[Ord. No. 972 §§1
— 2, 2-21-2012]
A. Purpose. The purpose of this Article is:
1. To protect the public potable water supply from contamination or
pollution by containing within the consumer's internal distribution
system or private water system contaminants or pollutants which could
backflow through the service connection into the public potable water
supply system.
2. To promote the elimination, containment, isolation or control of
existing cross-connections, actual or potential, between the public
or consumer's potable water system and non-potable water system, plumbing
fixtures, and industrial-process systems.
3. To provide for the maintenance of a continuing program of cross-connection
control which will systematically and effectively prevent the contamination
or pollution of all potable water systems.
B. Application. This Article shall apply to all premises served
by the public potable water system of the City of Concordia, Missouri.
C. Policy.
1. This Article will be reasonably interpreted by the Water Purveyor.
It is the Water Purveyor's intent to recognize the varying degrees
of hazard to apply the principle that the degree of protection shall
be commensurate with the degree of hazard.
2. The Water Purveyor shall be primarily responsible for protection
of the public potable water distribution system from contamination
or pollution due to backflow or contaminants or pollutants through
the water service connection. The cooperation of all consumers is
required to implement and maintain the program to control cross-connections.
The Water Purveyor and consumer are jointly responsible for preventing
contamination of the water system.
3. If, in the judgment of the Water Purveyor or his/her authorized representative,
cross-connection protection is required through either piping modification
or installation of an approved backflow prevention device, due notice
shall be given to the consumer. The consumer shall immediately comply
by providing the required protection at his/her own expense; and failure,
refusal or inability on the part of the consumer to provide such protection
shall constitute grounds for discontinuing water service to the premises
until such protection has been provided.
[Ord. No. 972 §§1
— 2, 2-21-2012]
The following definitions shall apply in the interpretations
and enforcement of this Article:
AIR-GAP SEPARATION
The unobstructed vertical distance through the free atmosphere
between the lowest opening from any pipe or faucet supplying water
to a tank, plumbing fixture, or other device and the overflow level
rim of the receptacle and shall be at least double the diameter of
the supply pipe measured vertically above the flood level rim of the
vessel, but in no case less than one (1) inch.
AUXILIARY WATER SUPPLY
Any water source or system, other than the public water supply,
that may be available in the building or premises.
BACKFLOW
The flow, other than the intended direction of flow, of any
foreign liquids, gases or substances into the distribution system
of a public water supply.
CONSUMER
The owner or person in control of any premises supplied by
or in any manner connected to a public water system.
CONTAINMENT
Protection of the water supply by installing a cross-connection
control device or air-gap separation on or to the main service line
to a facility.
CONTAMINATION
An impairment of the quality of the water by sewage, process
fluids, or other wastes to a degree which could create an actual hazard
to the public health through poisoning or through spread of disease
by exposure.
CROSS-CONNECTION
Any physical link between a potable water supply and other
substance, fluid or source which makes possible contamination of the
potable water supply due to the reversal of flow of the water in the
piping or distributing system.
HAZARD, DEGREE OF
An evaluation of the potential risk to public health and
the adverse effect of the hazard upon the potable water system.
1.
HAZARD, HEALTHAny condition, device or practice in the water supply system and its operation which could create or may create a danger to the health and well-being of the water consumer.
2.
HAZARD, PLUMBINGA plumbing type cross-connection in a consumer's potable water system that has not been properly protected by a vacuum breaker, air-gap separation or backflow prevention device.
3.
HAZARD, POLLUTIONAn actual or potential threat to the physical properties of the water system or to the potability of the public or the consumer's potable water system but which would constitute a nuisance or be aesthetically objectionable or could cause damage to the system or its appurtenances, but would not be dangerous to health.
4.
HAZARD, SYSTEMAn actual or potential threat of severe damage to the physical properties of the public potable water system or the consumer's potable water system, or of a pollution or contamination which would have a protracted effect on the quality of the potable water in the systems.
INDUSTRIAL PROCESS SYSTEM
Any system containing a fluid or solution which may be chemically,
biologically, or otherwise contaminated or polluted in a form or concentration
such as would constitute a health, system, pollution, or plumbing
hazard if introduced into a potable water supply.
ISOLATION
Protection of a facility service line by installing a cross-connection
device or air-gap separation on an individual fixture, appurtenance
or system.
POLLUTION
The presence of any foreign substance (organic, inorganic
or biological) in water which tends to degrade its quality so as to
constitute a hazard or impair the usefulness of the water to a degree
which does not create an actual hazard to the public health but which
does adversely and unreasonably affect such waters for domestic use.
