[Amended by Res. 05-08-14; and by Res. No. 10-28-21]
1. 
All sanitary sewers shall be designed in accordance with the applicable edition of the Sewerage Manual for the Pennsylvania Department of Environmental Protection, Water Quality Management Program, and these Specifications.
2. 
Construction of sanitary sewers will not be permitted until the proper commonwealth permits have been obtained in the name of the Township or the Authority.
1. 
Building Sewer. Building sewers shall in no case be less than four inches in diameter. An adapter, approved by the Logan Township inspector, connecting the building sewer to the lateral must be used. In accordance with the recommendation of the Township, the Township, at its discretion, may require the building sewer of a building having more than one residential equivalent to be greater than four inches in diameter.
2. 
Lateral. The lateral sewer between the sewer main and the building sewer upon the property must be six inches in diameter, unless otherwise approved by the Township.
3. 
Sewers. All sewers, except building sewers and laterals, shall in no case be less than six inches in diameter. The Township, at its discretion, may require that sewers be greater than six inches in diameter.
Sewer pipe, fittings and wye connections used for sewers shall conform to one of the following:
A. 
Polyvinyl chloride (PVC) sewer pipe meeting the requirements of ASTM D-3034, SDR 35 with integral bell-and-spigot-type joints meeting the requirements of ASTM D-3212 and elastomeric gaskets meeting the requirements of ASTM F-477. All trap and vent assemblies on structures constructed prior to January 1, 2011, shall be constructed with (Schedule 40 DVW ASTM D-1785-type fittings, utilizing purple primed, ASTM 656 and solvent cement.
B. 
Type PS-46 PolyVinyl chloride (PVC) sewer pipe meeting the requirements of ASTM F-789 with integral bell-and-spigot-type joints meeting the requirements of ASTM D-3212 and elastomeric gaskets meeting the requirements of ASTM F-477.
C. 
Polyvinyl chloride (PVC) sewer pipe meeting the requirements of ASTM D-1785, Schedule 40 with purple primed, ASTM F-656, solvent cement-type joints conforming to ASTM D-2564 — to be used in all interior plumbing work.
D. 
Ductile-iron sewer pipe shall conform to ANSI/AWWA C150/A21.50 and ANSI/AWWA C151/A21.51. Pipe joints shall be push-on type or mechanical joint type. All pipe joint systems shall conform to the provisions of ANSI/AWWA C111/A21.11, Fittings shall be ductile iron with mechanical joints conforming to ANSI/AWWA C110/A21.10 and ANSI/AWWA C1 11/A21.11 having a pressure rating of 350 psi. Pipe thickness shall be in no class less than Class 52. The Township, at its discretion, may require the pipe thickness to be greater than Class 52.
All area drains, including garage floor and basement floor drains, potentially discharging rain or "clear" water shall not be connected to the building sewer. As well, downspouts, sump pumps, and any other device not containing waste material is strictly prohibited from entering the Township's sanitary sewer system.
All sewers shall be installed in strict accordance with the manufacturer's recommendations and Township's Sewer Construction Standard Details. All sewers shall be installed using a pipe laser. No other methods or laser level equipment will be allowed. All sewers shall be installed by competent, skilled pipelayers. Each excavation for a sewer shall be guarded adequately with barricades and other protection devices to protect vehicle and pedestrian traffic from damage and injury. Any roadway, sidewalk and other Township property or public property disturbed in the installation of a sewer shall be restored to its original condition or better at the sole cost and expense of the person installing the sewer.
[Amended by Ord. 05-28-15]
A building sewer shall be connected to the public sanitary sewerage system at the place designated by the Township. The invert elevation of the building sewer at the point of connection shall be as required by the Township. A smooth, neat joint shall be made, and the connection of the building sewer to the lateral shall be made secure and watertight with a coupling adapter approved by the Township. Fernco-type couplings are not acceptable, unless a manufactured coupler is not available and prior approval from the Township is received. Building sewers shall be installed as direct as possible. Changes in direction must be made with wyes, combination wye and eighth-bends or half wyes, or one-eighth bends. Ninety-degree changes in direction shall be made with a two-foot minimum length of pipe between the approved fittings. Every change in direction which exceeds 45° shall include a cleanout. Changes in pipe size where the building sewer is connected to the lateral shall be made only with fittings. An inspection port of the same size as the lateral shall be placed in the sewer discharge pipe on or about the property line (as determined by the Township) of the building, house and/or structure being connected to the public sanitary sewer system. This inspection port shall be constructed by use of at least a six-inch tee fitting being placed in the lateral at the time of construction thereof. From the said tee fitting, a vertical stack pipe of at least six-inch diameter will extend upward to ground level. The top of said vertical stack pipe shall terminate with an adapter with a screw-on cap. The frame and cover over the inspection port shall be East Jordan Pattern #1565 or Neenah Model # R-1975-A2 or approved equal. The frame and cover must be installed such that no downward forces imparted by a load on the frame can be transferred to the observation stack. The frame must be installed on level ground as near to the property line as possible. The frame can be purchased at the Township office. The inspection port assembly shall remain in place and accessible at all times by Township personnel. All such connections shall be installed in such a manner as to be watertight. The building owner shall have the option to install a barrier for the purpose of preventing passage of stormwater and/or other waters and/or liquids from utilizing the trench in which the building sewer is located as a conduit to the building being serviced by the building sewer.
A building sewer shall be laid on a grade of not less than 1/4 inch per foot (2.0% grade) and shall have a minimum cover of 2 1/2 feet. The Township Engineer or authorized representative may grant special permission for a building sewer to be laid on a grade less than 1/4 inch per foot. A cleanout shall be placed at no more than every sixty-foot interval along the building sewer. The cleanout shall be constructed as detailed in the Township's Sewer Construction Standard Details.
The connection between the building sewer and the building drain shall be constructed as detailed in the Township's Sewer Construction Standard Details. Fernco couplings are permitted at this location to connect dissimilar pipe materials only when a manufactured connector is not available.
All commercial and institutional facilities processing and serving food must install a trap, based on acceptable design standards. The unit selection, computations and catalog cuts must be filed with the Township Engineer and approved prior to installation.
A. 
Total Discharge Flow Rate = Fixture Discharge + Dishwasher Discharge.
B. 
For plumbing fixtures and equipment wastes, determine fixture discharge. (If more than one fixture can discharge at the same time, include all discharges.)
(1) 
Fixture discharge (gpm): for drains discharging plumbing fixtures and equipment wastes or kitchen drains not discharging "clear" water.
(2) 
Dishwasher manufacturer's discharge rating (gpm).
1. 
The unit selection, computations and catalog cuts must be filed with the Township Engineer and approved prior to installation.
2. 
Oil interceptor sizing shall be achieved by determining the greater demand upon the proposed unit, either discharge flow rate or emergency oil spill capacity.
A. 
Discharge Flow Rate.
(1) 
For drains discharging plumbing fixtures and equipment wastes or floor drains not influenced by surface water from roof or exterior drainage areas:
Calculate fixture discharge (if more than one can discharge at same time, including all discharges)
Total Volume of Fixture (C.F.) x 7.48 Gal. x 0.75/2 min. C.F. = Discharge Flow Rate (gpm)
Where:
0.75% of fixture volume utilized (2 min. drainage period from fixture) 7.48 gal./C.F. conversion factor
(2) 
For drains discharging oily surface water crossing the floor areas:
Surface Area (S.F.) X 1.2 inches x 2.0 gal.-hr. x hr. 96.26 inc-S.F. = Discharge Flow Rate (gpm)
Where:
1.2 inches/hr. = two-year rainfall in Central Pennsylvania
2.0 = Minimum storage factor
96.26 in-min-SF units factor = Gal.-hr.
B. 
Emergency Oil Spill Capacity.
