[Ord. No. 96-807 Art. V §1, 3-4-1996; Ord. No. 2009-47 Art. V §1, 10-5-2009]
No person shall discharge any stormwater, surface water, ground
water, roof runoff, subsurface drainage, including interior and exterior
foundation drains, other sources of surface runoff or ground water,
uncontaminated cooling water or unpolluted industrial process waters
to any sanitary sewer.
[Ord. No. 96-807 Art. V §2, 3-4-1996; Ord. No. 2009-47 Art. V §2, 10-5-2009]
Stormwater and all other unpolluted drainage shall be discharged
to such sewers as are specifically designated as combined sewers or
storm sewers or to a natural outlet approved by the Superintendent.
Industrial cooling water or unpolluted process waters may be discharged,
on approval of the Superintendent to a storm sewer, combined sewer
or natural outlet.
[Ord. No. 96-807 Art. V §3, 3-4-1996; Ord. No. 2009-47 Art. V §3, 10-5-2009]
A. No
person shall discharge or cause to be discharged any of the following
described waters or wastes to any public sewers:
1. Any gasoline, benzene, naphtha, fuel oil or other flammable or explosive
liquid, solid or gas.
2. Any waters or wastes containing toxic or poisonous solids, liquids
or gases in sufficient quantity, either singly or by interaction with
other wastes, to injure or interfere with any sewage treatment process,
constitute a hazard in the receiving waters of the sewage treatment
plant including, but not limited to, cyanides in excess of two (2)
mg/1 as CN in the wastes as discharged to the public sewer.
3. Any waters or wastes having a pH lower than five and one-half (5.5)
or having any other corrosive property capable of causing damage or
hazard to structures, equipment and personnel of the sewage works.
4. Solid or viscous substances in quantities or of such size capable
of causing obstruction to the flow in sewers or other interference
with the proper operation of the sewage works such as, but not limited
to, ashes, cinders, sand, mud, straw, shavings, metal, glass, rags,
feathers, tar, plastics, wood, ungrounded garbage, whole blood, paunch
manure, hair and fleshings, entrails and paper dishes, cups, milk
containers, etc., either whole or ground by garbage grinders.
[Ord. No. 96-807 Art. V §4, 3-4-1996; Ord. No. 2009-47 Art. V §4, 10-5-2009]
A. No
person shall discharge or cause to be discharged the following described
substances, materials, waters or wastes if it appears likely in the
opinion of the Superintendent that such wastes can harm either the
sewers, sewage treatment process or equipment, have an adverse effect
on the receiving stream, or can otherwise endanger life, limb, public
property or constitute a nuisance. In forming an opinion as to the
acceptability of these wastes, the Superintendent will give consideration
to such factors as the quantities of subject wastes in relation to
flows and velocities in the sewers, materials of construction of the
sewers, nature of the sewage treatment process, capacity of the sewage
treatment plant, degree of treatability of wastes in the sewer treatment
plant and other pertinent factors. The substances prohibited are:
1. Any liquid or vapor having a temperature higher than one hundred
fifty degrees Fahrenheit (150°F) or sixty-five degrees Centigrade
(65°C).
2. Any water or wastes containing fats, wax, grease or oils, whether
emulsified or not, in excess of one hundred (100) mg/1 or containing
substances which may solidify or become viscous at temperatures between
thirty-two degrees Fahrenheit (32°F) and one hundred fifty degrees
Fahrenheit (150°F) or zero (0) and sixty-five degrees Centigrade
(65°C).
3. Any garbage that has not been properly shredded. The installation
and operation of any garbage grinder equipped with a motor of three-fourths
(¾) horsepower (0.76 hp metric) or greater shall be subject
to the review and approval of the Superintendent.
4. Any waters or wastes containing strong acid iron pickling wastes
or concentrated plating solutions whether neutralized or not.
5. Any waters or wastes containing iron, chromium, copper, zinc and
similar objectionable or toxic substances; or wastes exerting an excessive
chlorine requirement to such degree that any such material received
in the composite sewage at the sewage treatment works exceeds the
limits established by the Superintendent for such materials.
6. Any waters or wastes containing phenols or other taste- or odor-producing
substances in such concentrations exceeding limits which may be established
by the Superintendent as necessary, after treatment of the composite
sewage, to meet the requirements of the State, Federal or other public
agencies of jurisdiction for such discharge to the receiving waters.
7. Any radioactive wastes or isotopes of such half-life or concentration
as may exceed limits established by the Superintendent in compliance
with applicable State or Federal regulations.
8. Any waters or wastes having a pH in excess of nine and one-half (9.5).
9. Materials which exert or cause:
a. Unusual concentrations of inert suspended solids (such as, but not
limited to, Fuller's earth, lime slurries and lime residues) or of
dissolved solids (such as, but not limited to, sodium chloride and
sodium sulfate).
b. Excessive discoloration (such as, but not limited to, dye wastes
and vegetable tanning solutions).
c. Unusual BOD, chemical oxygen demand or chlorine requirements in such
quantities as to constitute a significant load on the sewage treatment
works.
d. Unusual volume of flow or concentration of wastes constituting "slugs"
as defined herein.
