[Adopted 8-22-1994 by Ord. No. 499 (Ch. 5, Part 1, of the
1981 Code of Ordinances)]
[Amended 6-8-1998 by Ord. No. 558; 6-28-2004 by Ord. No. 643]
A.
Peters Township hereby elects to administer and enforce the provisions
of the Pennsylvania Construction Code Act, Act 45 of 1999, 35 P.S.
§§ 7210.101 to 7210.1103, as amended from time to time,
and its regulations.
B.
The Uniform Construction Code, contained in 34 Pa. Code, Chapters
401 to 405, as amended from time to time, is hereby adopted and incorporated
herein by reference as the municipal building code of Peters Township.
[Amended 6-8-1998 by Ord. No. 558; 6-28-2004 by Ord. No. 643]
A.
Peters Township Ordinance No. 499, August 22, 1994, amended by Ordinance
No. 558, June 8, 1998, is replaced, with the exception that any existing
provisions exceeding the "Code" are maintained.
C.
Penalties. Any person who violates or permits a violation of this
article shall, upon conviction in a summary proceeding brought before
a Magisterial District Judge under the Pennsylvania Rules of Criminal
Procedure, be guilty of a summary offense and shall be punishable
by a fine of not more than $1,000, plus costs of prosecution. In default
of payment thereof, the defendant may be sentenced to imprisonment
for a term not exceeding 90 days. Each day or portion thereof that
such violation continues or is permitted to continue shall constitute
a separate offense, and each section of this article that is violated
shall also constitute a separate offense.[2]
D.
Existing codes.
(1)
All building code ordinances or portions of ordinances which were
adopted by this Township on or before July 1, 1999, and which equal
or exceed the requirements of the Code shall continue in full force
and effect until such time as such provisions fail to equal or exceed
the minimum requirements of the Code, as amended from time to time.
(2)
All building code ordinances or portions of ordinances which are
in effect as of the effective date of this article and whose requirements
are less than the minimum requirements of the Code are hereby amended
to conform to the comparable provisions of the Code.
(3)
All relevant ordinances, regulations and policies of this Township
not governed by the Code shall remain in full force and effect.
E.
Attachment A of Ordinance No. 499, August 22, 1994, is maintained,
Attachment A reads as follows:
FIRE-PROTECTION SYSTEMS
| |
901.1 Scope: The provisions of this article shall
specify where fire-protection systems are required and shall apply
to the design, installation, maintenance and operation of all fire-protection
systems in all buildings and structures.
| |
901.2 Required Systems: All fire-protection systems
required by this code shall be installed, repaired, operated and maintained
in accordance with this code and the fire prevention code listed in
Chapter 35. All required fire-suppression and standpipe systems shall
be provided with at least one automatic supply of fire-extinguishing
agent of adequate pressure, capacity and reliability to perform the
function intended.
| |
901.4 Maintenance: All fire-protection systems
shall be maintained in accordance with the requirements of the fire
prevention code listed in Chapter 35.
| |
901.5 Threads: All threads provided for Fire Department
connections to sprinkler systems, standpipes, yard hydrants or any
other fire hose connections shall be compatible with the connections
used by the local Fire Department.
| |
901.6 Signs: All signs required to identify fire-protection
equipment and equipment location shall be constructed of durable materials,
be permanently installed and be readily visible. Letters and numbers
shall contrast with the sign background and shall have an appropriate
width-to-height ratio to permit the sign to be read easily.
| |
901.7 Acceptance Tests: All fire-protection systems
shall be tested in accordance with the requirements of this code and
the fire prevention code listed in Chapter 35. The tests shall be
conducted in the presence of the Code Official. All tests required
by this code and the standards listed in this code shall be conducted
at the expense of the owner or the owner's representative.
| |
901.8 Certification: The contractor shall provide
the Code Official with a certificate indicating that the system is
installed in compliance with this code and the appropriate acceptance
tests have been conducted.
|
SECTION 902.0 DEFINITIONS
| |
902.1 General: The following words and terms shall,
for the purpose of this article and as used elsewhere in this code,
have the meanings shown herein.
| |
Alarm Verification: A feature of automatic fire-detection
systems to reduce unwanted alarms wherein automatic fire detectors
report alarm conditions for a minimum period of time, or confirm alarm
conditions within a given period, after being automatically reset
to be accepted as a valid alarm initiation signal. (See Section 918.0.)
| |
Automatic: As applied to fire-protection devices,
"automatic" refers to a device or system that provides an emergency
function without the necessity of human intervention and activated
as a result of a predetermined temperature rise, rate of temperature
rise or increase in the level of combustion products - such as incorporated
in an automatic sprinkler system, automatic fire door, etc.
| |
Automatic Fire-Suppression System: An engineered
system using carbon dioxide (CO2), foam, wet
or dry chemical, a halogenated extinguishing agent, or an automatic
sprinkler system to detect automatically and suppress a fire through
fixed piping and nozzles. (See Section 904.0.)
| |
Deluge System: An automatic sprinkler system consisting
of open sprinklers with water supply valves activated by a separate
automatic detection system. (See Section 908.0.)
| |
Detector, Duct: Same as "smoke detector."
| |
Detector, Heat: An alarm-initiating device that
detects abnormally high temperatures or rate of temperature rise.
(See Section 918.0.)
| |
Detector, Smoke: An alarm-initiating device that
detects the visible or invisible particles of combustion. (See Section
918.0.)
| |
Fire Alarm Box, Manual: A manually operated alarm-initiating
device that activates a fire-protective signaling system. (See Section
917.0.)
| |
Fire Command Station: The principal location where
the status of the detection, alarm, communications and control systems
is displayed, and from which the system(s) has the capacity for manual
control. (See Sections 403.7 and 917.9.)
| |
Fire Detector, Automatic: An alarm-initiating device
that automatically detects heat, smoke or other products of combustion.
(See Section 918.0.)
| |
Fire-Protection System: Devices, equipment and
systems to detect a fire, activate an alarm, suppress or control a
fire, or any combination thereof.
| |
Preaction System: A fire sprinkler system employing
automatic sprinklers attached to a piping system, containing air with
a supplemental fire-detection system installed in the same areas as
the sprinklers. Actuation of the fire-detection system automatically
opens a valve that permits water to flow into the sprinkler piping
system and to be discharged from any open sprinklers. (See Section
906.9.6.)
| |
Smoke Detector, Multiple Stations: Single-station
smoke detectors that are capable of being interconnected such that
actuation of one causes all integral or separate audible alarms to
operate. (See Section 919.0.)
| |
Smoke Detector, Single Station: An assembly incorporating
the detector, the control equipment and the alarm-sounding device
in one unit, which is operated from a power supply either in the unit
or obtained at the point of installation. (See Section 919.0.)
| |
Sprinkler: A device, connected to a water supply
system, that discharges water in a specific pattern for extinguishment
or control of fire. (See Section 906.0.)
| |
Sprinkler System, Automatic: A sprinkler system,
for fire-protection purposes, is an integrated system of underground
or overhead piping designed in accordance with fire-protection engineering
standards. The system includes a suitable water supply. The portion
of the system above the ground is a network of specially or hydraulically
designed piping installed in a building, structure or area, generally
overhead, and to which automatic sprinklers are connected in a systematic
pattern. The system is usually activated by heat from a fire and discharges
water over the fire area. (See Section 906.0.)
| |
Standpipe System: A standpipe system is a fire-protection
system consisting of an arrangement of hose outlets and allied equipment
installed in a building or structure. (See Section 914.0.)
| |
Supervisory Device: An initiating device used to
monitor the conditions that are essential for the proper operation
of automatic fire-suppression systems (i.e., switches used to monitor
the position of gate valves, a low-air-pressure switch on a dry-pipe
sprinkler system, etc.). (See Section 923.0.)
| |
Voice/Alarm Signaling System: A system that provides,
to the occupants of a building, dedicated manual or automatic facilities,
or both, for originating and distributing voice instructions, as well
as alert and evacuation signals that pertain for a fire emergency.
(See Section 917.0.)
| |
Water Supply, Automatic: A water supply that is
not dependent on any manual operation, such as making connections,
operating valves or starting pumps. (See Section 914.5.)
|
SECTION 903.0 CONSTRUCTION DOCUMENTS
| |
903.1 Required: Construction documents or shop
drawings, or both, for the installation of fire-protection systems
shall be submitted to indicate conformance to this code and shall
be reviewed by the Department prior to issuance of the permit.
| |
Note: Since the Fire Department is responsible
for inspecting for the proper maintenance of fire-protection systems
in the building, the administrative authority shall cooperate with
the Fire Department in the discharge of responsibility to enforce
this article.
| |
903.2 Construction Documents: The construction
documents and shop drawings submitted to the Department shall contain
sufficient detail as outlined herein to evaluate the protected hazard
and the effectiveness of the system.
| |
903.2.1 Information: Construction documents for
fire-protection systems shall be submitted with the construction documents
for the construction permit. Included shall be information on the
contents, the occupancy, the location and arrangement of the structure
and the contents involved, the exposure to any hazard, the extent
of the system coverage, the suppression system design criteria, the
supply and extinguishing agents, the location of any standpipes, and
the location and method of operation of detection and alarm devices.
| |
903.2.2 Shop Drawing: Shop drawings for the installation
of fire-protection systems shall be submitted for review and approval
prior to the installation of a fire-protection system. Included on
the shop drawings shall be information showing the basis for compliance
with the design density, the specific arrangement of the system, the
devices and their method(s) of operation, and the suppression agent.
