[Res. No. 129-92, § 2, 8-25-1992]
The following words, terms and phrases, when used in this article, shall have the meanings ascribed to them in this section, except where the context clearly indicates a different meaning:
ACCEPTABLE BACKFLOW PREVENTION DEVICE
An acceptable reduced pressure zone device or double check valve assembly as used to contain potential contamination within a facility. In order for the reduced pressure zone device or the double check valve assembly to be acceptable, it must be listed on the most current version of the state department of health list of acceptable devices.
AESTHETICALLY OBJECTIONABLE FACILITY
A facility in which substances are present which, if introduced into the public water supply system, could be a nuisance to other water customers but would not adversely affect human health. Typical examples of such substances are: food-grade dyes, hot water, stagnant water from fire lines in which no chemical additives are used, etc.
APPROVED
Accepted by the director of public works as meeting an applicable specification stated or cited in this article, or as suitable for the proposed use.
AUXILIARY WATER SUPPLY
Any water supply on or available to the premises other than the approved public water supply. These auxiliary waters may include water from another purveyor's public potable water supply or any natural source such as a well, spring, river, stream, harbor, etc., or used waters. These waters may be contaminated or they may be objectionable and constitute an unacceptable water source over which the water purveyor does not have sanitary control.
BACKFLOW
A flow condition induced by a differential in pressure that causes the flow of water or other liquids and/or gases into the distribution pipes of the supply system any source other than its intended source.
CERTIFIED TESTER
That individual or firm approved to accomplish the necessary inspections and operational tests of backflow prevention devices.
CONTAMINATION
The presence in water of a substance that tends to degrade its quality.
CUSTOMER
A water user served by the supply system.
CUSTOMER'S WATER SYSTEM
The piping used to convey water supplied by the City supply system throughout a customer's facility. The customer's water system shall include all those parts of the piping beyond the control point of the customer's service. The control point is either the curb valve or the main valve located in the public right-of-way that isolates the customer's facilities from the city distribution system.
DEGREE OF HAZARD
Whether a facility is rated as hazardous, aesthetically objectionable or nonhazardous.
DIRECTOR
The director of public works.
DOUBLE CHECK VALVE ASSEMBLY, ACCEPTABLE
An assembly composed of two single, independently acting check valves, including tightly closing shutoff valves located at each end of the assembly and suitable connections for testing the water tightness of each check valve.
HAZARDOUS FACILITY
Is one in which substances may be present which if introduced into the public water system would or may endanger or have an adverse effect on the health of other water customers. Typical examples are laboratories, sewage treatment plants, chemical plants, hospitals and mortuaries.
NONHAZARDOUS FACILITY
Is one which does not require the installation of an acceptable backflow prevention device.
PUBLIC WATER SUPPLY SYSTEM
The city system including the source, treatment works, transmission mains, distribution system and storage facilities. This includes the distribution system up to its connection with the customer's water system.
REDUCED PRESSURE ZONE DEVICE, ACCEPTABLE
A device containing a minimum of two independently acting check valves, together with an automatically operated pressure differential relief valve located between two check valves. During the normal flow and at the cessation of normal flow the pressure between these two checks shall be less than the upstream (supply) pressure. In case of leakage of either check valve, the differential relief valve, by discharging to the atmosphere, shall operate to maintain the pressure. The unit must include tightly closing shutoff valves located at each end of the device, and each device shall be fitted with properly located test cocks.
[Res. No. 129-92, § 1, 8-25-1992]
The purpose of this article is to:
(1) 
Protect the public potable water supply of the city from the possibility of contamination by isolating within its customers' internal distribution systems or its customers' private water systems such contaminations or pollutants which could backflow into the public water supply system; and
(2) 
To comply with the requirements of the New York State Sanitary Code § 5-1.31.
[Res. No. 129-92, § 1.2, 8-25-1992]
The director of public works shall be responsible for the protection of the city distribution system from contamination due to the backflow of contaminants through the water service connection. If, in the judgment of the director, an acceptable backflow prevention device is required at the city's water service connection to any customer's premises for the safety of the water system, the director shall give notice in writing to the customer to install such an acceptable backflow prevention device at each service connection to the premises. The customer shall immediately install such approved device or devices at the customer's own expense; and failure, refusal or inability on the part of the customer to install the device or devices immediately shall constitute a ground for discontinuing water service to the premises until such device or devices have been properly installed.
