A.
Vertical piping shall be secured at sufficiently close intervals to keep the pipe in alignment and to carry the weight of the pipe and contents.
B.
Supports shall provide secure support for the pipe without excessive strain on joints or connections and shall properly transmit the load to the building structure or to independent posts, piers and foundations.
C.
All vertical drainage piping shall have base supports and, when more than 30 feet in height, shall have intermediate supports spaced not more than two stories or 25 feet on centers, except for no-hub cast-iron soil pipe.
(1)
No-hub cast-iron soil pipe shall be supported with a riser clamp located at each floor. When the distance between floors is greater than 10 feet, the vertical piping shall be supported every 10 feet using riser clamps, where possible, or ridged supports securely fastened to the building structure.
(2)
Closet bends, traps, trap arms and similar branches must be firmly secured against movement in any direction.
D.
Building drains shall not be installed or arranged so as to support load from vertical piping. Pipe supports shall be of approved type. Pipe hooks shall not be used.
E.
ABS and PVC plastic pipe shall be supported and contained every five feet.