The details of the construction documents or shop drawings for the
fire-protection system shall include design considerations, spacing
and arrangement of fire-protection devices, protection agent supply
and discharge requirements, calculations with sizes and equivalent
lengths of pipe and fittings, and protection agent source. Sufficient
information shall be included to identify the apparatus and devices
utilized and other information as required by this code. The submittal
shall be designed by a minimum of a NICET Level III fire-protection
technician, and documents shall be sealed on all pages by this technician.
|
SECTION 904.0 FIRE-SUPPRESSION SYSTEMS
| |
904.1 Where Required: Automatic fire-suppression
systems shall be installed where required by this code, and in the
locations indicated in Sections 904.2 through 904.11.
| |
904.2 Use Groups A-1, A-3 and A-4: An automatic
fire-suppression system shall be provided throughout all Use Groups
A-1, A-3 and A-4 exceeding 10,000 square feet gross.
| |
904.3 Use Group A-2: An automatic fire-suppression
system shall be provided throughout all Use Group A-2 exceeding 5,000
square feet gross.
| |
904.4 Sue Group B: An automatic fire-suppression
system shall be provided throughout all Use Group B exceeding 10,000
square feet gross.
| |
904.5 Use Group E: An automatic fire-suppression
system shall be provided throughout all Use Group E exceeding 10,000
square feet gross.
| |
904.6 Use Group H: An automatic fire-suppression
system shall be provided throughout all Use Group H, regardless of
gross square footage.
| |
904.7 Use Group I: An automatic fire-suppression
system shall be provided throughout all buildings with Use Group I,
regardless of gross square footage.
| |
904.8 Use Group M, S-1 and F-1: Throughout all
buildings exceeding 10,000 square feet gross with a Use Group M, S-1
or F-1, an automatic fire-suppression system shall be provided as
follows:
| |
904.9 Use Group R-1: An automatic fire-suppression
system shall be provided throughout all buildings with a Use Group
R-1 fire are in accordance with Section 906.2.1 or 906.2.2.
| |
904.10 Use Group R-2 and R-3: An automatic fire-suppression
system shall be provided throughout all buildings with an occupancy
in Use Group R-2 in accordance with section 906.2.1 or 906.2.2.
| |
904.11 Other Required Suppression Systems: In addition
to the requirements of this section, the sections of this code indicated
in Table 904.11 also require the installation of an automatic fire-suppression
system for certain buildings and areas.
|
Table 904.11
Additional Required Suppression Systems
| ||
---|---|---|
Section
|
Subject
| |
302.1.1
|
Specific occupancy areas
| |
402.10; 402.15.2
|
Covered mail buildings
| |
403.2
|
High-rise buildings
| |
404.2
|
Atriums
| |
408.3.1
|
Public garages
| |
408.4
|
Fuel-dispensing areas
| |
411.7
|
Sound stages
| |
412.6
|
Stages and enclosed platforms
| |
413.4
|
Special amusement buildings
| |
416.4
|
HPM facilities
| |
419.3
|
Paint spray booths & storage rooms
| |
507.1
|
Unlimited area buildings
| |
1020.3
|
Exit lobbies
| |
2806.4
|
Drying rooms
| |
2807.6
|
Waste and linen chutes and termination and incinerator room/elevator
shafts
| |
2808.4
|
Refuse vaults
|
SECTION 905.0 SUPPRESSION SYSTEM AGENT COMPATIBILITY
| |
905.1 Agent Compatibility: The extinguishing agent
for each suppression system shall be compatible with the type of hazard
and fire. Each fixed fire-suppression system shall be of an approved
type and shall be designed and installed in accordance with the requirements
of this code.
| |
905.1.1 Special Hazards: In rooms or buildings
containing combustible (such as aluminum powder, calcium carbide,
calcium phosphate, metallic sodium and potassium, quick lime, magnesium
powder or sodium peroxide) that are incompatible with water as an
extinguishing agent, other extinguishing agents shall be utilized.
|
SECTION 906.0 SUPPRESSION SYSTEM AGENT COMPATIBILITY
| |
906.1 General: Automatic sprinkler systems shall
be approved and shall be designed and installed in accordance with
the provisions of this code.
| |
906.2 Equipped Throughout: Where the provisions
of this code require that a building be equipped throughout with automatic
sprinkler system, the system shall be designed and installed in accordance
with Section 906.2.1, 906.2.2 or 906.2.3.
| |
Exception: Where water as an extinguishing agent
is not compatible with the fire hazard (See Section 905.1.) or is
prohibited by a law, statute or ordinance, the affected area shall
be equipped with an approved automatic fire-suppression system utilizing
a suppression agent that is compatible with the fire hazard.
| |
906.3 Design: The details of the system indicated
on the construction documents shall include calculations and information
on the sprinkler spacing and arrangement, water supply and discharge
requirements, size and equivalent lengths of pipe and fittings and
water supply source. Sufficient information shall be included to identify
the apparatus and device used.
| |
906.4 Actuation: Water sprinkler systems shall
be automatically actuated unless otherwise specifically provided for
in this code.
| |
906.5 Sprinkler Alarms: Approved audible and visual
alarm devices shall be connected to every water sprinkler system.
Such alarm devices shall be activated by water flow and shall be placed
in an approved location on the exterior of the building, and an additional
audible and visual alarm device shall be installed in an approved
location.
| |
906.6 Water-Control Valve Identification: All valves
controlling water to fire-protection systems shall be provided with
permanently attached identification tags indicating the valves'
function and what is controlled. A sufficient protected area for water
controls will be determined by the Fire Department.
| |
906.7 Sprinkler Riser: A sprinkler system riser
which also serves as the wet standpipe riser in buildings required
to have or having both systems, shall conform to Section 914.6.
| |
906.8 Signs: Where sprinkler control valves are
located in separate room or building, a sign shall be provided on
the entrance door. The lettering for such sign shall conform to Section
901.6, shall be at least four inches (102 mm) in height and shall
read "Sprinkler Control Valves."
| |
906.9 Acceptance Tests: All sprinkler systems shall
be tested in accordance with Section 906.9.1 through 906.9.6.
| |
906.9.1 Underground Connections: Lead-in connections
shall be flushed and tested in accordance with NFPA 13 and 241 listed
in Chapter 35.
| |
906.9.2 Hydrostatic Test: All sprinkler systems
shall be tested hydrostatically for two hours without visible leakage
at not less than 200 psi (1379 kPa) or at 50 psi (344.75 kPa) in excess
of the maximum static pressure, whichever is greater. The test pressure
shall be read from a gauge located at the low elevation point of the
individual system or portion of the system being tested.
| |
Exception: When climatic conditions will not permit
testing with water, an interim test shall be conducted with air pressure
in accordance with Section 906.9.3 and the standard hydrostatic test
shall be conducted when weather conditions permit.
| |
906.9.3 Air Test: Before the water supply for a
dry pipe system is turned on and the system is placed into service,
the system shall be tested with air pressure of at least 40 psi (276
kPa) and be allowed to stand 24 hours with a maximum pressure loss
of 1 1/2 psi (10.34 kPa). To prevent damaging the valve, the
clapper valve of a differential-type dry-pipe valve shall be held
off the valve set during any test at a pressure in excess of 50 psi
(344.75 kPa). Automatic air-pressure maintenance devices shall be
capable of restoring normal operating air pressure in the system within
30 minutes except for low-differential dry pipe systems where the
maximum recovery time shall be 60 minutes.
| |
906.9.4 Main Drain test: A drain test shall be
performed in order to obtain both static and residual pressure readings.
| |
906.9.5 Flow Test: All systems shall be tested
at the test pipe to determine that water flow detecting devices, including
the associated alarm circuits, are in proper working order. Dry pipe
systems shall deliver water to the inspector's test pipe in not
more than 60 seconds.
| |
906.9.6 Preaction and Deluge Systems: Testing of
the supplemental fire-detection systems designed to activate the preaction
and deluge systems shall be in accordance with Section 917.10.
|
|
SECTION 908.0 WATER-SPRAY FIXED SYSTEMS
| |
908.1 General: Water-spray fixed systems for fire
suppression shall be of an approved type and shall be installed in
accordance with the provisions of this code and NFiPA 15 listed in
Chapter 35. A water-spray fixed system is a system connected to a
reliable source of water supply and equipped with normally open water-spray
nozzles for specific discharge and distribution over the surface or
area to be protected.
| |
908.2 Design: Complete construction documents and
hydraulic calculations shall be submitted for review prior to installation.