=Max. Grease and/or Oil Discharge (gpm) x 2 min. x .8/2.0
Where:
Maximum grease and/or oil discharge rate from all equipment that stores and/or delivers products
2 min. = Maximum spill time
0.8 = Separation feeder
2.0 = Sizing factor
The grease capacity (gal.) must be equal to the maximum grease and/or oil discharge x 2 min.
To convert gallons of oil/grease to pounds, use 6 gallons = 1 pound.
Knowing the proposed discharge flow rate and/or emergency oil capacity, select a unit with the proper sizing using manufacturer's catalog information.
Persons installing sewers must comply with the requirements of the Commonwealth of Pennsylvania Act No. 38 (1991), the provisions of which are incorporated herein by reference.
1. 
Manhole sections shall be precast concrete and shall be manufactured in accordance with the provisions of ASTM C-478. Waterproofing shall be obtained by using ZPEX C-1000 RED admixture to the concrete. All joints shall be tongue and groove. The inside diameter of the manhole sections shall be not less than 48 inches. Manhole tops shall be "eccentric cone" sections or flat tops having an opening not less than 27 inches in diameter.
2. 
All joints in the precast concrete manhole sections shall be thoroughly cleaned, primed and a joint-sealing compound (two strips per joint) equal to RAM-NEK Performed Plastic Gasket, as manufactured by K.T. Snyder Company, or equal, placed entirely around the joint immediately before the manhole sections are assembled. "Squeezed out" excess joint material must be neatly trimmed and removed. Through wall lifting holes shall not be permitted. Lifting keys or lugs shall be factory-installed integrally in the manhole components.
3. 
Manhole bases shall be precast concrete "flanged" type bases. At each point where the sewer pipe enters (or leaves) a manhole base, a cast-in-place flexible pipe gasket system shall be installed. Rubber gasket materials shall conform to the requirements of ASTM C-443.
4. 
All precast manhole sections shall be furnished with manhole steps at twelve-inch centers and properly aligned. The manhole steps shall be properly aligned vertically as the manhole sections are being assembled. Reinforced plastic manhole steps shall be 1/2 inch Grade 60, ASTM A615 deformed steel reinforcement completely encapsulated in Grade 49108, ASTM D4104 copolymer polypropylene plastic compound. Manhole steps shall be M.A. Industries, Inc.'s Type PSI-PF.
5. 
After the manhole is made watertight and completely cured, the exterior surfaces (and interior surfaces when used within the Innovative and Alternative District) shall be entirely coated with a coal tar epoxy coating system equal to one prime coat and the number of finish coats necessary to provide a final dry film thickness of not less than 20 mils. The coating shall be applied in strict conformance with the coating manufacturer's specifications. A written certification stating that the previously stated waterproofing specification has been met shall be provided to the Township.
6. 
Immediately prior to placing the concrete for the flow channels in the manholes, thoroughly clean the surfaces of the concrete that will make contact with the concrete for the flow channel, moisten these surfaces with water and place approximately 1/2 inch of mortar containing a latex bonding admixture thereon. The bonding mortar shall be field-mixed at the manhole site in strict conformance with the manufacturer's instructions. The flow channel concrete shall be PA-DOT Class A concrete with PA-DOT No. 1B coarse aggregate and shall be placed on the bonding grout immediately after the bonding grout is placed. Smooth flow channels cast in the manhole bases by the manhole manufacturer will be acceptable.
7. 
Manhole frames and covers shall be similar to Neenah Foundry Company Catalog No. R-1753-A self-sealing marked "Sanitary Sewer" and having an opening not less than 27 inches in diameter. Four holes shall be drilled in the manhole frame and the top of the precast concrete manhole eccentric cone section. After cleaning the manhole frame and the top of the precast concrete manhole eccentric cone section, place joint-sealing compound on the concrete and securely bolt the manhole frame to the eccentric cone section top with three-fourths-inch expanding head concrete anchors. If precast concrete grade adjustment rings are required to properly bring the manhole cover to finished grade, joint-sealing compound shall be placed between adjacent rings, between the ring and frame and between the ring and eccentric cone section. In all cases, the frame must be bolted to the eccentric cone section.
8. 
Provide adequate support in the form of a concrete cradle to undisturbed earth under all pipes entering or leaving manholes.
Inflow protection inserts shall be in all manholes which are not "self-sealing." The inflow protection insert and its associated components shall be manufactured from corrosion-proof materials suitable for atmosphere containing gases associated with wastewater collection systems. The thickness of the insert body shall not be less than 3/32 inch nor greater than 6/32 inch. The insert body shall not have an overall depth exceeding 6 1/2 inches. The insert shall have a sealing gasket made of close cell neoprene. The insert shall have a gas relief valve designed to relieve at a pressure of one pound or less. The valve shall have a leak-down rate not exceeding 10 gallons per 24 hours, to eliminate the ponding of water over the manhole. The gas relief valve shall have no metal parts. The valve shall be positioned so that it is protected and will not be broken by any movement of the manhole cover. The insert shall have a lift strap attached to the insert body. The lift strap shall be made of one-inch-width polyester, nylon and shall be seated at all ends to prevent unraveling or deterioration. The lift strap shall be attached to the insert body by means of a sealed aluminum rivet. Attachment of the lift strap to the insert body shall be recessed to prevent contact with the manhole cover during removal or replacement of the manhole cover. The manhole frame rim shall be cleaned of all dirt or debris before placing the insert upon the rim. The insert shall be fully seated around the manhole frame rim. Inserts shall not be installed until all testing of the sewer lines has been satisfactorily completed and the Township has issued written approval to install the inserts.
1. 
All sewers, except those building sewers that the Township grants permission not to be tested, shall be tested for alignment and deflection and exfiltration as follows:
A. 
Prior to testing, the person installing the sewer must submit to the Township for approval the test procedure and test equipment he proposes to use.
B. 
The person conducting the test shall furnish the labor, equipment, materials, and all else necessary to perform the testing specified herein. All sewers which do not meet the test limits established herein shall be repaired or removed and replaced to the satisfaction of the Township.
2. 
Alignment Test. A test mandrel, constructed according to the dimensional tolerances shown below, shall be pulled through the sewer line to determine whether the alignments and deflection of the pipe are correct and to ensure that all obstructions have been removed. In the case that the test shows poor alignment or improper deflection of the sewer pipe, misplaced pipe, obstructions or other defects, such defects shall be corrected to the satisfaction of the Township. The minimum mandrel length and outside diameter shall be:
Test Mandrel Construction
Pipe Diameter
(inches)
Minimum Mandrel Length
(inches)
Minimum Mandrel Outside
(inches)
Diameter
6
12.0
5.32
8
17.6
7.10
3. 
Exfiltration Test (Low-Pressure Air Test). After testing for alignment and flushing to remove all obstructions, the sewer shall be subjected to a low-pressure air test as follows:
A. 
The sewer being tested shall be properly capped and plugged and carefully braced to resist the thrust actions developed by the test.
B. 
If the sewer to be tested is submerged in groundwater, the depth of groundwater over the flow line of the sewer must be determined. All test pressures must be increased by the amount of backpressure due to groundwater.
C. 
Add air slowly to the portion of sewer under test until the internal air pressure is raised to 5.0 psi.
D. 
After the internal air pressure of 5.0 psi. is obtained, allow two minutes for the air temperature to stabilize, adding only the amount of air necessary to maintain test pressure.
E. 
After the stabilization period (minimum pressure in the pipe of 5.0 psi.), start the stop watch. Determine the time that is required for the internal air pressure to reach 4.5 psi. Minimum permissible holding time shall be 10 minutes for six-inch diameter pipe: 12 minutes for eight-inch diameter; pipe and 30 minutes for twelve-inch diameter pipe.
F. 
