresses.
On
Pounds Per Square Inch
Pins
13,500
Power-driven rivets
13,500
Hand-driven rivets
10,000
Unfinished bolts
10,000
Gross area of the webs of beams and girders
12,000
(5) 
Bearing stresses.
On
Double Shear
(pounds per square inch)
Single Shear
(pounds per square inch)
Pins
30,000
24,000
Power-driven rivets
30,000
24,000
Hand-driven rivets
20,000
16,000
Unfinished bolts
20,000
16,000
E. 
Cast iron.
(1) 
All structural members of cast iron shall be so proportioned that the sum of the maximum static stresses, in pounds per square inch, shall be within the following:
Stress
Pounds Per Square Inch
Tension
3,000
Shear
3,000
Bending:
Extreme fiber-compression side
16,000
Extreme fiber-tension side
3,000
(2) 
Compression on columns: 9,000 pounds per square inch minus 40 . In no case shall the ratio of L to r exceed 70 where "L" is the length in inches and "r" is the least radius of gyration.
F. 
Lumber and timbers.
(1) 
The net size of all lumber and timbers used structurally shall be sufficient to safely sustain their imposed loads within the allowable working stress fixed by this section.
(2) 
Stresses due to live and dead loads, acting singly or combined, shall be within those fixed in Tables I and II.
(3) 
Stresses due to wind load, singly or combined with live and dead loads, may be increased 30% of these allowable working stresses when the resulting section equals or exceeds that required for design of total live and dead load.
(4) 
All lumber and timber used as structural members of any structure shall bear the official grademark and trademark of the association under whose grade rules it was manufactured. Except for frame dwellings and accessory buildings, the Superintendent of Buildings may permit the use of lumber or timber not bearing an official grademark and trademark, provided that said lumber or timber is approved by the Superintendent as to quality and condition, and provided further that the allowable working stresses shall not exceed 66 2/3% of the allowable stresses shown in Tables I and II.[1]
[1]
Editor's Note: Tables I and II are included as attachments to this chapter.
A. 
Presumptive capacities.
(1) 
In the absence of satisfactory tests, the sustaining power per square foot, of different soils shall be deemed to be as follows:
Soil
Sustaining Power
(tons per square foot)
Quicksand
0.5
Softclay
1
Wet sand (confined)
2
Firm clay
2
Sand and clay, mixed or in layers
2
Fine dry sand
3
Coarse sand
4
Gravel
6
Softrock
8
Hardpan (overlaying rock)
10
Medium rock
25
Hard rock
40
(2) 
In case a structure rests partly on rock or hardpan and partly on some other soil, the bearing capacity of the latter shall be taken at not more than 1/2 of the capacity otherwise assumed.
B. 
Soil tests. When a doubt arises as to the safe sustaining power of the soil upon which a structure is to be erected or it is desired to exceed the presumptive capacity, the Superintendent of Buildings may direct that borings or tests be made by and at the expense of the owner of the proposed structure to determine the sustaining power of the soil. Whenever such a test is made, the Superintendent of Buildings shall be notified so that he may be present in person or by a representative. A complete record of the test shall be filed with the Superintendent of Buildings.
C. 
Filled ground. No foundation of a structure shall be placed on filled ground until proper tests to determine the safe sustaining power of such filled ground have been made to the satisfaction of the Superintendent of Buildings.
D. 
Indicative statement required. Applications for permits for new buildings and, when necessary, for alterations to existing buildings shall contain a statement of the character of the soil at the level of the footings.