The submittal shall include nozzle layouts, friction loss, detailed
layout of the entire area to be protected.
| |
908.3 Actuation: Water-spray systems shall be automatically
actuated and shall be provided with a manual means of actuation.
| |
908.4 Acceptance Tests: All new system piping shall
be flushed and tested in accordance with the provisions of NFiPA 15
listed in Chapter 35.
|
SECTION 909.0 CARBON DIOXIDE EXTINGUISHING SYSTEMS
| |
909.1 General: Carbon dioxide extinguishing systems
shall be of an approved type and shall be installed in accordance
with the provisions of this code and NFiPA 12 listed in Chapter 35.
A carbon dioxide extinguishing system is a system which supplies CO2 from a pressurized vessel through fixed pipes and nozzles.
| |
909.2 Design: The details of the system indicated
on the construction documents shall include information and calculations
of the amount of carbon dioxide; the location and flow rate of each
nozzle including equivalent orifice area; and the location and size
of the carbon dioxide storage facility. Information shall be submitted
pertaining to the location and function of detecting devices, operating
devices, auxiliary equipment and electrical circuitry, if used. Sufficient
information shall be indicated to identify properly the apparatus
and devices used. Any special features shall be adequately explained.
| |
909.3 Actuation: Carbon dioxide extinguishing systems
shall be automatically actuated and shall be provided with a manual
means of actuation.
| |
909.4 Safety Requirements: Where persons will enter
or be trapped in atmospheres made hazardous by carbon dioxide discharge,
warning signs and discharge alarms shall be provided.
| |
909.5 Acceptance Tests: All carbon dioxide extinguishing
systems shall be tested in accordance with NFiPA 12 listed in Chapter
35. A completed system shall be tested for tightness up to the selector
valve, and for continuity of piping with free unobstructed flow beyond
the selector valve. The labeling of devices with proper designations
and instructions shall be checked. Operational tests shall be conducted
on all devices except cylinder valves in multicylinder high-pressure
systems. Where conditions prevail that make it difficult to determine
adequately the system requirements or design, a suitable discharge
test and concentration analysis shall be made.
|
|
SECTION 910.0 DRY-CHEMICAL EXTINGUISHING SYSTEMS
| |
910.1 General: Dry-chemical extinguishing systems
shall be of an approved type and shall be installed in accordance
with the provisions of this code and NFiPA 17 listed in Chapter 35.
A dry-chemical extinguishing system is a system consisting of dry
chemical and expellant gas storage tanks, fixed piping and nozzles
used to assure proper distribution of approved extinguishing agent
to a specific fire hazard or into a potential fire area.
| |
910.2 Design: The details of the system indicated
on the construction documents shall include sufficient information
and calculations of the amount of dry chemical; the size, length and
arrangement of connected piping, and hose, and a description and location
of nozzles so that the adequacy of the system can be determined. Information
shall be submitted pertaining the location and function of detecting
devices, operating devices, auxiliary equipment and electrical circuitry,
if used. Sufficient information shall be indicated to identify properly
the apparatus and devices used. Any special features shall be adequately
explained.
| |
910.3 Actuation: Dry chemical extinguishing systems
shall be automatically actuated and shall be provided with a manual
means of actuation. The system will be required to be a part of the
building alarm system.
| |
910.4 Safety Requirements: Where persons will be
exposed to a dry-chemical discharge, warnings signs and discharge
alarms shall be provided.
| |
910.5 Acceptance Tests: All dry-chemical extinguishing
systems shall be tested in accordance with NFiPA 17 listed in Chapter
35. A completed system shall be tested by a discharge of expellant
gas through the piping and nozzles. Observations for gas leakage and
for continuity of piping with free obstructed flow shall be made.
Observations shall be made of the flow of expellant gas through all
nozzles. The labeling devices with proper designations and instructions
shall be checked. After testing, all piping and nozzles shall be blown
clean using compressed air or nitrogen, and the system shall be properly
charged and placed in that normal "set" condition.
| |
910.5.1 Discharge Test: All systems shall be tested
by a discharge of expellant gas through the piping nozzle with observations
being made of the flow of expellant gas through all nozzles as well
as observing for leakage and continuity of piping with free unobstructed
flow.
| |
910.6 Range Hoods: In addition to the requirements
of this section and the mechanical code listed in Chapter 35, range
hood dry-chemical systems shall bear the label of an approved agency.
The system shall be installed in accordance with the manufacturer's
installation instructions. The dry-chemical agent of the system shall
be non toxic.
|
SECTION 911.0 FOAM-EXTINGUISHING SYSTEMS
| |
911.1 General: Foam-extinguishing systems shall
be of an approved type and shall be installed in accordance with the
provisions of this code and NFiPA 11, 11A and 16 listed in Chapter
35. A foam-extinguishing system is a special system designed to discharge,
either mechanically or chemically, a foam made from concentrates,
over the area to be protected.
| |
911.2 Design: The details of the system indicated
on the construction documents shall include complete computation showing
pressure drop in all system piping, friction loss calculations of
liquid lines and a detailed layout of the entire hazard area to be
protected. Hydraulic characteristics of foam proportioners and foam
makers as determined by tests shall be supplied by the manufacturer
to the Department (including the range of operating conditions required
to the proposed installation) to permit determination of the adequacy
of the hydraulics of the proposed protection.
| |
911.3 Actuation: A foam-extinguishing system shall
be automatically actuated and shall be provided with a manual means
of actuation. (See Section 910-3.)
| |
911.4 Safety Requirements: In any proposed use
of a medium- or high-expansion foam where persons will be exposed
to the foam discharge, warning signs and discharge alarms shall be
provided.
| |
911.5 Acceptance Tests: All foam-extinguishing
systems shall be tested in accordance with NFiPA 11, 11A and 16 listed
in Chapter 35. The system shall be subjected to a flow test to insure
that the hazard area is fully protected in compliance with the design
specifications, and to determine flow pressures, actual discharge
capacity, foam quality, consumption rate of, foam-producing materials,
manpower requirements and other operating characteristics.
|
SECTION 912.0 HALOGENATED EXTINGUISHING SYSTEMS
| |
912.1 General: Halogenated extinguishing systems
shall be of an approved type and shall be installed in accordance
with the provisions of this code and NFiPA 12A and 12B listed in Chapter
35. A halogenated extinguishing system is a system consisting of pipes,
open nozzles and a container of halogenated agent under pressure.
| |
912.2 Design: The details of the system indicated
on the construction documents shall include information and calculations
of the amount of extinguishing agent; the container storage pressure;
the location equivalent orifice area; the location, size and equivalent
lengths of pipe fittings and hose; and the location and size of the
storage facility. Information shall be submitted pertaining to the
location and function of detecting devices, operating devices, auxiliary
equipment and electrical circuitry, if used. Sufficient information
shall be indicated to identify properly the apparatus and devices
used. Any special features shall be adequately explained.
| |
912.3 Actuation: Halogenated extinguishing shall
be automatically actuated and shall also be provided with a manual
means of actuation. (See Section 910.3.)
| |
912.4 Safety Requirements: Where persons will enter
or be trapped in atmospheres made hazardous by a halogenated system
discharge, warning signs and discharge alarms shall be provided.
| |
912.5 Acceptance Tests: All halogenated extinguishing
systems shall be tested in accordance with NFiPA 12A and 12B listed
in Chapter 35. A completed system shall be tested for tightness up
to the selector valve, and for continuity of piping with free unobstructed
flow beyond the selector valve. The labeling of devices with proper
designations and instructions shall be checked. Operational tests
shall be conducted on all devices except cylinder valves in multicylinder
systems; where conditions prevail that make it difficult to determine
adequately the system requirements or design, a suitable discharge
test and concentration analysis shall be made.
|
SECTION 913.0 WET-CHEMICAL RANGE HOOD EXTINGUISHING SYSTEMS
| |
913.1 General: Wet-chemical extinguishing systems
shall be installed in accordance with the provisions of its section,
and the mechanical code and NFiPA 17A listed in Chapter 35. The system
shall bear the label of an approved agency and shall be installed
in accordance with the manufacturer's installation instructions.