Should any test of sewer pipe laid not meet the test requirements specified above, the contractor shall, at his own expense, locate and repair the defective sewer pipe until the pipe meets the test requirements. In-place grouting to repair defective sewer pipe will not be permitted.
G. 
Safety precautions must be observed. Plugs must be braced to prevent blowouts. Pressurizing equipment must be capable of being operated remotely, and no one should be permitted in the manholes during testing.
1. 
The contractor shall vacuum test EACH manhole constructed in his contract. The tests shall be conducted in the presence of and to the complete satisfaction of the Township. Should a manhole not satisfactorily pass the test, the contractor shall discontinue manhole construction on the applicable contract until such manhole does test satisfactorily.
2. 
The contractor shall provide the tools, materials, equipment and instruments necessary to conduct manhole testing specified herein. Vacuum testing equipment and associated testing apparatus shall be subject to the Township's approval. The contractor shall use vacuum apparatus equipment equipped with the necessary piping, control valves and gauges to control the air-removal rate from the manhole and to monitor vacuum. An extra vacuum gauge of known accuracy shall be provided to frequently check test equipment and apparatus. A seal plate with vacuum piping connections for inserting in the manhole frame shall be provided.
3. 
Prior to testing, the contractor shall thoroughly clean the manhole and seal the openings, to the satisfaction of the Township. Properly sized plugs shall be used to seal the opening, taking care to securely brace the plugs. Testing shall be performed with the frame installed. The joint between the manhole eccentric cone and the manhole frame shall be included in the test. The contractor may select to make a test for his own purposes prior to backfilling. However, all vacuum tests of the manholes for acceptance shall be conducted only after the backfilling has been completed.
4. 
The contractor shall perform vacuum testing in accordance with the testing equipment manufacturer's written instructions: a vacuum of 10 inches of mercury and close the valves. The manhole shall be considered acceptable when the vacuum does not drop below nine inches of mercury for the following manhole sizes and themes:
A. 
Four-foot diameter: 60 seconds.
B. 
Five-foot diameter: 75 seconds.
5. 
The contractor shall determine the source or sources of leaks in manholes failing the vacuum test. The contractor shall repair or replace defective materials and workmanship, as is the case, and conduct additional vacuum tests and such subsequent repairs and retesting as required until all manholes meet testing requirements. All materials and methods used to make manhole repairs must meet with the Township approval prior to use. All repairs, replacements and retests shall be made at no additional expense to the Township.
1. 
Products.
A. 
Polyethylene septic tank shall be 1,000 gallons in capacity and be one of the following:
(1) 
Heavy-duty type manufactured by AK Industries.
(2) 
WR-4000 manufactured by Wedco Molded Products.
(3) 
Norwesco 1,000-gallon single compartment.
B. 
Manhole frame and cover meeting the specifications found in § L, must be installed over tank access cover upon a bed of sand or limestone dust using a four-inch concrete grade ring with 4 3/4 concrete anchors.
C. 
Tank-to-pipe adapter must be Schedule 40 PVC at tank inlet and SDR-35 at tank outlet.
D. 
Gaskets, materials, mastic sealant and screws must provide an odor-free, watertight installation.
2. 
Installation.
A. 
A.K. Industries Tank, Overexcavate no more than six inches under and around tank. Place tank on six inches of PA-DOT 2B aggregate. Once the tank is installed, level backfill excavation with PA-DOT 2B aggregate in six-inch lifts to the spring line being sure to fill in the corrugations under the haunches. Fill tank with water to spring line. Install riser with flared end downward and secure to tank with mastic and 20 stainless steel screws. Be sure that the tank and riser surfaces are clean and dry. Place PA-DOT 2B in six-inch lifts around the tank to an elevation equal to the tank and riser joint. Backfill riser with limestone dust or sand to an elevation of 13 inches below finish grade. This backfill material must be two feet in thickness. Approved backfill may be placed between dust or sand and the limit of excavation. Install four-inch concrete grade ring and manhole frame and cover to grade and backfill with topsoil. Install septic tank cover on riser with gasket, material, and stainless steel screws.
B. 
Wedco WR-4000 Tank. Overexcavate no more than 12 inches under and around the tank. Place six inches of compacted PA-DOT 2 RC aggregate in excavation for tank base. Install tank level and fill with water to 1/2 tank depth. Place PA-DOT 2RC aggregate in eight-inch compacted lifts to the midpoint of the tank. Backfill uniformly around the tank so that one side is not higher than any other during backfilling. Backfill must be compacted under inlet and outlet pipes. When making pipe connections, do not twist or deflect pipe stub installed in the tank. This may cause damage to baffle within the tank. Install the riser section with mastic and stainless steel screws. Fill the remainder of the septic tank with water and backfill with PA-DOT 2 RC aggregate in compacted lifts to the spring line of the tank. The remainder of backfill over the tank must be PA-DOT 2 RC aggregate in six-inch layers without compaction. Backfill riser with limestone dust or sand to the top of the tank lid. Secure tank lid with gasket material and stainless steel screws. Seal the threaded plug with pipe dope. Install four-inch concrete grade ring and manhole frame and cover over the tank lid to grade.
C. 
Norwesco Tank. Excavate to a depth that will provide a minimum of six inches and a maximum of 30 inches of cover over the top of the tank. Allow 18 inches to 24 inches on all sides of the tank. Bed the tank in well-packed sand - six-inch minimum in soil terrain, twelve-inch minimum in rocky terrain. Inlet and outlet piping should be solvent-welded using standard PVC cement. Prior to backfilling, install manhole extensions. Fill tank with water as the tank is backfilled with a sand/gravel mix compacting in twelve-inch lifts. Always compact ends first, making sure to compact around the inlet and outlet pipes.
3. 
Testing.
A. 
Vacuum. Upon receipt of tanks from the manufacturer, each tank must be vacuum-tested for structural integrity. The test is conducted by applying a vacuum of 54 psi to the interior of the tank where deflection of the length or width cannot exceed two inches after a five-minute test period. Failure of this test constitutes rejection of this tank. Retest of failed tanks may be granted by the Township, depending upon circumstances surrounding the failure. Testing equipment and labor must be supplied by the contractor or the local supply house.
B. 
Water. Once the tank is installed, a water test consisting of a full tank, including the riser section, must stand for 24 hours without any water loss to be deemed acceptable. The failure of this test constitutes the removal and replacement of this tank. Retesting after approved repairs or component replacement may be approved by the Township. The contractor must supply the equipment and labor for this test.
4. 
Cleanout.
A. 
Within three feet of the outlet of the Wedco WR-4000 tank, a four-inch cleanout must be installed meeting the requirements of the Township as shown in § U.
1. 
PVC Pressure Lateral Pipe. The discharge pipe and fittings (pressure laterals) for the effluent pumps shall be polyvinyl chloride (PVC) pressure pipe. The PVC pressure pipe shall meet the requirements of: ASTM D-1785, Schedule 80, Specification for Polyvinyl Chloride (PVC) Plastic Pipe Schedule 80 and 120, latest revision. The pipe shall be manufactured from Class 12454-B rigid PVC compounds with a hydrostatic design stress of 13.8 Mpa (2,000 psi) designated as PVC 1120. Joints shall be socket type. Fittings shall be either socket type manufactured from Class 12454-B rigid PVC compounds in accordance with the requirements of ASTM D-2467. Primed and solvent cement joints shall conform to ASTM F-656 D-2564.
2. 
