That a certain document, two copies of which are on file in the office of the Clerk of Council of the City of Harrington, being marked and designated as the International Building Code, 2018 edition, be and is hereby adopted as the Building Code of the City of Harrington for regulating and governing the conditions and maintenance of all property, buildings, and structures, by providing the standards for supplied utilities and facilities and other physical things and conditions essential to ensure that structures are safe, sanitary, and fit for occupation and use; and the condemnation of buildings and structures unfit for human occupancy and use and the demolition of such structures as herein provided; providing for the issuance of permits and collection of fees therefor; and each and all of the regulations, provisions, penalties, conditions, and terms of said Building Code on file in the office of the City of Harrington and hereby referred to, adopted, and made a part hereof, as if fully set out in this article, with the additions, insertions, deletions, and changes, if any, prescribed in §
102-2, Revisions.
The following sections are hereby revised:
A. Section 903.2.8 Group R. Modify language to read:
An automatic sprinkler system installed in accordance with section
903.3 shall be provided throughout all buildings with a Group R fire
area, except Group R-3 one and two family, detached and semi-detached
buildings, with a separate means of egress. Automatic Sprinkler system.
Group R-3 occupancies defined and regulated by the International Residential
Code as detached one- and two-family dwellings and townhouses not
more than three stories above grade plane in heigh with a separate
means of egress per dwelling, are exempt from the requirement to install
an automatic fire sprinkler system. Group R-1, R-2, R-3, R-4 dwelling
units and sleeping units located within and a part of mixed-use commercial
buildings and regulated by the International Building Code are not
exempted from the Group R sprinkler requirement.
|
Congregate living facilities, such as boarding houses, lodging
houses, care facilities, dormitories, fraternities, sororities, apartment
houses of two or more units classified as R-3 and mixed-use occupancy
buildings containing any Group R with any other occupancy use are
not exempted from the automatic sprinkler requirement.
|
B. Appendix E, Supplementary Accessibility Requirements, is hereby adopted.
That a certain document, two copies of which are on file in the office of the Clerk of Council of the City of Harrington, being marked and designated as the International Residential Code, 2018 edition, be and is hereby adopted as the Residential Code of the City of Harrington for regulating and governing the construction, alteration, movement, enlargement, replacement, repair, equipment, location, removal, and demolition of detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories in height with separate means of egress as herein provided; providing for the issuance of permits and collection of fees therefor; and each and all of the regulations, provisions, penalties, conditions, and terms of said Residential Code on file in the office of the City of Harrington and hereby referred to, adopted, and made a part hereof, as if fully set out in this article, with the additions, insertions, deletions, and changes, if any, prescribed in §
102-4, Revisions.
The following sections are hereby revised:
A. Section 301.2 (Climate and geographic design criteria). Fill in chart
as follows:
Ground snow load
|
25
|
Wind design
|
|
Speed (mph)(Vasd/Vult)
|
89/115 3-second gust
|
Topographic effects
|
No
|
Special wind region
|
No
|
Seismic design category subject to damage from
|
A
|
Weathering
|
Severe
|
Frost line depth
|
24"
|
Termite
|
Moderate to heavy
|
Winter design temperature
|
14 deg. F
|
Ice barrier underlayment required
|
No
|
Flood hazards
|
June 1, 1977
|
Air freezing index
|
250
|
Mean annual temperature
|
55.7
|
Assumed soil bearing
|
2,000 psf
|
Elevation
|
30'
|
Latitude
|
N3854
|
Winter heating
|
18° F.
|
Summer cooling
|
90° F.
|
Altitude correction factor
|
N/A
|
Indoor design temperature
|
72° F.
|
Design temperature cooling
|
75° F.
|
Heating temperature difference
|
54° F.
|
Cooling temperature difference
|
15° F.
|
Wind velocity heating
|
N/A
|
Wind velocity cooling
|
N/A
|
Daily range
|
L
|
Winter humidity
|
50%
|
Summer humidity
|
50%
|
B. Section 311.7.5 is revised by deleting the section in its entirety
and substituting the following:
311.7.5 Stair treads and risers. Stair treads and
risers shall meet the requirements of this section. For the purposes
of this section all dimensions and dimensioned surfaces shall be exclusive
of carpets, rugs or runners.
|
R311.7.5.1 Risers. 8 1/4 inches
(209.6 mm).
|
R311.7.5.2 Treads. 9 inches (229 mm).
|
C. Section 313 Automatic Fire Sprinkler systems is revised by deleting
the section in its entirety.
D. Add Section 614 Pole Buildings. Refer to current adopted Kent County
Supplement to the 2012 International Building Code and 2012 International
Residential Code.
E. Add Section 615 Pole Buildings. Refer to current adopted Kent County
Supplement to the 2012 International Building Code and 2012 International
Residential Code.
F. Add Section 616 Pole Buildings. Refer to current adopted Kent County
Supplement to the 2012 International Building Code and 2012 International
Residential Code.
G. Add Section 617 Pole Buildings. Refer to current adopted Kent County
Supplement to the 2012 International Building Code and 2012 International
Residential Code.
H. Chapter 11, Energy Efficiency, is revised by deleting the chapter
in its entirety and referring to the currently adopted Delaware State
Energy Code.
I. Part V - Mechanical (Chapters
12 through 23). Deleted in their entirety by way of DE Title 24, Chapter 1806. This reference adopts the 2015 IPC, IMC and IFGC for all installations in the State of Delaware.
J. Part VI - Fuel Gas (Chapter 24). Deleted in its entirety by way of
DE Title 24, Chapter 1806. This reference adopts the 2015 IPC, IMC
and IFGC for all installations in the State of Delaware.
K. Part VII - Plumbing (Chapters 25 through 33). Deleted in their entirety
by way of DE Title 24, Chapter 1806. This reference adopts the 2015
IPC, IMC and IFGC for all installations in the State of Delaware.
L. Part VIII - Electrical (Chapters 34 through 43). Deleted in their
entirety; refer to current adopted State Electrical Code by way of
the Office of the State Fire Marshal.
M. Appendix M, Home Day Care - R-3 Occupancy is hereby adopted.
N. Appendix Q, Tiny Houses is hereby adopted.