A wet-chemical system is a solution of water and potassium-carbonate-based
chemical, potassium-acetate-based chemical or a combination thereof
which forms the extinguishing agent.
| |
913.2 Design: The details of the system indicated
on the construction documents shall include sufficient information
and calculations on the amount of wet-chemical; the size, length and
arrangement of connected piping; and a description and the system
can be determined. Information shall be submitted pertaining to the
location and function of detection devices, operating devices, auxiliary
equipment and electrical circuitry, if used. Sufficient information
shall be indicated to identify properly the apparatus and devices
used. Any special features shall be adequately explained.
| |
913.3 Actuation: Wet-chemical extinguishing systems
shall be automatically actuated and shall be provided with a manual
means of actuation. (See Section 910.3.)
| |
913.4 Safety Requirements: Where persons will be
exposed to a wet-chemical discharge, warning sign and discharge alarms
shall be provided.
| |
913.5 Acceptance Tests: All wet-chemical extinguishing
systems shall be tested in accordance with NFiPA 17A listed in Chapter
35. A completed system shall be tested by discharge of wet chemical
in sufficient amounts to verify that the system is properly installed
and functional. Tests shall include a check of the detection systems,
the alarms and the releasing devices, including manual stations, fuel
and power shutoff devices and other associated equipment.
| |
913.5.1 Discharge Tests: All systems shall be tested
by a discharge of expellant gas through the piping and nozzles with
observations being made of the flow of expellant gas through all nozzles
as well as observing for leakage and continuity of piping with free
unobstructed flow.
|
|
SECTION 914.0 STANDPIPE SYSTEMS
| ||
914.1 General: Standpipe systems shall be installed
and maintained in accordance with the provisions of this code, and
the fire prevention code and NFiPA 14 listed in Chapter 35.
| ||
914.2 Where Required: Standpipe systems shall be
installed where required by this code and in the locations indicated
in Section 914.2.1 through 914.2.4.
| ||
914.2.1 Building Height: Standpipe systems shall
be installed throughout all buildings in which the floor level of
the highest story located more than 30 feet (9,144 mm) above the lowest
level of the Fire Department vehicle access or in which the floor
level of the lowest story is located more than 30 feet (9,144 mm)
below the highest level of Fire Department vehicle access.
| ||
914.2.2 Building Area: Standpipe systems shall
be installed in all buildings where any portion of the building floor
area is more than 100 feet of travel from the nearest point of Fire
Department vehicle access.
| ||
914.2.3 Malls: Standpipe systems shall be installed
in all malls in accordance with Section 402.11.
| ||
914.2.4 Stages: Standpipe systems shall be installed
in stages in accordance with Section 412.7.
| ||
914.3 Types of Systems: A standpipe system shall
be one of the following types:
| ||
1.
|
A wet standpipe system having the supply valve open and water
pressure maintained at all times;
| |
2.
|
A dry standpipe system so arranged through the use of approved
devices as to admit water to the system automatically by opening a
hose valve;
| |
3.
|
A dry standpipe system arranged to admit water to the system
through manual operation of approved remote control devices located
at each hose connection; or
| |
4.
|
A dry standpipe system that does not have a permanent water
supply.
| |
914.3.1 Type of Systems Required: Buildings required
by Section 914.2 to be equipped with standpipe systems shall be provided
with a wet standpipe system that complies with Section 914.3. Item
1.
| ||
914.4 Piping Design: The riser piping, supply piping
and the water service piping shall be sized to maintain a residual
pressure of at least 65 psi (488 kPa) at the topmost outlet of each
riser while flowing the minimum quantities of water specified in NFPA
14.[3]
| ||
914.4.1 and 914.4.2: The pipe size shall be based
on the capacity of the automatic water supply system or, where an
automatic water supply is neither required nor provided to maintain
the residual pressure of 65 psi (488 kPa), the pipe shall be based
on a pressure of 150 psi (1034 kPa) available at the Fire Department
connection.
| ||
914.4.1 Riser Sizing: The riser size shall be based
on hydraulic calculations for a minimum flow of 500 gallons per minute
(gpm) (0.032m3/s).
| ||
Exceptions:
| ||
1.
|
Where only 1 1/2 inch valves are provided, the riser(s)
shall be sized to provide a minimum flow of 100 gpm (0.006m 1/3).
| |
2.
|
In buildings where limited sprinkler systems are supplied with
water from a common standpipe riser, the riser shall be sized to satisfy
total demand.
| |
3.
|
For occupancies in Use Group B, I, R-1 or R-2 in buildings that
are equipped throughout with an automatic sprinkler system in accordance
with Section 906.2.1, each riser shall be sized for a minimum flow
of 250 gpm (0.016m 1/s).
| |
4.
|
Risers that are sized in accordance with the pipe schedule requirements
of NFiPA 14 listed in Chapter 35 are not subject to this requirement.
| |
914.4.2 System Pipe Sizing: The system piping,
including the horizontal or common feeder lines, shall be sized for
a minimum flow of 500 gpm (0.32m 1/s). Where more than one standpipe
riser is required or provided, all common system piping shall be sized
for a minimum flow of 500 gpm (0.0321/s) for the first riser plus
250 gpm (0.016m 1/s) for each additional riser, and the total shall
not be required to exceed 1,250 gpm (0.08m 1/s).
| ||
Exceptions:
| ||
1.
|
Where only 1 1/2 inch valves are provided, the supply piping
shall be sized for a minimum flow of 100 gpm (0.0063m 1/s) for each
riser, and the total shall not be required to exceed 500 gpm (0.032m
1/s).
| |
2.
|
In buildings where limited area sprinkler systems are supplied
with water from a common standpipe riser, the supply piping shall
be sized for a minimum flow of 500 gpm (0.032m 1/s) plus the sprinkler
demand for the first riser, plus 250 gpm (0.016m 1/s) for each additional
riser, and the total shall not be required to exceed 1,250 gpm (0.08m
1/s).
| |
3.
|
For occupancies in Use Group B, I, R-1 or R-2 in buildings that
are equipped throughout with an automatic sprinkler system in accordance
with Section 906.2.1, all common supply piping shall be sized for
a minimum flow of 250 gpm (0.0161/s) for the first riser plus 250
gpm (0.016m 1/s) for each additional riser, and the total shall not
be required to exceed 750 gpm (0.05m 1/s).
| |
914.5 Water Supply: A water supply for Fire Department
equipment shall be available to the building site. The water supply
shall be capable of a minimum flow as required by Section 914.4.2
for a duration of 30 minutes. The water supply shall not be more than
150 feet from system connection.
| ||
914.5.1 Automatic Water Supply: An automatic water
supply is required for all standpipe systems. The automatic water
supply and supply piping shall be capable of delivering a flow of
500 gpm (0.032m 1/s) at the residual pressure specified in Section
914.4 for a duration of 30 minutes.
| ||
914.6 Control Valves: Where a standpipe system
riser also serves as the automatic sprinkler system riser in buildings
required to have both systems or in buildings having both systems,
sprinkler control valves shall be installed at each floor level at
the connection to the riser.
| ||
914.7 Hose Connections: A standpipe hose connection
shall be located at each floor level at every exit stairway, and on
each side of the wall adjacent to the exit opening of a horizontal
exit.
| ||
914.7.1 Location: At each floor level, and not
more than five feet (1524 mm) above the floor, there shall be connected
to each standpipe a 2 1/2 inch hose connection with valves and
threads compatible with the connections used by the local Fire Department.
| ||
914.7.2 Roof Hydrants: Where standpipes are installed
in building more than six stories or 75 feet (22,860 mm) in height,
at least one riser shall extend through the roof and terminate in
a two-way, 2 1/2 inch hose connection. The main control valve
on a roof hydrant or manifolded hose connection shall be located in
an area that is not subject to freezing, is as close to the roof access
as practical and is plainly marked. (See Section 915.8.)
| ||
914.7.3 Pressure-Regulating Devices: Where residual
pressure at any standpipe hose outlet exceeds 100 psi (690 kPa), approved
pressure-regulating devices shall be installed at the outlets to limit
the pressure to 100 psi (690 kPa). Such devices shall regulate pressure
under flow and no-flow conditions and shall not be capable of being
adjusted to pressure higher than 100 psi (690 kPa) unless approved.
The pressure on the inlet side of the pressure-regulating device shall
not exceed the rated working pressure of the device.
| ||
914.7.4 Protection of Risers: Risers and laterals
of standpipe systems of the types complying with Section 914.3, Items
2 or 3, and not located within a fire resistance rated exit enclosure
shall be enclosed by construction having a minimum fire resistance
rating equal to that required for shaft enclosures in the building.
| ||
914.8 Test Gauges: An approved water pressure gauge
shall be attached to each discharge pipe from fire pump and public
supply, at the pressure tank, at the air pump that supplies pressure
to the tank and the top of each standpipe riser for inspection and
test purposes. Shutoff valves, with provisions for bleeding pressure
from the gauge, shall be installed between the gauge and the top of
the riser. Access to the gauge shall be provided and the gauges shall
be located in spaces not subject to freezing.
| ||
Exception: Where more than one standpipe riser
is interconnected at the top, a single gauge properly located is permitted
to be substituted for gauge at the top of each standpipe riser.
| ||
914.9 Materials: All standpipes shall be constructed
of approved materials. All pipe, fittings and valves shall be of an
extra-heavy pattern where the normal working pressure will exceed
175 psi (1270 kPa).
| ||
914.10 Unheated Areas: Portions of the standpipe
system which contain water shall be protected from freezing.
| ||
914.11 Signs: Where control valves are located
in a separate room or building, a sign shall be provided on the entrance
door. The lettering of such sign shall conform to Section 901.6 and
shall be at least four inches (102 mm) in height and shall read "Standpipe
Control Valves."
| ||
914.12 Acceptance Tests: All standpipe systems
shall be tested in accordance with Sections 914.12.1 through 914.12.4.
| ||
914.12.1 Underground Connections: Underground mains
and lead-in connections shall be flushed and tested in accordance
with NFiPA 14 and 24 listed in Chapter 35.
| ||
914.12.2 Hydrostatic Tests: All systems shall be
tested hydrostatically for two hours at not less than 200 psi (1379
kPa) or at 50 psi (345 kPa) in excess of the maximum static pressure,
whichever is greater. The hydrostatic pressure shall be measured at
the low elevation point of the individual system or zone being tested.
