Exciting enhancements are coming soon to eCode360! Learn more 🡪
Town of Brookhaven, NY
Suffolk County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
[Added 5-12-2016 by L.L. No. 11-2016, effective 5-25-2016]
This article shall outline the requirements for the installation, testing, inspection and maintenance of carbon monoxide detection systems, alarms, and associated components and devices, as prescribed herein and shall pertain to all commercial structures, newly constructed and/or relocated into the Town of Brookhaven, as well as all existing commercial structures regardless of date of construction. Occupancies included; A, B, E, F, H, I (regardless of sleeping area locations), M, and S. Detection systems and alarms shall be in compliance with the New York State Uniform Fire Prevention and Building Code, but in the event of a conflict between the Uniform Code and the requirements of the Town of Brookhaven specified herein, the requirements of the Town of Brookhaven specified herein shall apply.
A. 
As used in this article, the following terms shall have the meanings indicated:
APPROVED
Acceptable to the authority having jurisdiction.
CARBON MONOXIDE ALARM
A single- or multiple-station carbon monoxide alarm intended for the purpose of detecting carbon monoxide gas and alerting occupants by a distinct audible signal comprising an assembly that incorporates a sensor control component and an alarm notification appliance in a single unit operated from a power source either located in the unit or obtained at the point of installation.
CARBON MONOXIDE DETECTION CONTROL UNIT
A component of the carbon monoxide detection system, provided with primary and secondary power sources, which receives signals from initiating devices or other carbon monoxide detection control units, and processes these signals to determine part or all of the required carbon monoxide detection system output function(s).
CARBON MONOXIDE DETECTOR
A device connected to an alarm control unit having a sensor that responds to carbon monoxide.
CARBON MONOXIDE SAFETY FUNCTIONS
Building and carbon monoxide functions that are intended to increase the level of life safety for occupants or to control the spread of the harmful effects of carbon monoxide.
CHIEF FIRE MARSHAL
The Chief Fire Marshal of the Town of Brookhaven.
CONTROL UNIT
A system component that monitors inputs and controls outputs through various types of circuits.
FUEL-BURNING APPLIANCE
A device or equipment that burns solid, liquid or gaseous fuel or a combination thereof, for any process, including, but not limited to, heating, cooking, manufacturing and the like.
LISTED
A device, component and/or system which has been tested to an applicable standard and approved by a nationally recognized testing firm for a specific application/use. Carbon monoxide detectors and alarms installed in commercial buildings shall be listed in accordance with UL 2075. Where installation is permitted by these requirements, hard-wired carbon monoxide alarms shall be listed in accordance with UL 2034. A carbon monoxide control unit shall be listed for the purpose for which it is used. Where no carbon monoxide product standard exists, products listed for fire alarm service shall be permitted. A fire alarm control panel to which carbon monoxide detectors and alarms will be connected shall be listed in accordance with UL 864.
MULTI-PURPOSE ALARM
An alarm that incorporates detection capabilities for more than one hazardous condition, such as fire, fuel gas, or carbon monoxide.
MULTIPLE-STATION CARBON MONOXIDE ALARM
A single-station carbon monoxide detection alarm capable of being interconnected to one or more additional alarms so that the actuation of one causes the appropriate alarm signal to operate in all interconnected alarms.
NOTIFICATION APPLIANCE
A system component such as a bell, horn, speaker, light, or text display that provides audible, tactile, or visible outputs, or any combination thereof.
SINGLE-STATION CARBON MONOXIDE ALARM
A detector comprising an assembly that incorporates a sensor, control components, and an alarm notification appliance in one unit operated from a power source either located in the unit or obtained at the point of installation.
B. 
Signals:
CARBON MONOXIDE ALARM SIGNAL
A signal indicating a concentration of carbon monoxide at or above the alarm threshold that could pose a risk to the life safety of the occupants and that requires an immediate action.
