Exciting enhancements are coming soon to eCode360! Learn more 🡪
Village of Great Neck Plaza, NY
Nassau County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[Adopted 12-17-1974 as L.L. No. 10-1974]
Fire regulations are formulated by the Nassau County Fire Commission. The Board of Trustees of the Village of Great Neck Plaza believes that it would be in the best interests of its residents to exercise its police power by adopting these regulations so that there may be local enforcement of these regulations.
As used in this Article, the following terms shall have the meanings indicated:
EATING PLACE
Any restaurant, banquet hall, cafeteria, coffee shop, diner or other place where food is served.
PUBLIC ASSEMBLY
Any place where persons may assemble for civic, political, religious, social, recreational, educational or other purposes.
The following regulations are applicable to all public assembly and/or eating places.
Where a certificate of compliance showing the permissible capacity is issued by the village, it must be conspicuously posted and readily available to the fire inspector. Where no such certificate is issued or available, the capacity of the premises shall be based on one person per 15 square feet of floor space seated at tables or booths of the dining area and one person per three square feet of floor space standing, or six square feet seated at bars or counters.
The number of exits shall be as follows:
Number of Persons
Minimum Number of Exits
300 or fewer
2
301 to 600
3
601 to 1,200
4
[1]
Editor's Note: Amended at time of adoption of Code; see Chapter 1, General Provisions, Article I.
A. 
Exits must be as remote from each other as possible.
B. 
On the grade floor, the distance to any exit shall not exceed 100 feet for buildings erected on and after July 1, 1957; before July 1, 1957, 125 feet. Where the New York State Uniform Fire Prevention and Building Code applies, 150 feet if unsprinklered and 200 feet if sprinklered.
C. 
Above and below the grade floor, the distance to any exit shall not exceed 100 feet if unsprinklered and 150 feet if sprinklered.
The number and width of doors and stairways shall be determined by the capacity of the places, floors or tiers they serve.
A. 
No single exit door shall be less than 40 inches in width in new construction or 36 inches in existing construction, except that individual doors in double doors or banks of doors shall be not less than 24 inches in width in new construction and 22 inches in existing construction.
B. 
The capacity of doorways shall be based on 50 people per foot of door width.
C. 
Only 50% of width of main entrance door or doors may be used in figuring capacity.
A. 
No stairway shall be less than 44 inches in width in new construction and 36 inches in existing construction.
B. 
The capacity of stairways shall be based on 60 people for each 22 inches of width in new construction and 50 people per foot in existing construction.
Every door serving as a means of exit shall swing in the direction of egress.
No exit door shall be locked, bolted or otherwise fastened, except by locking devices approved by the Fire Marshal. When the premises are occupied, the door must be openable from the inside by pressure on the door or on an approved panic release device.
No aisle shall be less than 36 inches in width. Aisles leading to an exit shall be equal in width to the exit (except in theaters and schools).
Required exits shall not lead through a kitchen, serving pantry, boiler room, storage room or other place of similar hazard.
A. 
A clear and unobstructed passageway leading to a street or open area, passage or court shall be provided.
B. 
The exterior of exits and exitways shall be provided with illumination providing a light intensity of five-tenths (0.5) footcandle or more, while the premises are occupied after dark.
Internally illuminated exit signs shall be provided over all exit doors or equivalent opening forming part of an exit. Lighted directional signs shall be provided, as required. All signs shall have letters at least six inches in height.
No source of illumination shall be provided, except electricity. Decorative candles may be used on dining tables when enclosed in stable, hurricane-type holders.
Automatic emergency lighting must be provided to light all exits, stairways and passageways, as designated by the Fire Marshal.
A. 
Basement storage will only be permitted in rooms of one-hour fire resistance rating, with Underwriters' Laboratories labeled Class C self-closing fire doors and fire door assemblies.
B. 
All basement ceilings must have a one-hour minimum rating.
C. 
No storage will be permitted around or under any stairs.
A. 
In new construction, stairs from basement to first floor must be fully enclosed by fire-resistive partitions, one-hour minimum rating, with Underwriters' Laboratories labeled Class C self-closing fire doors and assemblies at top and bottom.
B. 
In existing buildings where the basement ceiling is fire-retarded, as provided in No. 18, an Underwriters' Laboratories labeled Class C self-closing fire door and assembly at the head or foot of the stairs may be accepted at the discretion of the Fire Marshal.
A. 
Central heating plants in new construction must be in a room of fire-resistive material, two-hour minimum rating, with Underwriters' Laboratories labeled Class B self-closing fire door and assembly. In existing construction, one-hour rating and Class C door will be accepted.
B. 
Adequate air supply and ventilation for heating plant must be obtained directly from outside.
C. 
Overhead oil- or gas-fired heaters may be used when installed in accordance with national standards and where approved by the Fire Marshal.
D. 
No portable space heaters will be permitted.
A. 
All combustible curtains, drapes and/or decorations shall be rendered flameproof, and a certificate shall be kept readily available for the inspector, showing the date of flameproofing, life of the flameproofing and by whom flameproofing was done.
B. 
In existing buildings, all combustible ceilings, walls and woodwork shall be replaced, covered or treated with a fire-retardant coating satisfactory to the Fire Marshal.
A. 
All gas meters and regulating equipment shall be located outside the building.
B. 
In existing buildings, meters and equipment may be enclosed in a fire-resistive room used for no other purpose, and ventilated directly to the outside, at the discretion of the Fire Marshal.
Underwriters' Laboratories approved fire extinguishers shall be provided, as required by the Fire Marshal. Fifteen-pound CO2 or equivalent dry powder extinguishers will be required for boiler rooms; ten-pound CO2 or equivalent dry powder extinguishers for kitchens; and two-and-one-half-gallon water-type extinguishers for other areas.
