[HISTORY: Adopted by the Board of Supervisors of the Township
of West Deer as indicated in article histories. Amendments noted where
applicable.]
[Adopted 2-16-2011 by Ord. No. 386]
A.
All buildings with standpipe hose connections shall be furnished
with 1.5-inch NST or 2.5-inch NST connections.
B.
All buildings with sprinkler feed lines (fire department connections)
or fire pumps shall be furnished with two 2.5-inch female NST connections
or one five-inch NFPA nonthreaded connection (Storz) when the gallons
per minute (GPM) rating permits such a connection.
C.
All public or private hydrants (excluding dry hydrants) shall be
furnished with two 2.5-inch NST threaded hose connections and one
five-inch NFPA nonthreaded connection (Storz) when the gallons per
minute (GPM) rating permits such a connection.
D.
All public or private dry hydrants shall be furnished with one six-inch
NST female connection.
E.
Furthermore, all fire department connections shall be covered with
nonlocking caps when not in use.