PUBLIC POTABLE WATER SYSTEM
Any public or privately owned water system supplying water
to the general public which is satisfactory for drinking, culinary,
and domestic purposes and meets the requirements of the Missouri Department
of Natural Resources.
SERVICE CONNECTION
The terminal end of a service line from the public water
system. If a meter is installed at the end of the service, then the
"service connection" means the downstream end of the meter.
WATER CONNECTION
The terminal end of a service line from responsible charge
of a public water system.
[Ord. No. 972 §§1
— 2, 2-21-2012]
A. No
water service connection shall be installed or maintained to any premises
where actual or potential cross-connections to the public potable
or consumer's water system may exist unless such actual or potential
cross-connections are abated or controlled to the satisfaction of
the Water Purveyor and as required by the laws and regulations of
the Missouri Department of Natural Resources.
B. No
connection shall be installed or maintained whereby an auxiliary water
supply may enter a public potable or consumer water system unless
such auxiliary water supply and the method of connection and use of
such supply shall have been approved by the Water Purveyor and the
Missouri Department of Natural Resources.
C. No
water service connection shall be installed or maintained to any premises
in which the plumbing system, facilities and fixtures have not been
constructed and installed using acceptable plumbing practices considered
by the Water Purveyor as necessary for the protection of health and
safety.
[Ord. No. 972 §§1
— 2, 2-21-2012]
A. The
consumer's premises shall be open at all reasonable times to the Water
Purveyor, or his/her authorized representative, for the conduction
of surveys and investigations of water use practices within the consumer's
premises to determine whether there are actual or potential cross-connections
to the consumer's water system through which contaminants or pollutants
could backflow into the public potable water system.
B. On
request by the Water Purveyor or his/her authorized representative,
the consumer shall furnish information on water use practices within
his/her premises.
C. It
shall be the responsibility of the water consumer to conduct periodic
surveys of water use practices on his/her premises to determine whether
there are actual or potential cross-connections to his/her water system
through which contaminants or pollutants could backflow into his/her
or the public potable water system.
[Ord. No. 972 §§1
— 2, 2-21-2012]
A. The
type of protection required by this Article shall depend on the degree
of hazard which exists, as follows:
1. An approved air-gap separation shall be installed where the public
potable water system may be contaminated with substance that could
cause a severe health hazard.
2. An approved air-gap separation or an approved reduced pressure principle
backflow prevention device shall be installed where the public potable
water system may be contaminated with a substance that could cause
a system or health hazard.
3. An approved air-gap separation or an approved reduced pressure principle
backflow prevention device or an approved double-check valve assembly
shall be installed where the public potable water system may be polluted
with substances that could cause a pollution hazard not dangerous
to health.
[Ord. No. 972 §§1
— 2, 2-21-2012]
A. An
approved backflow prevention device shall be installed on each service
line to a consumer's water system serving premises where, in the judgment
of the Water Purveyor or the Missouri Department of Natural Resources,
actual or potential hazards to the public potable water system exist.
The type and degree of protection required shall be commensurate with
the degree of hazard.
B. An
approved air-gap separation or reduced pressure principle backflow
prevention device shall be installed at the service connection or
within any premises where, in the judgment of the Water Purveyor or
the Missouri Department of Natural Resources, the nature and extent
of activities on the premises, or the material used in connection
with the activities, or materials stored on the premises would present
an immediate and dangerous hazard to health should a cross-connection
occur, even though such cross-connection may not exist at the time
the backflow prevention device is required to be installed. This includes,
but is not limited to, the following situations:
1. Premises having auxiliary water supply, unless the quality of the
auxiliary supply is acceptable to the Water Purveyor and the Missouri
Department of Natural Resources.
2. Premises having internal cross-connections that are not correctable
or intricate plumbing arrangements which make it impractical to ascertain
whether or not cross-connections exist.
3. Premises where entry is restricted so that inspection for cross-connections
cannot be made with sufficient frequency or at sufficiently short
notice to assure the cross-connections do not exist.
4. Premises having a repeated history of cross-connections being established
or re-established.
5. Premises which, due to the nature of the enterprise therein, are
subject to recurring modification or expansion.
6. Premises on which any substance is handled under pressure so as to
permit entry into the public water supply, or where a cross-connection
could reasonably be expected to occur. This shall include the handling
of process waters and cooling waters.
7. Premises where materials of a toxic or hazardous nature are handled
such that if back-siphonage or back pressure should occur, a serious
health hazard may result.
