The electrical regulations of this code shall not be construed to relieve from or lessen the responsibility or liability of any person owning, operating or installing electrical conductors, devices, appliances, fixtures, apparatus, motors, or equipment, for damages to persons or buildings caused by any defect therein by reason of the inspection herein authorized or the certificate of approved inspection issued by the electrical inspector's office as herein provided, nor shall the city be held liable for any damages by reason of the enforcement of this code.
(1958 Code, sec. 11-8; 1978 Code, sec. 6-110; Ordinance 24-011 adopted 3/19/2024)
(a) 
All installations of electrical wiring and equipment shall be reasonably safe to persons and property and in conformity with the provisions of this code, the applicable statutes of the state, and any rules or regulations issued by authority thereof.
(b) 
Due to the unusual climatic conditions prevailing in and about the city, certain exceptions to the wiring methods and materials, as set forth in the National Electrical Code herein adopted, shall be made as set forth in this division.
(c) 
Required power source.
Electrical system shall be provided with service from the public utility company or a power source approved by the building official. Portable generators may only be used when service is not available from a public utility company or an approved power source or when approved by the building official for temporary power.
(1958 Code, sec. 11-35; Ordinance 75-28, sec. 2, adopted 4/15/75; Ordinance 78-13, sec. 1, adopted 2/7/78; Ordinance 81-18, sec. 2, adopted 3/10/81; Ordinance 84-73, sec. 1, adopted 6/12/84; Ordinance 90-6, sec. 1, adopted 1/30/90; 1978 Code, sec. 6-111; Ordinance 08-006, sec. 1, adopted 1/8/08; Ordinance 10-057, sec. 8, adopted 8/3/10; Ordinance 24-011 adopted 3/19/2024)
(a) 
All electrical equipment installed or used shall be reasonably safe to persons and property in conformity with the provisions of this code, the applicable statutes of the state and any rules or regulations issued by authority thereof.
(b) 
Conformity of electrical equipment with the applicable standards of the Underwriters' Laboratories, Inc., shall be prima facie evidence that such equipment is reasonably safe to persons and property.
(c) 
Only standard parts and materials approved by the Underwriters' Laboratories, Inc., or by the chief electrical inspector, as set forth in section 24.03.036, shall be permitted in electrical repair or maintenance work.
(1958 Code, sec. 11-36; 1978 Code, sec. 6-112; Ordinance 17-008, sec. 22, adopted 2/7/17; Ordinance 24-011 adopted 3/19/2024)
(a) 
All electrically illuminated or electrically powered outdoor and indoor signs and displays shall be reasonably safe to persons and property and in conformity with the provisions of this code.
(b) 
Conformity of all types of electrical signs with applicable standards of the Underwriters' Laboratories, Inc., and the National Electrical Code shall be prima facie evidence that such installations are reasonably safe to persons and property; provided that the provisions of this division shall prevail in case of conflicting provisions.
(c) 
Conformity of construction, erection, foundation and means of support of all such signs with the city building code shall be approved by the city building official before permits for electrical inspection shall be issued under the authority of this code.
(d) 
A permit for an electrical sign must be obtained from the housing code enforcement division before any sign is installed.
(1958 Code, sec. 11-37; Ordinance 87-41, sec. 6, adopted 5/26/87; 1978 Code, sec. 6-113; Ordinance 24-011 adopted 3/19/2024)
Rules and regulations of the company supplying electricity to the city regarding service and meter installations for the kind and character of service to be rendered, as passed and approved by the governing body of the city from time-to-time, in accordance with franchise provisions, are hereby referred to, incorporated herein, and made a part hereof.
(1958 Code, sec. 11-38; 1978 Code, sec. 6-114; Ordinance 24-011 adopted 3/19/2024)
Wiring methods approved by the National Electrical Code shall be used with the exceptions listed below:
(1) 
Any approved method may be used for temporary work.
(2) 
In all buildings and on all properties, all commercial buildings, and all buildings used for commercial purposes, the following wiring methods are excluded from the approved methods, as listed in the National Electrical Code:
(A) 
Article 398-Open wiring on insulators.
