Exciting enhancements are coming soon to eCode360! Learn more 🡪
Village of Bronxville, NY
Westchester County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[HISTORY: Adopted by the Board of Trustees of the Village of Bronxville 2-9-1981 as Ch. 29 of the 1981 Code. Amendments noted where applicable.]
GENERAL REFERENCES
Building construction — See Ch. 112.
Fire prevention — See Ch. 150.
Plumbers and electricians — See Ch. 222.
This chapter shall be known and may be cited as the "Oil Burner Code of the Village of Bronxville, New York."
As used in this chapter, the following terms shall have the meanings indicated:
APPROVED
Applied to equipment, accessories, etc., means approved by or in compliance with the requirements of the National Board of Fire Underwriters and the Underwriters' Laboratories.
OIL BURNER EQUIPMENT
Comprehending oil burners and equipment connected thereto for heating buildings or water or for generating power in the village and to the use thereof.
No person shall install, remodel or cause to permit to be installed or remodeled any oil burning equipment, or any tank for the storage of fuel oil, in the village without having first obtained a permit to do so from the Superintendent of Buildings.
The application for the permit required by the preceding section shall contain complete information as the Superintendent of Buildings shall require and shall be filed in triplicate with the required fee. Upon the issuance of the permit by the Superintendent of Buildings, a copy thereof shall be transmitted to the Eastchester Fire Department.
[Amended 6-13-1988 by L.L. No. 7-1988; 3-13-1989 by L.L. No. 4-1989]
The fee for the permit for each burner equipment required by § 200-3 shall be as established by resolution of the Board of Trustees and shall not be refunded if the permit is refused.
A. 
All oil burner equipment installed in the village shall be of approved type and shall be installed and used subject to the limitations of the approval, and of this chapter.
B. 
Semiautomatic and manually operated burners shall be used only where a paid attendant is continuously in attendance during the entire period of operation.
A. 
Electric supply for any burner shall be through an approved safety switch located at the entrance to the room where the burner is located. In the case of all buildings, other than single family dwellings, one means for completely shutting off the electric supply shall be located at an exterior door designated by the Eastchester Fire Department.
B. 
Automatically operated oil burners shall be equipped with approved automatic devices to shut down the burner in the event of undue pressure in a steam boiler or overheating within a hot water boiler or warm air furnace, and in any event on failure of ignition. Oil burners used in connection with steam, water or vapor heating systems shall be equipped with an approved automatic device for shutting down the burner in the event of low water in the boiler.
C. 
Limiting controls and low water shutoffs intended to disconnect the burner from the electric power supply shall be connected into the burner supply circuit on the supply side of all other burner circuits.
D. 
In systems where either steam or air pressure is used for atomizing the oil, the oil and atomizing supply shall be interlocked in an approved manner so that in case of interruption of the atomizing supply, the oil supply will be immediately shutoff.
A. 
Oil burner equipment shall be securely installed in a workmanlike manner, in accordance with the instructions of the manufacturer, by qualified mechanics experienced in making such installations.
B. 
Where oil burners are installed in furnaces originally designed for solid fuel, the ash door of the furnace shall be removed or bottom ventilation otherwise provided to prevent the accumulation of vapors in the ash pit unless the burner is of a type which mechanically purges the ash pit. The sides of the fire box shall be lined with refractory brick set in fire clay. The water and steam carrying portions of the furnace shall be capable of withstanding a minimum hydrostatic pressure of 50 pounds per square inch, the crown plate shall be in serviceable condition and the feed door shall be securely closed. Where the conversion is made in a gravity hot air furnace, the furnace shall first be disassembled and reassembled in order to make all joints gastight.
C. 
Boilers and furnaces in which oil burners are installed shall be connected to flues having sufficient draft at all times to assure safe operation of the burner. No smoke pipe dampers shall be used but where desirable a draft balancing device may be installed.
D. 
