All utility connections, including but not limited to electrical,
telephone and gas connections, shall be located underground.
Mobile home parks shall be furnished with lighting units so
spaced and at such heights to provide illumination for safe pedestrian
and vehicular movement at night.
A. In all parts of the mobile home park road system, an average illumination
level of at least 0.8 footcandle and a minimum illumination level
of at least 0.3 footcandle shall be maintained.
B. Potentially hazardous locations shall be individually illuminated
with a minimum level of at least 1.0 footcandle where deemed necessary
by the Town Board.
[Amended 9-23-2004 by L.L. No. 7-2004]
Each mobile home site provided with piped gas shall have an
approved manual shutoff valve installed upstream of the gas outlet.
The outlet shall be equipped with an approved cap and locking device
to prevent accidental discharge of gas when the outlet is not in use.
All service structures, if not conventionally heated, shall
be provided with space heating equipment adequate to maintain a temperature
of 70° F. inside the building at an outside design condition of
-10° F., and such space heating equipment shall be subject to
the approval of the Building Inspector.
A. No space heating equipment or portable fuel-burning equipment shall
be used in any unvented, confined enclosure.
B. In all service buildings, heating facilities shall be capable of
maintaining sufficient hot water for all lavatory and laundry fixtures.