C. The
following type of facilities falls into one (1) or more of the categories
of premises where an approved air-gap separation or reduced pressure
principle backflow prevention device is required by the Water Purveyor
and the Missouri Department of Natural Resources to protect the public
water supply and must be installed at these facilities unless all
hazardous or potentially hazardous conditions have been eliminated
or corrected by other methods to the satisfaction of the Water Purveyor
and the Missouri Department of Natural Resources:
1. Aircraft and missile plants.
4. Beverage bottling plants.
5. Canneries, packing houses, and reduction plants.
7. Chemical manufacturing, processing, compounding or treatment plants.
10. Hazardous waste storage and disposal sites.
11. Hospitals, mortuaries, clinics.
12. Irrigation and sprinkler systems.
14. Metal manufacturing, cleaning, processing and fabricating plants.
15. Oil and gas production, storage or transmission properties.
16. Paper and paper products plants.
19. Printing and publishing facilities.
20. Radioactive material processing plants or nuclear reactors.
21. Research and analytical laboratories.
22. Rubber plants, natural and synthetic.
23. Sewage and storm drainage facilities — pumping stations.
24. Waterfront facilities and industries.
[Ord. No. 972 §§1
— 2, 2-21-2012]
A. Any
backflow prevention device required by this Article shall be of a
model or construction approved by the Water Purveyor and the Missouri
Department of Natural Resources.
1. Air-gap separation to be approved shall be at least twice the diameter
of the supply pipe, measured vertically above the top rim of the vessel,
but in no case less than one (1) inch.
2. A double-check valve assembly or a reduced pressure principle backflow
prevention device shall be approved by the Water Purveyor, and shall
appear on the current "list of approved backflow prevention devices"
established by the Missouri Department of Natural Resources.
B. Existing
backflow prevention devices approved by the Water Purveyor at the
time of installation and properly maintained shall, except for inspection
and maintenance requirements, be excluded from the requirements of
this Article so long as the Water Purveyor is assured that they will
satisfactorily protect the water system. Whenever the existing device
is moved from its present location, or requires more than minimum
maintenance, or when the Water Purveyor finds the maintenance constitutes
a hazard to health, the unit shall be replaced by a backflow prevention
device meeting the requirements of this Article.
[Ord. No. 972 §§1
— 2, 2-21-2012]
A. Backflow
prevention devices required by this Article shall be installed at
a location and in a manner approved by the Water Purveyor and shall
be installed at the expense of the water consumer.
B. Backflow
prevention devices installed on the service line to the consumer's
water system shall be located on the consumer's side of the water
meter, as close to the meter as is reasonably practical, and prior
to any other connection.
C. Backflow
prevention devices shall be located so as to be readily accessible
for maintenance and testing, protected from freezing, and where no
part of the device will be submerged or subject to flooding by any
fluid.
[Ord. No. 972 §§1
— 2, 2-21-2012]
A. It
shall be the duty of the consumer at the premises on which backflow
prevention devices required by this Article are installed to have
inspection, tests, and overhauls made in accordance with the following
schedule or more often where conditions indicate a need.
1. Air-gap separations shall be inspected at the time of installation
and at least every twelve (12) months thereafter.
2. Double-check valve assemblies shall be inspected and tested for tightness
at the time of installation and at least every twelve (12) months
thereafter. They shall be dismantled, inspected internally, cleaned
and repaired whenever they fail the test procedures as set forth by
the Missouri Department of Natural Resources.
3. Reduced pressure principle backflow prevention devices shall be inspected
and tested for tightness at the time of installation and at least
every twelve (12) months thereafter. They shall be dismantled, inspected
internally, cleaned and repaired whenever they fail the test procedures
as set forth by the Missouri Department of Natural Resources.
B. Inspections,
tests and overhauls of backflow prevention devices shall be made at
the expense of the water consumer and shall be performed by a State
of Missouri certified backflow prevention device tester.
C. Whenever
backflow prevention devices required by this Article are found to
be defective, they shall be repaired or replaced at the expense of
the consumer without delay.
D. The
water consumer must maintain a complete record of each backflow prevention
device from purchase to retirement. This shall include a comprehensive
listing that includes a record of all tests, inspections and repairs.
Records of inspection, tests, repairs and overhauls shall be made
available to the Water Purveyor upon request.
E. Backflow
prevention devices shall not be bypassed, made inoperative, removed,
or otherwise made ineffective without specific authorization by the
Water Purveyor.
[Ord. No. 972 §§1
— 2, 2-21-2012]
A. The
Water Purveyor shall deny or discontinue, after reasonable notice
to the occupants thereof, the water service to any premises wherein
any backflow prevention device required by this Article is not installed,
tested and maintained in a manner acceptable to the Water Purveyor,
or if it is found that the backflow prevention device has been removed
or bypassed, or if an unprotected cross-connection exists on the premises.
B. Water
service to such premises shall not be restored until the consumer
has corrected or eliminated such conditions or defects in conformance
with this Article to the satisfaction of the Water Purveyor.