Effluent Pump Discharge Pipe Testing. This subsection is applicable to the testing of the discharge piping from the septic effluent pumps to the sewer lateral connection. The contractor shall conduct pressure and leakage tests specified below to the Township's satisfaction. The contractor shall provide the test pump, pipe connections and all necessary tools, materials and equipment, including the proper test gauges to show pressure (psi) and flow (gallons per minute), required to properly perform the testing. The hydrostatic testing equipment and testing installation shall be satisfactory to the Township prior to testing, and the testing shall be conducted in the presence of the Township and to the satisfaction of the Township. Water for the testing shall be furnished by the contractor. When the pipe to be tested is completed, it shall be tested as follows: The pipe shall be filled by the contractor with water a minimum of 24 hours before the pipe is tested. Extreme care must be taken to ensure that all air is expelled from the pipe during the filling of the pipe with water. After the pipe has been filled with water for 24 hours, conduct the pressure test for a duration of at least four hours. The test pressure shall be 50 pounds per square inch (psi). A leakage test shall be conducted concurrently with the pressure test. The contractor shall provide suitable means to measure the leakage during the pressure test, and a record of the water added to the pipe shall be kept for the period of the test. The leakage shall be defined as the quantity of water that must be added to the pipe to maintain the pressure within five psi of the specified test pressure. There shall be no leakage during the four-hour leakage test. In case the pipe fails to pass the specified leakage test, take corrective measures necessary to repair the leaks and retest the pipe.
3. 
Septic Tank Effluent Pump Assemblies.
A. 
Basin. The septic tank effluent pump shall be mounted in the twenty-four-inch diameter by eight feet zero inches deep basin molded of fiberglass-reinforced polyester resin with smooth, resin-rich interior surface. The basin shall have a nominal wall thickness of 1/4 inch. A one-piece stainless steel antiflotation plate shall be molded into the bottom of the basin. A circular fiberglass antiflotation flange molded with the walls of the basin shall also be acceptable. The antiflotation plate shall have holes for a minimum of four stainless steel anchor bolts for securing the plate to the reinforced concrete base. The stainless steel anchor bolts shall conform to ASTM A320, Grade BB, AISC Type 303 or 304.
B. 
Basin Cover. The basin cover shall be of three-sixteenths-inch steel coated with high-temperature-baked epoxy paint. The cover shall be bolted to the basin with stainless steel cap screws. Cadmium-plated nuts for the screws shall be embedded in the fiberglass to prevent turning and for corrosion resistance. Tapped backoff holes shall be provided in the cover so that the cover can be lifted with screws instead of prying. Cover shall be sealed with close-cell high-density neoprene foam gasket. The gasket shall be a minimum of one inch wide by 1/4 inch thick. The gasket shall be cemented to the basin cover.
C. 
Pump. The pump shall be a submersible centrifugal-type pump with a heavy cast-iron motor housing, single vane, enclosed impeller and stainless steel pump/motor shaft. The pump housing shall be of high-tensile strength Class 30, ASTM A48, gray cast iron. The casting shall be treated with phosphate and chromate rinse and painted with high-quality dry alkyd enamel. The pump shall be capable of handling septic tank effluent and liquids with temperatures to 140° F. intermittent. The pump shall be capable of passing three-fourths-inch solids. The pump shall be capable of discharging 40 GPM against 42 TDH. The pump shall be Model P50 effluent pump as manufactured by F.E. Myers, or approved equal. The pump discharge fittings shall be of one-and-one-half-inch NPT. The pump shall be capable of running dry without damage to components. The pump motor shall of 1/2 HP (minimum), 115/230 volt, single-phase, 60 Hz, 3,450 RPM. The motor shall be capable of operating over the full range of the performance curve without overloading the motor or causing any objectionable noise or vibration. The motor shall be fully submerged in high-grade turbine oil, have permanently lubricated heavy-duty bearings (minimum B-10 life of 50,000), and double-tandem seal configuration. The common motor pump shaft shall be 416 stainless steel and shall be heat shrunk into the die-cast motor rotor. The impeller wear ring shall be Type 304 stainless steel. The replaceable volute sealing ring shall be Buna-N. The top shaft seal shall have carbon and ceramic seal faces, and the bottom shaft seal shall have tungsten carbide faces. All external hardware shall be Type 304 stainless steel. The motor power cord shall be SJOW/SOWA. The cable jacket shall be sealed at the motor entrance by means of a rubber compression washer and compression nut. A heat-shrunk tube filled with epoxy shall seal the outer cable jacket and individual leads to prevent liquid from entering the motor housing. The permanent split-capacitor motor shall have a built-in on-winding current, and thermal (stops the motor if the motor winding temperature reaches 266° F.) overload protectors with automatic reset switch shall be provided for the motor. Seal leak detector probes to detect water leakage in the seal housing shall be provided.
D. 
Stainless Steel Lift Chain. The pump shall be equipped with a stainless steel lifting chain. The chain shall fasten to the pump assembly by means of a stainless steel clevis. The cabin shall also be secured to the top of the basin. The chain shall be of the welded-link type and shall be a minimum of 1/4 inch.
E. 
Pump Discharge Piping. The discharge piping shall be two-inch Schedule 80 PVC pipe. A union ball valve (see Subsection 3F below) shall be provided to connect the pump discharge piping to the pressure lateral pipe.
F. 
Shutoff Valve. A PVC true union ball-type shutoff valve manufactured from PVC Class 1245B conforming to ASTM D1784 with Vitron O-ring seals and self-lubricating teflon seats shall be furnished and installed in the discharge piping.
G. 
Check Valve. A PVC double union ball-type check valve manufactured from PVC Class 1245AB conforming to ASTM D1784 with Vitron O-ring seals shall be furnished and installed in the discharge piping.
H. 
Basin Inlet Flange. A basin inlet flange for four-inch Schedule 40 PVC pipe shall be provided for field mounting. The flange shall be mounted in the field at inlet height required by the specific installation.
I. 
Basin Inlet Pipe. The polyvinyl chloride (PVC) basin inlet pipe shall be ASTM D1785, Schedule 40 manufactured from Class 12454-B rigid PVC compounds designated PVC 1120.
J. 
Basin Discharge and Electrical Conduit Connections. These connections shall be made watertight flanges and adapter furnished by the basin manufacturer as required for the type and size of pipe.
K. 
Liquid Level Controls. Provide three mercury-type float switches to control pump operations at the levels indicated on the drawings. A PVC float pole shall also be acceptable. Switches shall be waterproof design with mercury switch and eccentric weight housed in a smooth, chemical-resistant polypropylene casing. Provide sufficient heavy neoprene jacketed, waterproof cables and stainless steel mounting bracket to install the switches at the elevations shown. Cable attachments shall permit adjustment of the float level.
L. 
Junction Box. The junction box shall be constructed of fiberglass. The junction box shall have a fully gasket cover held in place by four captive stainless steel screws that cannot be removed from the cover, with heads totally encapsulated in PVC so that no metal parts are exposed. The cover shall be fastened to the main body of the junction box by means of a totally corrosion-resistant tether to prevent dropping the cover into the basin. The junction box shall be designed to NEMA 6 standards for occasional submergence. An adequate number of plug-in connectors shall be provided for incoming pump cord and level control switches. Waterproof male plugs shall be supplied on the pump power cord and control cord and the cords for the level control switches and soul mate to a female socket mounted in the junction box. The plugs and cords shall be of the proper size to handle the voltage and current requirements of the pump level switches. The plug and receptacle shall fit like a cork into the flexible shroud portion of the male. In addition, individual neoprene shoulders around the contacts shall fit into recesses in the female section. The cable shall be neoprene molded, one-piece design, and the connectors shall have threaded coupling for positive tight connections and quick release. The mating connectors shall have an indexing tab to ensure proper alignment.
M. 
Warranty. The pump manufacturer shall provide a warranty which guarantees the pumps to be free from defects in material and factory workmanship for a period of two years from the date of acceptance by the owner. All repairs, parts and parts replacement required as a result of such defects shall be made by the pump manufacturer free of charge to the owner, including all shipping and handling costs, during the warranty period.
4. 
Pump Control System.
A. 