The inside standpipe piping shall not show any leakage.
| ||
914.12.3 Flow Test: All systems shall have a flow
test conducted at the determine compliance with the single-riser criteria
of Section 914.4.
| ||
914.12.4 Dry Devices: A working test of valves,
quick-opening devices and air maintenance devices installed in systems
complying with Section 914.3, Item 2 or 3, shall be made before acceptance.
These systems shall deliver water at the most remote hose outlet in
not more than 60 seconds.
|
SECTION 915.0 FIRE DEPARTMENT CONNECTIONS
| |
915.1 Required: All required water fire extinguishing
and standpipe systems shall be provided with a Fire Department connection
in accordance with the applicable standards. Standpipes in buildings
under construction or demolition shall conform to Section 3305.3.
| |
915.2 Connections: Fire Department connections
shall be arranged in such a manner the attachments to any one water
sprinkler connection will serve all sprinklers, and the attachment
to any one standpipe connection will serve all standpipes within the
building.
| |
915.3 Location: Fire Department connections shall
be located and shall be visible on a street front or in a location
approved by the Fire Department. Such connections shall be located
so that immediate access is provided to the Fire Department. Fire
Department connections shall not be obstructed by fences, brushes,
trees, walls or any other similar object.
| |
915.4 Height: Fire Department connections shall
not be less than 24 inches and not more than 42 inches (1,067 mm)
in elevation, measured from the ground level to the center line of
the inlets.
| |
915.5 Projection: Where the Fire Department connection
will otherwise project beyond the property line or into the public
way, a flush-type Fire Department connection shall be provided.
| |
915.6 Hose Threads: Hose thread in the Fire Department
connection shall be uniform with that used by the local Fire Department.
| |
915.7 Fittings: Fire Department, inlet connections
shall be fitted with check valves, ball drip valves and plugs with
chains or frangible caps.
| |
915.8 Signs: A metal sign with raised letters at
least one inch (25 mm) in height shall be mounted on all Fire Department
connections serving sprinklers or standpipes. Signs shall read "automatic
sprinklers" or "standpipe," or both, as applicable.
|
SECTION 916.0 YARD HYDRANTS
| |
---|---|
916.1 Fire Hydrants: Fire hydrants installed on
private property shall be located and installed as directed by the
Fire Department. Hydrants shall conform to the standards of the administrative
authority of the jurisdiction and the Fire Department. Hydrants shall
not be installed on a water main less than eight inches in diameter.
|
SECTION 917.0 FIRE-PROTECTIVE SIGNALING SYSTEMS
| ||
917.1 General: Fire proactive signaling systems
shall be of an approved type and shall be installed in accordance
with the provisions of this code and NFiPA 72 listed in Chapter 35.
| ||
917.2 Construction Documents: Where a fire-protective
signaling system is required by this code, the construction documents
shall show the location and number of all alarm-initiating devices
and alarm-indicating appliances, and shall provide a description of
all equipment to be used, proposed zoning, a list of auxiliary control
functions (i.e., elevator capture), location of the control panel(s),
and a complete sequence of operation for the system.
| ||
917.3 Approval: All devices, combinations of devices,
appliances and equipment shall be approved for the fire-protective
signaling purposes for which equipment is used.
| ||
917.4 Where Required: A fire-protective signaling
system shall be installed and maintained in full operating condition
in the locations described in Section 917.4.1 through 917.4.6.
| ||
917.4.1 Use Group A-1, A-2, A-3, A-4, B, E, F, H, I, M
and S: A fire-protective signaling system shall be installed
and maintained in all occupancies in Use Group A-1, A-2, A-3, A-4,
B, E, F, H, I, M and S.
| ||
917.4.2 Use Group R-1, R-2, R-3: A fire-protective
signaling system shall be installed and maintained in all occupancies
in Use Group R-2 where any dwelling unit is located three or more
stories above the lowest level of exit discharge or more than one
story below the highest level of exit discharge of exits serving the
dwelling unit.
| ||
917.5 Location: Manual fire alarm boxes shall be
located not more than five feet (1,524 mm) from the entrance to each
exit.
| ||
917.5.1 Manual Fire Alarm Boxes: The height of
the manual fire alarm boxes shall be a minimum of 42 inches (1,067
mm) and a maximum of 54 inches (1,372 mm) measured vertically, from
the floor level to the activating handle or lever of the box, manual
fire alarm boxes shall be red in color, in all occupancies in Use
Group I-3, the manual fire alarm boxes shall be permitted to be locked
in areas where staff is present whenever such areas are occupied and
keys are readily available to unlock the boxes, or the boxes shall
be located in a manned staff location which has direct supervision
of the sleeping area.
| ||
917.6 Power Supply: The primary and secondary power
supply for the fire-protective signaling system shall be provided
in accordance with NFiPA 72 listed in Chapter 35.
| ||
917.7 Wiring: All wiring shall conform to the requirements
of NFiPA 72 listed in Chapter 35. Wireless systems utilizing radio
frequency transmitting devices shall comply with the special requirements
for supervision of low-power wireless systems in NFiPA 72 listed in
Chapter 35.
| ||
917.7.1 Activation: The alarm-indicating appliances
shall be automatically activated by all of the following where provided:
| ||
1.
|
Smoke detectors, other than single and multiple station smoke
detectors
| |
2.
|
Sprinkler water-flow devices
| |
3.
|
Manual fire alarm boxes, and duct detectors
| |
4.
|
Other approved types of automatic fire-detection devices or
suppression systems
| |
917.7.2 Presignal Systems: Presignal systems shall
not be installed unless approved by the Code Official and by the Fire
Department. Where a presignal system is installed, twenty-four-hour
personnel supervision shall be provided at the location approved by
the Fire Department, in order that the alarm signal can be actuated
in the event of fire or other emergency.
| ||
917.7.3 Zones: Each floor shall be zoned separately,
and a zone shall not exceed 2,000 square feet (465 m2). The length of any zone shall not exceed 100 feet in any direction.
A zoning indicator panel and the associated controls shall be provided
in an approval location. The visual zone indication shall lock in
until the system is reset and shall not be canceled by the operation
of an audible alarm-silencing switch. In buildings that have floors
located more than 75 feet (22,869 mm) above the lowest level of Fire
Department vehicle access which are occupied for human occupancy,
a separate zone by floor shall be provided for the following types
of alarm-initiating devices where provided.
| ||
1.
|
Smoke detectors
| |
2.
|
Sprinkler water-flow devices
| |
3.
|
Manual fire alarm boxes; and duct detection
| |
4.
|
Other approved types of automatic fire-detection devices or
suppression systems
| |
917.8 Alarm-Indicating Appliances: Alarm-indicating
appliances of the approved type shall be provided.
| ||
917.8.1 Visible Alarms: Visible alarm-indicating
appliances shall be provided in public and common areas of all buildings.
In occupancies in Use Group I-1 and R-1, all required accessible sleeping
rooms and suites plus an additional number of sleeping rooms or suites
in accordance with Table 917.8.1 shall be provided with a visible
alarm-indicating appliance, activated by both the in-room smoke detector
and the building fire-protective signaling system.
|
Table 917.8.1
Visible and Audible Alarms
| ||
---|---|---|
No. of Sleeping Room/Suites
|
Sleeping Rooms/Suites with Visible/Audible Alarms
| |
6 to 25
|
1
| |
26 to 50
|
2
| |
51 to 75
|
3
| |
76 to 100
|
4
| |
101 to 150
|
5
| |
151 to 200
|
6
| |
201 to 300
|
7
| |
301 to 400
|
8
| |
401 to 500
|
9
| |
501 to 1,000
|
2% of total
| |
1,000 and over
|
20 plus 1 for each 100 over 1,000
|
917.8.2 Audible Alarms: Audible alarm-indicating
appliances shall be provided and shall sound a distinctive sound which
shall not be used for any purpose other than that of a fire alarm.