Complete instructions for the care and operation of the oil burning equipment shall be conspicuously posted by the owner near the oil burner and maintained in readable condition.
E. 
At least one approved foam-type fire extinguisher shall be mounted and maintained in operating condition, in a position adjacent to the entrance to the room or space in which the burner is located.
A. 
All tanks, either within a building or outside of a building, for the supply of fuel to oil burner equipment shall be buried as provided in Subdivision B in the ground except as permitted in Subdivision C.
B. 
Inside tanks shall be considered to be sufficiently buried if completely surrounded by sand or well-tamped earth for a distance of one foot in all directions, retained by masonry walls at least eight inches thick and covered over with concrete not less than four inches thick and so constructed as to make it impossible for any tank leakage to escape through such surrounding medium into the compartment containing the burner.
C. 
Where unburied inside tanks are permitted, one unburied tank not exceeding 275 gallons capacity may be located in the lowest story of a building if not within seven feet of any flame or five feet when shielded by a masonry wall at least eight inches in thickness or by an equivalent barrier, and provided that any tank leakage is effectively prevented from approaching the burner or flame.
D. 
No tank whether exposed or buried or enclosed shall be installed within the walls of any frame building housing three or more families.
A. 
In frame buildings housing not more than two families, an inside tank shall not be of greater capacity than 550 gallons and not more than one such tank shall be installed.
B. 
In fire resistive buildings, an inside tank shall be of not more than 10,000 gallons capacity and in other buildings shall not exceed 5,000 gallons.
C. 
Every tank shall bear the Underwriters' Laboratories label, and no tank greater than 275 gallons shall have a gravity outlet.
D. 
Pressure tanks are prohibited.
All tanks shall be constructed of steel or wrought iron of a minimum gauge (U.S. Standard) in accordance with the following table:
Capacity
(gallons)
Minimum Thickness
Wgt. Lb. per sq. ft.
7 to 560
14 gauge
3.125
561 to 1,100
12 gauge
4.375
1,101 to 4,000
7 gauge
7.50
4,001 to 10,000 1/4 inch
(nominal)
10.00
All tanks shall be equipped with an open vent entirely separate from any other tank connected and visible from the fill point, and the vent shall be not less than 1 1/4 inches pipe size, extending to the open air without a trap, and terminating in a flame, excluding the hood which shall be located not less than two feet above the ground, and not more than 12 feet above the tank. The vent pipe connection shall not extend more than one inch inside the tank.
All tanks shall be filled only through fill pipes terminating at least five feet from the building and closed tight, when not in use, by a metal cover.
Auxiliary tanks inside the building shall be filled only by an enclosed pump from a storage tank, shall have an overflow pipe one size larger than supply pipe returning to the storage tank with no valves or obstructions. No auxiliary tank or other device shall have any opening by which oil or vapors can enter the burner room or compartment except to the burner itself.
Where tanks are required to be buried, they shall be covered by at least one foot of earth, and where unusual external pressures are likely in the opinion of the Superintendent of Buildings, they shall be more deeply buried or else be further protected by a reinforced concrete slab of dimensions in his or her opinion adequate for the situation.
Any fuel oil tank buried or installed at such level that the liquid level therein may at any time be or rise above the burner oil nozzle, or any other oil outlet inside the building, shall be equipped with approved means for automatically preventing flow of oil in the vent of failure of the normal functioning of the burner, and shall be further equipped with a heat operated valve for shutting off the flow of oil to the burner, or with a manual valve for shutting off the flow of oil to the burner which is accessible for operation without entering the room or compartment in which the burner is located. No tank-installed at the level herein referred to shall exceed a capacity of 275 gallons unless both the heat operated and manual valves are supplied and the latter is located outside the building and conspicuously marked "Fuel oil shutoff."
A. 
Oil pumps shall be of an approved type, secure against leaks and shall be rigidly fastened in place.
B. 
Automatic pumps not an integral part of the burner shall be arranged to stop the flow of oil automatically in case of breakage of the supply line to the burner.