Manufacturer. The control panels described herein shall be manufactured by EG Pump Controls, Inc., or approved equal. (Manufacturer's representative: John P. Place, Inc., 90 Clairton Boulevard, Pittsburgh, PA 15236, telephone: 412-892-2000).
B. 
General. The simplex pump control panel shall be of the float-controlled type. The factory assembled system shall include:
(1) 
NEMA 4X fiberglass enclosure.
(2) 
Intrinsically safe controller.
(3) 
Alarms and sensors as specified herein.
(4) 
Two-year warranty on all components.
C. 
Control System Operation. The control system shall provide automatic control for one electric-driven pump specified under § C herein. The control panel shall be built to accept 230 volts, single-phase, three-wire services. The necessary three float switches shall be supplied and installed by the pump supplier.
(1) 
The pump basin liquid level shall be monitored and controlled as follows:
(a) 
Level 3: high-level alarm.
(b) 
Level 2: start pump on rising level.
(c) 
Level 1: stop pump on falling level.
(2) 
Based upon the liquid level, the float switches shall energize the appropriate control contacts to start and stop the pump and to energize an audible and visual alarm.
D. 
Enclosure. All control elements shall be housed in an enclosure rated per NEMA 4X standards and suitable for outdoor installation. The enclosure shall be manufactured corrosion-resistant fiberglass and have provisions for padlocking. All hardware, including the hinges, latches and padlock provisions shall be stainless steel. The enclosure shall have a removable subpanel fabricated from Type 5052-H32, 0.080-thick, marine alloy aluminum. The enclosure shall have a continuous piano-hinged door (deadfront) fabricated from Type 5052-H32, 0.080-thick, marine alloy aluminum. The inner door shall be held closed by two hand-operated one-fourth-inch turn fasteners. All mounting holes shall be drilled and tapped. Self-tapping metal screws shall not be used to mount any components. All bolts, nuts, washers, lock washers, and machine screws shall be AISC Type 304 or 316 stainless steel. The enclosure shall have external mounting feet to allow for wall mounting. The contractor shall wall-mount the enclosure using AISC Type 304 and 316 stainless steel fasteners and anchors. The contractor shall provide a padlock conforming to the requirements of Federal Specifications FF-P-106 for each panel. All padlocks shall be keyed alike and shall be keyed into the Logan Township master key system. Six keys shall be provided.
E. 
Logic Controls. The simplex logic control shall consist of an intrinsically safe controller mounted on the subpanel and the pilot devices operable without opening the inner door (deadfront). The control circuit shall be protected by a separate 15A circuit breaker.
F. 
Intrinsically Safe Controller. The controller shall consist of a single solid-state module designed for ease of maintenance and replacement, complete with diagnostic capabilities. The use of individually mounted components will not be acceptable. The controller shall be EG Pump Controls, Model No. SIR-24-123.
(1) 
The controller shall consist of:
(a) 
Hand-Off-Auto selector switch.
(b) 
Call-to-run indicating light.
(c) 
Float condition indicator light/test switch. Each float shall have an indicator lamp to indicate when the control circuit is energized and one normally open spring return test switch to test pump operation.
(d) 
16 amp @ 120 volt rated output contacts (for starters and alarms).
(e) 
100 microamp @ 5 volt float control.
(f) 
Artificial intelligence to detect float switch failure. Should any float fail, the sequence of operation shall automatically shift to the next float (i.e., if FS1 "Off float fails, then FS2 shall become the "Off" float and FS3 shall become the "Start Pump and High Level Alarm" float).
(2) 
Separate metal barriers shall be supplied to completely isolate intrinsic safe wiring from all other wiring within the control panel enclosure.
G. 
Alarms. The following alarms shall be provided:
(1) 
Elapsed Time Meter. A nonresettable elapsed time meter shall be mounted on the deadfront to indicate pump run time. The elapsed time meter shall have five digits for hours, one digit for 1/10 hours, and one digit for 1/100 hours. A rotating mechanical indicator on the front of the elapsed time meter shall rotate to indicate that the meter is running.
(2) 
Seal Failure. A moisture-sensing system shall be installed and connected to the relay logic to illuminate an amber neon indicator on the inner door. Sensitivity shall be 60K ohms minimum. (Moisture-sensing probes shall be supplied and installed in the pumps by the pump manufacturer.)
(3) 
Pump Over-Temperature (Auto Reset). The over-temperature sensor shall lock out the pump motor starter and illuminate a red neon indicator on the inner door.
(4) 
Overload Trip. A contact on the overload relay shall be used to illuminate a red neon indicator on the inner door indicating a tripped condition. The circuit shall require a manual reset push-button.
(5) 
Control Circuit Breaker Trip. A red neon indicator on the inner door shall be illuminated indicating a tripped condition.
(6) 
High-Level Alarm Pilot Light. A full size (13/16 inch), oiltight pilot shall be mounted on front of the enclosure door. The pilot light shall be full voltage and shall include a closed-cell neoprene gasket to ensure watertight integrity. The lamp and socket shall be removable from the inside of the enclosure.
(7) 
Audible Alarm. A NEMA 4X encapsulated electronic horn shall be mounted on the side of the enclosure. Audible rating of the horn shall be a minimum of 85 decibels at two feet.
H. 
Silence Push-Button. A heavy-duty oiltight push-button located on the side of the enclosure shall be provided to silence the horn during an alarm. The alarm condition shall automatically reset itself upon lowering of the level.
5. 
Power Handling.
A. 
Main Lugs. Main lugs of the appropriate size shall be furnished for connecting the incoming supply power. The lugs shall be suitable for use with aluminum or copper conductors. Pump motor circuit breaker line side lugs shall not qualify as main lugs.
B. 
Ground Lugs. Ground lugs of appropriate size shall be bolted to the subpanel. Individual lugs shall be provided for incoming power and pump connection.
C. 
Motor Circuit Protection. Motor circuit protection shall be selected in accordance with the National Electric Code and be either a thermal magnetic circuit breaker or magnetic motor circuit protector. The breaker shall be interlocked with the deadfront so that the deadfront may not be opened with the breaker in the ON position. Thermal magnetic breakers shall comply with Federal Specification W-C 3 57A as Class 2 breakers. Symmetrical amperes interrupting ratings are 10,000 amps minimum for 240-volt rated breakers. Magnetic motor circuit protector shall have an adjustable instantaneous trip setting. Circuit breaker toggles shall be operated through cutouts in the inner door (deadfront). A circuit breaker shall be installed for the control circuit in place of a fuse.
D. 
Motor Starters. Motor starters shall be full voltage - non reversing (FVNR) rated for 1,000,000 full load operations minimum. Motor starters shall have three poles, Class 10, ambient compensated overload relays with automatic reset capability. All starters shall be size 00 minimum.
6. 
General Features. The following components shall be provided:
A. 
Receptacle. A duplex 120 VAC GFI receptacle shall be mounted in the enclosure.
B. 
Lightning/Surge Arrestor. A lightning/surge arrestor connected to the main circuit breaker. The lightning arrestor shall meet or exceed the requirements of ANSI/IEEE Standard C62.1-1984, Sections 8.6.1 and 8.7.3.
C. 
Space Heater. A heating system shall be supplied to maintain the interior temperature 2°-3° F. above ambient temperature to prevent corrosion due to condensation.
D. 
Wiring Diagram. Each panel shall have a complete laser-screened laminated Mylar wiring diagram (5 mil thickness minimum) placed on the inner door. The diagram shall contain an electrical schematic, physical component layout, and a complete bill of materials.
E. 
Wiring Channel. All wiring within the enclosure shall be neatly bundled inside a wiring channel. The channel shall have a removable cover for ease in troubleshooting.
F. 
UL Label. All control panels must have the capabilities and functions as outlined above and be assembled by a UL "ENCLOSED INDUSTRIAL CONTROL PANEL" label within the enclosure door to assure a high grade of quality.
