As used in this article, the following terms shall have the meanings indicated:
AIR-GAP SEPARATIONA physical break between a supply pipe and a receiving vessel. The air gap shall be at least double the diameter of the supply pipe, measured vertically above the top rim of the vessel, in no case less than one inch.
APPROVED CHECK VALVEA check valve that seats readily and completely. It must be carefully machined to have free moving parts and assured watertightness. The face of the closure element and valve seat must be bronze, composition, or other non-corrodible material which will seat tightly under all prevailing conditions of field use. Pins and bushings shall be of bronze or other non-corrodible, non-sticking material, machined for easy, dependable operation. The closure element, e.g., clapper, shall be internally weighted or otherwise equipped to promote rapid and positive closure in all sizes where this feature is obtainable.
APPROVED DOUBLE CHECK VALVE ASSEMBLYAn assembly of at least two independently acting check valves, including tightly closing shutoff valves on each side of the check valve assembly and suitable leak detector drains plus connections available for testing the watertightness of each check valve. This device must be approved as a complete assembly.
APPROVED REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION DEVICEA. A device incorporating two or more check valves and an automatically operating differential relief valve located between the two checks, two shutoff valves, and equipped with necessary appurtenances for testing. The device shall operate to maintain the pressure in the zone between the two check valves, less than the pressure on the public water supply side of the device.
B. At cessation of normal flow, the pressure between check valves shall be less than the supply pressure. In case of leakage of either check valve, the differential relief valve shall operate to maintain this reduced pressure by discharging to the atmosphere. When the inlet pressure is two pounds per square inch or less, the relief valve shall open to the atmosphere, thereby providing an air gap in the device. To be approved, these devices must be readily accessible for maintenance and testing and installed in a location where no part of the valve will be submerged. The enclosure must be self-draining, so that the large amount of water which the relief valve may vent will be disposed of reliably without submergence of the relief valve.
C. This device must also be approved as a complete assembly.
AUXILIARY SUPPLYAny water supply on or available to the premises other than the approved public water supply.
BAROMETRIC LOOPA loop of pipe rising approximately 35 feet, at its topmost point, above the highest fixture it supplies.
CERTIFIED BACKFLOW PREVENTION DEVICE TESTERA person who attends an accredited program and is found competent for the testing of backflow prevention devices. He shall be provided with an appropriate certification by the State Health Department, which must be renewed periodically. Failure to perform his duties competently and conscientiously will result in prompt withdrawal of his certification.
CROSS-CONNECTIONSAny unprotected connection between any part of a water system used or intended to supply water for drinking purposes and any source or system containing water or substance that is not or cannot be approved as equally safe, wholesome, and potable for human consumption.
SERVICE CONNECTIONThe point at which the consumer takes water from the approved water supply such as the discharge side of the customer's meter, or the curb stop if no meter is used, or the discharge nozzle of a fire hydrant or any other approved point of taking water.
WATER SUPERVISORThe consumer or a person on the premises charged with the responsibility of complete knowledge and understanding of the water supply piping within the premises and for maintaining the consumer's water system free from cross-connections and other sanitary defects, as required by regulations and laws.