(B) 
Article 394-Concealed knob and tube work.
(C) 
Article 394-Electrical non-metallic tubing.
(D) 
Article 334-Non-metallic sheathed cable.
(E) 
Article 338-Service entrance cable.
(F) 
Article 340-Underground feeder and branch circuit cable.
(3) 
The following equipment shall be installed on individual circuits:
(A) 
Attic fan and heating unit.
(B) 
Dishwasher.
(C) 
Disposal.
(D) 
Washing machine.
(E) 
Dryer.
(F) 
Water heaters and space heaters.
(G) 
Ranges, built-in ranges, tops and ovens.
(H) 
Air conditioning equipment.
(I) 
Other types of equipment that requires special circuits.
(J) 
Built-in microwave ovens.
(K) 
Refrigerators.
(4) 
Low voltage wiring.
All low voltage wiring and devices shall be installed according to the requirements of the National Electrical Code.
(5) 
The installation of A.C. or armored cable shall not be permitted in any place or places designed or intended for assembly occupancy purposes.
(1958 Code, sec. 11-65; Ordinance 79-62, sec. 2, adopted 8/21/79; Ordinance 83-34, sec. 8, adopted 4/5/83; Ordinance 87-41, sec. 7, adopted 5/26/87; Ordinance 87-53, sec. 1, adopted 7/7/87; Ordinance 91-11, sec. 1, adopted 2/12/91; 1978 Code, sec. 6-115; Ordinance 10-057, sec. 9, adopted 8/3/10; Ordinance 24-011 adopted 3/19/2024)
Service-entrance cable may be used on all one- and two-family residences where three (3) number six (6) copper conductors or larger are used.
(1958 Code, sec. 11-66; 1978 Code, sec. 6-116; Ordinance 10-057, sec. 10, adopted 8/3/10; Ordinance 24-011 adopted 3/19/2024)
It shall be unlawful for any person to bridge, tamper with or change from its original installation, except upon the approval of the chief electrical inspector, and then only after proper permit for alteration has been issued, any fuse of the plug, cartridge type, or link type, installed in panel boards, main switches or switchboards, or to alter or change circuit breakers so that the original calibration will be affected, or to tie down or secure any circuit breaker so that it will not function properly. Only eight (8) devices shall be installed on #14 wire and ten (10) devices on #12 wire.
(1958 Code, sec. 11-67(a); 1978 Code, sec. 6-117; Ordinance 10-057, sec. 11, adopted 8/3/10; Ordinance 24-011 adopted 3/19/2024)
Service clearances shall comply with the current requirements of "standard service practices" of the local utility company. Where these clearances are not covered by this standard, the National Electrical Code shall apply.
(1958 Code, sec. 11-68; Ordinance 87-41, sec. 8, adopted 5/26/87; 1978 Code, sec. 6-118; Ordinance 24-011 adopted 3/19/2024)
There shall be a service disconnect on the exterior of all commercial buildings.
(Ordinance 10-057, sec. 12, adopted 8/3/10; Ordinance 24-011 adopted 3/19/2024)
Each individual tenant space within a structure shall have an independent service. Two (2) services on an individual tenant space within a structure shall only be permitted with prior approval from the building official.
(Ordinance 10-057, sec. 13, adopted 8/3/10; Ordinance 24-011 adopted 3/19/2024)
Extension cords shall not be used in commercial buildings for powering of accessory appliances as defined by the building official.
(1958 Code, sec. 11-69; 1978 Code, sec. 6-119; Ordinance 10-057, sec. 14, adopted 8/3/10; Ordinance 24-011 adopted 3/19/2024)
Temporary poles shall comply with the requirements of the local utility company's standard service practices.
(Ordinance 76-90, sec. 1, adopted 8/17/76; Ordinance 87-41, sec. 9, adopted 5/26/87; 1978 Code, sec. 6-119.1; Ordinance 24-011 adopted 3/19/2024)