[Res. No. 129-92, § 3, 8-25-1992]
(a) 
The customer's water system shall be open for inspection at all reasonable times to authorized representatives of the city.
(b) 
The director shall rate a customer's water system according to its degree of hazard to the public water supply system.
(c) 
An acceptable backflow prevention device shall be installed on each service line to a customer's water system at or near the property line or immediately inside the building being served, but in all cases before the first branch line leading off the service line, as follows:
(1) 
Whenever a customer's water system is rated hazardous, an acceptable reduced pressure zone device shall be installed.
(2) 
Whenever a customer's water system is rated aesthetically objectionable, as a minimum, an acceptable double check valve assembly shall be installed.
(d) 
The design of the installation of an acceptable backflow prevention device must be prepared in accordance with state laws and regulations. The design must be approved by the director and all agencies required by the applicable state laws and regulations.
(e) 
It shall be the duty of the customer at any premises where backflow prevention devices are installed to have certified inspections and operational tests made at least once a year. In those instances where the director deems the hazard to be great enough, he may require certified inspections at more frequent intervals. Certified inspections and operational tests must also be made when any backflow prevention device is to be installed, repaired, overhauled or replaced, in addition to the requirement of an annual certified inspection and operational test. All inspections and tests shall be at the expense of the customer and shall be performed by the device manufacturer's representative, or by a certified tester approved by the state department of health. It shall be the duty of the director to see that certified inspections and operational tests of the backflow prevention devices are made. These devices shall be repaired, overhauled or replaced at the expense of the customer whenever the devices are found to be defective. Records of such test, repairs and overhaul shall be kept and also made available to the director. Copies of all testing and maintenance records shall be sent to the director immediately after the work is performed.
(f) 
All presently installed prevention devices which do not meet the requirements of this section but were approved devices for the purposes described in this section at the time of installation and which have been properly maintained, shall, except for the inspection and maintenance requirements under subsection (e) of this section, be excluded from the requirements of these rules so long as the director is assured that they will satisfactorily protect the utility system. Whenever the existing device is moved from the present location or requires more than minimum maintenance, or the director deems it constitutes a hazard to health, the unit shall be replaced by a backflow prevention device meeting the requirements of this section.
(g) 
No water service connection to any customer's water system shall be installed unless the water supply is protected as required by state laws and regulations and this article. Service of water to any premises shall be discontinued by the city if a backflow prevention device required by this chapter is not installed, tested or maintained, or if it is found that a backflow prevention device has been removed or bypassed. Service will not be restored until such conditions or defects are corrected.
[Res. No. 129-92, § 4, 8-25-1992]
(a) 
In accordance with Sanitary Code § 5-1.31, all users of a public water system shall prevent cross connections between the potable water piping system and any other piping system within the customer's premises. The plumbing inspector shall direct customers to make necessary modifications to internal plumbing systems whenever protection of potability of water within the premises against water quality degradation is required.
(b) 
Where a residential customer maintains an auxiliary water supply in addition to the public water supply, the two systems must not be interconnected. Where the two systems are interconnected, the following options will be deemed appropriate and within the requirements of existing state laws and regulations and with this article:
(1) 
Disconnection of the auxiliary water supply from the public water supply. An inspection to determine compliance will be made initially and at least every three years thereafter or whenever the property is sold. The inspection may be made by the water supplier or the local building codes inspector.
(2) 
Installation of an acceptable reduced pressure zone (RPZ) device on the public water supply connection.
(3) 
Proper abandonment of the auxiliary water supply.
(4) 
Sampling for the auxiliary water supply to determine quality in accordance with New York State Sanitary Code §§ 5-1.50 and 5-1.51. Sampling frequency will be specified by the state or local health department. Where water quality does not meet the standards, one of the first three alternatives would apply.
[Res. No. 129-92, § 6, 8-25-1992]
In addition to any other remedy provided by this article at law or in equity, the director of public works may order disconnection of water service at the service entrance for the affected premises.