G. 
Nameplates. All nameplates shall be weatherproof laser-screened laminated Mylar (five mil thickness minimum), gold in color with black letters. A nameplate shall be supplied to identify each switch, pilot light, and all components mounted to the back panel. Nameplates shall be attached such that all weather conditions shall not permit peeling.
H. 
Testing. Each panel shall be shop-tested to assure proper operation of every function. Test records shall be furnished to the Engineer prior to final approval of the control panel.
I. 
The control system shall include any additional devices required by the pump manufacturer to validate the pump warranty.
J. 
The manufacturer of the pump controller shall warrant it to be free from defects in materials and workmanship for two years from the date of acceptable installation as determined by the owner.
7. 
Electrical Work.
A. 
Codes/Rules/Ordinances/Certificates.
(1) 
All the electrical work, materials, and methods of installation to satisfactorily complete the contract shall comply with the following:
(a) 
The National Electrical Code (NEC).
(b) 
The National Electric Safety Code.
(c) 
The Federal Occupational Safety Health Act (OSHA).
(d) 
Installation rules and requirements of the Pennsylvania Electric Company.
(e) 
Regulations and ordinances of Logan Township.
(f) 
Federal and state codes and regulations applicable to the project.
(2) 
All of the above-specified regulations shall be of the latest published edition. These are hereby to be part of the contract documents. If conflict between these written specifications and the reference codes and regulations exist, the codes and regulations shall take preference.
(3) 
The contractor shall be solely responsible for obtaining all permits and inspections for approval and shall pay all fees for procuring permits and certificates pertaining to the electrical work.
(4) 
The contractor shall produce an inspection certificate or panel label at the completion of the contract. This shall be done by the prevailing authority regarding the installation and execution of this work. All costs for this service shall be solely borne by the contractor.
B. 
Tests. The tests and demonstrations shall be performed at the completion of the work and shall show that all work and materials for this contract are performing to their original intent and comply with the NEC.
C. 
Intent. Should anything be omitted from either plans or specifications, which is usual practice in first-class electrical work and is essential or necessary for the proper completion of the electrical work in the opinion of the Township, it shall be furnished by the contractor as though herein definitely specified or shown on the drawings. Should, in the contractor's opinion, the electrical work shown or specified prevent the installation of a first-class efficient plant or be inconsistent with such a result, he shall so notify the Township in writing when submitting his proposal. Electrical system layouts indicated on drawings are generally diagrammatic, and location of equipment is approximately correct; exact routing of conduit and locations of equipment shall be governed by structural conditions and obstructions. This is to be coordinated with an approval by the Township. The drawings shall not be scaled. The right is reserved to make any reasonable change in location of outlets and equipment prior to rough-in without involving additional expense.
D. 
Materials and Equipment. The installation shown on location plan sheets and more particularly described hereinafter shall be made by competent, skilled mechanics using the best of new materials. The various materials and apparatus hereinafter specified denote the standard of quality desired and shall be adhered to unless otherwise directed or approved by the Township. Materials and appliances of the types for which there are Underwriters' Laboratories standard requirements, listing and labels shall conform to their requirements, in which case certified statements and examination reports by a recognized independent testing laboratory acceptable to the Engineer are required. All materials and equipment offered under these specifications shall be limited to products regularly produced and recommended by the manufacturer for the service intended. The materials and equipment shall have capacities and ratings sufficient to amply meet the requirements of the contracts. Equipment shall be installed in strict accordance with manufacturer's instructions for type and capacity of each piece of equipment used. The contractor shall obtain these instructions from the manufacturer, and these instructions shall be considered part of these specifications. Insofar as possible, use one type and quality.
(1) 
The following materials and equipment will be required for the electrical work under the scope of this contract. Equipment provided must be similar to the catalog cut sheets attached.
(a) 
100 AMP, 12 space, rainproof load center.
(b) 
100 AMP, 20 space, interior load center.
(c) 
100 AMP, interior, breaker type, service disconnect.
(d) 
Stainless steel pedestal.
(e) 
Stainless steel mounting plate.
(f) 
100 AMP meter socket Kilowatt-hour (KWH) meter.
(2) 
The following materials and equipment will be required (but not all inclusive) for this electrical work under these contracts:
(a) 
100 AMP entrance cable.
(b) 
100 AMP service heads.
(c) 
100 AMP, three-wire, twisted, direct burial cable two-inch.
(d) 
PVC, Schedule 40 conduit.
(e) 
Two-inch rigid steel conduit (mast).
(f) 
Three-fourths-inch rigid steel conduit.
(g) 
Three-fourths-inch coated rigid steel conduit.
(h) 
10-3 OF wire to ground.
(i) 
No. 10 copper wire stranded.
(j) 
Ground rods.
(k) 
No. 6 copper ground wire.
(l) 
Single-pole circuit breakers.
(m) 
Double-pole circuit breakers hangers.
(n) 
Clamps.
(o) 
Connectors.
(p) 
Antioxidant paste fasteners.
E. 
Cutting and Patching. The contractor shall do all cutting, chasing, and drilling required and necessary in connection with his work. All such cutting, chasing, and drilling shall be done in a workmanlike manner without disfiguring or weakening the exterior of buildings, or any other work. The contractor shall be held responsible for any damage or defects due to neglect or carelessness on the part of his employees in connection with the work.
F. 
Underground Work. Underground work shall include all excavating, conduits, and backfilling required under this contract. The contractor shall be responsible for clearing all underground service line, such as sanitary and drainage piping. All excavation, trenching, backfilling, and compaction for electrical work shall be as set forth in the applicable sections of the General Technical Provisions, unless otherwise modified by this section of the Detailed Technical Provisions. Trench excavations shall be made by open cut to proper alignment and grade. Trenches shall be of sufficient width to provide free working space on each side of the conduit(s) to a maximum of the conduit's or conduits' width plus 12 inches. In earth excavation, the trench shall be carried to the elevations indicated on the drawings. Where rock is encountered, the trench shall be carried to a point six inches below the bottom of the conduit. Conduits shall not be allowed to rest directly upon the rock but shall be cushioned by a six-inch layer of PennDOT 2RC aggregate. Open trenches under driveways or other paved areas the entire depth of trench shall be backfilled with PennDOT 2RC aggregate in accordance with the applicable provisions of Section GT-33(d), "Trench Backfilling," of the General Technical Provisions of these contract documents. Upon completion of the backfill and construction operations, all excess soil, rocks, trash and debris shall be removed from the site and the construction area left neat and clean. Under no circumstances shall excavated material remain, even temporarily, where it will interfere with the project or other contractors' operations. Where excavation is required in seeded areas, the seeded areas shall be graded to match the existing grade and reseeded as specified herein.
G. 
Conduit. All conduits shall be installed in accordance with applicable provisions of the NEC, using approved fittings and couplings and as specified herein or as shown on the drawings. Rigid steel conduit shall be full-weight, heavy-wall, mild steel pipe with a protective coating inside and outside by sheradizing or galvanizing methods conforming to Federal Specifications WW-C-581. Rigid steel conduit installed underground shall be coated with two coats of bitumastic paint. Rigid PVC conduit shall be high-impact, Schedule 40 (except where required by NEC to use Schedule 80) PVC conduit and fittings conforming to NEMA. Specifications TC-2, 90C, UL-rated and labeled and made from compounds conforming to ASTM D1784. PVC conduit shall have material strengths of 5m500 psi tensile, 11,000 psi flexural and 8,600 psi compression; all at 78° F. In all instances, couplings and outlet connectors shall be made tight. Bends in rigid galvanized steel conduit shall be made only with approved mechanical benders. Fittings shall be constructed of the same material as the conduit to which they are attached and shall comply with the requirements of the National Electrical Code, Article 370, for materials and uses in conduit systems and Federal Specification W-J-800C. No set-screw or indented-type connectors or couplings will be permitted on the contract. All conduit shall be run as straight and direct as possible to reduce the number of bends. Conduit shall be installed in such a manner that wire may be removed and replaced at any later date. Running threads will not be permitted. Approved threaded couplings shall be used. All couplings shall be pulled up tight and made waterproof in such a manner as to not interrupt the electrical bond.