The audible alarm-indicating appliances shall provide a sound-pressure
level of 15 dBa above the average ambient sound level in every occupied
space within the buildings. The minimum sound-pressure levels shall
be 70 dBa in occupancies in Use Group R and I-1; 90 dBa in mechanical
equipment rooms; and 60 dBa in all other use groups. The maximum sound-pressure
level for audible alarm-indicating appliances shall be 130 dBa at
the minimum hearing distance from the audible appliance.
| |
917.9 Voice/Alarm Signaling System: A voice/alarm
signaling system shall be provided where required by other sections
of this code. When activated in accordance with Section 917.7.1, the
voice/alarm signaling system shall automatically sound an alert signal
to all occupants within the buildings on a general or selective basis
to the following terminal areas; elevators, elevator lobbies, corridor,
exit stairways, rooms and tenant space exceeding 1,000 square feet
in area; dwelling units in occupancies in Use Group R-2; and guest
rooms or suites in occupancies in Use Group R-1. The fire command
station shall contain controls to transmit manually an evacuation
signal and voice instructions on a selective and all-call basis to
the terminal areas indicate herein. The voice/alarm system shall be
installed in accordance with the provisions of this code and NFiPA
72 listed in Chapter 35.
| |
917.10 Acceptance Tests: Upon completion of the
fire-protective signaling system, all alarm-initiating devices and
circuits, supervisory-signal initiating devices and circuits, signaling
line circuits, and primary and secondary power supplies shall be subjected
to a 100% acceptance test in accordance with NFiPA 72 and 72E listed
in Chapter 35.
|
SECTION 918.0 AUTOMATIC FIRE-DETECTION SYSTEM
| |
918.1 General: Automatic fire-detection systems
shall be of an approved type and shall be installed in accordance
with the provisions of this code and NFiPA 72E listed in Chapter 35.
| |
918.2 Construction Documents: Where an automatic
fire-detection system is required by this code, the construction documents
shall show the location and number of all automatic fire detectors
with specifications of the type of fire sequence of operation for
the system. The system shall be installed in accordance with this
section and shall be part of and be subject to the requirements of
a fire-protective signaling system specified in Section 917.0.
| |
918.3 Approval: All devices, combinations of devices,
appliances and equipment shall be approved for the fire signaling
purpose for which such equipment is used. The automatic fire detectors
shall be smoke detectors, except an approved alternative type of detector
shall be installed in spaces such as boiler rooms where, during normal
operation, products of combustion are present in sufficient quantity
to actuate a smoke detector.
| |
918.4 Where required: An automatic fire-detection
system shall be installed and maintained in full operating condition
in the locations described in Section 918.4.1 through 918.4.4.
| |
918.4.1 Use Group I-1: An automatic fire-detection
system shall be installed and maintained in all occupancies in Use
Group I-1.
| |
918.4.2 Use Group I-2: An automatic fire-detection
system shall be installed and maintained in all occupancies in Use
Group I-2.
| |
918.4.3 Use Group I-3: An automatic fire-detection
system shall be installed and maintained in all resident housing areas
of Use Group I-3. Smoke detectors shall be arranged and positioned
to prevent damage or tampering, provided that the function and speed
of detecting a fire is equivalent to that provided by the spacing
and arrangements of NFiPA 72E listed in Chapter 35.
| |
918.4.4 Use Group R-1: An automatic fire-detection
system shall be installed and maintained in all occupancies in Use
Group R-1.
| |
918.4.5 Use Groups A-1, A-2, A-3, A-4, B, E, F, H, I,
M and S: An automatic fire detector system shall be installed
and maintained in all occupancies in Use Groups A-1, A-2, A-3, A-4,
B, E, F, H, I, M and S.
| |
918.4.6 Special Use: Fire-detection devices shall
be installed in elevator shafts, mechanical room, and elevator discharge
lobbies. This system will activate the elevator capture mode incorporated
into the elevator operation.
| |
918.6 Zones: Zoning shall be provided in accordance
with Section 917.7.3.
| |
918.7 Alarm Verification: Alarms activated by smoke
detectors required by this section shall be activated by either two
cross-zoned smoke detectors within a single protected area or a single
smoke detector monitored by an alarm verification zone or an approved
equivalent method.
| |
918.8 Local Control Functions: Automatic fire detectors
utilized for the purpose of performing local control functions shall
be a part of a fire-protective signaling system. The detector shall,
upon actuation, perform the intended function and activate the alarm-indicating
devices or activate a visible and audible supervisory signal at a
constant attended location.
| |
918.9 Access: Access shall be provided to each
detector for periodic inspection, maintenance and testing.
|
SECTION 919.0 SINGLE AND MULTIPLE STATION SMOKE DETECTORS
| ||
919.1 General: Single and multiple station smoke
detectors shall be of an approved type and shall be installed in accordance
with the provisions of NFiPA 74 listed in Chapter 35.
| ||
919.2 Construction Documents: Where single and
multiple station smoke detectors are required by this code, the construction
documents shall show the location and number with specifications of
the type of detector.
| ||
919.3 Where Required: Single or multiple station
smoke detectors shall be installed and maintained in full operating
condition in the locations described in Sections 919.3 through 919.3.3.
| ||
919.3.1 Use Group R-1: Single and multiple station
smoke detectors shall be installed and maintained in the following
locations in Use Group R-1:
| ||
1.
|
In all sleeping areas
| |
2.
|
In every room in the path of the means of egress from the sleeping
area to the door leading from the guest room or suite; and
| |
3.
|
In each story within the guest room or suite, including basements
| |
919.3.2 Use Group R-2 and R-3: Single and multiple
station smoke detectors shall be installed and maintained in all occupancies
in Use Groups R-2 and R-3 at the following locations:
| ||
1.
|
In the immediate vicinity of bedrooms;
| |
2.
|
In all bedrooms; and
| |
3.
|
In each story within a dwelling unit, including basements.
| |
919.3.3 Use Group I-1: Single or multiple station
smoke detectors shall be installed and maintained in all sleeping
areas in occupancies in Use Group I-1.
| ||
919.4 Interconnection: Where more than one connector
is required to be installed within an individual dwelling unit in
an occupancy in Use Group R-2 or R-3, or within an individual guest
room or suite in an occupancy in Use Group R-1, the detectors shall
be wired in such a manner that the actuation of one alarm will actuate
all of the alarms in the individual unit.
| ||
919.5 Battery Back-up: In addition to the required
AC primary power source, required smoke detectors in occupancies in
Use Groups R-2, R-3 and I-1 shall receive power from a battery when
the AC primary power source is interrupted.
| ||
919.6 Acceptance Testing: When the installation
of the detectors is complete, each detector - and all interconnecting
wiring for multiple station detectors - shall be subject to a 100%
acceptance test in accordance with NFiPA 74 listed in Chapter 15.
|
SECTION 920.0 FIRE EXTINGUISHER
| ||
920.1 Approval: Portable fire extinguisher shall
bear the label of an approved agency, be of an approved type and be
installed in a location visible and available to the occupants.
| ||
920.2 Where Required: A portable fire extinguisher
shall be installed in the following locations in accordance with NFiPA
10 listed in Chapter 35.
| ||
1.
|
In all occupancies in Use Group A, B, E, F, H, I, M, R, And
S;
| |
2.
|
In all areas containing commercial kitchen exhaust hood systems;
| |
3.
|
In all areas where fuel is dispensed;
| |
4.
|
In all areas where flammable or combustible liquid is used in
the operation of spraying, coating or dipping;
| |
5.
|
In all occupancies in Use Group I-3 at staff locations; access
to portable extinguisher shall be permitted to be locked;
| |
6.
|
On each completed floor buildings under construction, other
than occupancies in Use Group R-3;
| |
7.
|
In any laboratory, shop or other room occupied for similar purposes;
and
| |
8.
|
Where required by the fire prevention code listed in Chapter
35.
|
SECTION 921.0 SMOKE CONTROL SYSTEMS
| |
921.1 General: Smoke control systems required by
this code shall conform to the provisions of this section.
| |
921.2 Design Criteria: The smoke control system
shall be designed to keep the smoke layer interface above the highest
of either: the highest unprotected opening to adjoining spaces, or
six feet (1,829 mm) above the highest floor level of exit access open
to the atrium for a period of 20 minutes. This limiting height of
the smoke interface above the atrium floor is "z." Provisions shall
also be made to provide for smoke removal from the atrium at a rate
of not less than two air changes per hour by means of natural or mechanical
ventilation.
| |
921.2.1 Passive System: Active smoke control is
not required where it is shown that the smoke interface level requirement
will be met without operating smoke exhaust.
|
921.2.1.1 Regular Spaces: For spaces with flat
ceilings, a constant horizontal cross-section area above the smoke
layer interface, and an A/H2 ratio between 0.9 and 21, the following
equation shall be used to estimate the height of the interface at
20 minutes:
| ||||
Z = 0.67 H - 0.28H In
| ||||
Where:
| ||||
z
|
=
|
Height from floor to the smoke interface (feet)
| ||
t
|
=
|
Time for interface to descent to z; use 1,200 seconds
| ||
H
|
=
|
Atrium height; floor to flat ceiling (feet)
| ||
Q
|
=
|
Steady heat release rate; use 4,400 Btu/sec. where the primary
use groups is M, S-1, or F-1. Otherwise use 2,000 Btu/sec.
| ||
A
|
=
|
Horizontal cross-sectional are of the above ceiling space being
filled (square feet). Maximum A to be used shall be: A = 21 H2
|
921.2.1.2 Irregular Spaces: For spaces with sloped
or irregular ceilings, A/H2 ratios outside the specified range, or
varying cross sections, the filling time shall be determined using
numerical integration from the ceiling to the critical smoke interface.