SUPERVISORY SIGNAL
A signal indicating the need for action in connection with a pre-alarm condition, or in connection with the supervision of protected premises carbon monoxide safety functions or equipment, or the maintenance features of related systems.
TROUBLE SIGNAL
A signal initiated by a system or device indicative of a fault in a monitored circuit, system, or component.
C. 
Systems:
CARBON MONOXIDE DETECTION SYSTEM
A system or portion of a combination system that consists of a control unit, components, and circuits arranged to monitor and annunciate the status of carbon monoxide initiating devices and to initiate the appropriate response to those signals.
COMBINATION CARBON MONOXIDE DETECTION SYSTEM
A carbon monoxide detection system in which components are used, in whole or in part, in common with a non-carbon monoxide signaling system, and in which components are not used as part of a fire alarm system.
COMBINATION SYSTEM
A fire alarm system in which components are used, in whole or in part, in common with a non-fire signaling system, such as approved carbon monoxide devices.
A. 
Carbon monoxide detection alarms and systems installed within the Town of Brookhaven shall provide life safety protection and notification for the premises that requires said installation.
B. 
All carbon monoxide detection systems and, where permitted, carbon monoxide alarms, installed and maintained within the Town of Brookhaven, shall be in compliance with these requirements, the New York State Uniform Fire Prevention and Building Code, NFPA 70, NFPA 72, and NFPA 720.
C. 
All carbon monoxide detection devices, including but not limited to detectors, alarms, and associated components, shall be listed or approved as specified herein by a nationally recognized testing laboratory for the purpose for which they are used and shall be installed in conformity with nationally recognized standards and the manufacturer's installation specifications.
D. 
Where an approved fire alarm system exists within a building that is capable of being interconnected to carbon monoxide detection devices, the carbon monoxide detection shall be interconnected to the existing fire alarm system. Activation of any carbon monoxide detector or alarm so connected shall neither cause activation of the fire alarm system and associated audible and visual devices, nor cause transmission of a fire alarm signal to the central station monitoring said system. Activation of any carbon monoxide detector or alarm so connected shall cause activation of a temporal 4 audible alarm, annunciation of a carbon monoxide activation at the control panel, the transmission of a carbon monoxide activation signal to the central station monitoring said system, and initiate the shut-down of all heating, ventilation and air-conditioning equipment, with the exception of exhaust systems related to cooking operations.
E. 
In buildings without an existing fire alarm system where such system is not required, and buildings with an approved existing fire alarm system that is incapable of interconnection of carbon monoxide detection, carbon monoxide alarms may be permitted to be installed in a manner prescribed by the Chief Fire Marshal following a review of the existing conditions.
F. 
Where carbon monoxide alarms are permitted, such alarms shall be hard-wired to the building electrical system and equipped with battery backup. Such work shall be performed by a licensed electrician.
A. 
All carbon monoxide detection and carbon monoxide systems installed and maintained within the Town of Brookhaven shall be in compliance with these requirements, the New York State Uniform Fire Prevention and Building Code, NFPA 70, NFPA 72 and NFPA 720.
B. 
All carbon monoxide detection devices shall be listed or approved by a nationally recognized testing laboratory for the purpose for which they will be used and shall be installed in conformity with nationally recognized standards and the manufacturer's instructions and specifications. All initiating devices and/or circuits, when part of a carbon monoxide detection system or combination system, shall latch upon alarm activation. Non-latching system initiating devices or circuits shall not be permitted.
C. 
Carbon monoxide detectors shall be located and installed on the ceiling in the same room as permanently installed fuel-burning appliances, in addition to other locations specified by these requirements.
D. 
Carbon monoxide detectors shall be centrally located on every habitable level and in every heating, ventilation and air-conditioning (HVAC) zone of a building. Where multiple HVAC zones exist in the same open area, and said area is less than 10,000 square feet, one carbon monoxide detector centrally located in said area shall be permitted. Where a HVAC zone of a building is 10,000 square feet or more in area, additional carbon monoxide detectors shall be installed such that no point in said area is more than 100 feet from a carbon monoxide detector. In all instances, any spacing requirements specified by the manufacturer of the carbon monoxide detector(s) installed shall be complied with and take precedence over the area requirements of this section when such manufacturer's spacing requirements are more restrictive than those specified herein.