A. 
Test wells shall not be installed or permitted inside buildings and where permitted for outside service shall be closed tight, when not in use, by a metal cover. The gauging of inside tanks by means of measuring sticks is prohibited.
B. 
Liquid level indicators or signals shall be so constructed that neither oil nor vapor can be discharged from the tank into the building while filling or in any other circumstance.
All piping shall be standard full weight wrought iron or steel pipe or equivalent copper tubing with standard fittings, not smaller than one-half-inch iron pipe size, rigidly secured in place and adequately protected from heat and from mechanical injury by burying underground or in another approved manner. It shall be made up with shellacked or equivalent joints and ground joint unions with due allowance for expansion and settlement and so far as possible shall pitch toward the tank. Oil supply lines to burners shall be provided with approved strainers unless a strainer is incorporated in the burner.
All valves shall be of an approved type. Where any valve is installed in the discharge line of an oil pump, an approved pressure relief passage shall be connected into the discharge line between the pump and the valve and arranged to return surplus oil to the storage tank or to by pass it around the pump.
After installation and before being covered, the contractor shall test, in the presence of a representative of the Eastchester Fire Department, the tanks and piping hydrostatically or pneumatically at a pressure not less than 1 1/2 times the maximum working pressure but not less than 10 pounds per square inch at the highest point of the system. In order to be acceptable, the test shall continue for a period of 30 minutes without noticeable drop in pressure. The system shall not be placed in operation until after such test and the filing of the certificate of completion required by § 200-25.
No fuel oil shall be used other than the grade and type for which the burner has been approved by the Underwriters' Laboratories.
No electric wiring or equipment in connection with oil burning equipment shall be installed except in accordance with the requirements of the New York Board of Fire Underwriters.
As to any pertinent matter or situation connected with the subject matter of this chapter and upon which the chapter is silent, the Superintendent of Buildings shall have the power to promulgate and file in the Building Department such rules and regulations consistent with the regulations of the National Board of Fire Underwriters as are in his or her opinion advisable, and thereupon and thereafter and on approval by the Board of Trustees, such rules and regulations shall have the same force and effect as if herein set forth in full. When the circumstances or conditions of any particular installation are so unusual as to render the strict application of this chapter impracticable and where the circumstances and conditions are stated in the application for permit, the Superintendent of Buildings and the Eastchester Fire Department, acting jointly, may permit such modifications as will provide a substantially equivalent degree of safety, subject to approval of the Board of Trustees.
A. 
As soon as any installation has passed the inspection of the Eastchester Fire Department, the Superintendent of Buildings shall immediately issue a certificate of approval to the permit holder or owner, as the case may be.
B. 
No installation shall be placed in serve until such certificate has been issued, nor continued in service unless such certificate or a duplicate copy thereof is fastened to the wall of the room in which the oil burner is located.
All of the provisions and requirements of this chapter and the prohibitions therein contained shall apply to oil burning equipment installed before July 11, 1949, and the use thereof, except the provisions for permits and the issuance of certificates of completion.
A. 
The Superintendent of Buildings or the representative of the Eastchester Fire Department shall have the right to inspect any oil burner equipment in any premises for the purpose of ascertaining that the installation and maintenance and operation thereof comply with the requirements of this chapter. In the event of noncompliance, tending in his or her opinion to make a fire hazard, the Superintendent of Buildings shall have the right to revoke any certificate of occupancy outstanding with respect to such premises, and in the event that no such certificate is outstanding, he or she shall have the right to stop the operation of the equipment.
B. 
The provisions of § 112-17 of Chapter 112, Building Construction, of this Code shall be followed in making inspections.
Any person violating any of the provisions of this chapter shall, upon conviction thereof, be subject to a fine of not more than $250 or to imprisonment for not more than 15 days, or to both such fine and imprisonment.
[1]
Editor's Note: Amended at time of adoption of Code (see Ch. 1, General Provisions, Art. I).