The following equations shall be used to determine the rate of smoke
production:
| ||||
Where the interface level is above the limiting elevation (z)
use:
| ||||
V = 20.8Q 1/3 z 5/3 + 3.98 Q
| ||||
Where the interface level is below the limiting elevation (Z)
use:
| ||||
V = 19.7 Q 3/8 z
| ||||
Where:
| ||||
V
|
=
|
the volumetric rate of smoke production (cubic feet per minute)
| ||
z1
|
=
|
limiting elevation (feet) = 0.533 Q 2/3
|
921.2.2 Mechanical Systems: Where the smoke filling
predicted in Section 921.2.1 does not meet the design criteria of
Section 921.2, mechanical exhaust shall be provided to maintain these
conditions.
| ||||
Sufficient mechanical exhaust shall be provided to maintain
the smoke layer interface at or above the critical elevation for the
twenty-minute period. The volumetric rate of smoke production (v)
as determined by the equations in Section 921.2.1.2 shall be used
to determine the exhaust rate to maintain the interface at the critical
level (z). The minimum exhaust rate to be supplied for smoke control
shall be adjusted in accordance with Table 921.2.2.1.
|
Table 921.2.2.1
Minimum Exhaust Rate Adjustment Factora
| |||||||
---|---|---|---|---|---|---|---|
Z/H
|
t/to
V/Ve
| ||||||
0.25
|
0.35
|
0.50
|
0.70
|
0.85
|
0.95
| ||
0.2
|
1.12
|
1.19
|
1.30
|
1.55
|
1.89
|
2.49
| |
0.3
|
1.14
|
1.21
|
1.35
|
1.63
|
2.05
|
2.78
| |
0.4
|
1.16
|
1.24
|
1.40
|
1.72
|
2.24
|
3.15
| |
0.5
|
1.17
|
1.28
|
1.45
|
1.84
|
2.48
|
3.57
| |
0.6
|
1.20
|
1.32
|
1.52
|
2.00
|
2.78
|
4.11
| |
0.7
|
1.23
|
1.36
|
1.61
|
2.20
|
3.17
|
4.98
| |
0.8
|
1.26
|
1.41
|
1.71
|
2.46
|
3.71
|
6.25
|
Note a. Notation:
| |||
Z
|
=
|
Design height of smoke layer interface above fire source
| |
H
|
=
|
Ceiling height above fire source
| |
t
|
=
|
Time for smoke layer interface to descent to z (with exhaust)
(seconds)
| |
to
|
=
|
Value of t in absence of smoke exhaust (see Sections 921.2.1.1
or 921.2.1.2) (seconds)
| |
Ve
|
=
|
Smoke control exhaust rate (minus any airflow into the smoke
layer other than that from the plume)
| |
V
|
=
|
Volumetric smoke production rate (from the equations in Section
921.2.1.2)
|
921.2.3 Operation: The smoke control system shall
be a dedicated system or shall be integrated with the mechanical ventilation
system of the building. Operation of smoke control system shall automatically
shut down all systems and devices which interfere with the effective
operation of the smoke control system. Where the mechanical ventilation
system is designed for smoke control, the return air shall be moved
directly to the outside without recirculation to other areas of the
building.
| ||||
921.2.4 Alternative Systems: An engineered design
which will achieve the same level of smoke control as described in
this section is permitted in lieu of these requirements.
| ||||
921.3 Smoke Removal: Provisions shall be made to
provide ventilation at a rate of at least two air changes per hour
from the atrium. This ventilation shall be through operable vents,
separate mechanical exhaust, or through the building mechanical ventilation
system. The exhaust inlets shall be located a minimum of six feet
(1,829 mm) above any exit access walkway and above any openings into
adjoining spaces. The smoke removal system shall be activated by manual
controls provided for Fire Department use unless it is part of the
smoke control system.
|
921.4 Activation: The smoke control system shall
be activated by actuation of the following:
| ||
1.
|
Automatic sprinkler system;
| |
2.
|
Smoke detectors required by this section that comply with NFiPA
72E listed in Chapter 35
| |
3.
|
Manual controls provided for Fire Department use. The system
shall be activated by a manual fire-protective signaling system
| |
921.4.1 Manual Control: Manual controls shall be
provided at a location approved by the Fire Department.
| ||
921.4.2 Smoke Detector Activation: Where the height
of the atrium ceiling exceeds 30 feet (9,144 mm) above the floor of
the atrium, approved smoke detectors shall be provided to detect smoke
above the highest floor level open to the atrium. The installation
of smoke detectors shall comply with Section 918.0.
| ||
921.5 Standby Power: All equipment required to
provide smoke control in floor openings connecting three or more stories
shall be equipped with a standby source of power that complies with
Section 2707.0.
| ||
921.6 Acceptance: Any required smoke control design
that requires operation of mechanical equipment shall be functionally
tested in accordance with Section 921.6.2 until proper operation of
all required mechanical equipment and control is demonstrated.
| ||
921.6.1 System Operation Report: Prior to acceptance
testing, a report of the required system operations shall be provided
to the Code Official. The following items shall be included in the
report if part of the required system:
| ||
1.
|
Identify type(s) of smoke control activation signal(s), such
as sprinkler water flow, smoke detection, manual, etc., and associated
smoke control systems operation(s) that are activated by the signals.
| |
2.
|
Identify building area(s) where maximum mechanical exhaust to
the outside is implemented and supply air is not provided.
| |
3.
|
Identify building area(s) where maximum air supply is implemented
and exhaust to the outside is not provided.
| |
4.
|
Identify fan(s) which shall be "ON" as required to implement
the smoke control system. If multiple-speed fans are used, the capacity
at which the fans shall operate in the smoke control mode shall be
identified.
| |
5.
|
Identify fan(s) which shall be "OFF" as required to implement
the smoke control system.
| |
6.
|
Identify damper(s) which shall be "OPEN" to implement the smoke
control system.
| |
7.
|
Identify damper(s) which shall be "CLOSED" to implement system.
| |
8.
|
Identify other functions required to implement the smoke control
system.
| |
9.
|
Identify building areas which smoke and heat vents and method
of operation of vents.
| |
10.
|
If required, identify the type(s) of standby power and the equipment
that is served.
| |
921.6.2 Testing Procedures: The acceptance test
procedure shall be approved. Acceptance testing shall be conducted
in the presence of the Code Official or shall include documentation
indicating that all mechanical equipment, control sequences, devices
and components have been operationally tested and are functioning
properly in accordance with the system operation report. All documentation
from operational testing shall be available for inspection. Acceptance
testing shall include the following:
| ||
1.
|
Prior to beginning acceptance teaming, all building smoke control
equipment shall be placed in the normal operation mode.
| |
2.
|
Acceptance testing shall demonstrate that each initiating device,
fan, damper and other required equipment is operational and performs
to the limits and capacity required.
| |
3.
|
Acceptance testing shall demonstrate the correct control outputs
are produced for a given control input for each control sequence specified
by the system operation report.
| |
4.
|
If standby power is required for the operation of the smoke
control system, acceptance tests shall be conducted while on both
normal building power and standby power.
| |
5.
|
Opening of smoke/heat vents shall be demonstrated if the vent
is capable of being opened in a manner that does not require destructive
testing.
|
SECTION 922.0 SMOKE AND HEAT VENTS
| |
922.1 General: Where exit access travel distance
is increased in accordance with Section 1006.5.1, smoke and heat vents
shall be constructed and installed in accordance with this section.
| |
922.2 Vent Size and Spacing: The vent area and
the spacing of the vents shall comply with Table 922.2.
| |
922.2.1 Releasing Devices: Smoke and heat vents
shall open automatically by activation of a heat-responsive device
rated at 100° F. (38° C.), 220° F. (104° C.) above
ambient. The releasing mechanism shall be capable of operation such
that the vent shall fully open when the vent is exposed to a time-temperature
gradient that reaches an air temperature of 500° F. (260°
C.) within five minutes. Vents shall be capable of being opened by
an approved manual operation.
| |
922.3 Curtain Board Construction: Curtain boards
shall be provided to subdivide a vented building. Curtain boards shall
be constructed of material that will resist the passage of smoke and
is consistent with the building type construction. Curtain board location
and depth shall comply with Table. The bottom of the curtain board
shall be level.
|
SECTION 923.0 SUPERVISION
| ||
923.1 Fire-Suppression Systems: All automatic fire-suppression
systems required for occupancies in Use Group A, B, E, H, I, M or
R shall be supervised by Method 1 or 2 below. All automatic fire-suppression
systems in other use groups shall be supervised by one of the following
methods:
| ||
1.
|
Approved central-station system in accordance with NFiPA 71
listed in Chapter 35
| |
2.
|
Approved proprietary system, approve remote-station system or
approved remote-station system or approved supervisory service which
will cause the actuation of an audible appliance at a constantly attended
location, in accordance with NFiPA 72 listed in Chapter 35
| |
3.
|
Locking open all valves on connections to water supplies, sectional
control valves and other valves in supply pipes to fire-protection
devices.
| |
923.2 Fire-protection Signaling Systems: All required
fire-protective signaling systems shall terminate alarm and trouble
signals to an approved central-station system, proprietary system
or remote-station.
|
F.