E. 
In "I" occupancies, carbon monoxide detectors shall be installed on every story containing a sleeping area, within 15 feet of a sleeping area. More than one carbon monoxide detector shall be provided where necessary to assure that no sleeping area on such story is more than 15 feet away from a carbon monoxide detector. Carbon monoxide alarms shall be installed in each sleeping area containing a carbon monoxide source.
F. 
Assembly occupancies shall require additional carbon monoxide detectors in every room accommodating 50 or more occupants, in addition to other locations specified by these requirements.
G. 
Public waiting areas shall require carbon monoxide detection devices within the space, in addition to other locations specified by these requirements.
H. 
Upon activation of any system or device detecting carbon monoxide, a temporal 4 audible signal separate and distinct from a fire alarm audible signal shall be initiated, advising the occupants of the presence of carbon monoxide.
I. 
The activation of a carbon monoxide detection system shall initiate the shut-down of all heating, ventilation and air-conditioning equipment, with the exception of exhaust systems related to cooking operations.
J. 
Carbon monoxide detectors that are ceiling-mounted shall be located a minimum of 12 inches from any wall or as specified by manufacturer's specifications.
K. 
Carbon monoxide detectors that are wall-mounted shall be a minimum of 80 inches off the finished floor and at least six inches from the ceiling or as specified by manufacturer's specifications.
L. 
Carbon monoxide detectors shall be located a minimum of 36 inches from any HVAC supply or return register.
M. 
Carbon monoxide detectors are considered life safety devices and therefore shall send trouble signals to the control panel and facilitate wiring supervision.
N. 
Carbon monoxide detectors interconnected to fire alarm control panels shall initiate a temporal four alarm sequence upon activation of the carbon monoxide detector.
O. 
Where an approved existing fire alarm control panel is not capable of a temporal four-alarm sequence, internal sounding bases for the carbon monoxide detectors may be an acceptable alternative, upon review and approval of the Chief Fire Marshal.
P. 
All system-initiating devices and circuits shall latch upon alarm activation.
All carbon monoxide detection systems shall be supervised by a UL-listed central station or, where permitted, a continuously staffed supervising station located on the premises, with means of initiating the notification sequence as prescribed below.
A. 
Upon receipt of a carbon monoxide detection alarm signal by the central station or supervising station, the following notification sequence shall be followed:
(1) 
Local fire department/emergency response agency.
(2) 
Building occupants.
(3) 
Any other emergency contact; i.e., building management/owner.
B. 
Upon receipt of a carbon monoxide detection supervisory or trouble signal by the central station or supervising station, the following notification shall be made: building management/owner and/or other emergency contact(s).
A. 
The following reference standards shall be utilized for design, installation, testing, inspection and maintenance. The applicable edition of each reference standard specified herein shall be that as specified by the New York State Uniform Fire Prevention and Building Code.
(1) 
NFPA 70: National Electric Code.
(2) 
NFPA 72: National Fire Alarm and Signaling Code.
(3) 
NFPA 72: Installation of Carbon Monoxide (CO) Detection and Warning Equipment.
B. 
Where a conflict exists between the reference standards and the requirements of the Town of Brookhaven specified herein, the requirements of the Town of Brookhaven as specified herein shall apply.
A. 
Buildings/Structures exempted.
(1) 
No carbon monoxide detection shall be required in buildings/structures that:
(a) 
Do not utilize fossil-fuel-burning equipment for cooking, heating or any other processes; and
(b) 
Do not have vehicles or other equipment which are powered by fossil fuel stored or located at any time within the building or structure; and
(c) 
Do not have attached parking garages.