No place of public assembly shall be permitted in a building any part of which is used for a hazardous occupancy such as, but not limited to:
A. 
The storage or handling of explosives.
B. 
The storage or sale of paints in bulk.
C. 
Service stations or garages.
D. 
Dry-cleaning plants using Class II or Class III liquids.
No Class I or Class II flammable liquids shall be kept or stored on the premises.
A. 
Kitchens and serving pantries must be cut off from the remainder of the premises with fire-resistive walls and ceilings of two-hour minimum rating in new construction and one-hour for existing construction.
B. 
Door openings between kitchens and/or pantries and the dining rooms they serve shall be protected by Underwriters' Laboratories labeled Class B self-closing fire doors and assemblies in new construction and Class C in existing construction.
C. 
Serving counter openings must be protected by automatic two-hour rated, self-closing doors in new construction and one-hour in existing construction or by automatic sprinklers.
D. 
If kitchens and pantries are protected by an automatic sprinkler system, fire resistance rating of walls and ceilings may be reduced to one hour and doors to Class C in new construction.
E. 
View panels will be permitted in fire doors, provided that they are protected by one-fourth-inch clear wire glass of not more than 100 square inches in area in Class B doors and not more than 1,296 square inches in Class C doors.
A. 
Range hoods must comply with Pamphlet No. 96 National Fire Protection Association.
B. 
Hoods equal to the length and breadth of the ranges and cooking equipment shall be provided. They shall be not more than seven feet above the floor and shall not be within 18 inches of any combustible material. Where 18 inches clearance is required to unprotected combustible material, the clearance may be reduced to that indicated below when the combustible material is protected as follows:
Type of Protection
Clearance
(inches)
1/4-inch asbestos millboard spaced out 1 inch on noncombustible spacers
12
28-gauge sheet metal on 1/4-inch asbestos millboard
12
28-gauge sheet metal spaced out 1 inch on noncombustible spacers
9
28-gauge sheet metal on 1/8-inch asbestos millboard spaced out 1 inch on noncombustible spacers
19
l/4-inch asbestos millboard on 1-inch mineral wool bats reinforced with wire mesh or equivalent
6
22-gauge sheet metal on 1-inch mineral wool bats reinforced with wire mesh or equivalent
3
NOTES:
1 Asbestos millboard referred to above is a different material than asbestos cementboard. It is not intended that asbestos cementboard be used in complying with these requirements.
C. 
"Combustible material" as pertaining to materials adjacent to or in contact with heat-producing appliances, chimneys, chimney connectors, vents, vent connectors, steam and hot-water pipes, warm-air ducts, grease ducts and rubbish chutes means material made of or surfaced with wood, compressed paper, plant fibers or other material that will ignite and burn. Such material shall be considered as combustible even though flameproofed, fire-retardant treated or plastered.
D. 
Hoods shall be provided with mechanical exhaust ducts, which shall be connected to an independent chimney or stack, insulated from contact with combustible material and terminating above the roof.
E. 
All hood and duct seams and joints shall have a liquidtight external weld.
F. 
Exhaust ducts must be provided with an adequate number of access doors for easy inspection and cleaning.
G. 
Hoods, ducts, chimneys and stacks must be cleaned as often as may be necessary, but not less than twice a year. A record shall be kept available for the inspector, showing date of cleaning and by whom cleaned.
H. 
Electric wiring under hoods shall be in conduit, and all fixtures shall be vaporproof.
A. 
An automatic fire-extinguishing system must be installed to protect hoods, ducts, chimneys, stacks, deep fat fryers and broilers. Range top protection is also required and all systems must be installed in accordance with the National Fire Protection Association Standard No. 96. Special engineered systems may be used if approved by the Fire Marshal.
B. 
All gas-operated equipment in the kitchen shall be provided with an automatic shutoff device activated by the extinguishing system. The shutoff device must be designed so that it can only be reset manually. Operation of this valve shall not interrupt the supply of gas to any other areas in the building. A metal tag shall be affixed to the cylinder giving the location of the shutoff valve.
C. 
Automatic shutoff devices shall also be provided for electric deep fat fryers, ranges and griddles. New electric deep fat fryers shall be equipped with a separate high limit control in addition to the adjustable operating control (thermostat) to shut off fuel or energy in the event that fat exceeds a temperature of 425° F.
D. 
Carbon dioxide (CO2) systems shall be equipped with an automatic exhaust fan shutoff device activated by the extinguishing system.
E. 
Exhaust fans must remain on when dry chemical systems are activated.
F. 
Plans for automatic extinguishing systems and shutoff devices must be submitted to the Nassau County Fire Marshal for approval prior to installation.
G. 
Automatic extinguishing systems shall be inspected every six months by a qualified person engaged in such work. A tag attesting to this inspection shall be affixed to the supply cylinder of the system, showing the date and by whom the work was performed.
Properly rated BC extinguishers shall be provided, as required by the Fire Marshal (minimum 20 BC rating).
A. 
All new automatic extinguishing system installations must comply with all of the above regulations.
B. 
Any alterations, additional or modifications to existing automatic extinguishing system installations will necessitate full compliance with § 114-3 above.
C. 
It shall be the responsibility of the owner or operator of the business and the authorized installer to complete the installation in compliance with the manufacturer's specifications and the requirements of the Fire Marshal's Office.
The Chief Fire Inspector of the village as well as those fire inspectors operating under his supervision shall have the power to enforce the provisions of this Article.
Any person who violates a provision of this Article shall be liable to pay a penalty not to exceed $250 or imprisoned for a period not exceeding 15 days, or both, for each day that said violation continues.
[1]
Editor's Note: Amended at time of adoption of Code; see Ch. 1, General Provisions, Art. I.