Building Sewer Code amendments. Amendments to 2003 ICC International
Plumbing Code:
(1)
Section
306 Trenching, Excavation and Backfill. Add:
306.5. Underground Installation of Thermoplastic Pipe
for Building Sewers. Installation of all thermoplastic sewer
pipe for building sewers shall be in strict conformance with ASTM
D 2321, Standard Practice for Underground Installation of Thermoplastic
Pipe for Sewers and Other Gravity-Flow Applications. Pipe foundation
and embedment materials shall be limited to Class IA or Class 1B materials.
(2)
Section
701, General, Paragraph 701.5:
701.5. Damage to drainage system or public sewers. Wastes detrimental to the public sewer system or to the functioning
of the sewage-treatment plant shall be prohibited, regulated, and/or
receive pretreatment in accordance with the provisions of the sewer
use rules and regulations of the publicly opened treatment works responsible
for operation of the public sewer system receiving said sewage discharge,
and the governing federal and state laws and regulations pertaining
to prohibited discharges and pretreatment requirements.
(3)
Section
702, Materials, Paragraph 702.3 Building Sewer Pipe. Add the following
paragraph at the end of the existing paragraph: For pipe material
other than thermoplastic pipe identified in Table 702.3, special application
shall be made with the sewer connection permit application which provides
all necessary data to evaluate the proposed pipe material for the
application intended. Data required may include pipe depth profile,
backfill soil density, superimposed loads that pipe may be exposed
to, trench width, trench shoring methods, and other data appropriate
to the installation. The Code Official is authorized to require specific
pipe material and/or pipe strength for installations where excessive
burial depths may be encountered or where superimposed loads cause
a concern.
(4)
Section
702 Materials, Table 702.3 Building Sewer Pipe:
(a)
Amend: Acrylonitrile butadiene styrene (ABS) plastic pipe Standard
"CSA F 628" to read "ASTM F 628."
(b)
Delete: Coextruded composite ABS DWV schedule 40 IPS Pipe (solid).
(c)
Delete: Coextruded composite ABS DWV schedule 40 IPS pipe (cellular
core).
(d)
Delete: Coextruded composite PVC DWV schedule 40 IPS pipe (solid).
(e)
Delete: Coextruded composite PVC DWV schedule 40 IPS pipe (cellular
core).
(f)
Delete: Coextruded composite PVC IPS-DR, PS140, PA200, DWV.
(g)
Delete: Coextruded composite ABS sewer and drain DR-PS in PS35, PS50,
PS100, PS140, PS200.
(h)
Delete: Coextruded composite PVC sewer and drain DR-PS in PS35, PS50,
PS100, PS140, PS200.
(i)
Amend: Polyvinyl chloride (PVC) plastic pipe (Type DWV, SDR26, SDR35,
SDR41, PS50 or PS100) by deleting "SDR41" as a permissible pipe wall
thickness, and "ASTM D 2949" as a permissible standard.
(j)
Delete: Vitrified clay pipe.
(k)
Add: "Polyvinyl chloride (PVC) plastic pipe, Schedules 40, 80 and
120," referencing standard "ASTM D1785."
(l)
Add: "Ductile Iron Pipe," referencing standard "ANSI A21.50 and A21.51,
Class 52."
(5)
Section
702, Materials, Table 702.4 Pipe Fittings. Add: "Polyvinyl chloride
(PVC) plastic pipe, Schedules 40, 80 and 120," referencing standard
"ASTM D2466; ASTM D2467."
(6)
Section
703, Building Sewer, Paragraph 703.3 Sanitary and storm sewers. Add
to end of first sentence: "provided a minimum spacing of 12 inches
is maintained at all points between the outside walls of the parallel
pipes."
(7)
Section
703, Building Sewer. Add new paragraph:
703.6 Inspection Ports on Building Sewers. An inspection
port shall be installed on each building sewer located just prior
to the connection with the pubic sewer at the easement line. The inspection
port shall consist of a tee and a vertical riser pipe brought to above
grade. Minimum diameter of the riser pipe shall be four inches. The
riser pipe shall be capped with a tamperproof cap. Provide support
for vertical riser in accordance with Section 7.0 Installation, of
ASTM D2321, Standard Practice for Underground Installation of Thermoplastic
Pipe for Sewers and Other Gravity-Flow Applications.
(8)
Section
708, Cleanouts, Paragraph 708.3.2 Building Sewers. Insert new sentence
after first sentence: "Cleanouts shall also be provided at the public
road right-of-way where the building sewer or its service connection
extend under public roads."
(9)
Section
708, Cleanouts. Add new paragraph:
708.10 Cleanout covers. Where cleanouts are installed
on building sewers, the cleanout shall be protected from damage by
lawn mowers and vehicles by an approved cast-iron cleanout cover or
housing set in 12 inch x 12 inch x four-inch deep concrete pad to
secure the housing. Cover shall be flush with grade.
(10)
Section
710, Drainage System Sizing, Paragraph 710.1 Maximum fixture unit
load. Insert new sentence after first sentence: "The building sewer
shall be a minimum diameter of four inches for residential construction,
and a minimum diameter of six inches for commercial construction."
(11)
Section
803, Special Wastes, Paragraph 803.2 Neutralizing device required
for corrosive wastes. Revise paragraph to read: "Corrosive waste shall
not be discharged to the sewer system except as provided for in Section
701, Paragraph 701.5."
(12)
Section
803, Special Wastes, Paragraph 803.3 System Design. Delete last sentence
and replace with: "Chemical waste shall not be discharged to the sewer
system except as provided for in Section 701, Paragraph 701.5."
(13)
Chapter
10, Traps, Interceptors and Separator, Paragraph 1003.3.4 Grease traps
and interceptors. Add new sentence at the end of paragraph: "The responsible
official of the Publicly Owned Treatment Works (POTW) may require
that generators of large volumes of wastewater containing fats, oils
and/or greases from food preparation such as high-volume restaurants,
school cafeterias, assisted living homes, or hospitals install large
outdoor grease interceptors, designed in general conformance with
PDI G101 consisting of a two-compartment vault with a minimal working
volume of 1,000 gallons and provides a minimum hydraulic detention
time of 30 minutes with all fixtures discharging, and other features
as required by the responsible official. All generators of grease-laden
waste shall comply at all times with the POTW's sewer use discharge
limit for grease, fats and oils.
(14)
Chapter
10, Traps, Interceptors and Separators. Add new paragraph as follows:
1003.3.4.3 Maintenance Requirements. The use of
chemical and/or biological additives to grease traps or grease interceptors
shall be prohibited. The cleaning method used shall be of the suction
type and/or skimming of the grease, and shall be performed at regular
intervals. Flushing of traps and interceptors shall be prohibited.
A written record of said cleaning shall be kept on file at the site
of the grease trap or interceptor and available for inspection by
the Code Official and/or the responsible official of the POTW upon
request. The record shall include the date and time of cleaning, and
the signature of the person performing the cleaning. The Code Official
and/or the responsible official of the POTW is authorized to require
more frequent cleanings.
[Added 6-28-2004 by Ord. No. 643; amended 11-22-2004 by Ord. No.
647]
A.
Administration and enforcement of the Code within Peters Township
shall be undertaken in any of the following ways as determined by
the governing body of this Township from time to time by resolution:
(1)
By the designation of an employee of the Township to serve as the
Township Code Official to act on behalf of the Township;
(2)
By the retention of one or more construction Code Officials or third-party
agencies to act on behalf of the Township;
(3)
By agreement with one or more other townships for the joint administration
and enforcement of this Act through an intermunicipal agreement;
(4)
By entering into a contract with another municipality for the administration
and enforcement of this Act on behalf of this Township;
(5)
By entering into an agreement with the Pennsylvania Department of
Labor and Industry for plan review, inspections and enforcement of
structures other than one-family or two-family dwelling units and
utility and miscellaneous use structures.
B.
A Board of Appeals shall be established by resolution of the governing
body of this Township in conformity with the requirements of the relevant
provisions of the Code, as amended from time to time, and for the
purposes set forth therein. If at any time enforcement and administration
is undertaken jointly with one or more other townships, said Board
of Appeals shall be established by joint action of the participating
townships.
[Amended 6-8-1998 by Ord. No. 588; 6-28-2004 by Ord. No. 643]
The Township Manager shall certify to the adoption of this article
and cause the same to be published as required by law; and this article
shall take full force and effect five days after this date of final
passage and approval.