10. Waters or wastes containing substances which are not amenable to
treatment or reduction by the sewage treatment processes employed
or are amenable to treatment only to such degree that the sewage treatment
plant effluent cannot meet the requirements of the other agencies
having jurisdiction over discharge to the receiving waters.
11. Any waters or wastes having:
a. A BOD greater than three hundred (300) parts per million by weight,
or
b. Containing more than three hundred fifty (350) parts per million
by weight of suspended solids, or
c. Having an average daily flow greater than two percent (2%) of the
average sewage flow of the City shall be subject to the review of
the Superintendent.
Where necessary in the opinion of the Superintendent, the owner
shall provide, at his expense, such preliminary treatment as may be
necessary to:
(1)
Reduce the biochemical oxygen demand to three hundred (300)
parts per million by weight, or
(2)
Reduce the suspended solids to three hundred fifty (350) parts
per million by weight, or
(3)
Control the quantities and rates of discharge of such waters
or wastes.
|
Plans, specifications and any other pertinent information relating
to proposed preliminary treatment facilities shall be submitted for
the approval of the Superintendent and no construction of such facilities
shall be commenced until said approvals are obtained in writing.
|
[Ord. No. 96-807 Art. V §5, 3-4-1996; Ord. No. 2009-47 Art. V §5, 10-5-2009]
A. If any waters or wastes are discharged or are proposed to be discharged to the public sewers, which waters contain the substances or possess the characteristics enumerated in Section
705.280 of this Article, and which in the judgment of the Superintendent may have a deleterious effect upon the sewage works, processes, equipment or receiving waters, or which otherwise create a hazard to life or constitute a public nuisance, the Superintendent may:
2. Require pretreatment to an acceptable condition for discharge to
the public sewers,
3. Require control over the quantities and rates of discharge, and/or
4. Require payment to cover the added cost of handling and treating the wastes not covered by existing taxes or sewer charges under the provisions of Section
705.340 of this Article.
|
If the Superintendent permits the pretreatment or equalization
of waste flows, the design and installation of the plants and equipment
shall be subject to the review and approval of the Superintendent
and subject to the requirements of all applicable codes, ordinances
and laws.
|
[Ord. No. 96-807 Art. V §6, 3-4-1996; Ord. No. 2009-47 Art. V §6, 10-5-2009]
Grease, oil and sand interceptors shall be provided when, in
the opinion of the Superintendent, they are necessary for the proper
handling of liquid wastes, sand or other harmful ingredients; except
that such interceptors shall not be required for private living quarters
or dwelling units. All interceptors shall be of a type and capacity
approved by the Superintendent and shall be located as to be readily
and easily accessible for cleaning and inspection.
[Ord. No. 96-807 Art. V §7, 3-4-1996; Ord. No. 2009-47 Art. V §7, 10-5-2009]
Where preliminary treatment or flow-equalizing facilities are
provided for any waters or wastes, they shall be maintained continuously
in satisfactory and effective operation by the owner at his expense.
[Ord. No. 96-807 Art. V §8, 3-4-1996; Ord. No. 2009-47 Art. V §8, 10-5-2009]
When required by the Superintendent, the owner of any property
serviced by a building sewer carrying industrial wastes shall install
a suitable control manhole together with such necessary meters and
other appurtenances in the building sewer to facilitate observation,
sampling and measurement of the wastes. Such manhole, when required,
shall be accessibly and safely located and shall be constructed in
accordance with plans approved by the Superintendent. The manhole
shall be installed by the owner at his expense and shall be maintained
by him so as to be safe and accessible at all times.
[Ord. No. 96-807 Art. V §9, 3-4-1996; Ord. No. 2009-47 Art. V §9, 10-5-2009]
All measurements, tests and analyses of the characteristics
of waters and wastes to which reference is made in this Chapter shall
be determined in accordance with the latest edition of "Standard Methods
for the Examination of Water and Wastewater" published by the American
Public Health Association, and shall be determined at the control
manhole provided or upon suitable samples taken at said control manhole.
In the event that no special manhole has been required, the control
manhole shall be considered to be the nearest downstream manhole in
the public sewer to the point at which the building sewer is connected.
Sampling shall be carried out by customarily accepted methods to reflect
the effect of constituents upon the sewage works and to determine
the existence of hazards to life, limb and property. (The particular
analyses involved will determine whether a twenty-four (24) hour composite
of all outfalls of a premise is appropriate or whether a grab sample
or samples should be taken. Normally, but not always, BOD and suspended
solids analyses are obtained from twenty-four (24) hour composites
of all outfalls whereas pH analyses are determined from periodic grab
samples.)
[Ord. No. 96-807 Art. V §10, 3-4-1996; Ord. No. 2009-47 Art. V §10, 10-5-2009]
No statement contained in this Article shall be construed as
preventing any special agreement or arrangement between the City and
any industrial concern whereby an industrial waste of unusual strength
or character may be accepted by the City for treatment, subject to
payment therefore by the industrial concern.