H. 
Installation of Wire. All wiring shall be installed in accordance with the applicable provisions of the NEC and specified herein or shown on the drawings. Conductor sizes shall be in accordance with sizes shown on the drawings. Conductor sizes shall not be less than No. 12 AWG for branch circuits whose total length from panel to center outlet exceeds 100 feet, including switch leg. Conductors shall be continuous from outlet to outlet, and no splices or joints shall be made except in outlet boxes. Conductors for secondary distribution circuits for installation in raceways shall be high-conductivity copper metal, 600 volts with thermoplastic insulation of heat-resistant grade, Type THW or TBHN. All wiring shall be installed in rigid galvanized steel or PVC conduit, as indicated otherwise on the drawings and specified herein. Aboveground conduit runs shall be surface-mounted as specified on the drawings. Make taps and splices in wire No. 8 and smaller mechanically tight by using Western Union or pigtail splice. Splices may be made with copper-sleeve-type solderless connectors such as manufactured by Buchanan Electrical Products Co., Scotch-Lok or equal. The pressure tool shall take three or more indentions in the solderless connector, and the solderless connector shall be insulated with a vinolite insulating cap. Make taps and splices in wire No. 6 and larger by means of brass or copper pressure connectors applied after wire has been cleaned; make tight and fully insulate as specified in these Specifications. Use parallel taps where necessary to conserve space. The sizes of wire specified herein or as shown on the drawings are the minimum that will be acceptable. Wire and cable shall be as follows: building wire - No. 12 AWG through No. 750 MCM AWG - 600 volt - Type THW or THEN thermoplastic insulation. Wiring in the pump basin must be UL-approved to meet the requirements for use in Class I, Group D, Division 1, locations as defined in Article 500, "Hazardous Locations," of the National Electrical Code.
I. 
Grounding. All conduit, motors, and equipment installed under this contract shall be properly bonded and grounded. Method and size of ground wire shall be installed in accordance with the NEC, latest edition, and the National Fire Protection Association. A bonding jumper shall connect the grounding terminal of all receptacles to the grounded box. Bonding jumpers shall be of copper or other corrosion-resistant materials and shall be of sufficient size to have a current-carrying capacity not less than is required in Table 250-95 of the NEC. The jumper shall be connected to the grounded box by means of a grounding screw which shall be used for no other purpose. All grounding wire shall be green color coded and may be run in the same conduit or raceway as phase and neutral wires. Neutral wiring systems will not be used for the purpose of grounding. No ground wire may be less than No. 12 AWG wire and shall conform to the capacity as set forth by NEC, as specified above. The entire system shall be grounded by means of a connection between the system and a driven ground rod system on the exterior of the building in the earth.
J. 
Disconnects. Switches shall be heavy-duty, enclosed, nonfusible switches with NEMA 3R weatherproof enclosure. All current carrying parts shall be plated with a suitable material such as silver to prevent corrosion and oxidation. Switches shall be rated 250 or 600 volts, AC, as indicated on the drawings. Switches shall be I-T-E, Square "D" or approved equal. Provide ground lugs in all switches.
K. 
Wire Identification. Factory color code all wires per the schedule below. Identify wires by the actual circuit number of all important junction boxes. Wiring shall be one-phase as indicated on the drawings.
Wire
120/208 or 120/240
Neutral
White
Phrase "A"
Black
Phase "B"
Red
Phase "C"
Blue
Ground
Green
8. 
Electrical Service.
A. 
The contractor shall provide and install a complete electrical service for each pumping installation as detailed on the contract drawings.
B. 
In general, this service shall include:
(1) 
A complete 120/240 volt, one-phase, three-wire underground service.
C. 
Provide all necessary accessories and appurtenances for a complete and operational system as herein specified and as shown on the drawings.
D. 
The contractor shall install the electrical service to the pump control system from the property owner's existing panelboard and provide all necessary accessories and appurtenances and pay all costs involved. The contractor shall coordinate and schedule his work with the property owner to reduce disruption of the property owner's activities. Any damage to private property of the property owner shall be corrected by the contractor, at the contractor's sole expense, to the satisfaction of the property owner and the owner.
E. 
If 100 amp minimum capacity is not existing, the contractor shall upgrade existing service to meet 100 amp minimum requirement. The contractor shall verify the new complete service entrance with the utility company to assure that it complies with their requirements and make changes as necessary.
All manhole/cleanout covers and frames shall fit properly to prevent "clanking." "Clanking manhole/cleanout covers shall be machined to produce a proper fit, or "clanking" manhole/cleanout covers shall be removed.
1. 
Unless otherwise noted on the contract drawings, all concrete used shall be PennDOT Class A concrete (6.00 bags/cubic yard). There will be no admixtures allowed unless approved by the Township Engineer. The concrete shall be in accordance with all applicable provisions of PennDOT Publication Form 408 Specifications, latest edition. All references to "concrete" on the contract drawings and in these Specifications and contract documents shall mean "cement concrete." Where "bituminous concrete" is specified or meant, it shall be noted "bituminous concrete."
2. 
All reinforcing steel shall be deformed as defined in ASTM Specifications. All reinforcing steel, unless noted on the contract drawings, shall be Grade 60 as defined in the American Society for Testing and Materials, "Specifications for Steel Bars of Concrete Reinforcement" (ASTM A615, A616, or A617). Bar and rod mats for concrete reinforcement shall conform to specifications for "Fabricated Steel Bar or Rod Mats for Concrete Reinforcement" (ASTM A184).
1. 
The epoxy cement grout shall be a moisture-insensitive, solvent-free, high-solids, high-modulus, epoxy-resin grout formulated of epoxy component and selected silica aggregate in a preproportioned package. The grout properties shall be as follows;
A. 
Compressive strength, ASTM D695: minimum 12,000 psi in 28 days at 73° F. ambient and material temperature.
B. 
Flexural strength, ASTM D970: minimum 3,800 psi in 28 days at 73° F., ambient strength and material temperature.
C. 
Tensile, shear strength, ASTM D638: minimum 1,500 psi in 28 days at 73° F., ambient and material temperature.
D. 
Acceptable manufacturers:
(1) 
Sika Corporation: Sikadur Grout-Pak;
(2) 
The Euclid Chemical Company: Poly-Patch;
(3) 
Or equal.
2. 
Surfaces to receive the grout shall be prepared in accordance with the manufacturer's instructions. The epoxy cement grout shall be mixed in accordance with the manufacturer's instructions for preconditioning and two-component mixing. Place the grout in accordance with the manufacturer's instructions.
1. 
Wye connections and service laterals shall be provided for each house and building and at vacant lots as directed by the Township. The location of the wye connections and the service laterals will be determined by the Township. Laterals shall run from the wye connection to the right-of-way line or property line as shown on the drawings and as directed in the field by the Township. Where directed by the Township, a drop-type service lateral shall conform to the applicable details on the drawings. Pipe caps shall be installed at the ends of all laterals. All lateral end points shall be designated by using a wooden post no less than two inches by four inches and shall extend from the lateral stub to two feet above the ground surface. Each marking post shall clearly indicate the depth to the lateral stub.
2. 
Wye connections, service laterals, fittings and caps shall be PVC pipe conforming to ASTM D3034, SDR 35, as specified therein.
3. 
Wye connections must be installed CONCURRENT with the installation of the sanitary sewer pipe. Under no circumstances will the contractor be permitted to install the wye connections subsequent to sanitary sewer pipe installation.