(2) 
Should, at any time, conditions change that cause a building/structure to not comply with any of the above exceptions, the building owner shall immediately make notification to the Division of Fire Prevention, and the appropriate carbon monoxide detection shall be installed in compliance with the requirements herein.
B. 
The Chief Fire Marshal may allow deviations from the listed reference standards and/or these requirements in whole or in part, when it has been conclusively proven to the Chief Fire Marshal that such deviations are necessary and practical, while ensuring the performance intent of these requirements is met.
All persons, firms, business entities or corporations installing, inspecting, testing, and providing maintenance on any carbon monoxide detection system, combination carbon monoxide detection system or combination system shall possess a valid security or fire alarm systems installer license issued by the New York State Department of State, Division of Licensing Services, and shall possess a certification or approval from the system(s) manufacturer indicating the installer is factory-trained and/or certified/authorized for the specific brand/model of system and/or components being installed or maintained.
A. 
Prior to the commencement of any installation or modification of a carbon monoxide detection system, combination carbon monoxide detection system or combination system, a permit shall be obtained from the Division of Fire Prevention.
B. 
All submissions shall comply with these requirements, applicable reference standards, and the New York State Uniform Fire Prevention and Building Code, and shall include the following:
(1) 
Fire prevention permit application (FP-10).
(2) 
Property owner/agent authorization form.
(3) 
A copy of the security or fire alarm installer's license issued by the NYS Department of State, Division of Licensing Services.
(4) 
Permit submission shall include the required fee pursuant to the current fee schedule.
(5) 
Two sets of plans, bearing the stamp/seal of a New York State licensed design professional; ensure HVAC zones are clearly depicted on the submission. Exception: Buildings/Structures where carbon monoxide detection and associated components are being interconnected with an existing fire alarm system, and where the building is a single occupancy, and where installation of five or fewer carbon monoxide devices is required for adequate protection, a scope of work description submitted by the installer to the Division of Fire Prevention on a form prescribed by the Chief Fire Marshal will be accepted in lieu of plans.
(6) 
Manufacturer's documentation for all components of the system.
(7) 
Proof of installer's certification or approval from the system(s) manufacturer indicating the installer is factory-trained and/or certified/authorized for the specific brand/model of system and/or components being installed.
C. 
Permit not required. Where carbon monoxide alarms are permitted pursuant to § 80-175 of these requirements, an affidavit of installation on a form prescribed by the Chief Fire Marshal shall be filed with the Division of Fire Prevention by the building owner, in lieu of the permit process and fee required herein.
A. 
Once the installation or modification of a carbon monoxide detection system, combination carbon monoxide detection system or combination system has been completed in accordance with the approved permit submission and verified by the installer to be in full operating condition, the installer shall contact the Division of Fire Prevention to schedule a certificate of compliance inspection.
B. 
A certificate of compliance inspection shall be conducted in the presence of a Fire Marshal from the Division of Fire Prevention, during which the following shall be witnessed and/or verified:
(1) 
Testing of all systems/detection devices shall be performed by the introduction of carbon monoxide into the sensing chamber or element. Test/Activation by other means, such as magnets, is not acceptable.
(2) 
The result of each carbon monoxide detector test shall be confirmed through indication at the detector and the control panel.
(3) 
The operation of all occupant notification devices shall be witnessed.
(4) 
Circuit supervision, "Trouble," "Supervisory" and "Alarm" conditions, shall be witnessed.
(5) 
Receipt of alarm at central station or supervising station shall be verified.
C. 
A certificate of completion shall be submitted to the Fire Marshal upon completion of the inspection.
A. 
Testing of all systems/detection devices shall be performed by the introduction of carbon monoxide into the sensing chamber or element. Test/Activation by other means, such as magnets, is not acceptable.
B. 
Unless otherwise specified by the manufacturer's instructions/specifications, intervals of inspection, testing and maintenance shall be in compliance with the applicable reference standard.
C. 
End of life. Replacement of detection devices shall be at intervals indicated by the applicable reference standards or manufacturer's instructions/specifications, whichever is more stringent.