Cleanouts shall be constructed as detailed on the contract drawings. The pipe shall be as specified herein. Concrete shall be as specified herein. The client frames shall be an Allegheny Foundry Company Pattern 345, or approved equal, having ten-and-one-half-inch openings. The cleanout covers shall be Allegheny Foundry Company Pattern No. 346, or approved equal, marked "SEWER." The frame shall be secured to the concrete encasement, as detailed on the drawings.
1. 
Materials and Method of Construction. All materials and methods of construction for restoration of disturbed areas shall comply with the applicable sections of PennDOT Publication 408 Specifications, latest edition.
A. 
Section 305: Bituminous Concrete Base Course.
B. 
Section 350: Subbase.
C. 
Section 401: Plant Mixed Bituminous Concrete Base.
D. 
Section 420: Bituminous Wearing Course ID-2 and Bituminous Wearing Course ID-2, RPS.
E. 
Section 421: Bituminous Binder Course ID-2 and Bituminous Binder Course ID-2, RPS.
F. 
Section 460: Bituminous Tack Coat.
G. 
Section 491: Milling of Bituminous Pavement Surface.
H. 
Section 630: Plain Cement Concrete Club.
I. 
Section 641: Plain Cement Concrete Curb Gutter.
J. 
Section 653: Paved Should, Type 3.
K. 
Section 703.3: Select Granular Material.
L. 
Section 802: Topsoil Furnished and Placed.
M. 
Section 804: Seeding and Soil Supplements.
N. 
Section 805: Mulching.
O. 
Section 806: Water Course Erosion Protection.
P. 
Section 962: Painting Traffic Lines and Markings.
2. 
Pennsylvania Department of Transportation Roadways. Repaving of Pennsylvania Department of Transportation (PennDOT) roadways shall be as specified herein and as shown on the contract drawings.
A. 
On all PennDOT roadways, the upper 1 1/2 inches of existing pavement shall be milled in preparation for the overlay pavement in accordance with PennDOT Publication 408 Specifications, Section 491.
B. 
Prior to placement of the overlay pavement, condition the milled surface in accordance with PennDOT Publication 408 Specifications, Section 401.3(f).
C. 
Patch existing pavement to the satisfaction of the Pennsylvania Department of Transportation.
D. 
Repair or replace, to the satisfaction of the utility owner, utility facilities damaged by the milling operation.
E. 
Prior to placing the finished pavement, paint the inside faces of existing curbs and curb and gutter sections with a thin application of asphaltic compound to provide a closely bonded watertight joint.
F. 
Remove all surplus material to the satisfaction of the Township Engineer and PennDOT.
3. 
Logan Township and City of Altoona Roadways. Repaving of Logan Township (and City of Altoona) streets will require conforming to the standards and specifications of each entity that are in effect at the time of construction and do not necessarily follow what roadway material is excavated from the construction area.
4. 
Stabilized Areas. Restoration of stabilized areas shall be completed as detailed on the drawings and as set forth in the contract documents. The contractor is to understand that since the pipe trenches under stabilized areas will be backfilled with PennDOT 2RC select granular material, there will be no payment for restoration of stabilized areas. Contractor shall grade, shape and compact the full width of the stabilized roadway and all other stabilized areas.
5. 
Ninety-Day Temporary Pavement Restoration. Refer to drawings for requirements for ninety-day temporary pavement restoration on Pennsylvania Department of Transportation roadways.
6. 
Prior to placing the bituminous concrete overlay pavement, apply a bituminous tack coat consisting of a thin application of emulsified asphalt at such rate and in such manner as set forth in PennDOT Publication 408 Specifications, Section 460.
7. 
The contractor shall adjust existing shoulders, driveways, street approaches, accesses, businesses, parking areas, etc., to conform to the finished pavement elevation. This work will be considered incidental to the placement of the bituminous wearing course and will not be paid for separately.
8. 
Restoration of driveways, street approaches, sidewalks, parking areas, curbs, curb gutters, etc., shall be replaced "IN KIND," in accordance with PennDOT Standards or as detailed on the drawings and in the contract documents. As a minimum, concrete pavement restoration shall be six inches thick with six by 6 4/4 welded wire fabric reinforcing, and bituminous concrete pavement restoration shall be four inches thick, after proper compaction, PennDOT bituminous concrete base course with a one-inch-thick, after proper compaction, PennDOT bituminous wearing course ID-2, SRL-L. Cement concrete curb and cement concrete curb gutter shall be replaced to the same shame, thickness, workmanship and finish as the original curb or curb gutter unless otherwise required by the Township.
9. 
All pipe trenches under bituminous concrete surfaces and stabilized surfaces shall be backfilled with PennDOT 2RC select granular material. The contractor is to understand that payment for this backfill material will not be made directly but will be considered incidental and subsidiary obligations to the other pay items as set forth in the contract form of proposal.
10. 
Prior to the placement of the permanent pavement, the existing pavement must be concrete saw cut in a neat, straight line, to the bottom elevation of the existing base course, one foot on each side of the trench removed, or the existing pavement shall be removed to the edge of the existing pavement, if so directed by the Township Engineer. No separate payment will be made under this project for removing existing pavement. The contractor must adjust all necessary storm inlets of the Pennsylvania Department of Transportation, Township of Logan and City of Altoona and shall be responsible to coordinate (and bear the cost of, if required) the adjustment of all private and public utilities (valve boxes, curb boxes, manhole covers and cleaned covers) to conform to the finished pavement elevation. No separate payment will be made under this project for adjusting the height of storm inlets and utility boxes.
11. 
All joints between the new pavement and existing pavement, between curbs (curb gutters) and new pavement and around storm inlets, valve boxes, curb boxes, manhole covers and cleaned covers shall be sealed with a hot bituminous material of the class and type designated for the wearing course. The hot bituminous material shall have a minimum width of 12 inches at the joints and shall extend 12 inches from the curb (curb gutters), storm inlets, valve boxes, curb boxes, manhole covers and cleanout covers. Prior to sealing, clean and free harmful material from the area to be sealed.
12. 
The contractor shall perform temporary restoration of trenched areas immediately upon satisfactory completion of laying and backfilling of the sewer pipe in order to return all roadways to a condition that will permit safe, free and unobstructed movement of vehicular and pedestrian traffic. Failure of the contractor to comply with this requirement will constitute sufficient cause of the Township to order an immediate stoppage of all construction work until trench restoration requirements are completed to the satisfaction of the Township.
13. 
Dust Control. The contractor shall provide effective dust control during the entire project. Dust control shall be accomplished by the use of water or calcium chloride or by other methods approved by the Township.
The contractor shall be required to make the connections between existing sewer laterals, sewer mains and manholes owned by the Township or any other municipal entity. The construction of each connection shall be completed in strict conformance with the drawings and the requirements of the applicable public entity. The contractor shall furnish all pipe, fittings, couplings, adapters and other materials necessary to make the connections. The contractor shall take all necessary precautions and provide the necessary plant, labor, materials, and equipment to prevent interruption of the flow in the existing sewers. The contractor shall be responsible for and shall correct, to the satisfaction of the public entity and the owner, any and all damages to the existing manhole sewage treatment plant and sewer lines caused by the contractor's operations. All pipe and fittings shall be as specified herein for sanitary sewer pipe and laterals.
When required by Chapter 18 of the Logan Township Code of Ordinances, the installation of a water meter upon the portable water sources must meet the Altoona Water Authority Specifications as amended from time to time.
Prior to final acceptance of any sanitary sewer extension by the Township, the developer shall furnish to the Township "as-built plans" showing the angle and distance between manholes, the top and invert elevation of each manhole and the exact location of all sewer lateral connections relative to the nearest manhole both downstream and upstream, including the depth at lateral end.